10.5 Variable Air Volume (VAV) Systems, Terminal Boxes & Space Air Diffusion (ADPI)
PE Mechanical: HVAC and Refrigeration Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview, Reference Handbook & Engineering Foundations
1.1 NCEES Exam Specification, CBT Delivery & Reference Handbook Strategy 1.2 Engineering Units, Dimensional Analysis & Physical Property Lookups 1.3 Engineering Economics, Life Cycle Cost Analysis & Equipment Financial Evaluation 1.4 Electrical Foundations, Motor Ratings & Variable Frequency Drives (VFDs)
2 Chapter 2: Thermodynamics & Energy Balances
2.1 First and Second Laws of Thermodynamics & Open/Closed System Energy Balances 2.2 Thermodynamic Cycles: Carnot, Rankine, Brayton & Reversed Carnot Limit 2.3 Gas & Vapor Property Evaluation: Steam Tables, Superheat & Subcooling 2.4 Mass, Energy & Combustion Balances for HVAC Equipment
3 Chapter 3: Psychrometrics, Moist Air Processes & Humidity Equipment
3.1 Psychrometric Properties: DBT, WBT, DPT, RH, Humidity Ratio & Enthalpy 3.2 Chart Reading & Psychrometric Equations at Sea Level vs. Altitude (5,000 ft) 3.3 Basic Psychrometric Processes: Sensible Heating/Cooling, Humidification & Dehumidification 3.4 Mixed Air Calculations & Complex Air Conditioning Cycles (Preheat, Reheat & Bypass) 3.5 Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP) & Coil Bypass Factor 3.6 Humidification & Dehumidification Equipment: Steam, Adiabatic, Desiccant & Low-Temperature Processes
4 Chapter 4: Heat Transfer Principles & Sizing
4.1 Steady-State Conduction & Multilayer Thermal Resistance (R-Value & U-Factor) 4.2 Convective Heat Transfer & Forced/Natural Convection Coefficients 4.3 Radiation Heat Transfer, Surface Emissivity & View Factors 4.4 Overall Heat Transfer Coefficients, Fouling Factors & Transient/Thermal Mass Effects 4.5 Heat Exchanger Analysis: Log Mean Temperature Difference (LMTD) & Effectiveness-NTU (ε-NTU)
5 Chapter 5: Fluid Mechanics & Hydraulic Fundamentals
5.1 Fluid Statics, Incompressible Continuity & Bernoulli Energy Equation 5.2 Pipe Friction, Moody Diagram & Darcy-Weisbach / Hazen-Williams Calculations 5.3 Minor Losses: Equivalent Length, Loss Coefficients (K-factors) & Total System Head 5.4 Pump Sizing, Net Positive Suction Head (NPSHa vs NPSHr) & Cavitation Prevention 5.5 Affinity Laws & Parallel/Series Pump/Fan System Curves
6 Chapter 6: Heating & Cooling Load Calculations
6.1 Outdoor & Indoor Design Conditions (ASHRAE Fundamentals, Climatic Data & Indoor Setpoints) 6.2 Envelope Heat Transmission & Infiltration/Exfiltration Load Methods 6.3 Solar Heat Gain (SHGC), Fenestration & Cooling Load Temperature Difference / Radiant Time Series (CLTD/RTS) 6.4 Internal Heat Gains: Lighting, People, Equipment & Diversity Factors 6.5 Ventilation Loads & Sensible / Latent / Total Cooling Load Synthesis
7 Chapter 7: Refrigeration Principles, Cycles & Cold Storage Applications
7.1 Standard Vapor-Compression Refrigeration Cycle on P-h & T-s Diagrams 7.2 Refrigeration Cycle Performance Metrics: COP, EER, SEER, kW/ton & Ton of Refrigeration 7.3 Cycle Enhancements: Subcooling, Superheating, Liquid-Suction Heat Exchangers & Economizers 7.4 Multi-Stage & Cascade Refrigeration Systems: Intercooling & Flash Gas Removal 7.5 Absorption Refrigeration Cycles: Water-Lithium Bromide & Ammonia-Water Systems 7.6 Food Processing & Cold Storage Refrigeration: Product Load, Pull-Down & Storage Design
8 Chapter 8: Refrigerants, Environmental Regulations & Safety
