14.2 Protective Relaying Schemes (Differential 87, Distance 21, Undervoltage 27)
PE Electrical and Computer: Power Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview, Strategy & Reference Handbook
1.1 PE Power Exam Format, CBT Navigation & Reference Handbook 1.2 2026 Reference Standards (NEC 2020, NFPA 70E-2021, NESC) & Scoring Mechanics 1.3 CBT Pacing, AIT Question Formats & Formula Sheet Mastery
2 Chapter 2: Measurement, Metering & Field Testing
2.1 Current Transformers (CTs), Potential Transformers (PTs) & Meter Connections 2.2 Instrument Transformer Burdens, Saturation Curves & Ratio Correction Factors 2.3 Insulation Resistance Testing (Megger, Polarization Index, Dielectric Absorption) 2.4 Ground Resistance Testing (Fall-of-Potential 62% Rule & Clamp-on Methods)
3 Chapter 3: General Applications — Grounding & Surge Protection
3.1 Substation Ground Grid Design & IEEE 80 Touch/Step Voltage Criteria 3.2 Lightning Protection Systems & Rolling Sphere / Cone of Protection Methods 3.3 Surge Protective Devices (SPDs) & Voltage Surge Arresters
4 Chapter 4: General Applications — Lighting & Energy Management
4.1 Illumination Engineering & Zonal Cavity / Lumen Method Calculations 4.2 Energy Management, Demand Factors & Load Factor Calculations 4.3 Economic Dispatch, Energy Efficiency & Load Profile Analysis
5 Chapter 5: Electrical Safety & NFPA Standards
5.1 NFPA 70E Shock Protection, Approach Boundaries & PPE Requirements 5.2 Arc-Flash Hazard Analysis & IEEE 1584-2018 Incident Energy Calculations 5.3 Hazardous (Classified) Locations (Class I, II, III & Division/Zone Systems) 5.4 Special Occupancies & Critical Systems (NEC Articles 517 Health Care, 700/701/702 Emergency)
6 Chapter 6: NEC Wiring Methods & Installation Requirements
6.1 Conductor Ampacity & NEC Table 310.16 Derating Adjustments 6.2 Raceway Fill, Box Sizing & Conduit Bending Calculations (Chapter 9 Tables) 6.3 Equipment Grounding Conductors & Grounding Electrode Sizing (NEC Article 250)
7 Chapter 7: Circuit Analysis — Fundamentals & Symmetrical Components
7.1 DC & Single-Phase AC Network Analysis (Thevenin, Norton, Superposition) 7.2 Balanced Three-Phase Circuits (Wye-Delta Configurations & Power Formulas) 7.3 Symmetrical Components & Fortescue Sequence Transformation Matrices 7.4 Sequence Impedances & Positive, Negative, Zero Sequence Network Construction
8 Chapter 8: Circuit Analysis — Per-Unit & Phasor Analysis
8.1 Per-Unit System Fundamentals & Base Conversion Formulas 8.2 Three-Phase Per-Unit Network Modeling & Equipment Impedance Conversion 8.3 Phasor Diagrams, Complex Power & Power Triangle Relationships
9 Chapter 9: Power Electronics & Logic Controls
9.1 Power Electronic Converters (Rectifiers, Inverters & DC-DC Topologies) 9.2 Inverter-Based Resources (IBRs), Grid-Forming & Grid-Following Controls 9.3 Variable Frequency Drives (VFDs), PWM Operation & Harmonic Mitigation 9.4 Boolean Algebra, Logic Gates, De Morgan's Laws & Ladder Logic Control Diagrams
10 Chapter 10: Rotating Machines — Induction & Synchronous
10.1 Three-Phase Induction Motors (Equivalent Circuits, Slip & Performance) 10.2 Induction Motor Torque-Speed Characteristics & NEMA Design Classes 10.3 Synchronous Machines (Operating Principles, Power-Angle Curves & V-Curves) 10.4 Motor Starting Methods (DOL, Wye-Delta, Autotransformer, Soft-Start) & Voltage Dip
