10.1 Air Handling Units (AHUs), Dedicated Outdoor Air Systems (DOAS) & Fan-Coil Units

PE Mechanical: HVAC and Refrigeration Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Overview, Reference Handbook & Engineering Foundations

1.1 NCEES Exam Specification, CBT Delivery & Reference Handbook Strategy 1.2 Engineering Units, Dimensional Analysis & Physical Property Lookups 1.3 Engineering Economics, Life Cycle Cost Analysis & Equipment Financial Evaluation 1.4 Electrical Foundations, Motor Ratings & Variable Frequency Drives (VFDs)

2 Chapter 2: Thermodynamics & Energy Balances

2.1 First and Second Laws of Thermodynamics & Open/Closed System Energy Balances 2.2 Thermodynamic Cycles: Carnot, Rankine, Brayton & Reversed Carnot Limit 2.3 Gas & Vapor Property Evaluation: Steam Tables, Superheat & Subcooling 2.4 Mass, Energy & Combustion Balances for HVAC Equipment

3 Chapter 3: Psychrometrics, Moist Air Processes & Humidity Equipment

3.1 Psychrometric Properties: DBT, WBT, DPT, RH, Humidity Ratio & Enthalpy 3.2 Chart Reading & Psychrometric Equations at Sea Level vs. Altitude (5,000 ft) 3.3 Basic Psychrometric Processes: Sensible Heating/Cooling, Humidification & Dehumidification 3.4 Mixed Air Calculations & Complex Air Conditioning Cycles (Preheat, Reheat & Bypass) 3.5 Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP) & Coil Bypass Factor 3.6 Humidification & Dehumidification Equipment: Steam, Adiabatic, Desiccant & Low-Temperature Processes

4 Chapter 4: Heat Transfer Principles & Sizing

4.1 Steady-State Conduction & Multilayer Thermal Resistance (R-Value & U-Factor) 4.2 Convective Heat Transfer & Forced/Natural Convection Coefficients 4.3 Radiation Heat Transfer, Surface Emissivity & View Factors 4.4 Overall Heat Transfer Coefficients, Fouling Factors & Transient/Thermal Mass Effects 4.5 Heat Exchanger Analysis: Log Mean Temperature Difference (LMTD) & Effectiveness-NTU (ε-NTU)

5 Chapter 5: Fluid Mechanics & Hydraulic Fundamentals

5.1 Fluid Statics, Incompressible Continuity & Bernoulli Energy Equation 5.2 Pipe Friction, Moody Diagram & Darcy-Weisbach / Hazen-Williams Calculations 5.3 Minor Losses: Equivalent Length, Loss Coefficients (K-factors) & Total System Head 5.4 Pump Sizing, Net Positive Suction Head (NPSHa vs NPSHr) & Cavitation Prevention 5.5 Affinity Laws & Parallel/Series Pump/Fan System Curves

6 Chapter 6: Heating & Cooling Load Calculations

6.1 Outdoor & Indoor Design Conditions (ASHRAE Fundamentals, Climatic Data & Indoor Setpoints) 6.2 Envelope Heat Transmission & Infiltration/Exfiltration Load Methods 6.3 Solar Heat Gain (SHGC), Fenestration & Cooling Load Temperature Difference / Radiant Time Series (CLTD/RTS) 6.4 Internal Heat Gains: Lighting, People, Equipment & Diversity Factors 6.5 Ventilation Loads & Sensible / Latent / Total Cooling Load Synthesis

7 Chapter 7: Refrigeration Principles, Cycles & Cold Storage Applications

7.1 Standard Vapor-Compression Refrigeration Cycle on P-h & T-s Diagrams 7.2 Refrigeration Cycle Performance Metrics: COP, EER, SEER, kW/ton & Ton of Refrigeration 7.3 Cycle Enhancements: Subcooling, Superheating, Liquid-Suction Heat Exchangers & Economizers 7.4 Multi-Stage & Cascade Refrigeration Systems: Intercooling & Flash Gas Removal 7.5 Absorption Refrigeration Cycles: Water-Lithium Bromide & Ammonia-Water Systems 7.6 Food Processing & Cold Storage Refrigeration: Product Load, Pull-Down & Storage Design

8 Chapter 8: Refrigerants, Environmental Regulations & Safety

8.1 Refrigerant Classifications, Nomenclature & Thermodynamic Properties (ASHRAE Standard 34) 8.2 AIM Act, EPA Technology Transitions Sector GWP Limits & Low-GWP Refrigerants (R-32, R-454B) 8.3 Refrigerant Safety Requirements & Machinery Room Design (ASHRAE Standard 15) 8.4 Refrigerant Piping Sizing, Oil Return, Traps & Double Risers

9 Chapter 9: HVAC Equipment & Primary Machinery

9.1 Compressors: Reciprocating, Rotary, Scroll, Screw & Centrifugal 9.2 Condensers: Air-Cooled, Water-Cooled & Evaporative Condensers 9.3 Evaporators & Direct Expansion (DX) vs Liquid Chilling Coils 9.4 Water Chillers: Centrifugal, Screw & Scroll with ASHRAE 90.1 Path A/B IPLV Ratings 9.5 Cooling Towers: Range, Approach, Evaporation, Blowdown & Legionella Control 9.6 Heat Pumps & Variable Refrigerant Flow (VRF): Balance Point, Defrost & Heat Recovery 9.7 Thermal Energy Storage: Full vs. Partial Storage, Chilled Water & Ice Systems