8.1 Refrigerant Classifications, Nomenclature & Thermodynamic Properties (ASHRAE Standard 34) 8.2 AIM Act, EPA Technology Transitions Sector GWP Limits & Low-GWP Refrigerants (R-32, R-454B) 8.3 Refrigerant Safety Requirements & Machinery Room Design (ASHRAE Standard 15) 8.4 Refrigerant Piping Sizing, Oil Return, Traps & Double Risers
9 Chapter 9: HVAC Equipment & Primary Machinery
9.1 Compressors: Reciprocating, Rotary, Scroll, Screw & Centrifugal 9.2 Condensers: Air-Cooled, Water-Cooled & Evaporative Condensers 9.3 Evaporators & Direct Expansion (DX) vs Liquid Chilling Coils 9.4 Water Chillers: Centrifugal, Screw & Scroll with ASHRAE 90.1 Path A/B IPLV Ratings 9.5 Cooling Towers: Range, Approach, Evaporation, Blowdown & Legionella Control 9.6 Heat Pumps & Variable Refrigerant Flow (VRF): Balance Point, Defrost & Heat Recovery 9.7 Thermal Energy Storage: Full vs. Partial Storage, Chilled Water & Ice Systems
10 Chapter 10: Air-Side Systems & Distribution
10.1 Air Handling Units (AHUs), Dedicated Outdoor Air Systems (DOAS) & Fan-Coil Units 10.2 Duct Design Methodologies: Equal Friction, Static Regain & Velocity Reduction 10.3 Duct Fittings, Dynamic Pressure Losses & SMACNA Construction Standards 10.4 Fan Types, Performance Curves, System Effect Factors & Surge/Stall Dynamics 10.5 Variable Air Volume (VAV) Systems, Terminal Boxes & Space Air Diffusion (ADPI) 10.6 Cooling & Heating Coil Selection: Face Velocity, Rows, Circuiting & Freeze Protection
11 Chapter 11: Hydronic, Steam & Fuel Distribution and Heating Plant
11.1 Hydronic System Architectures: Primary-Only, Primary-Secondary & Variable Primary Flow (VPF) 11.2 Hydronic Pipe Sizing, Velocity Limits & Closed/Open Expansion Tank Sizing 11.3 Control Valves: 2-Way vs 3-Way, Valve Authority (N), Cv Calculations & Characteristic Curves 11.4 Boilers & Heating Hot Water Systems: Condensing vs Non-Condensing & Water Treatment 11.5 Furnaces & Gas-Fired Heating Equipment: AFUE, Temperature Rise, Combustion Air & Vent Categories 11.6 Steam & Condensate Distribution: Latent Heat, Trap Selection, Flash Steam & Stall 11.7 Fuel Gas & Fuel Oil Piping: Demand, Sizing Method, Pressure Drop & Storage Systems
12 Chapter 12: HVAC Control Concepts, Sensors & Sequences
12.1 Sensors, Actuators & Dampers: Selection, Placement, Fail-Safe Position & Damper Authority 12.2 Control Loops: Proportional Offset, PID Action, Reset Strategies & Standard Sequences
13 Chapter 13: Building Energy, Ventilation & Indoor Environmental Quality Codes
13.1 ASHRAE Standard 62.1: Ventilation Rate Procedure (VRP), Indoor Air Quality Procedure & DCV 13.2 ASHRAE Standard 90.1: Building Energy Envelope, Mechanical Efficiency & Economizer Mandates 13.3 ASHRAE Standard 55: Thermal Environmental Conditions, PMV/PPD & Adaptive Comfort Models 13.4 Energy Recovery Systems: Enthalpy Wheels, Fixed-Plate Exchangers, Heat Pipes & Runaround Loops
14 Chapter 14: Supportive Engineering Knowledge, Life Safety & Operations
14.1 Air Filtration Standards: MERV Ratings (ASHRAE 52.2), HEPA & Gas-Phase Adsorption 14.2 Life Safety Systems: Fire/Smoke Dampers, Stairwell Pressurization (NFPA 92) & Smoke Control (NFPA 90A) 14.3 Acoustical Control & Vibration Isolation in HVAC Systems (NC / RC Criteria)
10.5 Variable Air Volume (VAV) Systems, Terminal Boxes & Space Air Diffusion (ADPI)
Key Takeaways Explain This Topic AI
Variable Air Volume (VAV) systems modulate zone supply airflow to match sensible cooling loads while maintaining constant 55 ∘ F 55^\circ\text{F} 5 5 ∘ F supply temperature, relying on minimum airflow setpoints ( 20 % 20\% 20% to 30 % 30\% 30% ) to satisfy ASHRAE 62.1 ventilation.