11 Chapter 11: Electric Power Devices & Renewable Energy
11.1 Power Transformers (Equivalent Circuits, Efficiency & Voltage Regulation) 11.2 Power Factor Correction Capacitors & Shunt Bank Sizing 11.3 Battery Energy Storage Systems (BESS) & Ultracapacitors 11.4 Renewable Energy Generation (Solar Photovoltaic Systems & Wind Turbines)
12 Chapter 12: Transmission & Distribution — Steady-State & Power Quality
12.1 Transmission Line Modeling, Voltage Drop & Conductor Sizing 12.2 Voltage Regulation, Reactive Power Support & Tap-Changer Controls 12.3 Power Quality, Harmonics, THD & IEEE 519 Compliance 12.4 Power Flow Analysis & System Stability (Steady-State, Transient & Swing Equation)
13 Chapter 13: Transmission & Distribution — Fault Analysis & Transformer Shifts
13.1 Symmetrical Three-Phase Bolted Fault Calculations 13.2 Unsymmetrical Fault Analysis (SLG, L-L, DLG Fault Calculations) 13.3 Transformer Connection Types, Zero-Sequence Paths & 30-Degree Phase Shifts
14 Chapter 14: Protection Systems & Device Coordination
14.1 Overcurrent Protection & Time-Current Characteristic (TCC) Curves 14.2 Protective Relaying Schemes (Differential 87, Distance 21, Undervoltage 27) 14.3 Circuit Breakers, Fuses & Automatic Reclosers 14.4 Protection Coordination, Selectivity & Coordination Time Intervals (CTI)
14.2 Protective Relaying Schemes (Differential 87, Distance 21, Undervoltage 27)
Key Takeaways Explain This Topic AI
Differential protection (ANSI 87) enforces Kirchhoff's Current Law across a strictly bounded zone: operating current I d i f f = ∣ I 1 − I 2 ′ ∣ I_{diff} = |\mathbf{I}_1 - \mathbf{I}_2'| I d i ff = ∣ I 1 − I 2 ′ ∣ trips when exceeding the dual-slope restraint characteristic I d i f f > Slope × I r e s t + I p i c k u p I_{diff} > \text{Slope} \times I_{rest} + I_{pickup} I d i ff > Slope × I res t + I p i c k u p , providing high-speed unit protection without coordination delays.
Transformer differential relays (87T) must compensate for CT ratio mismatch, 30 ∘ 30^\circ 3 0 ∘ Wye-Delta phase shifts, zero-sequence ground fault trapping, magnetizing inrush (using 2nd harmonic restraint where I 2 f / I f u n d > 15 % I_{2f}/I_{fund} > 15\% I 2 f / I f u n d > 15% ), and overexcitation (using 5th harmonic restraint where I 5 f / I f u n d > 30 % I_{5f}/I_{fund} > 30\% I 5 f / I f u n d > 30% ).
Distance relays (ANSI 21) compute apparent impedance Z a p p = V / I \mathbf{Z}_{app} = \mathbf{V}/\mathbf{I} Z a pp = V / I on the R − X R-X R − X plane across stepped reach zones: Zone 1 (80-85% instantaneous), Zone 2 (120-150% with 0.3-0.4 s delay), and Zone 3 (remote backup with 0.6-1.0 s delay).
Pilot communication schemes (POTT, PUTT, DCB, and Line Differential 87L) overcome Zone 1 underreach by exchanging permissive or blocking signals across high-speed teleprotection channels for 100% line coverage at high speed.
System stability relays safeguard critical infrastructure: ANSI 27 (undervoltage) prevents motor stalling and drives UVLS, while ANSI 81U (under-frequency) coordinates NERC-mandated Under-Frequency Load Shedding (UFLS) stages.