10 Chapter 10: Air-Side Systems & Distribution

10.1 Air Handling Units (AHUs), Dedicated Outdoor Air Systems (DOAS) & Fan-Coil Units 10.2 Duct Design Methodologies: Equal Friction, Static Regain & Velocity Reduction 10.3 Duct Fittings, Dynamic Pressure Losses & SMACNA Construction Standards 10.4 Fan Types, Performance Curves, System Effect Factors & Surge/Stall Dynamics 10.5 Variable Air Volume (VAV) Systems, Terminal Boxes & Space Air Diffusion (ADPI) 10.6 Cooling & Heating Coil Selection: Face Velocity, Rows, Circuiting & Freeze Protection

11 Chapter 11: Hydronic, Steam & Fuel Distribution and Heating Plant

11.1 Hydronic System Architectures: Primary-Only, Primary-Secondary & Variable Primary Flow (VPF) 11.2 Hydronic Pipe Sizing, Velocity Limits & Closed/Open Expansion Tank Sizing 11.3 Control Valves: 2-Way vs 3-Way, Valve Authority (N), Cv Calculations & Characteristic Curves 11.4 Boilers & Heating Hot Water Systems: Condensing vs Non-Condensing & Water Treatment 11.5 Furnaces & Gas-Fired Heating Equipment: AFUE, Temperature Rise, Combustion Air & Vent Categories 11.6 Steam & Condensate Distribution: Latent Heat, Trap Selection, Flash Steam & Stall 11.7 Fuel Gas & Fuel Oil Piping: Demand, Sizing Method, Pressure Drop & Storage Systems

12 Chapter 12: HVAC Control Concepts, Sensors & Sequences

12.1 Sensors, Actuators & Dampers: Selection, Placement, Fail-Safe Position & Damper Authority 12.2 Control Loops: Proportional Offset, PID Action, Reset Strategies & Standard Sequences

13 Chapter 13: Building Energy, Ventilation & Indoor Environmental Quality Codes

13.1 ASHRAE Standard 62.1: Ventilation Rate Procedure (VRP), Indoor Air Quality Procedure & DCV 13.2 ASHRAE Standard 90.1: Building Energy Envelope, Mechanical Efficiency & Economizer Mandates 13.3 ASHRAE Standard 55: Thermal Environmental Conditions, PMV/PPD & Adaptive Comfort Models 13.4 Energy Recovery Systems: Enthalpy Wheels, Fixed-Plate Exchangers, Heat Pipes & Runaround Loops

14 Chapter 14: Supportive Engineering Knowledge, Life Safety & Operations

14.1 Air Filtration Standards: MERV Ratings (ASHRAE 52.2), HEPA & Gas-Phase Adsorption 14.2 Life Safety Systems: Fire/Smoke Dampers, Stairwell Pressurization (NFPA 92) & Smoke Control (NFPA 90A) 14.3 Acoustical Control & Vibration Isolation in HVAC Systems (NC / RC Criteria)

10.1 Air Handling Units (AHUs), Dedicated Outdoor Air Systems (DOAS) & Fan-Coil Units

Key Takeaways Explain This Topic AI

Air Handling Units (AHUs) condition and circulate mixed air using modular component trains; Draw-Through configurations provide uniform air velocity across cooling coils to prevent moisture carryover, whereas Blow-Through configurations place fan heat upstream of cooling coils.

Supply and return fan motor heat adds sensible temperature rise to the airstream via Δ T fan = 0.3707 × Δ P total η total \Delta T_{\text{fan}} = 0.3707 \times \frac{\Delta P_{\text{total}}}{\eta_{\text{total}}} Δ T fan ​ = 0.3707 × η total ​ Δ P total ​ ​ , which must be added to cooling loads or credited to heating loads.

Dedicated Outdoor Air Systems (DOAS) decouple ventilation from space sensible cooling, conditioning 100% outdoor air to handle the entire building latent ventilation and internal space moisture loads while delivering dry neutral or cold air.

Total energy recovery wheels in DOAS exchange both sensible and latent energy between exhaust and outdoor airstreams, reducing peak ventilation cooling loads by 60% to 75% and complying with ASHRAE 90.1 energy recovery mandates.

Four-pipe fan-coil units (FCUs) provide simultaneous heating and cooling flexibility with separate supply and return hydronic coils, eliminating seasonal changeover lag and thermal mixing losses characteristic of two-pipe systems.

Last updated: August 2026

10.1 Air Handling Units (AHUs), Dedicated Outdoor Air Systems (DOAS) & Fan-Coil Units

Air-side distribution systems are the primary thermal and ventilation delivery mechanisms in commercial, institutional, and industrial HVAC applications. The primary function of an Air Handling Unit (AHU) or Dedicated Outdoor Air System (DOAS) is to process, filter, condition (heat, cool, humidify, dehumidify), and circulate moist air throughout building zones to satisfy indoor environmental quality, ventilation, and thermal comfort criteria. On the PE Mechanical: HVAC and Refrigeration exam, air-handling equipment questions test psychrometric coil processes, fan heat temperature rise, freeze protection, sensible-latent decoupling, energy recovery effectiveness, and hydronic terminal selection.

