Study guide
12.2 Voltage Regulation, Reactive Power Support & Tap-Changer Controls
PE Electrical and Computer: Power Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview, Strategy & Reference Handbook
1.1 PE Power Exam Format, CBT Navigation & Reference Handbook 1.2 2026 Reference Standards (NEC 2020, NFPA 70E-2021, NESC) & Scoring Mechanics 1.3 CBT Pacing, AIT Question Formats & Formula Sheet Mastery
2 Chapter 2: Measurement, Metering & Field Testing
2.1 Current Transformers (CTs), Potential Transformers (PTs) & Meter Connections 2.2 Instrument Transformer Burdens, Saturation Curves & Ratio Correction Factors 2.3 Insulation Resistance Testing (Megger, Polarization Index, Dielectric Absorption) 2.4 Ground Resistance Testing (Fall-of-Potential 62% Rule & Clamp-on Methods)
3 Chapter 3: General Applications — Grounding & Surge Protection
3.1 Substation Ground Grid Design & IEEE 80 Touch/Step Voltage Criteria 3.2 Lightning Protection Systems & Rolling Sphere / Cone of Protection Methods 3.3 Surge Protective Devices (SPDs) & Voltage Surge Arresters
4 Chapter 4: General Applications — Lighting & Energy Management
4.1 Illumination Engineering & Zonal Cavity / Lumen Method Calculations 4.2 Energy Management, Demand Factors & Load Factor Calculations 4.3 Economic Dispatch, Energy Efficiency & Load Profile Analysis
5 Chapter 5: Electrical Safety & NFPA Standards
5.1 NFPA 70E Shock Protection, Approach Boundaries & PPE Requirements 5.2 Arc-Flash Hazard Analysis & IEEE 1584-2018 Incident Energy Calculations 5.3 Hazardous (Classified) Locations (Class I, II, III & Division/Zone Systems) 5.4 Special Occupancies & Critical Systems (NEC Articles 517 Health Care, 700/701/702 Emergency)
6 Chapter 6: NEC Wiring Methods & Installation Requirements
6.1 Conductor Ampacity & NEC Table 310.16 Derating Adjustments 6.2 Raceway Fill, Box Sizing & Conduit Bending Calculations (Chapter 9 Tables) 6.3 Equipment Grounding Conductors & Grounding Electrode Sizing (NEC Article 250)
7 Chapter 7: Circuit Analysis — Fundamentals & Symmetrical Components
7.1 DC & Single-Phase AC Network Analysis (Thevenin, Norton, Superposition) 7.2 Balanced Three-Phase Circuits (Wye-Delta Configurations & Power Formulas) 7.3 Symmetrical Components & Fortescue Sequence Transformation Matrices 7.4 Sequence Impedances & Positive, Negative, Zero Sequence Network Construction
8 Chapter 8: Circuit Analysis — Per-Unit & Phasor Analysis
8.1 Per-Unit System Fundamentals & Base Conversion Formulas 8.2 Three-Phase Per-Unit Network Modeling & Equipment Impedance Conversion 8.3 Phasor Diagrams, Complex Power & Power Triangle Relationships
9 Chapter 9: Power Electronics & Logic Controls
9.1 Power Electronic Converters (Rectifiers, Inverters & DC-DC Topologies) 9.2 Inverter-Based Resources (IBRs), Grid-Forming & Grid-Following Controls 9.3 Variable Frequency Drives (VFDs), PWM Operation & Harmonic Mitigation 9.4 Boolean Algebra, Logic Gates, De Morgan's Laws & Ladder Logic Control Diagrams
10 Chapter 10: Rotating Machines — Induction & Synchronous
10.1 Three-Phase Induction Motors (Equivalent Circuits, Slip & Performance) 10.2 Induction Motor Torque-Speed Characteristics & NEMA Design Classes 10.3 Synchronous Machines (Operating Principles, Power-Angle Curves & V-Curves) 10.4 Motor Starting Methods (DOL, Wye-Delta, Autotransformer, Soft-Start) & Voltage Dip
11 Chapter 11: Electric Power Devices & Renewable Energy