Last updated: August 2026
14.2 Protective Relaying Schemes (Differential 87, Distance 21, Undervoltage 27)
Executive Overview: Modern power systems rely on specialized relaying schemes to protect apparatus and maintain grid stability. While simple overcurrent relays provide non-unit backup, critical infrastructure—transformers, generators, transmission lines, and major switchgear buses—demands unit protection (ANSI 87 Differential), impedance-based protection (ANSI 21 Distance), and voltage/frequency health monitoring (ANSI 27/59, ANSI 81). On the PE Power examination, candidates must understand ANSI device numbering, dual-slope percentage differential calculations, harmonic restraint for inrush, stepped distance zone parameterization, and teleprotection pilot schemes.
1. ANSI Standard Device Numbers & Function Taxonomy
The standard IEEE/ANSI C37.2 device numbers categorize protective relay functions across electrical substations:
ANSI Code Standard Device Function Operating Philosophy & Application
21 Distance / Impedance Relay Measures apparent impedance Z = V / I \mathbf{Z} = \mathbf{V}/\mathbf{I} Z = V / I ; protects transmission and subtransmission lines
25 Synchronism-Check Relay Verifies Δ V , Δ θ , Δ f \Delta V, \Delta \theta, \Delta f Δ V , Δ θ , Δ f across an open breaker prior to interconnection closure
27 Undervoltage Relay Senses voltage collapse ( V < V s e t V < V_{set} V < V se t ); drives motor drop-out, bus transfer, and UVLS load shedding
46 Reverse-Phase / Negative-Sequence Protects generators and motors against unbalance rotor overheating ( I 2 2 t = K I_2^2 t = K I 2 2 t = K )
49 Thermal Overload Relay Protects transformer and machine windings based on RTD or thermal replica models
50 / 51 Instantaneous / Time-Overcurrent Senses phase overcurrents with zero delay (50) or inverse time curves (51)
50N / 51N Residual Ground Overcurrent Calculated neutral/ground current ( 3 I 0 = I a + I b + I c 3\mathbf{I}_0 = \mathbf{I}_a + \mathbf{I}_b + \mathbf{I}_c 3 I 0 = I a + I b + I c ) from 3-phase CT secondary residual
50G / 51G Direct Ground Overcurrent Senses ground return current directly via a dedicated window / zero-sequence CT
59 Overvoltage Relay Senses excessive system voltage ( V > V s e t V > V_{set} V > V se t ); protects against insulation stress and Ferranti rise
67 / 67N Directional Overcurrent Relay Evaluates current relative to polarizing voltage/current; used in loop or multi-source lines
81U / 81O Under- / Over-Frequency Relay Detects active power imbalance ( P g e n ≠ P l o a d P_{gen} \ne P_{load} P g e n = P l o a d ); drives NERC UFLS stages
86 Master Lockout Relay High-speed electromechanical latching auxiliary relay; trips all sources and blocks reclosing
87 Differential Protective Relay Compares current entering and leaving bounded zone; instantaneous unit protection
87T / 87G / 87L Transformer / Generator / Line Diff Specialized differential relays with harmonic restraint (87T) or teleprotection (87L)
2. Differential Protection (ANSI 87)
Differential protection is based on Kirchhoff's Current Law : under normal or external through-fault conditions, the sum of currents entering a bounded zone equals the sum of currents leaving the zone. If a fault occurs inside the zone, current flows into the fault from one or both ends, creating an imbalance. Percentage Differential Relay Schematic (External Through-Fault vs. Internal Fault):
External Through-Fault (NO TRIP):
