Study guide
10.3 Synchronous Machines (Operating Principles, Power-Angle Curves & V-Curves)
PE Electrical and Computer: Power Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview, Strategy & Reference Handbook
1.1 PE Power Exam Format, CBT Navigation & Reference Handbook 1.2 2026 Reference Standards (NEC 2020, NFPA 70E-2021, NESC) & Scoring Mechanics 1.3 CBT Pacing, AIT Question Formats & Formula Sheet Mastery
2 Chapter 2: Measurement, Metering & Field Testing
2.1 Current Transformers (CTs), Potential Transformers (PTs) & Meter Connections 2.2 Instrument Transformer Burdens, Saturation Curves & Ratio Correction Factors 2.3 Insulation Resistance Testing (Megger, Polarization Index, Dielectric Absorption) 2.4 Ground Resistance Testing (Fall-of-Potential 62% Rule & Clamp-on Methods)
3 Chapter 3: General Applications — Grounding & Surge Protection
3.1 Substation Ground Grid Design & IEEE 80 Touch/Step Voltage Criteria 3.2 Lightning Protection Systems & Rolling Sphere / Cone of Protection Methods 3.3 Surge Protective Devices (SPDs) & Voltage Surge Arresters
4 Chapter 4: General Applications — Lighting & Energy Management
4.1 Illumination Engineering & Zonal Cavity / Lumen Method Calculations 4.2 Energy Management, Demand Factors & Load Factor Calculations 4.3 Economic Dispatch, Energy Efficiency & Load Profile Analysis
5 Chapter 5: Electrical Safety & NFPA Standards
5.1 NFPA 70E Shock Protection, Approach Boundaries & PPE Requirements 5.2 Arc-Flash Hazard Analysis & IEEE 1584-2018 Incident Energy Calculations 5.3 Hazardous (Classified) Locations (Class I, II, III & Division/Zone Systems) 5.4 Special Occupancies & Critical Systems (NEC Articles 517 Health Care, 700/701/702 Emergency)
6 Chapter 6: NEC Wiring Methods & Installation Requirements
6.1 Conductor Ampacity & NEC Table 310.16 Derating Adjustments 6.2 Raceway Fill, Box Sizing & Conduit Bending Calculations (Chapter 9 Tables) 6.3 Equipment Grounding Conductors & Grounding Electrode Sizing (NEC Article 250)
7 Chapter 7: Circuit Analysis — Fundamentals & Symmetrical Components
7.1 DC & Single-Phase AC Network Analysis (Thevenin, Norton, Superposition) 7.2 Balanced Three-Phase Circuits (Wye-Delta Configurations & Power Formulas) 7.3 Symmetrical Components & Fortescue Sequence Transformation Matrices 7.4 Sequence Impedances & Positive, Negative, Zero Sequence Network Construction
8 Chapter 8: Circuit Analysis — Per-Unit & Phasor Analysis
8.1 Per-Unit System Fundamentals & Base Conversion Formulas 8.2 Three-Phase Per-Unit Network Modeling & Equipment Impedance Conversion 8.3 Phasor Diagrams, Complex Power & Power Triangle Relationships
9 Chapter 9: Power Electronics & Logic Controls
9.1 Power Electronic Converters (Rectifiers, Inverters & DC-DC Topologies) 9.2 Inverter-Based Resources (IBRs), Grid-Forming & Grid-Following Controls 9.3 Variable Frequency Drives (VFDs), PWM Operation & Harmonic Mitigation 9.4 Boolean Algebra, Logic Gates, De Morgan's Laws & Ladder Logic Control Diagrams
10 Chapter 10: Rotating Machines — Induction & Synchronous
10.1 Three-Phase Induction Motors (Equivalent Circuits, Slip & Performance) 10.2 Induction Motor Torque-Speed Characteristics & NEMA Design Classes 10.3 Synchronous Machines (Operating Principles, Power-Angle Curves & V-Curves) 10.4 Motor Starting Methods (DOL, Wye-Delta, Autotransformer, Soft-Start) & Voltage Dip
11 Chapter 11: Electric Power Devices & Renewable Energy
11.1 Power Transformers (Equivalent Circuits, Efficiency & Voltage Regulation) 11.2 Power Factor Correction Capacitors & Shunt Bank Sizing 11.3 Battery Energy Storage Systems (BESS) & Ultracapacitors 11.4 Renewable Energy Generation (Solar Photovoltaic Systems & Wind Turbines)