1. Central Air Handling Unit (AHU) Architecture & Component Sequence

A custom or packaged commercial AHU consists of an insulated sheet metal casing enclosing a sequential train of aerodynamic, thermal, and filtration components. The physical arrangement of these components determines thermal performance, acoustic generation, filtration efficiency, and maintenance longevity. +---------------------------------------------------------------------------------------------------------+

  • | STANDARD DRAW-THROUGH AHU COMPONENT TRAIN |
  • +---------------------------------------------------------------------------------------------------------+
  • | |
  • | Outdoor Air (OA) ---\ |
  • | [Mixing Box / Dampers] ==> [Prefilter (MERV 8)] ==> [Final Filter (MERV 13-14)] |
  • | Return Air (RA) ----/ |
  • | |
  • | ==> [Preheat / Glycol Coil] ==> [Cooling / Dehum Coil] ==> [Supply Fan] ==> [Sound Attenuator] |
  • | (with Drain Pan) (Draw-Thru) ===> Supply Air (SA) |
  • +---------------------------------------------------------------------------------------------------------+
  • Standard Component Sequence (Airflow Direction)

Air Mixing Plenum (Economizer Section): Interlinked motorized outdoor air (OA), return air (RA), and relief/exhaust air (EA) dampers modulate to control the mixed air ratio and execute airside economizer free cooling.

Filtration Bank:

Pre-filters: Typically 2-inch or 4-inch pleated filters rated MERV 8 (ASHRAE 52.2) to capture large particulate matter and protect downstream coils.

Final Filters: High-efficiency bag, cartridge, or mini-pleat filters rated MERV 13 to 14 (standard LEED/ASHRAE 55 baseline) or MERV 16/HEPA (healthcare/cleanroom applications).

Preheat Coil: Located upstream of the chilled water cooling coil in cold climates to temper incoming mixed air above 40 ∘ F 40^\circ\text{F} 4 0 ∘ F ( 4.4 ∘ C 4.4^\circ\text{C} 4. 4 ∘ C ), preventing coil freeze-up. Utilizes hot water with a dedicated circulating pump, ethylene/propylene glycol, steam distributing tubes (non-freeze type), or face-and-bypass dampers.

Cooling and Dehumidification Coil: Finned-tube heat exchanger circulating chilled water ( 42 ∘ F 42^\circ\text{F} 4 2 ∘ F to 45 ∘ F 45^\circ\text{F} 4 5 ∘ F ) or direct expansion (DX) evaporating refrigerant. Operates with face velocities restricted to 400 400 400 to 500 FPM 500\text{ FPM} 500 FPM ( 2.0 2.0 2.0 to 2.5 m/s 2.5\text{ m/s} 2.5 m/s ) . Face velocities exceeding 500 − 550 FPM 500-550\text{ FPM} 500 − 550 FPM cause condensed moisture droplet blow-off from fins into the downstream casing.

Sloped Condensate Drain Pan: Stainless steel dual-sloped drain pan conforming to ASHRAE Standard 62.1 to prevent standing water, biological slime, and mold amplification. P-traps must be engineered with sufficient water seal depth to overcome negative casing static pressure.

Reheat / Heating Coil: Hot water, electric resistance, or indirect gas-fired heat exchanger positioned downstream of the cooling coil for zone temperature control or humidity trim.

Supply Air Fan: Centrifugal airfoil, plenum/plug fan, or fan array (FANWALL) driven by electronically commutated (EC) motors or premium-efficiency motors with variable frequency drives (VFDs).

Sound Attenuator (Silencer): Factory-engineered dissipative silencer baffles to attenuate blade pass frequencies and broadband fan noise before discharge into the duct system.

2. Draw-Through vs. Blow-Through Configurations

The relative placement of the supply fan with respect to the cooling coil creates two distinct thermodynamic and aerodynamic architectures: DRAW-THROUGH CONFIGURATION: BLOW-THROUGH CONFIGURATION:

  • Coil Under Negative Static Pressure Coil Under Positive Static Pressure
  • Fan Heat Added AFTER Cooling Coil Fan Heat Added BEFORE Cooling Coil
  • Negative (-) Positive (+) Positive (+) Positive (+)
  • [Coil] ===> [Fan] ===> Supply Duct [Fan] ===> [Coil] ===> Supply Duct
  • | |
  • Fan Heat Fan Heat
  • Added Here Added Here
  • Comparative Engineering Matrix

Engineering Parameter Draw-Through Configuration Blow-Through Configuration

Coil Velocity Profile Highly uniform velocity distribution across the entire coil face due to fan suction plenum drawing air evenly. Non-uniform velocity profile; high-velocity air jet from fan discharge strikes center of coil unless diffuser baffles are installed.

Moisture Carryover Risk Low risk; uniform face velocity prevents localized high-velocity hot spots that strip water droplets. Higher risk of condensate blow-off directly opposite the fan discharge cone.

Casing Static Pressure Casing upstream of fan (filters, coils, mixing box) operates under negative static pressure ( P s < P atm P_s < P_{\text{atm}} P s ​ < P atm ​ ). Casing downstream of fan (coils, discharge plenum) operates under positive static pressure ( P s > P atm P_s > P_{\text{atm}} P s ​ > P atm ​ ).