11.1 Power Transformers (Equivalent Circuits, Efficiency & Voltage Regulation) 11.2 Power Factor Correction Capacitors & Shunt Bank Sizing 11.3 Battery Energy Storage Systems (BESS) & Ultracapacitors 11.4 Renewable Energy Generation (Solar Photovoltaic Systems & Wind Turbines)
12 Chapter 12: Transmission & Distribution — Steady-State & Power Quality
12.1 Transmission Line Modeling, Voltage Drop & Conductor Sizing 12.2 Voltage Regulation, Reactive Power Support & Tap-Changer Controls 12.3 Power Quality, Harmonics, THD & IEEE 519 Compliance 12.4 Power Flow Analysis & System Stability (Steady-State, Transient & Swing Equation)
13 Chapter 13: Transmission & Distribution — Fault Analysis & Transformer Shifts
13.1 Symmetrical Three-Phase Bolted Fault Calculations 13.2 Unsymmetrical Fault Analysis (SLG, L-L, DLG Fault Calculations) 13.3 Transformer Connection Types, Zero-Sequence Paths & 30-Degree Phase Shifts
14 Chapter 14: Protection Systems & Device Coordination
14.1 Overcurrent Protection & Time-Current Characteristic (TCC) Curves 14.2 Protective Relaying Schemes (Differential 87, Distance 21, Undervoltage 27) 14.3 Circuit Breakers, Fuses & Automatic Reclosers 14.4 Protection Coordination, Selectivity & Coordination Time Intervals (CTI)
12.2 Voltage Regulation, Reactive Power Support & Tap-Changer Controls
Key Takeaways Explain This Topic AI
The Ferranti Effect creates dangerous receiving-end overvoltages on lightly loaded or open-ended long transmission lines ( V R = V S / cos ( β l ) V_R = V_S / \cos(\beta l) V R = V S / cos ( βl ) ), mitigated by switching in shunt reactors to absorb capacitive charging VARs.
Surge Impedance Loading ( S I L = V L L 2 / Z c SIL = V_{LL}^2 / Z_c S I L = V LL 2 / Z c ) defines the natural power loading where reactive power generated by line shunt capacitance equals reactive power consumed by line series inductance ( Q C = Q L Q_C = Q_L Q C = Q L ), maintaining a flat voltage profile.
Series capacitor compensation cancels line inductive reactance ( X n e t = X L − X C X_{net} = X_L - X_C X n e t = X L − X C ), raising steady-state transfer limits ( P m a x = V 1 V 2 X L − X C P_{max} = \frac{V_1 V_2}{X_L - X_C} P ma x = X L − X C V 1 V 2 ), but introduces Subsynchronous Resonance (SSR) torsional risks.
Load Tap Changers (LTCs) provide on-load voltage adjustment across 33 steps (Neutral ± 16 \pm 16 ± 16 steps) at 5 / 8 % = 0.625 % 5/8\% = 0.625\% 5/8% = 0.625% per tap ( ± 10 % \pm 10\% ± 10% total regulation range).
Line Drop Compensator (LDC) analog or digital controls replicate feeder impedance drop ( R s e t , X s e t R_{set}, X_{set} R se t , X se t ) to hold a constant target voltage at a distant load center regardless of load current fluctuations.
Last updated: August 2026
12.2 Voltage Regulation, Reactive Power Support & Tap-Changer Controls
Executive Overview: Voltage stability and reactive power balance govern the secure operation of transmission and distribution networks. When lines are lightly loaded, distributed shunt capacitance causes receiving-end overvoltages via the Ferranti effect; under heavy loading, line inductive reactance causes severe voltage drop and limits power transfer. On the PE Power exam, candidates must master the application of reactive compensation (shunt reactors, shunt capacitors, series capacitors, FACTS) and calculate precise transformer Load Tap Changer (LTC) steps and Line Drop Compensator (LDC) settings.