12 Chapter 12: Transmission & Distribution — Steady-State & Power Quality
12.1 Transmission Line Modeling, Voltage Drop & Conductor Sizing 12.2 Voltage Regulation, Reactive Power Support & Tap-Changer Controls 12.3 Power Quality, Harmonics, THD & IEEE 519 Compliance 12.4 Power Flow Analysis & System Stability (Steady-State, Transient & Swing Equation)
13 Chapter 13: Transmission & Distribution — Fault Analysis & Transformer Shifts
13.1 Symmetrical Three-Phase Bolted Fault Calculations 13.2 Unsymmetrical Fault Analysis (SLG, L-L, DLG Fault Calculations) 13.3 Transformer Connection Types, Zero-Sequence Paths & 30-Degree Phase Shifts
14 Chapter 14: Protection Systems & Device Coordination
14.1 Overcurrent Protection & Time-Current Characteristic (TCC) Curves 14.2 Protective Relaying Schemes (Differential 87, Distance 21, Undervoltage 27) 14.3 Circuit Breakers, Fuses & Automatic Reclosers 14.4 Protection Coordination, Selectivity & Coordination Time Intervals (CTI)
10.3 Synchronous Machines (Operating Principles, Power-Angle Curves & V-Curves)
Key Takeaways Explain This Topic AI
Synchronous machines operate at fixed synchronous speed ( n s = 120 f / P n_s = 120f/P n s = 120 f / P ), where mechanical power is governed by the power angle δ \delta δ and reactive power is independently controlled by DC field excitation current ( I f I_f I f ).
For a cylindrical-rotor machine with negligible stator resistance, active power is P = 3 E f V t X s sin δ P = \frac{3 E_f V_t}{X_s} \sin \delta P = X s 3 E f V t sin δ with theoretical steady-state pull-out limit at δ = 90 ∘ \delta = 90^\circ δ = 9 0 ∘ , while reactive power is Q = 3 E f V t X s cos δ − 3 V t 2 X s Q = \frac{3 E_f V_t}{X_s} \cos \delta - \frac{3 V_t^2}{X_s} Q = X s 3 E f V t cos δ − X s 3 V t 2 .
Overexcited synchronous machines ( E f cos δ > V t E_f \cos \delta > V_t E f cos δ > V t ) supply reactive power to the system (lagging current for generators, leading current for motors), whereas underexcited machines absorb reactive power.
A Synchronous Condenser is an unloaded synchronous motor ( δ ≈ 0 ∘ \delta \approx 0^\circ δ ≈ 0 ∘ ) operated in the overexcited regime to provide dynamically adjustable leading VARs for power factor correction and grid voltage stabilization.
V-Curves illustrate armature current I a I_a I a versus field current I f I_f I f for constant active power contours, reaching minimum I a I_a I a at unity power factor ( PF = 1.0 \text{PF} = 1.0 PF = 1.0 ).
Last updated: August 2026
10.3 Synchronous Machines (Operating Principles, Power-Angle Curves & V-Curves)
Synchronous machines are the primary source of bulk electrical power generation worldwide and serve as specialized high-horsepower industrial drives and dynamic reactive power compensators. Unlike induction machines, synchronous machines operate at strictly synchronous speed ( n s = 120 f / P n_s = 120f/P n s = 120 f / P ) under steady-state conditions, with real power exchange mediated by the rotor power angle ( δ \delta δ ) and reactive power exchange controlled by DC field excitation ( I f I_f I f ).
1. Machine Construction & Rotor Topologies
A synchronous machine consists of a stationary 3-phase armature winding on the stator and a DC-excited field winding on the rotor.
Rotor Topologies
Cylindrical (Round) Rotor :
Uniform air-gap geometry.
High-speed 2-pole or 4-pole machines ( 1 , 800 rpm 1,800\text{ rpm} 1 , 800 rpm or 3 , 600 rpm 3,600\text{ rpm} 3 , 600 rpm at 60 Hz 60\text{ Hz} 60 Hz ).
Driven by steam or gas turbines (turbogenerators).
