Study guide
6.1 Conductor Ampacity & NEC Table 310.16 Derating Adjustments
PE Electrical and Computer: Power Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview, Strategy & Reference Handbook
1.1 PE Power Exam Format, CBT Navigation & Reference Handbook 1.2 2026 Reference Standards (NEC 2020, NFPA 70E-2021, NESC) & Scoring Mechanics 1.3 CBT Pacing, AIT Question Formats & Formula Sheet Mastery
2 Chapter 2: Measurement, Metering & Field Testing
2.1 Current Transformers (CTs), Potential Transformers (PTs) & Meter Connections 2.2 Instrument Transformer Burdens, Saturation Curves & Ratio Correction Factors 2.3 Insulation Resistance Testing (Megger, Polarization Index, Dielectric Absorption) 2.4 Ground Resistance Testing (Fall-of-Potential 62% Rule & Clamp-on Methods)
3 Chapter 3: General Applications — Grounding & Surge Protection
3.1 Substation Ground Grid Design & IEEE 80 Touch/Step Voltage Criteria 3.2 Lightning Protection Systems & Rolling Sphere / Cone of Protection Methods 3.3 Surge Protective Devices (SPDs) & Voltage Surge Arresters
4 Chapter 4: General Applications — Lighting & Energy Management
4.1 Illumination Engineering & Zonal Cavity / Lumen Method Calculations 4.2 Energy Management, Demand Factors & Load Factor Calculations 4.3 Economic Dispatch, Energy Efficiency & Load Profile Analysis
5 Chapter 5: Electrical Safety & NFPA Standards
5.1 NFPA 70E Shock Protection, Approach Boundaries & PPE Requirements 5.2 Arc-Flash Hazard Analysis & IEEE 1584-2018 Incident Energy Calculations 5.3 Hazardous (Classified) Locations (Class I, II, III & Division/Zone Systems) 5.4 Special Occupancies & Critical Systems (NEC Articles 517 Health Care, 700/701/702 Emergency)
6 Chapter 6: NEC Wiring Methods & Installation Requirements
6.1 Conductor Ampacity & NEC Table 310.16 Derating Adjustments 6.2 Raceway Fill, Box Sizing & Conduit Bending Calculations (Chapter 9 Tables) 6.3 Equipment Grounding Conductors & Grounding Electrode Sizing (NEC Article 250)
7 Chapter 7: Circuit Analysis — Fundamentals & Symmetrical Components
7.1 DC & Single-Phase AC Network Analysis (Thevenin, Norton, Superposition) 7.2 Balanced Three-Phase Circuits (Wye-Delta Configurations & Power Formulas) 7.3 Symmetrical Components & Fortescue Sequence Transformation Matrices 7.4 Sequence Impedances & Positive, Negative, Zero Sequence Network Construction
8 Chapter 8: Circuit Analysis — Per-Unit & Phasor Analysis
8.1 Per-Unit System Fundamentals & Base Conversion Formulas 8.2 Three-Phase Per-Unit Network Modeling & Equipment Impedance Conversion 8.3 Phasor Diagrams, Complex Power & Power Triangle Relationships
9 Chapter 9: Power Electronics & Logic Controls
9.1 Power Electronic Converters (Rectifiers, Inverters & DC-DC Topologies) 9.2 Inverter-Based Resources (IBRs), Grid-Forming & Grid-Following Controls 9.3 Variable Frequency Drives (VFDs), PWM Operation & Harmonic Mitigation 9.4 Boolean Algebra, Logic Gates, De Morgan's Laws & Ladder Logic Control Diagrams
10 Chapter 10: Rotating Machines — Induction & Synchronous
10.1 Three-Phase Induction Motors (Equivalent Circuits, Slip & Performance) 10.2 Induction Motor Torque-Speed Characteristics & NEMA Design Classes 10.3 Synchronous Machines (Operating Principles, Power-Angle Curves & V-Curves) 10.4 Motor Starting Methods (DOL, Wye-Delta, Autotransformer, Soft-Start) & Voltage Dip
11 Chapter 11: Electric Power Devices & Renewable Energy
11.1 Power Transformers (Equivalent Circuits, Efficiency & Voltage Regulation) 11.2 Power Factor Correction Capacitors & Shunt Bank Sizing 11.3 Battery Energy Storage Systems (BESS) & Ultracapacitors 11.4 Renewable Energy Generation (Solar Photovoltaic Systems & Wind Turbines)
12 Chapter 12: Transmission & Distribution — Steady-State & Power Quality
12.1 Transmission Line Modeling, Voltage Drop & Conductor Sizing 12.2 Voltage Regulation, Reactive Power Support & Tap-Changer Controls 12.3 Power Quality, Harmonics, THD & IEEE 519 Compliance 12.4 Power Flow Analysis & System Stability (Steady-State, Transient & Swing Equation)