Series Fan-Powered VAV terminal units run their internal fan continuously to deliver constant airflow to space diffusers, mixing cold primary air with warm plenum air to eliminate cold air dumping and maintain constant room air motion.
Parallel Fan-Powered VAV terminal units operate their fan intermittently only during heating/reheat mode, offering lower annual fan electrical consumption than series units but exhibiting backdraft damper leakage.
The Air Diffusion Performance Index (ADPI) defines the percentage of occupied zone points where Effective Draft Temperature is − 3.0 ∘ F ≤ θ ≤ + 2.0 ∘ F -3.0^\circ\text{F} \le \theta \le +2.0^\circ\text{F} − 3. 0 ∘ F ≤ θ ≤ + 2. 0 ∘ F at air velocity V x ≤ 70 FPM V_x \le 70\text{ FPM} V x ≤ 70 FPM , where θ = ( T x − T c ) − 0.07 ( V x − 30 ) \theta = (T_x - T_c) - 0.07(V_x - 30) θ = ( T x − T c ) − 0.07 ( V x − 30 ) .
Diffuser selection optimizes the Throw-to-Length ratio ( T 50 / L T_{50}/L T 50 / L ), relying on the Coanda effect (ceiling surface attachment) to induce room air and prevent cold supply air from dumping into the occupied zone at low VAV part-load airflows.
Last updated: August 2026
10.5 Variable Air Volume (VAV) Systems, Terminal Boxes & Space Air Diffusion (ADPI)
Variable Air Volume (VAV) systems are the predominant air distribution design for modern commercial and institutional office buildings. Rather than varying supply air temperature at a constant flow rate, a VAV system delivers conditioned air at a constant supply temperature (typically 55.0 ∘ F 55.0^\circ\text{F} 55. 0 ∘ F / 12.8 ∘ C 12.8^\circ\text{C} 12. 8 ∘ C ) while modulating volumetric airflow rate ( CFM \text{CFM} CFM ) to match dynamic zone sensible thermal loads. On the PE Mechanical: HVAC and Refrigeration exam, VAV and air diffusion problems evaluate terminal box architectures (single-duct, series/parallel fan-powered), dual-maximum reheat sequences, Effective Draft Temperature ( θ \theta θ ), Air Diffusion Performance Index (ADPI), diffuser throw selection, and duct static pressure reset algorithms.