Characterized by a single per-phase synchronous reactance: X s = X a l + X a r X_s = X_{al} + X_{ar} X s = X a l + X a r (leakage reactance plus armature reaction reactance).
Salient-Pole Rotor :
Non-uniform air gap with projecting (salient) pole shoes.
Low-speed multipole machines ( 72 rpm 72\text{ rpm} 72 rpm to 900 rpm 900\text{ rpm} 900 rpm , e.g., 12 to 72 poles).
Driven by hydro turbines or large diesel/gas reciprocating engines.
Analyzed using Blondel's Two-Axis Theory : Direct-axis synchronous reactance ( X d X_d X d ) along the magnetic pole axis, and Quadrature-axis synchronous reactance ( X q X_q X q ) along the interpolar axis ( X d > X q X_d > X_q X d > X q ).
DC Field Excitation Systems
The rotor DC field is supplied either through stationary carbon brushes riding on rotating slip rings or via modern brushless exciters (an inverted alternator with shaft-mounted rotating diode rectifiers). Adjusting the field current I f I_f I f adjusts the internal generated excitation voltage magnitude ( E f E_f E f ) along the open-circuit saturation curve.
2. Per-Phase Equivalent Circuit and Phasor Conventions
For a cylindrical-rotor machine on a per-phase (wye) basis:
V t V_t V t : Terminal phase voltage ( V t = V L L / 3 ∠ 0 ∘ V_t = V_{LL}/\sqrt{3} \angle 0^\circ V t = V LL / 3 ∠ 0 ∘ ).
E f E_f E f : Internal generated excitation voltage ( E f ∠ δ E_f \angle \delta E f ∠ δ ).
I a I_a I a : Armature phase current ( I a ∠ θ I_a \angle \theta I a ∠ θ ).
R a R_a R a : Stator armature winding resistance per phase (often neglected in power calculations, R a ≈ 0 R_a \approx 0 R a ≈ 0 ).
X s X_s X s : Synchronous reactance per phase ( X s = X l + X a X_s = X_l + X_a X s = X l + X a ).
Phasor Equations
Synchronous Generator Mode (current flowing out of machine to grid): E f = V t + I a ( R a + j X s ) ≈ V t + j I a X s \mathbf{E}_f = \mathbf{V}_t + \mathbf{I}_a (R_a + jX_s) \approx \mathbf{V}_t + j\mathbf{I}_a X_s E f = V t + I a ( R a + j X s ) ≈ V t + j I a X s
Power angle δ > 0 ∘ \delta > 0^\circ δ > 0 ∘ ( E f \mathbf{E}_f E f leads V t \mathbf{V}_t V t in the direction of rotation).
Synchronous Motor Mode (current flowing into machine from grid): V t = E f + I a ( R a + j X s ) ≈ E f + j I a X s ⟹ E f = V t − j I a X s \mathbf{V}_t = \mathbf{E}_f + \mathbf{I}_a (R_a + jX_s) \approx \mathbf{E}_f + j\mathbf{I}_a X_s \implies \mathbf{E}_f = \mathbf{V}_t - j\mathbf{I}_a X_s V t = E f + I a ( R a + j X s ) ≈ E f + j I a X s ⟹ E f = V t − j I a X s
Power angle δ < 0 ∘ \delta < 0^\circ δ < 0 ∘ ( E f \mathbf{E}_f E f lags V t \mathbf{V}_t V t ).