Drain Pan Trap Design Requires a deep P-trap with negative trap seal ( H = P static, suction + 1 to 2 in. H = P_{\text{static, suction}} + 1\text{ to }2\text{ in.} H = P static, suction ​ + 1 to 2 in. ) to prevent air being sucked into the pan, which halts drainage and overflows the pan. Requires standard positive pressure trap ; air blows out through drain line if untrapped.

Fan Heat Addition Fan work heat is added after the cooling coil; increases supply air temperature delivered to ductwork ( T SA = T leaving coil + Δ T fan T_{\text{SA}} = T_{\text{leaving coil}} + \Delta T_{\text{fan}} T SA ​ = T leaving coil ​ + Δ T fan ​ ). Fan work heat is added before the cooling coil; cooling coil must absorb both space cooling load and fan heat load ( T entering coil = T mix + Δ T fan T_{\text{entering coil}} = T_{\text{mix}} + \Delta T_{\text{fan}} T entering coil ​ = T mix ​ + Δ T fan ​ ).

Primary Application Commercial VAV systems, DOAS units, single-zone constant volume AHUs (dominant > 90 % >90\% > 90% of designs). Multi-zone dual-duct AHUs with separate hot/cold decks, or applications requiring ultra-low discharge temperatures.

3. Supply Fan Heat Temperature Rise Equations

All mechanical energy losses and thermodynamic work imparted by the fan impeller into the airstream convert into thermal internal energy (heat). For a fan with total pressure rise Δ P t \Delta P_t Δ P t ​ (in inches of water gauge, in. wg \text{in. wg} in. wg ) and total efficiency η t \eta_t η t ​ : Fan Brake Horsepower: BHP = CFM × Δ P t (in. wg) 6 , 356 × η t \text{Fan Brake Horsepower: } \text{BHP} = \frac{\text{CFM} \times \Delta P_t\text{ (in. wg)}}{6,356 \times \eta_t} Fan Brake Horsepower: BHP = 6 , 356 × η t ​ CFM × Δ P t ​ (in. wg) ​ Q ˙ fan heat (Btu/hr) = BHP × 2 , 544.43 Btu/(hp ⋅ hr) \dot{Q}_{\text{fan heat}}\text{ (Btu/hr)} = \text{BHP} \times 2,544.43\text{ Btu/(hp}\cdot\text{hr)} Q ˙ ​ fan heat ​ (Btu/hr) = BHP × 2 , 544.43 Btu/(hp ⋅ hr)

Substituting Q ˙ = 1.08 × CFM × Δ T fan \dot{Q} = 1.08 \times \text{CFM} \times \Delta T_{\text{fan}} Q ˙ ​ = 1.08 × CFM × Δ T fan ​ (for standard air density ρ = 0.075 lbm/ft 3 \rho = 0.075\text{ lbm/ft}^3 ρ = 0.075 lbm/ft 3 and specific heat c p = 0.240 Btu/(lbm ⋅ ∘ F) c_p = 0.240\text{ Btu/(lbm}\cdot^\circ\text{F)} c p ​ = 0.240 Btu/(lbm ⋅ ∘ F) ): 1.08 × CFM × Δ T fan = CFM × Δ P t 6 , 356 × η t × 2 , 544.43 1.08 \times \text{CFM} \times \Delta T_{\text{fan}} = \frac{\text{CFM} \times \Delta P_t}{6,356 \times \eta_t} \times 2,544.43 1.08 × CFM × Δ T fan ​ = 6 , 356 × η t ​ CFM × Δ P t ​ ​ × 2 , 544.43 Δ T fan ( ∘ F) = ( 2 , 544.43 6 , 356 × 1.08 ) × Δ P t η t = 0.3707 × Δ P t (in. wg) η t \Delta T_{\text{fan}}\text{ (}{}^\circ\text{F)} = \left(\frac{2,544.43}{6,356 \times 1.08}\right) \times \frac{\Delta P_t}{\eta_t} = 0.3707 \times \frac{\Delta P_t\text{ (in. wg)}}{\eta_t} Δ T fan ​ ( ∘ F) = ( 6 , 356 × 1.08 2 , 544.43 ​ ) × η t ​ Δ P t ​ ​ = 0.3707 × η t ​ Δ P t ​ (in. wg) ​

Where:

  • Δ P t \Delta P_t Δ P t ​ = Total pressure rise across fan ( in. wg \text{in. wg} in. wg )
  • η t \eta_t η t ​ = Fan total efficiency (decimal, typically 0.60 0.60 0.60 to 0.80 0.80 0.80 )

If the motor is located inside the airstream (common in packaged units and plug fans), motor electrical inefficiency heat ( 1 − η m 1 - \eta_m 1 − η m ​ ) is also transferred to the air: Δ T fan+motor ( ∘ F) = 0.3707 × Δ P t (in. wg) η t × η m \Delta T_{\text{fan+motor}}\text{ (}{}^\circ\text{F)} = 0.3707 \times \frac{\Delta P_t\text{ (in. wg)}}{\eta_t \times \eta_m} Δ T fan+motor ​ ( ∘ F) = 0.3707 × η t ​ × η m ​ Δ P t ​ (in. wg) ​

Exam Rule of Thumb: For a typical commercial AHU with Δ P t = 3.5 in. wg \Delta P_t = 3.5\text{ in. wg} Δ P t ​ = 3.5 in. wg and total fan-motor efficiency η = 0.65 \eta = 0.65 η = 0.65 , fan heat produces a temperature rise of Δ T = 0.3707 × 3.5 0.65 ≈ 2.0 ∘ F \Delta T = 0.3707 \times \frac{3.5}{0.65} \approx 2.0^\circ\text{F} Δ T = 0.3707 × 0.65 3.5 ​ ≈ 2. 0 ∘ F . If the leaving cooling coil temperature is 53.0 ∘ F 53.0^\circ\text{F} 53. 0 ∘ F , the air leaves the draw-through AHU at 55.0 ∘ F 55.0^\circ\text{F} 55. 0 ∘ F .