- 1. Transmission Line Voltage Profiles & The Ferranti Effect
- The Ferranti Effect
When a long transmission line operates at no-load (open receiving end) or very light load, the receiving-end voltage V R V_R V R rises significantly above the sending-end voltage V S V_S V S . The line charging current flows through the distributed shunt capacitance and series inductance, creating an in-phase voltage rise along the line. Ferranti Effect Phasor Relationship (Open-Circuit Receiving End):
- I_C = j*omega*C*V_R (leads V_R by 90 deg)
- Delta_V = I_C * (j*X_L) = (j*omega*C*V_R) * (j*omega*L) = - omega^2 * L * C * V_R
- V_S = V_R + Delta_V = V_R * (1 - omega^2 * L * C / 2)
- ==> V_R > V_S
From distributed parameter line equations, with I R = 0 \mathbf{I}_R = 0 I R = 0 : V S = V R cosh ( γ l ) \mathbf{V}_S = \mathbf{V}_R \cosh(\boldsymbol{\gamma} l) V S = V R cosh ( γ l )
For a lossless line ( r = 0 , α = 0 , γ = j β r = 0, \alpha = 0, \boldsymbol{\gamma} = j\beta r = 0 , α = 0 , γ = j β where β = ω l c \beta = \omega\sqrt{lc} β = ω l c ): V S = V R cos ( β l ) ⟹ V R = V S cos ( β l ) \mathbf{V}_S = \mathbf{V}_R \cos(\beta l) \implies \mathbf{V}_R = \frac{\mathbf{V}_S}{\cos(\beta l)} V S = V R cos ( βl ) ⟹ V R = cos ( βl ) V S
Using Taylor series expansion for cos ( β l ) ≈ 1 − ( β l ) 2 2 \cos(\beta l) \approx 1 - \frac{(\beta l)^2}{2} cos ( βl ) ≈ 1 − 2 ( βl ) 2 : V R ≈ V S ( 1 + ω 2 l 2 L C 2 ) = V S ( 1 + X L Y C 2 ) V_R \approx V_S \left( 1 + \frac{\omega^2 l^2 L C}{2} \right) = V_S \left( 1 + \frac{X_L Y_C}{2} \right) V R ≈ V S ( 1 + 2 ω 2 l 2 L C ) = V S ( 1 + 2 X L Y C )
To prevent dielectric breakdown of substation insulation and transformer saturation, shunt reactors (inductive coils) are connected at line terminals to absorb the charging VARs ( Q L = ω C V 2 Q_L = \omega C V^2 Q L = ω C V 2 ).
2. Surge Impedance Loading (SIL)
Surge Impedance Loading ( S I L SIL S I L ), also termed natural loading, is the active power delivered by a lossless transmission line to a pure resistive load equal to its characteristic impedance ( Z c = L / C Z_c = \sqrt{L/C} Z c = L / C ): S I L = V L L 2 Z c [ MW ] SIL = \frac{V_{LL}^2}{Z_c} \quad [\text{MW}] S I L = Z c V LL 2 [ MW ]
where V L L V_{LL} V LL is the rated line-to-line voltage in kV \text{kV} kV and Z c Z_c Z c is typically 350 − 400 Ω 350 - 400\;\Omega 350 − 400 Ω for overhead single-conductor lines and 250 − 300 Ω 250 - 300\;\Omega 250 − 300 Ω for bundled conductor lines ( 30 − 50 Ω 30 - 50\;\Omega 30 − 50 Ω for underground cables).
Operating Condition Line Reactive Behavior Voltage Profile Along Line Net VAR Contribution
P l o a d < S I L P_{load} < SIL P l o a d < S I L (Light Load) Q C > Q L Q_{C} > Q_{L} Q C > Q L (Capacitive dominant) Voltage rises toward receiving end ( V R > V S V_R > V_S V R > V S ) Supplies net VARs to system (Ferranti effect)
P l o a d = S I L P_{load} = SIL P l o a d = S I L (Natural Load) Q C = Q L Q_{C} = Q_{L} Q C = Q L (Exact balance) Perfectly flat voltage profile ( V ( x ) = V S = V R V(x) = V_S = V_R V ( x ) = V S = V R ) Zero net reactive power exchange
P l o a d > S I L P_{load} > SIL P l o a d > S I L (Heavy Load) Q L > Q C Q_{L} > Q_{C} Q L > Q C (Inductive dominant) Voltage sags along line ( V R < V S V_R < V_S V R < V S ) Absorbs net VARs from system Voltage Profiles Along Line for Different Loading Conditions:
- Voltage |
- |V| | P < SIL (Ferranti Rise)
- | . - - - - - - - - - - - - - - - - o V_R
- V_S |--------o---------------------------------o V_R (P = SIL, Flat Profile)
- | ` - - - - - - - - - - - - - - - -
- | o V_R (P > SIL, Voltage Drop)
- +---------------------------------------------> Distance x (km)
- Sending End Receiving End
- 3. Reactive Power Compensation Technologies
- Shunt Capacitor Banks
Installed at distribution and transmission substations to supply localized lagging reactive power, elevating bus voltage and improving system power factor: Q c a p , 3 ϕ = P l o a d ( tan θ 1 − tan θ 2 ) = ω C b a n k V L L 2 Q_{cap,3\phi} = P_{load} \left( \tan\theta_1 - \tan\theta_2 \right) = \omega C_{bank} V_{LL}^2 Q c a p , 3 ϕ = P l o a d ( tan θ 1 − tan θ 2 ) = ω C bank V LL 2
Warning
Voltage Dependency of Shunt Capacitors: The reactive power output of a shunt capacitor is strictly proportional to the square of the applied voltage ( Q ∝ V 2 Q \propto V^2 Q ∝ V 2 ). During low-voltage conditions when reactive support is most critically needed, shunt capacitor output drops dramatically, aggravating voltage instability.