- Zone In -------------------[ Protected Equipment ]-------------------> Zone Out
- I_1 = 1000 A ---> I_2 = 1000 A --->
- (CT 1) 1000:5 (CT 2) 1000:5
- | |
- i_1 = 5 A i_2 = 5 A
- +-----[ Restraint 1 ]----o----[ Restraint 2 ]-------+
- |
- i_op = i_1 - i_2 = 0 A
- [ Operating Coil ]
- |
- (No Trip: i_op = 0)
Internal Fault (TRIP):
- Zone In -------------------[ Fault: 2000 A ]<------------------------- Zone Out
- I_1 = 1000 A ---> | I_2 = 1000 A <---
- (CT 1) 1000:5 v (CT 2) 1000:5
- | |
- i_1 = 5 A i_2 = -5 A
- +-----[ Restraint 1 ]----o----[ Restraint 2 ]-------+
- |
- i_op = i_1 - (-i_2) = 10 A
- [ Operating Coil ]
- |
- (TRIP: i_op > Pickup)
- Dual-Slope Percentage Differential Characteristic
CT errors, CT saturation during asymmetric through-faults, and transformer LTC tap changes create fictitious differential currents during external faults. To prevent misoperation, differential relays utilize a restraint current ( I r e s t I_{rest} I res t ) and a dual-slope operating curve: I d i f f = ∣ I 1 − I 2 ∣ [ Operating Current ] \mathbf{I}_{diff} = |\mathbf{I}_1 - \mathbf{I}_2| \quad [\text{Operating Current}] I d i ff = ∣ I 1 − I 2 ∣ [ Operating Current ] I r e s t = ∣ I 1 ∣ + ∣ I 2 ∣ 2 or I r e s t = max ( ∣ I 1 ∣ , ∣ I 2 ∣ ) [ Restraint Current ] I_{rest} = \frac{|\mathbf{I}_1| + |\mathbf{I}_2|}{2} \quad \text{or} \quad I_{rest} = \max(|\mathbf{I}_1|, |\mathbf{I}_2|) \quad [\text{Restraint Current}] I res t = 2 ∣ I 1 ∣ + ∣ I 2 ∣ or I res t = max ( ∣ I 1 ∣ , ∣ I 2 ∣ ) [ Restraint Current ] Dual-Slope Operating Characteristic:
- I_diff (Operating Current) ^
- | / Slope 2 (50% - 80%)
- | / (Severe CT Saturation Region)
- | /
- | Slope 1 /
- | (20% - 40%) /
- I_pickup ---- |----.--------o (Break Point I_BP)
- | / |
- | / TRIP | BLOCK (Restraint Region)
- | / |
- +-------------+---------------------> I_rest (Restraint)
- I_BP
Slope 1 Region ( I r e s t < I B P I_{rest} < I_{BP} I res t < I BP ): Set low ( 20 % − 35 % 20\% - 35\% 20% − 35% ) to provide high sensitivity for high-impedance internal faults while accommodating minor CT ratio mismatch and transformer LTC tap excursions (typically ± 10 % \pm 10\% ± 10% ).
Slope 2 Region ( I r e s t ≥ I B P I_{rest} \ge I_{BP} I res t ≥ I BP ): Set steep ( 50 % − 80 % 50\% - 80\% 50% − 80% ) to prevent false tripping during heavy through-faults where severe DC offset causes CT core saturation and large false differential currents.
Transformer Differential Protection (87T) Challenges
Transformer differential protection requires four critical compensations:
Voltage & Current Ratio Matching: CT ratios must be balanced so that secondary currents equal each other at rated MVA: I s e c 1 ≈ I s e c 2 I_{sec1} \approx I_{sec2} I sec 1 ≈ I sec 2 .
Phase Angle Displacement: A Delta-Wye transformer introduces a 30 ∘ 30^\circ 3 0 ∘ phase shift ( { D A B , Y } = 30 ∘ \{DAB, Y\} = 30^\circ { D A B , Y } = 3 0 ∘ lag). Legacy electromechanical relays used Delta-connected CTs on the Wye winding and Wye-connected CTs on the Delta winding to cancel the shift. Modern microprocessor relays use Wye-Wye CTs everywhere and execute numerical matrix phase-angle compensation internally.
Zero-Sequence Filtering: External ground faults on the Wye-grounded side create zero-sequence current I 0 I_0 I 0 that does not pass through the Delta winding, producing a false differential current. Numerical algorithms filter out zero-sequence currents ( I a ′ = I a − I 0 I_{a}' = I_a - I_0 I a ′ = I a − I 0 ).