4. Dedicated Outdoor Air Systems (DOAS)

A Dedicated Outdoor Air System (DOAS) is an HVAC architecture that completely decouples building ventilation and latent humidity control from space sensible cooling and heating. +-----------------------------------------------------------------------------------------+

  • | DECOUPLED DOAS + PARALLEL TERMINAL ARCHITECTURE |
  • +-----------------------------------------------------------------------------------------+
  • | |
  • | 100% Outdoor Air ===> [ DOAS AHU ] ======> Dry Neutral Air (70°F DB, 48°F DP) |
  • | (Ventilation & (Cool to 50°F DP, - Handles 100% Latent Load |
  • | Latent Control) Reheat to 70°F) - Handles 100% Ventilation Air |
  • | | |
  • | v |
  • | +-------------------+ |
  • | | Occupied Zone | |
  • | +-------------------+ |
  • | ^ |
  • | | |
  • | Recirculating Zone Air =================> [ Parallel Sensible ] |
  • | [ Terminal Device ] |
  • | • Fan-Coil Units (FCUs) |
  • | • Active Chilled Beams |
  • | • Radiant Cooling Panels |
  • | • VRF Indoor Units |
  • +-----------------------------------------------------------------------------------------+
  • Core Engineering Principles of DOAS

Latent Load Decoupling: Traditional variable air volume (VAV) systems dehumidify by overcooling mixed air down to 55 ∘ F 55^\circ\text{F} 5 5 ∘ F at the central AHU. In spaces with high latent loads (auditoriums, classrooms, gyms), central VAV requires wasteful terminal reheat. DOAS processes 100% outdoor air down to a low dew point ( 45 ∘ F 45^\circ\text{F} 4 5 ∘ F to 50 ∘ F 50^\circ\text{F} 5 0 ∘ F ), removing all outdoor air moisture plus internal occupant latent generation.

Delivery Strategies:

Cold Air Delivery ( 55 ∘ F 55^\circ\text{F} 5 5 ∘ F DB / 48 ∘ F 48^\circ\text{F} 4 8 ∘ F DP): DOAS air provides sensible cooling capacity directly to the zone, reducing the sizing of parallel sensible cooling terminals.

Neutral Air Delivery ( 70 ∘ F 70^\circ\text{F} 7 0 ∘ F DB / 48 ∘ F 48^\circ\text{F} 4 8 ∘ F DP): DOAS air enters at room temperature, handling zero space sensible load. Parallel terminal systems handle 100% of space sensible loads.

ASHRAE Standard 62.1 Multiple Spaces Compliance: In a multi-zone recirculating VAV system, system ventilation efficiency ( E v E_v E v ​ ) is governed by the critical zone requiring the highest outdoor air fraction, forcing significant over-ventilation of uncritical zones. Because DOAS delivers dedicated, measured outdoor air directly to each zone, E v = 1.0 E_v = 1.0 E v ​ = 1.0 , reducing total building outdoor air intake by 20 % 20\% 20% to 40 % 40\% 40% .

Total Energy Recovery in DOAS (Enthalpy Wheels)

Modern DOAS units incorporate an air-to-air energy recovery device between the exhaust/relief airstream and incoming outdoor airstream:

Total Enthalpy Wheel: A rotating honeycomb matrix impregnated with a desiccant (silica gel or molecular sieve) rotating at 10 10 10 to 30 RPM 30\text{ RPM} 30 RPM . It transfers both sensible heat (via matrix thermal mass) and latent moisture (via desiccant adsorption/desorption).

Effectiveness Equation (Sensible, Latent, or Total): ε = m ˙ o a ( X o a , i n − X o a , o u t ) m ˙ min ⁡ ( X o a , i n − X e a , i n ) \varepsilon = \frac{\dot{m}_{oa} (X_{oa,in} - X_{oa,out})}{\dot{m}_{\min} (X_{oa,in} - X_{ea,in})} ε = m ˙ m i n ​ ( X o a , in ​ − X e a , in ​ ) m ˙ o a ​ ( X o a , in ​ − X o a , o u t ​ ) ​

Where X X X represents dry-bulb temperature ( T T T ), humidity ratio ( W W W ), or enthalpy ( h h h ), and m ˙ min ⁡ = min ⁡ ( m ˙ o a , m ˙ e a ) \dot{m}_{\min} = \min(\dot{m}_{oa}, \dot{m}_{ea}) m ˙ m i n ​ = min ( m ˙ o a ​ , m ˙ e a ​ ) . For equal mass flows ( m ˙ o a = m ˙ e a ): h o a , o u t = h o a , i n − ε t ( h o a , i n − h e a , i n ) \text{For equal mass flows (}\dot{m}_{oa} = \dot{m}_{ea}\text{): } h_{oa,out} = h_{oa,in} - \varepsilon_t (h_{oa,in} - h_{ea,in}) For equal mass flows ( m ˙ o a ​ = m ˙ e a ​ ): h o a , o u t ​ = h o a , in ​ − ε t ​ ( h o a , in ​ − h e a , in ​ ) Q ˙ recovered = 4.5 × CFM o a × ε t × ( h o a , i n − h e a , i n ) \dot{Q}_{\text{recovered}} = 4.5 \times \text{CFM}_{oa} \times \varepsilon_t \times (h_{oa,in} - h_{ea,in}) Q ˙ ​ recovered ​ = 4.5 × CFM o a ​ × ε t ​ × ( h o a , in ​ − h e a , in ​ )