Series Capacitors
Series capacitors are inserted directly in series with transmission line phase conductors to cancel a portion of the line inductive reactance: X n e t = X L − X C = X L ( 1 − k s e ) where k s e = X C X L = Degree of Compensation (typically 20 % − 70 % ) X_{net} = X_L - X_C = X_L (1 - k_{se}) \quad \text{where } k_{se} = \frac{X_C}{X_L} = \text{Degree of Compensation (typically } 20\% - 70\%\text{)} X n e t = X L − X C = X L ( 1 − k se ) where k se = X L X C = Degree of Compensation (typically 20% − 70% )
Benefits: Drastically increases steady-state power transfer capability ( P m a x = V 1 V 2 X L − X C P_{max} = \frac{V_1 V_2}{X_L - X_C} P ma x = X L − X C V 1 V 2 ) and improves transient stability margins.
Risks: Introduces Subsynchronous Resonance (SSR) , where electrical resonant frequencies of the series R − L − C R-L-C R − L − C network ( f e r = f 0 X C / X L < 60 Hz f_{er} = f_0 \sqrt{X_C/X_L} < 60\text{ Hz} f er = f 0 X C / X L < 60 Hz ) interact with torsional mechanical vibrational modes of turbine-generator shafts, potentially causing catastrophic mechanical shaft shear.
Flexible AC Transmission Systems (FACTS)
Static Var Compensator (SVC): Employs thyristor-switched capacitors (TSC) and thyristor-controlled reactors (TCR) to provide variable, step-less shunt reactive compensation.
Static Synchronous Compensator (STATCOM): Employs a voltage-source converter (VSC) with IGBTs. Unlike shunt capacitors or SVCs, a STATCOM provides constant rated reactive current even under severe voltage depressions ( I i n j = constant I_{inj} = \text{constant} I inj = constant , so Q ∝ V Q \propto V Q ∝ V ).
- 4. Transformer Tap Changers (DETC vs. LTC)
- De-Energized Tap Changer (DETC)
Located on the high-voltage winding; must only be operated when the transformer is completely de-energized.
Typically provides ± 2 \pm 2 ± 2 taps of 2.5 % 2.5\% 2.5% each ( ± 5 % \pm 5\% ± 5% total range) for seasonal voltage matching.
Load Tap Changer (LTC / OLTC)
Changes taps while carrying full load current without interrupting power flow using preventive autotransformers (reactors) or high-speed vacuum/oil transition resistors.
Standard Industry Configuration: 33 total positions (1 Neutral position, 16 Raise steps, 16 Lower steps).