1. VAV Terminal Box Architectures & Operational Sequences
VAV terminal boxes (often called VAV units) regulate primary cold air entering individual thermal zones from the central AHU supply trunk. +---------------------------------------------------------------------------------------------------------+
- | VAV TERMINAL UNIT ARCHITECTURES |
- +---------------------------------------------------------------------------------------------------------+
- | |
- | 1. SINGLE-DUCT VAV WITH REHEAT: |
- | Primary Air (55°F) ===> [ Airflow Sensor + Damper ] ===> [ Reheat Coil (HW/Elec) ] ===> Diffusers |
- | |
- | 2. SERIES FAN-POWERED VAV (Constant Volume to Space): |
- | Primary Air (55°F) ===\ |
- | [ Continuous Terminal Fan ] ===> [ Reheat Coil ] ===> Diffusers (Constant CFM)|
- | Plenum Return (75°F) ==/ |
- | |
- | 3. PARALLEL FAN-POWERED VAV (Variable Volume to Space): |
- | Primary Air (55°F) ====================================> [ Reheat Coil ] ===> Diffusers (Variable) |
- | ^ |
- | Plenum Return (75°F) ===> [ Backdraft Damper + Fan ] ========/ (Fan runs ONLY during Reheat) |
- +---------------------------------------------------------------------------------------------------------+
- Detailed Engineering Comparison: Terminal Unit Types
Feature / Parameter Single-Duct VAV Series Fan-Powered VAV (FPU) Parallel Fan-Powered VAV (FPU)
Terminal Fan Operation No internal fan; relies 100% on central AHU fan. Terminal fan runs continuously whenever space is occupied. Terminal fan runs intermittently (only during heating/reheat mode).
Airflow Delivered to Room Variable: Drops from 100% cooling max down to 20%-30% minimum airflow. Constant: Delivers 100% constant design airflow to diffusers at all times. Variable: Variable in cooling (primary only); constant total in heating (primary min + fan).
Plenum Air Induction Zero plenum air induction. Induces warm ceiling plenum air ( 75 ∘ F 75^\circ\text{F} 7 5 ∘ F ) as primary damper modulates closed. Induces warm plenum air only when terminal fan cycles energized.
Diffuser Performance at Low Load High risk of cold air dumping if diffuser throw decays at minimum CFM. Zero dumping risk: Constant airflow preserves diffuser throw, induction, and room air mixing. Moderate dumping risk during low-load deadband cooling before fan starts.
Acoustic Characteristics Quietest operation; sound generated only by primary damper throttling. Constant white noise floor; sound does not change between heating and cooling. Intermittent noise stepping when terminal fan cycles on and off (can annoy occupants).
Annual Fan Energy Lowest fan energy; central VFD fan handles all airflow. Higher annual fan kWh (small fractional HP terminal motors run continuously). Low fan energy; terminal fan runs only during heating hours.
2. ASHRAE 90.1 Dual-Maximum Control Logic
Energy conservation standards (ASHRAE Standard 90.1) prohibit simultaneous heating and cooling (reheating primary cold air) unless airflow is throttled to a minimum ventilation baseline. ASHRAE 90.1 DUAL-MAXIMUM VAV CONTROL SEQUENCE:
- Airflow (CFM)
- ^
- Max +=============== ==============+ Max Heating
- Cool | \ / | Flow (~50%)
- Flow | \ / (Zone calls |
- | \ / for heat) |
- Min | \ / |
- Flow | +=====================================+ |
- | | DEADBAND (No Heat / No Cool) | |
- +-------------------+-------------------------------------+------------------+------> Zone Temp
- 68°F 72°F
- [ Cooling Mode ] [ Reheat Valve CLOSED ] [ Heating Mode: Reheat Active ]
Cooling Mode ( T zone > 72 ∘ F T_{\text{zone}} > 72^\circ\text{F} T zone > 7 2 ∘ F ): Reheat coil valve is closed. Primary damper modulates between V min V_{\min} V m i n ( 20 % 20\% 20% to 30 % 30\% 30% of maximum) and V max , cool V_{\max,\text{cool}} V m a x , cool ( 100 % 100\% 100% ).
Deadband ( 68 ∘ F ≤ T zone ≤ 72 ∘ F 68^\circ\text{F} \le T_{\text{zone}} \le 72^\circ\text{F} 6 8 ∘ F ≤ T zone ≤ 7 2 ∘ F ): Primary damper stays at V min V_{\min} V m i n to satisfy ASHRAE 62.1 outdoor air ventilation. Reheat valve remains closed.