13 Chapter 13: Transmission & Distribution — Fault Analysis & Transformer Shifts
13.1 Symmetrical Three-Phase Bolted Fault Calculations 13.2 Unsymmetrical Fault Analysis (SLG, L-L, DLG Fault Calculations) 13.3 Transformer Connection Types, Zero-Sequence Paths & 30-Degree Phase Shifts
14 Chapter 14: Protection Systems & Device Coordination
14.1 Overcurrent Protection & Time-Current Characteristic (TCC) Curves 14.2 Protective Relaying Schemes (Differential 87, Distance 21, Undervoltage 27) 14.3 Circuit Breakers, Fuses & Automatic Reclosers 14.4 Protection Coordination, Selectivity & Coordination Time Intervals (CTI)
6.1 Conductor Ampacity & NEC Table 310.16 Derating Adjustments
Key Takeaways Explain This Topic AI
NEC Table 310.16 establishes baseline allowable conductor ampacities across 60°C, 75°C, and 90°C insulation temperature ratings for copper and aluminum/copper-clad aluminum conductors.
Equipment terminal temperature limitations per NEC 110.14(C) govern final allowable ampacity: 60°C for circuits ≤ 100 A or #14–#1 AWG, and 75°C for circuits > 100 A or larger than #1 AWG.
The 90°C column (e.g., THHN, THWN-2, XHHW-2) is utilized as the starting baseline for ambient temperature (CF_T) and conductor bundling (CF_A) derating calculations, but the resulting derated ampacity cannot exceed the terminal rating column (typically 75°C).
Continuous loads (operating continuously for 3 hours or more) mandate a 125% sizing multiplier per NEC 210.19(A)(1) and 215.2(A)(1); conductors must independently satisfy both the unadjusted continuous load terminal check and the derated ampacity under conditions of use.
Bundling adjustment factors from Table 310.15(C)(1) apply when more than 3 current-carrying conductors are in a raceway (4–6: 80%, 7–9: 70%, 10–20: 50%); neutrals carrying triplen harmonic currents from non-linear loads count as current-carrying per NEC 310.15(E)(3).
Last updated: August 2026
6.1 Conductor Ampacity & NEC Table 310.16 Derating Adjustments
Executive Overview: Conductor sizing is one of the most heavily tested topics on the NCEES PE Electrical and Computer: Power examination. Selecting the correct conductor requires synthesizing multiple articles of NFPA 70 (National Electrical Code / NEC 2020): Table 310.16 for baseline ampacities, NEC 110.14(C) for termination temperature limits, NEC 210.19/215.2 for continuous load multipliers, Table 310.15(B)(1) correction factors for elevated ambient temperatures, and Table 310.15(C)(1) adjustment factors for conduit bundling. Mastering the rigorous dual-evaluation workflow ensures full compliance and prevents common exam traps.
1. NEC Table 310.16 Structure & Conductor Insulation Types
NEC Table 310.16 ( Allowable Ampacities of Insulated Conductors Rated Up to and Including 2000 Volts, 60°C Through 90°C, Not More Than Three Current-Carrying Conductors in Raceway, Cable, or Earth, Based on Ambient Temperature of 30°C / 86°F ) forms the bedrock of electrical feeder and branch circuit design. +---------------------------------------------------------------------------------------------------+
- | NEC TABLE 310.16 ARCHITECTURE OVERVIEW (30°C / 86°F Ambient, <= 3 Current-Carrying Conductors) |
- +-------------------+-----------------------------------+-----------------------------------+
- | Temperature Rating| Copper (Cu) Conductor Types | Aluminum / Cu-Clad Al Types |
- +-------------------+-----------------------------------+-----------------------------------+
- | 60°C (140°F) | TW, UF | TW, UF |
- | 75°C (167°F) | RHW, THHW, THW, THWN, XHHW, USE | RHW, THHW, THW, THWN, XHHW, USE |
- | 90°C (194°F) | RHH, RHW-2, THHN, THHW, THWN-2, | RHH, RHW-2, THHN, THHW, THWN-2, |
- | | USE-2, XHH, XHHW, XHHW-2, ZW-2 | USE-2, XHH, XHHW, XHHW-2, ZW-2 |
- +-------------------+-----------------------------------+-----------------------------------+
- Common Conductor Insulation Codes & Applications
TW / UF: Thermoplastic, Moisture-Resistant ( 60 ∘ C 60^\circ\text{C} 6 0 ∘ C wet/dry; UF = Underground Feeder).