Step Size: Standard step regulation is 5 8 % = 0.625 % \frac{5}{8}\% = 0.625\% 8 5 % = 0.625% per step, providing a total regulation span of ± 10 % \pm 10\% ± 10% ( 16 × 0.625 % = 10.0 % 16 \times 0.625\% = 10.0\% 16 × 0.625% = 10.0% ). Tap Position = V a c t u a l % − V t a r g e t % 0.625 % or Tap Step = V d e s i r e d − V a c t u a l V n o m i n a l × 0.00625 \text{Tap Position} = \frac{V_{actual\% } - V_{target\% }}{0.625\%} \quad \text{or} \quad \text{Tap Step} = \frac{V_{desired} - V_{actual}}{V_{nominal} \times 0.00625} Tap Position = 0.625% V a c t u a l % − V t a r g e t % or Tap Step = V n o mina l × 0.00625 V d es i re d − V a c t u a l
5. Line Drop Compensator (LDC) Controls
An LTC at a substation regulates voltage not at the transformer terminals, but at a fictitious or real load center miles down the distribution feeder. The Line Drop Compensator emulates the physical feeder resistance ( R R R ) and reactance ( X X X ) within the analog/digital regulator circuit. Line Drop Compensator (LDC) Control Schematic:
- Substation Bus -----------------[ Feeder: R_line + jX_line ]-----------------> Load Center
- | |
- (PT) V_bus (V_load)
- |
- v
- +---------+ I_CT
- | Voltage | <---(CT)---/\/\/\-------UUUUUUUU--- (Ground)
- | Control | R_set X_set
- | Relay | <================== V_reg = V_PT - I_CT*(R_set + j*X_set)
- +---------+
- Mathematical Formulation of LDC Settings
The voltage sensed by the regulator relay is: V r e g = V P T , s e c − I C T , s e c ( R s e t + j X s e t ) \mathbf{V}_{reg} = \mathbf{V}_{PT,sec} - \mathbf{I}_{CT,sec} (R_{set} + j X_{set}) V re g = V PT , sec − I CT , sec ( R se t + j X se t )
Given the physical feeder impedance ( R l i n e , X l i n e R_{line}, X_{line} R l in e , X l in e in Ω \Omega Ω ), Potential Transformer ratio ( N P T = V p r i / V s e c N_{PT} = V_{pri} / V_{sec} N PT = V p r i / V sec ), and Current Transformer ratio ( N C T = I p r i / I s e c N_{CT} = I_{pri} / I_{sec} N CT = I p r i / I sec ), the calibrated dial settings (in secondary volts) are: R s e t = R l i n e × ( N C T N P T ) [ Volts ] , X s e t = X l i n e × ( N C T N P T ) [ Volts ] R_{set} = R_{line} \times \left( \frac{N_{CT}}{N_{PT}} \right) \quad [\text{Volts}], \qquad X_{set} = X_{line} \times \left( \frac{N_{CT}}{N_{PT}} \right) \quad [\text{Volts}] R se t = R l in e × ( N PT N CT ) [ Volts ] , X se t = X l in e × ( N PT N CT ) [ Volts ]
Note: If R l i n e R_{line} R l in e and X l i n e X_{line} X l in e are given in ohms, multiplying by ( N C T / N P T ) (N_{CT}/N_{PT}) ( N CT / N PT ) converts the ohmic impedance directly to the equivalent secondary voltage drop produced when rated primary CT current flows.
- 6. Comprehensive Worked Calculation: LTC & LDC Settings
- Problem Statement
A 13.8 kV / 7.967 kV 13.8\text{ kV} / 7.967\text{ kV} 13.8 kV /7.967 kV single-phase distribution substation regulator feeds a 4-mile overhead feeder. The system parameters are:
Feeder impedance: Z l i n e = ( 0.35 + j 0.65 ) Ω / mile \mathbf{Z}_{line} = (0.35 + j0.65)\;\Omega/\text{mile} Z l in e = ( 0.35 + j 0.65 ) Ω/ mile
PT ratio: 7 , 200 V : 120 V 7,200\text{ V} : 120\text{ V} 7 , 200 V : 120 V ( N P T = 7200 / 120 = 60 N_{PT} = 7200/120 = 60 N PT = 7200/120 = 60 )
CT ratio: 600 A : 5 A 600\text{ A} : 5\text{ A} 600 A : 5 A ( N C T = 600 / 5 = 120 N_{CT} = 600/5 = 120 N CT = 600/5 = 120 )
- Voltage regulator base setpoint (voltage level dial): 120.0 V 120.0\text{ V} 120.0 V
- Peak load current: 450 A 450\text{ A} 450 A at 0.80 0.80 0.80 power factor lagging
Calculate:
The required LDC R s e t R_{set} R se t and X s e t X_{set} X se t dial settings in volts.
The secondary voltage V r e g \mathbf{V}_{reg} V re g measured by the regulator relay during peak load if substation bus voltage is held at 120 V 120\text{ V} 120 V .
The actual voltage at the load center 4 miles away.