Magnetizing Inrush & Overexcitation Restraint:
Magnetizing Inrush (2nd Harmonic): Energizing a transformer creates high, unipolar inrush currents ( 8 − 12 × F L A 8-12 \times FLA 8 − 12 × F L A ) rich in second harmonic content. Relays block tripping if I 2 n d I f u n d a m e n t a l ≥ 15 % \frac{I_{2nd}}{I_{fundamental}} \ge 15\% I f u n d am e n t a l I 2 n d ≥ 15% .
Overexcitation (5th Harmonic): System overvoltage or low frequency ( V / H z V/Hz V / Hz ) drives core saturation, generating fifth harmonic currents. Relays block or alarm if I 5 t h I f u n d a m e n t a l ≥ 30 % \frac{I_{5th}}{I_{fundamental}} \ge 30\% I f u n d am e n t a l I 5 t h ≥ 30% .
3. Distance Protection (ANSI 21)
Distance relays measure the ratio of local voltage to local current to calculate the apparent positive-sequence impedance from the relay terminal to the fault point: Z a p p = V r e l a y I r e l a y = z l i n e ⋅ d f a u l t [ Ω ] \mathbf{Z}_{app} = \frac{\mathbf{V}_{relay}}{\mathbf{I}_{relay}} = z_{line} \cdot d_{fault} \quad [\Omega] Z a pp = I re l a y V re l a y = z l in e ⋅ d f a u lt [ Ω ]
Since transmission line impedance is strictly proportional to physical length ( z l i n e = r + j x Ω / mile z_{line} = r + jx \; \Omega/\text{mile} z l in e = r + j x Ω/ mile ), the apparent impedance directly indicates the distance to the fault. Complex R-X Impedance Plane and Mho Operating Characteristic:
- +jX (Reactance) ^
- | Zone 3 Reach (100% Line 1 + 120% Line 2, t3 = 0.8s)
| .-----------------------------.
| / Zone 2 Reach (120% Line 1, t2 = 0.35s)
| / .---------------------.
- | / / Zone 1 Reach \
- | / / (80-85% Line 1, t1=0) \
| | | .-------------.
- Line Angle Theta ->| | | / \
- . - - - - -|-+--|--o-----------------o
- / | | | \ /
- / | | | `-------------'
- / | \ \
- / | \ `---------------------'
- / | \ /
- ------o----------------+------------------------------------> +R (Resistance)
- Relay Location (0,0) | `-----------------------------'
- |
- Stepped Distance Zones of Protection
Zone Reach Coverage Operating Time Purpose & Design Rationale
Zone 1 80 % − 85 % 80\% - 85\% 80% − 85% of protected line ( Z L Z_L Z L ) Instantaneous ( t 1 = 0 s t_1 = 0\text{ s} t 1 = 0 s , < 30 ms <30\text{ ms} < 30 ms ) High-speed primary protection for the line interior. Never set to 100 % 100\% 100% to prevent overreaching past the remote bus due to CT/PT transient errors, line parameter errors, and DC offset.
Zone 2 120 % − 150 % 120\% - 150\% 120% − 150% of protected line ( Z L Z_L Z L ) Time-Delayed ( t 2 = 0.30 − 0.40 s t_2 = 0.30 - 0.40\text{ s} t 2 = 0.30 − 0.40 s ) Covers the remaining 15 − 20 % 15-20\% 15 − 20% of the line and provides backup for the remote substation bus. Time delay coordinates with adjacent line Zone 1 clearing.
Zone 3 100 % Z L + 120 % − 150 % 100\% Z_L + 120\% - 150\% 100% Z L + 120% − 150% of longest adjacent line Time-Delayed ( t 3 = 0.60 − 1.00 s t_3 = 0.60 - 1.00\text{ s} t 3 = 0.60 − 1.00 s ) Full remote backup protection for the entire adjacent transmission line and substation.