5. Fan-Coil Units (FCUs) & Parallel Hydronic Terminals

Fan-Coil Units (FCUs) are decentralized zone conditioning units consisting of a small centrifugal fan, filter, and one or two water coils. 2-PIPE FCU (Seasonal Changeover): 4-PIPE FCU (Simultaneous Heating/Cooling):

  • +----------------------+ +----------------------+
  • | Single Coil for | | Heating | Cooling |
  • | Heating OR Cooling | | Coil | Coil |
  • +----------------------+ +----------------------+
  • | | | | | |
  • Supply Return HW-S HW-R CW-S CW-R
  • (Seasonally switched at plant) (Independent simultaneous loops)
  • 2-Pipe vs. 4-Pipe System Comparison

Feature 2-Pipe System 4-Pipe System

Piping Distribution 1 supply pipe, 1 return pipe; single shared coil. 2 supply pipes, 2 return pipes; dedicated heating and cooling coils.

Operational Flexibility The entire building loop must be in either 100% cooling mode or 100% heating mode. Any zone can heat while an adjacent zone cools simultaneously.

Seasonal Changeover Lag High; changing modes requires circulating loop water through a bypass until water temperature normalizes before switching chiller/boiler. Zero changeover lag; instant response to variable solar/internal loads.

Installed Capital Cost Lower initial cost (50% less piping, 1 valve per unit). Higher initial cost (4 pipes, 2 control valves per unit).

Energy Waste & Complaints High occupant dissatisfaction during shoulder seasons (spring/fall); zones with perimeter solar heat gain overheat while shaded zones freeze. Outstanding thermal comfort; minimal energy waste.

Chilled Beams (Active vs. Passive)

Passive Chilled Beams: Natural convection coils mounted at ceiling level. Room air warms, rises, passes through the chilled coil, cools, and sinks back into the occupied zone. Zero fan power, quiet. Handles sensible cooling only.

Active Chilled Beams: Pressurized primary air from a DOAS unit discharges through aerodynamic nozzles at high velocity, inducing room air through an integrated chilled water coil at an induction ratio of 3 : 1 3:1 3 : 1 to 5 : 1 5:1 5 : 1 .

Condensation Prevention Rule: Chilled water supply temperature entering chilled beams must be maintained 2 ∘ F 2^\circ\text{F} 2 ∘ F to 3 ∘ F 3^\circ\text{F} 3 ∘ F above the zone dew point temperature (typically T CHWS ≥ 58 ∘ F T_{\text{CHWS}} \ge 58^\circ\text{F} T CHWS ​ ≥ 5 8 ∘ F to 60 ∘ F 60^\circ\text{F} 6 0 ∘ F ). If the zone dew point rises near T CHWS T_{\text{CHWS}} T CHWS ​ , condensation sensors automatically close the hydronic control valve.

6. Worked Example: DOAS Enthalpy Wheel & Coil Load Analysis

Problem: A commercial DOAS unit supplies 8 , 000 CFM 8,000\text{ CFM} 8 , 000 CFM of outdoor air to an office building at sea level ( P = 14.696 psia P = 14.696\text{ psia} P = 14.696 psia , ρ = 0.075 lbm/ft 3 \rho = 0.075\text{ lbm/ft}^3 ρ = 0.075 lbm/ft 3 ). Summer outdoor design conditions are 95.0 ∘ F 95.0^\circ\text{F} 95. 0 ∘ F Dry-Bulb (DB) and 78.0 ∘ F 78.0^\circ\text{F} 78. 0 ∘ F Wet-Bulb (WB) ( h o a = 41.38 Btu/lbm h_{oa} = 41.38\text{ Btu/lbm} h o a ​ = 41.38 Btu/lbm , W o a = 0.0168 lbm w / lbm d a W_{oa} = 0.0168\text{ lbm}_w/\text{lbm}_{da} W o a ​ = 0.0168 lbm w ​ / lbm d a ​ ). Building exhaust air enters the energy recovery wheel at 75.0 ∘ F 75.0^\circ\text{F} 75. 0 ∘ F DB and 62.0 ∘ F 62.0^\circ\text{F} 62. 0 ∘ F WB ( h e a = 27.80 Btu/lbm h_{ea} = 27.80\text{ Btu/lbm} h e a ​ = 27.80 Btu/lbm , W e a = 0.0092 lbm w / lbm d a W_{ea} = 0.0092\text{ lbm}_w/\text{lbm}_{da} W e a ​ = 0.0092 lbm w ​ / lbm d a ​ ) with an exhaust flow rate of 8 , 000 CFM 8,000\text{ CFM} 8 , 000 CFM .