Heating Mode ( T zone < 68 ∘ F T_{\text{zone}} < 68^\circ\text{F} T zone < 6 8 ∘ F ): As zone temperature drops, the reheat coil modulates open while maintaining V min V_{\min} V m i n . If maximum supply water temperature limit is reached ( T discharge ≤ 90 ∘ F T_{\text{discharge}} \le 90^\circ\text{F} T discharge ≤ 9 0 ∘ F to prevent ceiling thermal stratification), the damper is permitted to increase airflow up to V max , heat V_{\max,\text{heat}} V m a x , heat (typically 50 % 50\% 50% of cooling max).
3. Space Air Diffusion & Air Diffusion Performance Index (ADPI)
Space air diffusion is the aerodynamic process of distributing conditioned air into an occupied room to achieve uniform temperature, humidity, and velocity distribution without generating drafts or stagnant zones.
Occupied Zone Boundaries
ASHRAE Standard 55 defines the occupied zone as the room volume between:
Floor level to 6.0 feet 6.0\text{ feet} 6.0 feet ( 1.8 m 1.8\text{ m} 1.8 m ) above the floor.
2.0 feet 2.0\text{ feet} 2.0 feet ( 0.6 m 0.6\text{ m} 0.6 m ) inward from perimeter walls or stationary air conditioning equipment. CEILING AIR DIFFUSER DISCHARGE JET & COANDA ATTACHMENT:
- [ Supply Diffuser ]
- ===================+===================================== Ceiling Surface
- | ---> Supply Jet Clings to Ceiling (Coanda Effect)
- | Entrains Room Air & Warms Up
- |
- | Drop (d)
- \ /
- \ /
- v v
- +--------------------------------------------------------+ <--- 6.0 ft Occupied Zone Ceiling
- | |
- | OCCUPIED ZONE (-3°F <= Effective Draft Temp <= +2°F) |
- | Air Velocity: 30 FPM <= Vx <= 70 FPM (Ideal Comfort) |
- | |
- +--------------------------------------------------------+ <--- Floor Level
- Effective Draft Temperature ( θ \theta θ )
Thermal comfort combines air temperature differences and local convective air velocity. The Effective Draft Temperature ( θ \theta θ ) is defined by ASHRAE Fundamentals as: θ = ( T x − T c ) − 0.07 ( V x − 30 ) \theta = (T_x - T_c) - 0.07 (V_x - 30) θ = ( T x − T c ) − 0.07 ( V x − 30 )
Where:
- θ \theta θ = Effective Draft Temperature ( ∘ F ^\circ\text{F} ∘ F )
- T x T_x T x = Local airstream dry-bulb temperature at test point ( ∘ F ^\circ\text{F} ∘ F )
- T c T_c T c = Average room control dry-bulb temperature ( ∘ F ^\circ\text{F} ∘ F )
- V x V_x V x = Local air velocity at test point in feet per minute ( FPM \text{FPM} FPM )
- ADPI Comfort Criteria
A test point within the occupied zone satisfies thermal comfort if: − 3.0 ∘ F ≤ θ ≤ + 2.0 ∘ F and V x ≤ 70 FPM -3.0^\circ\text{F} \le \theta \le +2.0^\circ\text{F} \quad \text{and} \quad V_x \le 70\text{ FPM} − 3. 0 ∘ F ≤ θ ≤ + 2. 0 ∘ F and V x ≤ 70 FPM
If θ < − 3.0 ∘ F \theta < -3.0^\circ\text{F} θ < − 3. 0 ∘ F : Occupants perceive an unacceptable cold draft .
If θ > + 2.0 ∘ F \theta > +2.0^\circ\text{F} θ > + 2. 0 ∘ F : Occupants perceive stagnant, stuffy conditions .
If V x > 70 FPM V_x > 70\text{ FPM} V x > 70 FPM : Excessive air movement causes draft discomfort regardless of temperature.