THW / THWN: Thermoplastic, Heat- and Moisture-Resistant ( 75 ∘ C 75^\circ\text{C} 7 5 ∘ C wet/dry for THW; 75 ∘ C 75^\circ\text{C} 7 5 ∘ C wet for dual-rated THWN/THHN).
THHN: Thermoplastic, High Heat-Resistant, Nylon jacket ( 90 ∘ C 90^\circ\text{C} 9 0 ∘ C dry only; in wet locations, standard dual-rated THHN drops to 75 ∘ C 75^\circ\text{C} 7 5 ∘ C THWN rating).
THWN-2 / XHHW-2: Thermoplastic/Cross-linked synthetic polymer, rated for 90 ∘ C 90^\circ\text{C} 9 0 ∘ C in both dry and wet locations .
Baseline Ampacity Reference (Selected Common Copper Sizes per Table 310.16)
- Conductor Size (AWG/kcmil) 60°C Rating (Cu) 75°C Rating (Cu) 90°C Rating (Cu)
- #14 AWG 15 A ∗ 15\text{ A}^* 15 A ∗ 20 A 20\text{ A} 20 A 25 A 25\text{ A} 25 A
- #12 AWG 20 A ∗ 20\text{ A}^* 20 A ∗ 25 A 25\text{ A} 25 A 30 A 30\text{ A} 30 A
- #10 AWG 30 A ∗ 30\text{ A}^* 30 A ∗ 35 A 35\text{ A} 35 A 40 A 40\text{ A} 40 A
- #8 AWG 40 A 40\text{ A} 40 A 50 A 50\text{ A} 50 A 55 A 55\text{ A} 55 A
- #6 AWG 55 A 55\text{ A} 55 A 65 A 65\text{ A} 65 A 75 A 75\text{ A} 75 A
- #4 AWG 70 A 70\text{ A} 70 A 85 A 85\text{ A} 85 A 95 A 95\text{ A} 95 A
- #2 AWG 95 A 95\text{ A} 95 A 115 A 115\text{ A} 115 A 130 A 130\text{ A} 130 A
- #1/0 AWG 125 A 125\text{ A} 125 A 150 A 150\text{ A} 150 A 170 A 170\text{ A} 170 A
- #2/0 AWG 145 A 145\text{ A} 145 A 175 A 175\text{ A} 175 A 195 A 195\text{ A} 195 A
- #3/0 AWG 165 A 165\text{ A} 165 A 200 A 200\text{ A} 200 A 225 A 225\text{ A} 225 A
- #4/0 AWG 195 A 195\text{ A} 195 A 230 A 230\text{ A} 230 A 260 A 260\text{ A} 260 A
- 250 kcmil 215 A 215\text{ A} 215 A 255 A 255\text{ A} 255 A 290 A 290\text{ A} 290 A
- 350 kcmil 260 A 260\text{ A} 260 A 310 A 310\text{ A} 310 A 350 A 350\text{ A} 350 A
- 500 kcmil 320 A 320\text{ A} 320 A 380 A 380\text{ A} 380 A 430 A 430\text{ A} 430 A
Small Conductor Rule (NEC 240.4(D)): Note that despite the higher table ampacities, overcurrent protection for small copper conductors shall not exceed: 15 A for #14 AWG , 20 A for #12 AWG , and 30 A for #10 AWG , unless specifically permitted elsewhere in the Code (e.g., motor circuits in Art. 430 or hermetic compressors in Art. 440).
2. Equipment Terminal Limitations (NEC 110.14(C))
Electrical equipment terminations (circuit breakers, disconnect switches, panelboards, motor terminals) are rated to operate safely up to specific maximum temperatures. Conductors connected to these terminals must not run hotter than the terminal's rating at full operating current, or the termination hardware will degrade and fail.