3. Power-Angle Equations and Stability Limits
Neglecting armature resistance ( R a = 0 R_a = 0 R a = 0 ), the per-phase complex power delivered by a synchronous generator to an infinite bus is: I a = E f ∠ δ − V t ∠ 0 ∘ j X s = E f sin δ X s − j ( E f cos δ − V t X s ) \mathbf{I}_a = \frac{E_f \angle \delta - V_t \angle 0^\circ}{jX_s} = \frac{E_f \sin \delta}{X_s} - j \left( \frac{E_f \cos \delta - V_t}{X_s} \right) I a = j X s E f ∠ δ − V t ∠ 0 ∘ = X s E f sin δ − j ( X s E f cos δ − V t ) S 3 ϕ = 3 V t I a ∗ = 3 V t [ E f sin δ X s + j ( E f cos δ − V t X s ) ] \mathbf{S}_{3\phi} = 3 \mathbf{V}_t \mathbf{I}_a^* = 3 V_t \left[ \frac{E_f \sin \delta}{X_s} + j \left( \frac{E_f \cos \delta - V_t}{X_s} \right) \right] S 3 ϕ = 3 V t I a ∗ = 3 V t [ X s E f sin δ + j ( X s E f cos δ − V t ) ]
Active and Reactive Power Formulas P 3 ϕ = 3 E f V t X s sin δ = E f , L L V t , L L X s sin δ [ W ] P_{3\phi} = \frac{3 E_f V_t}{X_s} \sin \delta = \frac{E_{f,LL} V_{t,LL}}{X_s} \sin \delta \quad [\text{W}] P 3 ϕ = X s 3 E f V t sin δ = X s E f , LL V t , LL sin δ [ W ] Q 3 ϕ = 3 E f V t X s cos δ − 3 V t 2 X s [ VAR ] Q_{3\phi} = \frac{3 E_f V_t}{X_s} \cos \delta - \frac{3 V_t^2}{X_s} \quad [\text{VAR}] Q 3 ϕ = X s 3 E f V t cos δ − X s 3 V t 2 [ VAR ]
where E f E_f E f and $V_t in the three-phase formulas are per-phase line-to-neutral magnitudes (or line-to-line magnitudes if the factor of 3 is omitted).
Salient-Pole Power Equation (Reluctance Torque)
In salient-pole machines, the saliency ( X d ≠ X q X_d \neq X_q X d = X q ) creates a reluctance power component that operates independently of field excitation: P 3 ϕ = 3 E f V t X d sin δ ⏟ Field Excitation Power + 3 V t 2 2 ( 1 X q − 1 X d ) sin 2 δ ⏟ Reluctance Power P_{3\phi} = \underbrace{\frac{3 E_f V_t}{X_d} \sin \delta}_{\text{Field Excitation Power}} + \underbrace{\frac{3 V_t^2}{2} \left( \frac{1}{X_q} - \frac{1}{X_d} \right) \sin 2\delta}_{\text{Reluctance Power}} P 3 ϕ = Field Excitation Power X d 3 E f V t sin δ + Reluctance Power 2 3 V t 2 ( X q 1 − X d 1 ) sin 2 δ
Steady-State Stability Limit (Pull-Out Power)
Cylindrical Machine : Maximum theoretical power occurs at δ = 90 ∘ \delta = 90^\circ δ = 9 0 ∘ : P m a x , 3 ϕ = 3 E f V t X s P_{max,3\phi} = \frac{3 E_f V_t}{X_s} P ma x , 3 ϕ = X s 3 E f V t If mechanical turbine power exceeds P m a x P_{max} P ma x (or if electrical load increases such that δ > 90 ∘ \delta > 90^\circ δ > 9 0 ∘ ), the synchronizing power coefficient d P d δ \frac{dP}{d\delta} d δ d P becomes negative, causing the generator to lose synchronism and "slip poles."
Salient-Pole Machine : Peak power occurs at δ < 90 ∘ \delta < 90^\circ δ < 9 0 ∘ (typically δ ≈ 65 ∘ − 75 ∘ \delta \approx 65^\circ - 75^\circ δ ≈ 6 5 ∘ − 7 5 ∘ ) due to the second-harmonic reluctance term ( sin 2 δ \sin 2\delta sin 2 δ ).
4. Excitation Regimes, Reactive Power Control & Synchronous Condensers
By adjusting field current I f I_f I f (and hence E f E_f E f ), the synchronous machine can supply or absorb reactive power independently of active power delivery:
Operating Regime Excitation Condition Generator Behavior Motor Behavior Reactive Power ( Q Q Q )
Overexcited E f cos δ > V t E_f \cos \delta > V_t E f cos δ > V t Delivers lagging current (supplies + Q +Q + Q to grid) Draws leading current (supplies + Q +Q + Q to bus) + Q +Q + Q exported to grid (boosts bus voltage)
Normal Excitation E f cos δ = V t E_f \cos \delta = V_t E f cos δ = V t Unity power factor ( PF = 1.0 \text{PF} = 1.0 PF = 1.0 ) Unity power factor ( PF = 1.0 \text{PF} = 1.0 PF = 1.0 ) Q = 0 Q = 0 Q = 0
Underexcited E f cos δ < V t E_f \cos \delta < V_t E f cos δ < V t Delivers leading current (absorbs − Q -Q − Q from grid) Draws lagging current (absorbs − Q -Q − Q from bus) − Q -Q − Q imported from grid (lowers bus voltage)
Synchronous Condenser Operation
A Synchronous Condenser is a synchronous machine connected to the electrical grid with no mechanical load on its shaft ( P s h a f t ≈ 0 ⟹ δ ≈ 0 ∘ P_{shaft} \approx 0 \implies \delta \approx 0^\circ P s ha f t ≈ 0 ⟹ δ ≈ 0 ∘ ): Q 3 ϕ ≈ 3 V t ( E f − V t ) X s Q_{3\phi} \approx \frac{3 V_t (E_f - V_t)}{X_s} Q 3 ϕ ≈ X s 3 V t ( E f − V t )
When overexcited ( E f > V t E_f > V_t E f > V t ), it supplies variable capacitive VARs to the substation bus, supporting system voltage during heavy transmission loading.