Pilot Teleprotection Communication Schemes
To achieve 100 % 100\% 100% instantaneous clearing across the entire line length without waiting for Zone 2 time delays, relays at both line terminals exchange logic signals over fiber optic, power line carrier (PLC), or microwave channels:
Permissive Overreaching Transfer Trip (POTT): Both ends set Zone 2 (overreaching, > 100 % >100\% > 100% ). If terminal A sees an in-zone fault, it sends a permissive key to terminal B. Terminal B trips instantaneously only if it simultaneously senses a forward Zone 2 fault and receives the permission signal.
Directional Comparison Blocking (DCB): Relays look reverse into their own system. If terminal B sees a reverse external fault, it immediately transmits a high-speed BLOCK signal to terminal A to prevent terminal A's overreaching Zone 2 element from tripping.
Line Current Differential (87L): Direct digital exchange of synchronized current phasors via fiber-optic communication. Enforces strict unit differential protection without impedance reach limitations.
- 4. Voltage, Frequency & Auxiliary Relaying
- Undervoltage Protection (ANSI 27)
Motor Stall Protection: Severe voltage depressions ( V < 70 − 80 % V < 70-80\% V < 70 − 80% ) cause induction motors to decelerate toward high-current stall conditions. ANSI 27 trips feeder breakers or unlatches contactors.
Under-Voltage Load Shedding (UVLS): Deployed across transmission load pockets experiencing reactive power deficits to prevent catastrophic system voltage collapse.
Frequency Protection (ANSI 81U / 81O)
Operating Dynamic: System frequency reflects active power balance: d f d t = f 0 2 H ( P g e n − P l o a d ) \frac{df}{dt} = \frac{f_0}{2H} (P_{gen} - P_{load}) d t df = 2 H f 0 ( P g e n − P l o a d ) . Sudden loss of generation causes system frequency to plunge.
NERC Under-Frequency Load Shedding (UFLS): Regional entities mandate stepped automatic customer load shedding to arrest frequency decline:
Stage 1: 59.5 Hz 59.5\text{ Hz} 59.5 Hz , drop 10 % 10\% 10% total system load.
Stage 2: 59.1 Hz 59.1\text{ Hz} 59.1 Hz , drop additional 10 % 10\% 10% load.
Stage 3: 58.7 Hz 58.7\text{ Hz} 58.7 Hz , drop additional 10 % 10\% 10% load.
- 5. Comprehensive Worked Calculations
- Part A: Dual-Slope Transformer Differential (87T) Evaluation
A 30 MVA 30\text{ MVA} 30 MVA , 115 kV / 13.8 kV 115\text{ kV} / 13.8\text{ kV} 115 kV /13.8 kV Delta-Wye transformer has:
High-Voltage CT Ratio: 200 : 5 A 200:5\text{ A} 200 : 5 A ( C T R 1 = 40 CTR_1 = 40 CT R 1 = 40 )
Low-Voltage CT Ratio: 1 , 500 : 5 A 1,500:5\text{ A} 1 , 500 : 5 A ( C T R 2 = 300 CTR_2 = 300 CT R 2 = 300 )
Differential Relay Settings: I p i c k u p = 0.30 A sec I_{pickup} = 0.30\text{ A sec} I p i c k u p = 0.30 A sec , Slope 1 = 30 % \text{Slope 1} = 30\% Slope 1 = 30% , I B P = 2.0 A sec I_{BP} = 2.0\text{ A sec} I BP = 2.0 A sec , Slope 2 = 60 % \text{Slope 2} = 60\% Slope 2 = 60% .
Restraint current formulation: I r e s t = ∣ I 1 , s e c ∣ + ∣ I 2 , s e c ∣ 2 I_{rest} = \frac{|I_{1,sec}| + |I_{2,sec}|}{2} I res t = 2 ∣ I 1 , sec ∣ + ∣ I 2 , sec ∣ .
Calculate:
Full-load primary and secondary currents on HV and LV sides.