The Standard Terminal Rules
Per NEC 110.14(C)(1) , unless the equipment is listed and marked otherwise:
Circuits Rated 100 A or Less (or #14 through #1 AWG conductors):
Conductors must be sized based on the 60°C column of Table 310.16.
Exception: Conductors with higher temperature ratings (e.g., 75°C or 90°C) may be used, but their ampacity is evaluated at the 60°C column unless the terminal equipment is explicitly listed for 75°C.
Circuits Rated Over 100 A (or conductors larger than #1 AWG):
Conductors must be sized based on the 75°C column of Table 310.16.
Equipment terminals in modern commercial/industrial installations are almost universally rated for 75°C . +-----------------------------------------------------------------------------------------+
- | THE 90°C DERATING ANCHOR PRINCIPLE |
- | |
- | 1. High-temp conductors (e.g., 90°C THHN/XHHW-2) allow derating to START at the 90°C |
- | column: |
- | I_derated = I_table(90°C) * CF_T * CF_A |
- | |
- | 2. However, the conductor ampacity CONNECTED TO THE TERMINAL cannot exceed the |
- | terminal's rated temperature column (typically 75°C): |
- | I_allowable_final = MIN( I_derated, I_table(75°C) ) |
- +-----------------------------------------------------------------------------------------+
- 3. Continuous Load Requirements (NEC 210.19(A)(1) & 215.2(A)(1))
A continuous load is defined in NEC Article 100 as a load where the maximum current is expected to continue for 3 hours or more (e.g., commercial office lighting, data centers, store display lighting). Noncontinuous loads operate intermittently (e.g., water heaters, standard receptacle loads, elevators).
Sizing Rule for Overcurrent Protection and Conductors
To prevent thermal buildup in enclosed circuit breakers and switchgear: I t e r m i n a l − r e q = 1.25 × I c o n t i n u o u s + 1.00 × I n o n c o n t i n u o u s I_{terminal-req} = 1.25 \times I_{continuous} + 1.00 \times I_{noncontinuous} I t er mina l − re q = 1.25 × I co n t in u o u s + 1.00 × I n o n co n t in u o u s I O C P D − m i n ≥ 1.25 × I c o n t i n u o u s + 1.00 × I n o n c o n t i n u o u s I_{OCPD-min} \ge 1.25 \times I_{continuous} + 1.00 \times I_{noncontinuous} I OCP D − min ≥ 1.25 × I co n t in u o u s + 1.00 × I n o n co n t in u o u s
The Critical PE Distinction: The 125% continuous load multiplier is an equipment/terminal heating factor , NOT a physical conductor heating factor under ambient conduit conditions. Therefore:
Do not multiply the continuous load by 1.25 when applying ambient temperature and bundling derating factors.
Conductors must satisfy a two-step verification .
4. The Dual-Evaluation Conductor Sizing Workflow
To size a feeder or branch circuit correctly under all NEC requirements, the engineer must perform two independent checks: +-----------------------------------------------------------------------------------------+
- | DUAL-EVALUATION WORKFLOW FOR CONDUCTOR SIZING |
- |
- | CHECK 1: Terminal Rating Sizing (Unadjusted Continuous Load Check)
- | I_table(Terminal Temp, e.g. 75°C) >= 1.25 * I_continuous + 1.00 * I_noncontinuous
- |
- | CHECK 2: Conditions of Use Sizing (Derated Ampacity Check)
- | I_derated = I_table(Conductor Insulation Temp, e.g. 90°C) * CF_T * CF_A
- | Requirement: I_derated >= I_continuous + I_noncontinuous (Total Actual Load)
- |
| Final Selection: Conductor must satisfy BOTH Check 1 and Check 2.
- +-----------------------------------------------------------------------------------------+
- 5. Derating Factors: Ambient Temperature & Conductor Bundling
- Ambient Temperature Correction ( C F T CF_T C F T )
Table 310.16 is normalized to an ambient temperature of 30 ∘ C 30^\circ\text{C} 3 0 ∘ C ( 86 ∘ F 86^\circ\text{F} 8 6 ∘ F ). When conduits run through boiler rooms, attics, or outdoor rooftop environments where T a m b i e n t > 30 ∘ C T_{ambient} > 30^\circ\text{C} T ambi e n t > 3 0 ∘ C , the conductor cannot dissipate heat effectively. The correction factor is derived from the thermodynamic heat transfer equation: C F T = T c − T a T c − T r e f CF_T = \sqrt{\frac{T_c - T_a}{T_c - T_{ref}}} C F T = T c − T re f T c − T a
where T c T_c T c is conductor temperature rating ( 90 ∘ C 90^\circ\text{C} 9 0 ∘ C ), T a T_a T a is actual ambient temperature, and T r e f = 30 ∘ C T_{ref} = 30^\circ\text{C} T re f = 3 0 ∘ C .