When underexcited ( E f < V t E_f < V_t E f < V t ), it acts as an adjustable shunt reactor, absorbing inductive VARs during light load / Ferranti effect conditions.
- 5. Synchronous Machine V-Curves & Generator Capability Limits
- V-Curves ( I a I_a I a vs. I f I_f I f )
Plotting armature current I a I_a I a against field current I f I_f I f for constant mechanical power outputs generates a family of V-shaped curves:
The bottom vertex of each V-curve corresponds to unity power factor where armature current I a I_a I a is minimized for that MW level.
Operating to the right of the vertex represents the overexcited regime (lagging PF for generator, leading PF for motor).
Operating to the left of the vertex represents the underexcited regime (leading PF for generator, lagging PF for motor).
Generator Capability Curve (P-Q Operating Envelope)
A synchronous generator's safe operating region in the P-Q plane is constrained by three physical limits:
Armature Current Limit (Stator Heating) : A circle centered at ( P = 0 , Q = 0 ) (P=0, Q=0) ( P = 0 , Q = 0 ) with radius equal to rated MVA: P 2 + Q 2 ≤ S r a t e d 2 P^2 + Q^2 \le S_{rated}^2 P 2 + Q 2 ≤ S r a t e d 2 .
Field Current Limit (Rotor Heating) : A circle centered at ( 0 , − 3 V t 2 / X s ) (0, -3V_t^2/X_s) ( 0 , − 3 V t 2 / X s ) with radius 3 E f , m a x V t X s \frac{3 E_{f,max} V_t}{X_s} X s 3 E f , ma x V t . Limits maximum overexcited lagging VAR output.
Stator End-Core Heating & Stability Limit : Limits maximum underexcited leading VAR absorption to prevent localized eddy-current heating in stator core laminations and preserve steady-state transient stability margins.
- 6. Worked Numeric Example: Synchronous Generator Excitation & Power Angle
- Problem Statement
A 3-phase, 25 MVA, 13.8 kV, 60 Hz, Y-connected cylindrical-rotor synchronous generator has a synchronous reactance of X s = 6.4 Ω X_s = 6.4\,\Omega X s = 6.4 Ω per phase and negligible armature resistance ( R a ≈ 0 R_a \approx 0 R a ≈ 0 ). The generator is connected to an infinite bus operating at rated 13.8 kV and delivers 20.0 MW 20.0\text{ MW} 20.0 MW at 0.80 0.80 0.80 power factor lagging.
Calculate:
Stator terminal phase voltage V t V_t V t and armature current phasor I a \mathbf{I}_a I a .
Internal excitation voltage phasor E f \mathbf{E}_f E f (magnitude in line-to-neutral and line-to-line, and power angle δ \delta δ ).
Total three-phase reactive power Q 3 ϕ Q_{3\phi} Q 3 ϕ supplied by the generator.
Steady-state maximum pull-out power ( P m a x , 3 ϕ P_{max,3\phi} P ma x , 3 ϕ ) under this field excitation.