Relay tap compensation multipliers ( C T C CTC CTC ) required to balance secondary currents.
Differential current I d i f f I_{diff} I d i ff and restraint current I r e s t I_{rest} I res t during an external through-fault producing I H V , p r i = 1 , 800 A I_{HV,pri} = 1,800\text{ A} I H V , p r i = 1 , 800 A and a 10 % 10\% 10% CT saturation error on the LV side ( I L V , s e c = 0.90 × I b a l a n c e d I_{LV,sec} = 0.90 \times I_{balanced} I L V , sec = 0.90 × I ba l an ce d ). Determine if the relay restrains properly. ============================== STEP-BY-STEP SOLUTION ==============================
Step 1: Compute Rated Full-Load Currents
HV Full-Load Primary Current:
I_FLA,HV = S / (sqrt(3) * V_HV) = 30,000,000 / (sqrt(3) * 115,000) = 150.61 A pri
LV Full-Load Primary Current:
I_FLA,LV = S / (sqrt(3) * V_LV) = 30,000,000 / (sqrt(3) * 13,800) = 1,255.1 A pri
Secondary Currents at Rated Load:
- I_sec,HV = 150.61 A / (200 / 5) = 150.61 / 40 = 3.765 A sec
- I_sec,LV = 1,255.1 A / (1500 / 5) = 1,255.1 / 300 = 4.184 A sec
Step 2: Establish Digital Relay Tap Balancing (CTC Factors)
To equalize secondary currents, define matching factors:
Tap_HV = 3.765 A, Tap_LV = 4.184 A
Normalized per-unit secondary current = 1.0 pu at rated load for both sides.
- Step 3: Evaluate External Through-Fault with 10% CT Saturation Error
- HV Through-Fault Current: I_fault,HV = 1,800 A pri (11.95x rated FLA)
- Ideal LV Through-Fault Current: I_fault,LV = 1,800 * (115 / 13.8) = 15,000 A pri
Secondary Currents entering relay:
- I_1 = 1,800 A / 40 = 45.0 A sec
- Normalized I_1,pu = 45.0 / 3.765 = 11.952 pu
With 10% saturation error on LV side:
Normalized I_2,pu = 0.90 * 11.952 pu = 10.757 pu
Compute Differential and Restraint Currents in per-unit:
- I_diff = |I_1,pu - I_2,pu| = |11.952 - 10.757| = 1.195 pu
- I_rest = (I_1,pu + I_2,pu) / 2 = (11.952 + 10.757) / 2 = 11.355 pu
Step 4: Verify Relay Restraint Threshold
Since I_rest = 11.355 pu > I_BP (where I_BP = 2.0 / 3.765 = 0.531 pu):
- Operating Threshold I_diff,trip = I_pickup + Slope 1 * I_BP + Slope 2 * (I_rest - I_BP)
- Let base threshold = Slope 2 * I_rest = 0.60 * 11.355 = 6.813 pu
Compare Operating vs Trip Threshold:
- Actual I_diff = 1.195 pu
- Required Trip I_diff = 6.813 pu
Since 1.195 pu << 6.813 pu, the relay RESTRAINS (Does NOT false trip!).
- ===================================================================================
- Part B: Transmission Line Distance (ANSI 21) Mho Reach Sizing
A 230 kV 230\text{ kV} 230 kV , 60 Hz 60\text{ Hz} 60 Hz , 40 mile 40\text{ mile} 40 mile overhead transmission line connects Substation A to Substation B. An adjacent line of 30 miles 30\text{ miles} 30 miles extends from Substation B to Substation C.
Line positive-sequence impedance: z 1 = 0.12 + j 0.68 Ω / mile \mathbf{z}_1 = 0.12 + j0.68\; \Omega/\text{mile} z 1 = 0.12 + j 0.68 Ω/ mile
C T R = 1200 : 5 = 240 CTR = 1200:5 = 240 CTR = 1200 : 5 = 240 , P T R = 230 , 000 : 115 = 2000 PTR = 230,000:115 = 2000 PTR = 230 , 000 : 115 = 2000
Calculate:
Total primary impedance Z A B , p r i \mathbf{Z}_{AB,pri} Z A B , p r i .