The DOAS unit features a total enthalpy wheel with a total effectiveness of ε t = 0.72 \varepsilon_t = 0.72 ε t ​ = 0.72 and sensible effectiveness of ε s = 0.75 \varepsilon_s = 0.75 ε s ​ = 0.75 . Downstream of the wheel, a chilled water cooling coil dehumidifies the air to a leaving coil condition of 52.0 ∘ F 52.0^\circ\text{F} 52. 0 ∘ F DB and 51.0 ∘ F 51.0^\circ\text{F} 51. 0 ∘ F WB ( h c c = 20.80 Btu/lbm h_{cc} = 20.80\text{ Btu/lbm} h cc ​ = 20.80 Btu/lbm , W c c = 0.0078 lbm w / lbm d a W_{cc} = 0.0078\text{ lbm}_w/\text{lbm}_{da} W cc ​ = 0.0078 lbm w ​ / lbm d a ​ ). The draw-through supply fan has a total pressure rise of Δ P t = 2.80 in. wg \Delta P_t = 2.80\text{ in. wg} Δ P t ​ = 2.80 in. wg and total efficiency of η t = 0.68 \eta_t = 0.68 η t ​ = 0.68 .

Find:

The condition of the air leaving the enthalpy wheel (enthalpy h h h , dry-bulb temperature T T T , and humidity ratio W W W ).

The cooling capacity reduction provided by the energy recovery wheel in Tons of Refrigeration.

The net cooling coil load in Btu/hr \text{Btu/hr} Btu/hr and Tons.

The final supply air dry-bulb temperature ( T SA T_{\text{SA}} T SA ​ ) delivered to the ductwork after fan heat addition.

Step-by-Step Solution:

Step 1: Calculate air properties leaving the enthalpy wheel. Mass flows are equal ( 8 , 000 CFM OA = 8 , 000 CFM EA) ⟹ m ˙ o a = m ˙ min ⁡ \text{Mass flows are equal (}8,000\text{ CFM OA} = 8,000\text{ CFM EA)} \implies \dot{m}_{oa} = \dot{m}_{\min} Mass flows are equal ( 8 , 000 CFM OA = 8 , 000 CFM EA) ⟹ m ˙ o a ​ = m ˙ m i n ​ h wheel,out = h o a − ε t ( h o a − h e a ) = 41.38 − 0.72 × ( 41.38 − 27.80 ) = 41.38 − 0.72 ( 13.58 ) h_{\text{wheel,out}} = h_{oa} - \varepsilon_t (h_{oa} - h_{ea}) = 41.38 - 0.72 \times (41.38 - 27.80) = 41.38 - 0.72(13.58) h wheel,out ​ = h o a ​ − ε t ​ ( h o a ​ − h e a ​ ) = 41.38 − 0.72 × ( 41.38 − 27.80 ) = 41.38 − 0.72 ( 13.58 ) h wheel,out = 41.38 − 9.778 = 31.60 Btu/lbm h_{\text{wheel,out}} = 41.38 - 9.778 = 31.60\text{ Btu/lbm} h wheel,out ​ = 41.38 − 9.778 = 31.60 Btu/lbm T wheel,out = T o a − ε s ( T o a − T e a ) = 95.0 − 0.75 × ( 95.0 − 75.0 ) = 95.0 − 15.0 = 80.0 ∘ F T_{\text{wheel,out}} = T_{oa} - \varepsilon_s (T_{oa} - T_{ea}) = 95.0 - 0.75 \times (95.0 - 75.0) = 95.0 - 15.0 = 80.0^\circ\text{F} T wheel,out ​ = T o a ​ − ε s ​ ( T o a ​ − T e a ​ ) = 95.0 − 0.75 × ( 95.0 − 75.0 ) = 95.0 − 15.0 = 80. 0 ∘ F W wheel,out = W o a − ε t ( W o a − W e a ) = 0.0168 − 0.72 × ( 0.0168 − 0.0092 ) = 0.0168 − 0.72 ( 0.0076 ) = 0.0113 lbm w / lbm d a W_{\text{wheel,out}} = W_{oa} - \varepsilon_t (W_{oa} - W_{ea}) = 0.0168 - 0.72 \times (0.0168 - 0.0092) = 0.0168 - 0.72(0.0076) = 0.0113\text{ lbm}_w/\text{lbm}_{da} W wheel,out ​ = W o a ​ − ε t ​ ( W o a ​ − W e a ​ ) = 0.0168 − 0.72 × ( 0.0168 − 0.0092 ) = 0.0168 − 0.72 ( 0.0076 ) = 0.0113 lbm w ​ / lbm d a ​

Step 2: Calculate thermal energy recovered by the wheel. Q ˙ recovered = 4.5 × CFM × ( h o a − h wheel,out ) = 4.5 × 8 , 000 × ( 41.38 − 31.60 ) \dot{Q}_{\text{recovered}} = 4.5 \times \text{CFM} \times (h_{oa} - h_{\text{wheel,out}}) = 4.5 \times 8,000 \times (41.38 - 31.60) Q ˙ ​ recovered ​ = 4.5 × CFM × ( h o a ​ − h wheel,out ​ ) = 4.5 × 8 , 000 × ( 41.38 − 31.60 ) Q ˙ recovered = 36 , 000 × 9.78 = 352 , 080 Btu/hr \dot{Q}_{\text{recovered}} = 36,000 \times 9.78 = 352,080\text{ Btu/hr} Q ˙ ​ recovered ​ = 36 , 000 × 9.78 = 352 , 080 Btu/hr Cooling Capacity Saved = 352 , 080 Btu/hr 12 , 000 Btu/(hr ⋅ ton) = 29.34 Tons \text{Cooling Capacity Saved} = \frac{352,080\text{ Btu/hr}}{12,000\text{ Btu/(hr}\cdot\text{ton)}} = 29.34\text{ Tons} Cooling Capacity Saved = 12 , 000 Btu/(hr ⋅ ton) 352 , 080 Btu/hr ​ = 29.34 Tons