- Step-by-Step Solution
- Step 1: Terminal Voltage and Armature Current Phasors
Terminal line-to-neutral voltage: V t = 13 , 800 3 = 7 , 967.43 V ∠ 0 ∘ V_t = \frac{13,800}{\sqrt{3}} = 7,967.43\text{ V} \angle 0^\circ V t = 3 13 , 800 = 7 , 967.43 V ∠ 0 ∘
Apparent power: S 3 ϕ = P cos θ = 20.0 MW 0.80 = 25.0 MVA S_{3\phi} = \frac{P}{\cos \theta} = \frac{20.0\text{ MW}}{0.80} = 25.0\text{ MVA} S 3 ϕ = cos θ P = 0.80 20.0 MW = 25.0 MVA
Armature current magnitude: I a = S 3 ϕ 3 V L L = 25 , 000 , 000 3 × 13 , 800 = 1 , 045.92 A I_a = \frac{S_{3\phi}}{\sqrt{3} V_{LL}} = \frac{25,000,000}{\sqrt{3} \times 13,800} = 1,045.92\text{ A} I a = 3 V LL S 3 ϕ = 3 × 13 , 800 25 , 000 , 000 = 1 , 045.92 A
Power factor angle for lagging current: θ = − arccos ( 0.80 ) = − 36.87 ∘ \theta = -\arccos(0.80) = -36.87^\circ θ = − arccos ( 0.80 ) = − 36.8 7 ∘ I a = 1 , 045.92 ∠ − 36.87 ∘ A = ( 836.74 − j 627.55 ) A \mathbf{I}_a = 1,045.92 \angle -36.87^\circ\text{ A} = (836.74 - j627.55)\text{ A} I a = 1 , 045.92∠ − 36.8 7 ∘ A = ( 836.74 − j 627.55 ) A
Step 2: Internal Excitation Voltage Phasor ( E f \mathbf{E}_f E f ) E f = V t + j I a X s \mathbf{E}_f = \mathbf{V}_t + j \mathbf{I}_a X_s E f = V t + j I a X s j I a X s = j ( 836.74 − j 627.55 ) × 6.4 = j 5 , 355.14 + 4 , 016.32 = 4 , 016.32 + j 5 , 355.14 V j \mathbf{I}_a X_s = j (836.74 - j627.55) \times 6.4 = j 5,355.14 + 4,016.32 = 4,016.32 + j 5,355.14\text{ V} j I a X s = j ( 836.74 − j 627.55 ) × 6.4 = j 5 , 355.14 + 4 , 016.32 = 4 , 016.32 + j 5 , 355.14 V
Summing with V t \mathbf{V}_t V t : E f = 7 , 967.43 + 4 , 016.32 + j 5 , 355.14 = 11 , 983.75 + j 5 , 355.14 V \mathbf{E}_f = 7,967.43 + 4,016.32 + j 5,355.14 = 11,983.75 + j 5,355.14\text{ V} E f = 7 , 967.43 + 4 , 016.32 + j 5 , 355.14 = 11 , 983.75 + j 5 , 355.14 V
Converting to polar coordinates: ∣ E f ∣ = ( 11 , 983.75 ) 2 + ( 5 , 355.14 ) 2 = 143 , 610 , 264 + 28 , 677 , 525 = 172 , 287 , 789 = 13 , 125.84 V (line-to-neutral) |E_f| = \sqrt{(11,983.75)^2 + (5,355.14)^2} = \sqrt{143,610,264 + 28,677,525} = \sqrt{172,287,789} = 13,125.84\text{ V (line-to-neutral)} ∣ E f ∣ = ( 11 , 983.75 ) 2 + ( 5 , 355.14 ) 2 = 143 , 610 , 264 + 28 , 677 , 525 = 172 , 287 , 789 = 13 , 125.84 V (line-to-neutral) δ = arctan ( 5 , 355.14 11 , 983.75 ) = arctan ( 0.44686 ) = 24.08 ∘ \delta = \arctan\left(\frac{5,355.14}{11,983.75}\right) = \arctan(0.44686) = 24.08^\circ δ = arctan ( 11 , 983.75 5 , 355.14 ) = arctan ( 0.44686 ) = 24.0 8 ∘
Line-to-line excitation voltage: E f , L L = 3 × 13 , 125.84 V = 22 , 734.6 V = 22.73 kV E_{f,LL} = \sqrt{3} \times 13,125.84\text{ V} = 22,734.6\text{ V} = 22.73\text{ kV} E f , LL = 3 × 13 , 125.84 V = 22 , 734.6 V = 22.73 kV E f = 13.13 kV ∠ 24.08 ∘ \mathbf{E}_f = 13.13\text{ kV} \angle 24.08^\circ E f = 13.13 kV ∠24.0 8 ∘