The required LTC tap position (number of 5 / 8 % 5/8\% 5/8% steps) to restore load center voltage to rated 120 V 120\text{ V} 120 V base. ============================== STEP-BY-STEP SOLUTION ==============================
- Step 1: Compute Total Feeder Impedance and LDC Settings
- Feeder length = 4 miles
- R_line_total = 0.35 * 4 = 1.40 ohms
- X_line_total = 0.65 * 4 = 2.60 ohms
Scale Factor = N_CT / N_PT = 120 / 60 = 2.0
- R_set = R_line_total * (N_CT / N_PT) = 1.40 * 2.0 = 2.80 Volts
- X_set = X_line_total * (N_CT / N_PT) = 2.60 * 2.0 = 5.20 Volts
- Step 2: Determine Secondary Current Phasor
- Primary current I_pri = 450 A at 0.80 lag (theta = -36.87 deg)
- I_CT,sec = (450 / 120) /_ -36.87 deg = 3.75 /_ -36.87 deg A
- = 3.00 - j 2.25 A
- Step 3: Compute Compensator Voltage Drop and Regulated Voltage
- Z_set = 2.80 + j 5.20 ohms (secondary)
- V_drop_LDC = I_CT,sec * (R_set + j X_set)
- = (3.75 /_ -36.87 deg) * (5.906 /_ 61.70 deg)
- = 22.147 /_ 24.83 deg V = 20.098 + j 9.300 V
If substation bus voltage V_PT = 120.0 /_ 0 deg V:
- V_reg = V_PT - V_drop_LDC = 120.0 - (20.098 + j 9.300)
- = 99.902 - j 9.300 V = 100.33 /_ -5.32 deg V
Step 4: Verify Actual Physical Voltage at Load Center
Primary line voltage drop:
- Delta_V_pri = I_pri * Z_line_total = (450 /_ -36.87 deg) * (2.953 /_ 61.70 deg)
- = 1,328.85 /_ 24.83 deg V = 1,205.9 + j 558.0 V
- V_bus_pri = 120 V * 60 = 7,200 /_ 0 deg V
- V_load_pri = 7,200 - (1,205.9 + j 558.0) = 5,994.1 - j 558.0 V = 6,020.0 V
Referred to 120 V base:
V_load_sec = 6,020.0 / 60 = 100.33 V (Matches V_reg perfectly!)
- Step 5: Determine LTC Tap Change to Restore Load Voltage to 120 V Base
- Voltage deficit = V_target - V_measured = 120.0 V - 100.33 V = 19.67 V
- Required percentage boost = (19.67 V / 120.0 V) * 100% = 16.39%
- Standard tap step size = 5/8% = 0.625% per tap
- Number of tap steps = 16.39% / 0.625% = 26.22 steps
Since standard LTCs have a maximum of +16 Raise steps (10% max boost):
- With 16 Raise steps, voltage boost = 16 * 0.625% = +10.0%
- Boosted load voltage = 100.33 V * 1.10 = 110.36 V (on 120 V base)
- *Engineering Insight:* The load drop of 16.39% exceeds the +/-10% LTC regulation
envelope. A mid-line capacitor bank or line reconductoring is required.
- ===================================================================================
- 7. Common Exam Traps & Strategic Pitfalls
Inverting the CT/PT Ratio in LDC Formulas: Multiplying R l i n e R_{line} R l in e by ( N P T / N C T ) (N_{PT}/N_{CT}) ( N PT / N CT ) instead of ( N C T / N P T ) (N_{CT}/N_{PT}) ( N CT / N PT ) . Always dimensionally verify: multiplying primary ohms by amperes/volts yields dimensionless units that, when multiplied by secondary current, produce secondary volts.
Confusing DETC with LTC Capability: Attempting to adjust DETC under energized conditions. DETC taps can only be changed de-energized.
Assuming Shunt Capacitors Provide Constant MVAR: Treating shunt capacitor MVAR as invariant when bus voltage drops. Since Q = V 2 / X C Q = V^2 / X_C Q = V 2 / X C , a 10 % 10\% 10% drop in bus voltage results in a 19 % 19\% 19% reduction in reactive output ( 0.90 2 = 0.81 0.90^2 = 0.81 0.9 0 2 = 0.81 ).
Neglecting SSR with Series Compensation: Forgetting that high degrees of series compensation ( > 70 % >70\% > 70% ) increase the risk of Subsynchronous Resonance, which damages generator shafts.