Ambient Temperature Correction Factors ( C F T CF_T C F T ) for 90°C Rated Conductors
- Ambient Temperature (°C) Ambient Temperature (°F) 90°C Conductor Correction Factor ( C F T CF_T C F T )
- 21 – 25°C 70 – 77°F 1.04 1.04 1.04
- 26 – 30°C 78 – 86°F 1.00 1.00 1.00
- 31 – 35°C 87 – 95°F 0.96 0.96 0.96
- 36 – 40°C 96 – 104°F 0.91 0.91 0.91
- 41 – 45°C 105 – 113°F 0.87 0.87 0.87
- 46 – 50°C 114 – 122°F 0.82 0.82 0.82
- 51 – 55°C 123 – 131°F 0.76 0.76 0.76
- 56 – 60°C 132 – 140°F 0.71 0.71 0.71
- Conductor Bundling Adjustment ( C F A CF_A C F A )
When more than three current-carrying conductors are installed in a raceway or cable, mutual heating occurs. Per NEC Table 310.15(C)(1) :
- Number of Current-Carrying Conductors Adjustment Factor ( C F A CF_A C F A )
- 1 – 3 1.00 1.00 1.00 ( 100 % 100\% 100% )
- 4 – 6 0.80 0.80 0.80 ( 80 % 80\% 80% )
- 7 – 9 0.70 0.70 0.70 ( 70 % 70\% 70% )
- 10 – 20 0.50 0.50 0.50 ( 50 % 50\% 50% )
- 21 – 30 0.45 0.45 0.45 ( 45 % 45\% 45% )
- 31 – 40 0.40 0.40 0.40 ( 40 % 40\% 40% )
- 41 and above 0.35 0.35 0.35 ( 35 % 35\% 35% )
- Neutral Conductor Counting Rules (NEC 310.15(E))
Not every wire in a conduit is counted as "current-carrying":
Equipment Grounding / Bonding Conductors: Never counted (NEC 310.15(F)).
Linear Balanced Neutral (NEC 310.15(E)(1)): A neutral carrying only unbalanced current from a 3-wire single-phase or 4-wire 3-phase wye system is not counted .
2-Phase + Neutral of 3-Phase Wye (NEC 310.15(E)(2)): In a 3-wire circuit consisting of 2 phase conductors and the neutral of a 4-wire, 3-phase wye system, the common conductor carries approximately the same current as the phase lines. The neutral is counted (3 conductors total).
Non-Linear Loads & Harmonics (NEC 310.15(E)(3)): In a 4-wire, 3-phase wye circuit supplying non-linear loads (LED drivers, computers, server power supplies, VFDs), the 3rd harmonic (triplens: 180 Hz) and odd multiples add arithmetically in the neutral. The neutral carries substantial continuous current and must be counted as a 4th current-carrying conductor .
- 6. Comprehensive Multi-Step Calculation Example
- Problem Statement
A commercial data facility requires a 3-phase, 4-wire, 480Y/277 V feeder routed through an industrial plant mezzanine where the ambient temperature is 40 ∘ C 40^\circ\text{C} 4 0 ∘ C ( 104 ∘ F 104^\circ\text{F} 10 4 ∘ F ) .
Continuous Load: 180 A 180\text{ A} 180 A of solid-state IT/server loads (non-linear loads).
Noncontinuous Load: 60 A 60\text{ A} 60 A of linear heating loads.
Installation: Conductors are installed in a single EMT raceway that also contains a separate 3-phase, 3-wire branch circuit (3 current-carrying phase conductors).
Conductor Specification: Single-conductor Copper with THHN/THWN-2 insulation.
Terminations: 75°C-rated circuit breaker terminals.