Step 3: Reactive Power Supplied Q 3 ϕ = P × tan θ = 20.0 MW × tan ( 36.87 ∘ ) = 20.0 × 0.750 = 15.0 MVAR Q_{3\phi} = P \times \tan \theta = 20.0\text{ MW} \times \tan(36.87^\circ) = 20.0 \times 0.750 = 15.0\text{ MVAR} Q 3 ϕ = P × tan θ = 20.0 MW × tan ( 36.8 7 ∘ ) = 20.0 × 0.750 = 15.0 MVAR
Verification via reactive power formula: Q 3 ϕ = 3 E f V t X s cos δ − 3 V t 2 X s = 3 × 13 , 125.84 × 7 , 967.43 6.4 cos ( 24.08 ∘ ) − 3 × ( 7 , 967.43 ) 2 6.4 Q_{3\phi} = \frac{3 E_f V_t}{X_s} \cos \delta - \frac{3 V_t^2}{X_s} = \frac{3 \times 13,125.84 \times 7,967.43}{6.4} \cos(24.08^\circ) - \frac{3 \times (7,967.43)^2}{6.4} Q 3 ϕ = X s 3 E f V t cos δ − X s 3 V t 2 = 6.4 3 × 13 , 125.84 × 7 , 967.43 cos ( 24.0 8 ∘ ) − 6.4 3 × ( 7 , 967.43 ) 2 Q 3 ϕ = ( 48 , 995 , 780 × 0.91299 ) − 29 , 756 , 238 = 44 , 732 , 860 − 29 , 756 , 238 = 14 , 976 , 622 VAR ≈ 15.0 MVAR Q_{3\phi} = (48,995,780 \times 0.91299) - 29,756,238 = 44,732,860 - 29,756,238 = 14,976,622\text{ VAR} \approx 15.0\text{ MVAR} Q 3 ϕ = ( 48 , 995 , 780 × 0.91299 ) − 29 , 756 , 238 = 44 , 732 , 860 − 29 , 756 , 238 = 14 , 976 , 622 VAR ≈ 15.0 MVAR
Step 4: Maximum Pull-Out Power ( P m a x P_{max} P ma x )
Pull-out power occurs at δ = 90 ∘ \delta = 90^\circ δ = 9 0 ∘ ( sin 90 ∘ = 1.0 \sin 90^\circ = 1.0 sin 9 0 ∘ = 1.0 ): P m a x , 3 ϕ = 3 E f V t X s = 3 × 13 , 125.84 × 7 , 967.43 6.4 = 48 , 995 , 780 W = 49.0 MW P_{max,3\phi} = \frac{3 E_f V_t}{X_s} = \frac{3 \times 13,125.84 \times 7,967.43}{6.4} = 48,995,780\text{ W} = 49.0\text{ MW} P ma x , 3 ϕ = X s 3 E f V t = 6.4 3 × 13 , 125.84 × 7 , 967.43 = 48 , 995 , 780 W = 49.0 MW
7. Common Exam Traps & High-Yield Summary
Warning
Exam Trap 1: Confusing Generator vs. Motor Power Angle Signs In synchronous generators, field excitation leads terminal voltage ( δ > 0 ∘ \delta > 0^\circ δ > 0 ∘ ). In synchronous motors, mechanical shaft load retards the rotor so field excitation lags terminal voltage ( δ < 0 ∘ \delta < 0^\circ δ < 0 ∘ ).
- Warning
- Exam Trap 2: Generator vs. Motor Overexcitation Conventions
An overexcited generator supplies lagging reactive power ( + Q +Q + Q ) to the grid.
An overexcited motor operates at a leading power factor , which also supplies capacitive reactive power ( + Q +Q + Q ) to the local distribution bus.
Important
Exam Trap 3: Infinite Bus Voltage & Frequency Invariance An infinite bus has constant voltage and frequency. Increasing turbine governor mechanical input P m e c h P_{mech} P m ec h increases active power P P P and power angle δ \delta δ , but does NOT change machine speed. Increasing field current I f I_f I f increases reactive power Q Q Q and terminal voltage support, but does NOT change active power P P P .