Step 3: Calculate cooling coil thermal load. Q ˙ coil, total = 4.5 × CFM × ( h wheel,out − h c c ) = 4.5 × 8 , 000 × ( 31.60 − 20.80 ) \dot{Q}_{\text{coil, total}} = 4.5 \times \text{CFM} \times (h_{\text{wheel,out}} - h_{cc}) = 4.5 \times 8,000 \times (31.60 - 20.80) Q ˙ ​ coil, total ​ = 4.5 × CFM × ( h wheel,out ​ − h cc ​ ) = 4.5 × 8 , 000 × ( 31.60 − 20.80 ) Q ˙ coil, total = 36 , 000 × 10.80 = 388 , 800 Btu/hr \dot{Q}_{\text{coil, total}} = 36,000 \times 10.80 = 388,800\text{ Btu/hr} Q ˙ ​ coil, total ​ = 36 , 000 × 10.80 = 388 , 800 Btu/hr Coil Capacity (Tons) = 388 , 800 Btu/hr 12 , 000 Btu/(hr ⋅ ton) = 32.40 Tons \text{Coil Capacity (Tons)} = \frac{388,800\text{ Btu/hr}}{12,000\text{ Btu/(hr}\cdot\text{ton)}} = 32.40\text{ Tons} Coil Capacity (Tons) = 12 , 000 Btu/(hr ⋅ ton) 388 , 800 Btu/hr ​ = 32.40 Tons

(Note: Without the energy recovery wheel, the cooling coil would require 4.5 × 8 , 000 × ( 41.38 − 20.80 ) = 740 , 880 Btu/hr = 61.74 Tons 4.5 \times 8,000 \times (41.38 - 20.80) = 740,880\text{ Btu/hr} = 61.74\text{ Tons} 4.5 × 8 , 000 × ( 41.38 − 20.80 ) = 740 , 880 Btu/hr = 61.74 Tons . The wheel reduces cooling coil size by 47.5 % 47.5\% 47.5% ).

Step 4: Calculate fan heat temperature rise and final supply air temperature. Δ T fan = 0.3707 × Δ P t η t = 0.3707 × 2.80 in. wg 0.68 = 0.3707 × 4.1176 = 1.526 ∘ F ≈ 1.53 ∘ F \Delta T_{\text{fan}} = 0.3707 \times \frac{\Delta P_t}{\eta_t} = 0.3707 \times \frac{2.80\text{ in. wg}}{0.68} = 0.3707 \times 4.1176 = 1.526^\circ\text{F} \approx 1.53^\circ\text{F} Δ T fan ​ = 0.3707 × η t ​ Δ P t ​ ​ = 0.3707 × 0.68 2.80 in. wg ​ = 0.3707 × 4.1176 = 1.52 6 ∘ F ≈ 1.5 3 ∘ F T SA = T leaving coil + Δ T fan = 52.0 ∘ F + 1.53 ∘ F = 53.53 ∘ F T_{\text{SA}} = T_{\text{leaving coil}} + \Delta T_{\text{fan}} = 52.0^\circ\text{F} + 1.53^\circ\text{F} = 53.53^\circ\text{F} T SA ​ = T leaving coil ​ + Δ T fan ​ = 52. 0 ∘ F + 1.5 3 ∘ F = 53.5 3 ∘ F

7. NCEES Reference Handbook Navigation & Exam Tips

Psychrometric Energy Equations: Look in the HVAC section for Q ˙ s = 1.08 ⋅ CFM ⋅ Δ T \dot{Q}_s = 1.08 \cdot \text{CFM} \cdot \Delta T Q ˙ ​ s ​ = 1.08 ⋅ CFM ⋅ Δ T , Q ˙ l = 4840 ⋅ CFM ⋅ Δ W \dot{Q}_l = 4840 \cdot \text{CFM} \cdot \Delta W Q ˙ ​ l ​ = 4840 ⋅ CFM ⋅ Δ W , and Q ˙ t = 4.5 ⋅ CFM ⋅ Δ h \dot{Q}_t = 4.5 \cdot \text{CFM} \cdot \Delta h Q ˙ ​ t ​ = 4.5 ⋅ CFM ⋅ Δ h .

Fan Power & Heat Relations: Verify whether fan motor is inside or outside the airstream. If the motor is inside, divide total pressure by η fan × η motor \eta_{\text{fan}} \times \eta_{\text{motor}} η fan ​ × η motor ​ .

Enthalpy Wheel Conservation: When outdoor airflow ( CFM o a \text{CFM}_{oa} CFM o a ​ ) equals exhaust airflow ( CFM e a \text{CFM}_{ea} CFM e a ​ ), the effectiveness formula simplifies directly to linear interpolation of enthalpy, temperature, and humidity ratio.

Loading diagram... AHU & DOAS Functional Architecture