Determine the minimum required conductor size (AWG or kcmil) and the required standard overcurrent protective device (OCPD) rating. =========================================================================================
CALCULATION WORKFLOW & SOLUTION:
=========================================================================================
- Step 1: Determine Total Actual Load & Minimum Terminal Ampacity Requirement
- Continuous Load (I_cont) = 180 A
- Noncontinuous Load (I_noncont) = 60 A
- Total Actual Load (I_actual) = 180 A + 60 A = 240 A
Terminal Ampacity Requirement (Check 1 per NEC 215.2(A)(1)):
- I_terminal_min = 1.25 * I_cont + 1.00 * I_noncont
- = (1.25 * 180 A) + 60 A
- = 225 A + 60 A = 285 A
Step 2: Determine Standard OCPD Rating per NEC 240.6(A)
The OCPD must be rated at least equal to I_terminal_min:
OCPD_min >= 285 A
Next standard ampere rating from NEC 240.6(A) above 285 A is 300 A.
-> Selected OCPD = 300 A.
Step 3: Count Total Current-Carrying Conductors in the Raceway
- Feeder circuit: 3 phase conductors + 1 neutral.
Since IT server power supplies are non-linear, triplen harmonics require the neutral
to be counted as current-carrying per NEC 310.15(E)(3) => 4 conductors.
- Second circuit: 3 phase conductors => 3 conductors.
- Total current-carrying conductors in raceway = 4 + 3 = 7 conductors.
Step 4: Determine Adjustment and Correction Factors
- Ambient Temperature: T_amb = 40°C.
From Table 310.15(B)(1)(1) for the 90°C column at 36–40°C:
CF_T = 0.91
- Conductor Bundling: 7 current-carrying conductors.
From Table 310.15(C)(1) for 7–9 conductors:
CF_A = 0.70
- Total Combined Derating Multiplier:
CF_total = CF_T * CF_A = 0.91 * 0.70 = 0.637
Step 5: Conductor Evaluation under Dual Criteria
Criteria A (Terminal Rating Check at 75°C):
The conductor's 75°C rating from Table 310.16 must be >= 285 A.
- 250 kcmil Cu (75°C) = 255 A (< 285 A -> FAILS)
- 300 kcmil Cu (75°C) = 285 A (>= 285 A -> PASSES Check 1)
- 350 kcmil Cu (75°C) = 310 A (>= 285 A -> PASSES Check 1)
Criteria B (Conditions of Use Derated Ampacity Check at 90°C):
The derated ampacity must carry the actual total load (240 A):
- I_derated = I_table(90°C) * CF_total >= 240 A
- I_table(90°C)_req >= 240 A / 0.637 = 376.77 A
Let's test copper sizes from Table 310.16 (90°C Column):
- 300 kcmil Cu: 90°C rating = 320 A
- I_derated = 320 A * 0.637 = 203.8 A (< 240 A -> FAILS Check 2!)
- 350 kcmil Cu: 90°C rating = 350 A
- I_derated = 350 A * 0.637 = 222.95 A (< 240 A -> FAILS Check 2!)
- 500 kcmil Cu: 90°C rating = 430 A
- I_derated = 430 A * 0.637 = 273.91 A (>= 240 A -> PASSES Check 2!)
Check Terminal Cap on 500 kcmil Cu:
500 kcmil Cu (75°C column) = 380 A.
Final allowable ampacity = MIN(273.91 A, 380 A) = 273.91 A >= 240 A.
=========================================================================================
FINAL CONCLUSION:
- Minimum Required Conductor Size: 500 kcmil THHN/THWN-2 Copper
- Overcurrent Protective Device: 300 A Circuit Breaker
- =========================================================================================
- 7. Common Exam Traps & Strategic Pitfalls
The 125% Derating Multiplier Trap: Candidates frequently multiply the continuous load by 1.25 when dividing by derating factors (e.g., computing ( 1.25 × 240 ) / 0.637 (1.25 \times 240) / 0.637 ( 1.25 × 240 ) /0.637 ). This is double-penalizing the circuit! Continuous load 1.25 is strictly for OCPD and terminal sizing (Check 1); physical conduit heating derating applies to actual continuous + noncontinuous current (Check 2).
The Blind 75°C Starting Point Trap: Taking derating factors on the 75°C column for THHN conductors. Per NEC 110.14(C), as long as the conductor insulation is rated 90°C, derating factors are applied to the 90°C ampacity , provided the final result does not exceed the 75°C terminal rating.
Ignoring Non-Linear Neutrals: Assuming neutrals are never counted in 3-phase wye systems. If the problem mentions electronic ballasts, LED drivers, data servers, or rectifiers, the neutral is a current-carrying conductor.