Secondary impedance scale factor k Z = C T R P T R k_Z = \frac{CTR}{PTR} k Z = PTR CTR .
Zone 1 reach in primary and secondary ohms ( 85 % 85\% 85% reach).
Zone 2 reach in primary and secondary ohms ( 125 % 125\% 125% reach). ============================== STEP-BY-STEP SOLUTION ==============================
- Step 1: Compute Total Primary Line Impedance (Z_AB)
- Length l_AB = 40 miles
- Z_AB,pri = (0.12 + j0.68) * 40 = 4.80 + j27.20 ohms = 27.620 /_ 79.99 deg ohms pri
- Step 2: Determine Impedance Conversion Factor (k_Z)
- k_Z = Z_sec / Z_pri = CTR / PTR = 240 / 2,000 = 0.120
- Z_AB,sec = Z_AB,pri * 0.120 = (4.80 + j27.20) * 0.120
- = 0.576 + j3.264 ohms = 3.314 /_ 79.99 deg ohms sec
Step 3: Calculate Zone 1 Mho Reach Setting (85% Reach, t1 = 0 s)
Primary Reach:
Z_Z1,pri = 0.85 * Z_AB,pri = 0.85 * 27.620 ohms = 23.477 ohms pri
Secondary Reach Setting:
Z_Z1,sec = 0.85 * Z_AB,sec = 0.85 * 3.314 ohms = 2.817 ohms sec
Step 4: Calculate Zone 2 Mho Reach Setting (125% Reach, t2 = 0.35 s)
Primary Reach:
Z_Z2,pri = 1.25 * Z_AB,pri = 1.25 * 27.620 ohms = 34.525 ohms pri
Secondary Reach Setting:
- Z_Z2,sec = 1.25 * Z_AB,sec = 1.25 * 3.314 ohms = 4.143 ohms sec
- ===================================================================================
- 6. Common Exam Traps & Strategic Pitfalls
Setting Distance Zone 1 to 100%: Attempting to protect 100 % 100\% 100% of the transmission line with Zone 1 instantaneous tripping. Transient overreach caused by DC offset, CVT transient response, and line data errors will cause the relay to trip instantaneously on out-of-zone faults past the remote bus.
Overlooking Phase Angle Compensation in Delta-Wye 87T Relays: Failing to recognize that a Delta-Wye transformer shifts currents by 30 ∘ 30^\circ 3 0 ∘ . If not compensated numerically or via CT connections, full load current creates a 52 % 52\% 52% false differential current ( ∣ 1 − 1 ∠ 30 ∘ ∣ = 0.518 |1 - 1\angle 30^\circ| = 0.518 ∣1 − 1∠3 0 ∘ ∣ = 0.518 ), causing instant trip upon energization.
Inverting the Impedance Ratio ( k Z k_Z k Z ): Multiplying primary ohms by P T R / C T R PTR/CTR PTR / CTR instead of C T R / P T R CTR/PTR CTR / PTR . Because secondary voltage is small ( 1 / 2000 1/2000 1/2000 ) and secondary current is moderate ( 1 / 240 1/240 1/240 ), secondary impedance is always much smaller than primary impedance: Z s e c = Z p r i × ( C T R / P T R ) Z_{sec} = Z_{pri} \times (CTR/PTR) Z sec = Z p r i × ( CTR / PTR ) .
Confusing 2nd Harmonic Inrush with 5th Harmonic Overexcitation: 2nd harmonic ( 120 Hz 120\text{ Hz} 120 Hz ) indicates magnetizing inrush during transformer energization; 5th harmonic ( 300 Hz 300\text{ Hz} 300 Hz ) indicates severe core overfluxing ( V / H z V/Hz V / Hz ) from overvoltage.