Air Diffusion Performance Index (ADPI) Definition ADPI = ( Number of Measurement Points Meeting Comfort Criteria Total Number of Measurement Points in Occupied Zone ) × 100 % \text{ADPI} = \left(\frac{\text{Number of Measurement Points Meeting Comfort Criteria}}{\text{Total Number of Measurement Points in Occupied Zone}}\right) \times 100\% ADPI = ( Total Number of Measurement Points in Occupied Zone Number of Measurement Points Meeting Comfort Criteria ) × 100%
Design Target: A high-performance air distribution system achieves ADPI ≥ 80 % \text{ADPI} \ge 80\% ADPI ≥ 80% across both full-load and part-load VAV operating conditions.
- 4. Diffuser Throw, Induction & The Coanda Effect
- Key Diffuser Aerodynamic Metrics
Throw ( T 150 , T 100 , T 50 T_{150}, T_{100}, T_{50} T 150 , T 100 , T 50 ): The linear distance from the diffuser face to the point where the discharge jet centerline velocity decays to 150 FPM 150\text{ FPM} 150 FPM , 100 FPM 100\text{ FPM} 100 FPM , or 50 FPM 50\text{ FPM} 50 FPM .
Characteristic Room Length ( L L L ): The distance from the diffuser centerline to the nearest wall or to the mid-point collision line between opposing diffusers.
Throw-to-Length Ratio ( T 50 / L T_{50}/L T 50 / L ): The primary engineering sizing ratio for diffuser selection to maximize ADPI.
Coanda Effect (Surface Attachment): When cold air is discharged parallel to a ceiling, the constraint of the solid surface prevents ambient air from being entrained from above. This generates a localized low-pressure zone between the air jet and ceiling, causing the jet to cling to the ceiling surface for extended distances. This surface attachment allows cold primary air ( 55 ∘ F 55^\circ\text{F} 5 5 ∘ F ) to induce warm room air and temper to 68 ∘ − 70 ∘ F 68^\circ-70^\circ\text{F} 6 8 ∘ − 7 0 ∘ F before dropping into the occupied space.
Optimal T 50 / L T_{50}/L T 50 / L Sizing Matrix for Maximum ADPI
Diffuser Type Characteristic Length ( L L L ) Optimal T 50 / L T_{50}/L T 50 / L Ratio Max ADPI Achievable
Louvered / Cone Ceiling Diffuser (4-Way) Distance to wall or mid-point 1.0 1.0 1.0 to 2.0 2.0 2.0 (Peak at 1.5 1.5 1.5 ) 85 % 85\% 85% to 92 % 92\% 92%
Perforated Face Diffuser Distance to wall or mid-point 1.0 1.0 1.0 to 2.0 2.0 2.0 (Peak at 1.4 1.4 1.4 ) 88 % 88\% 88% to 95 % 95\% 95%
Linear Slot Diffuser Distance to wall perpendicular to slot 1.0 1.0 1.0 to 1.8 1.8 1.8 (Peak at 1.2 1.2 1.2 ) 80 % 80\% 80% to 90 % 90\% 90%
High-Induction Swirl Diffuser Distance to mid-point 0.6 0.6 0.6 to 1.2 1.2 1.2 (Peak at 0.8 0.8 0.8 ) 90 % 90\% 90% to 96 % 96\% 96%
5. Duct Static Pressure Reset (Trim and Respond)
ASHRAE Standard 90.1 mandates that multi-zone VAV systems with DDC controls implement dynamic static pressure reset .
Traditional Control: Supply fan modulates VFD to maintain a fixed static pressure setpoint ( 1.5 in. wg 1.5\text{ in. wg} 1.5 in. wg ) measured at a static pressure sensor located 2 / 3 2/3 2/3 down the main duct trunk.
Trim and Respond Algorithm: The building automation system (BAS) continuously monitors all VAV box damper positions. If the most open damper is only 60 % 60\% 60% open, the AHU fan speed is trimmed downward, dropping the duct static setpoint until at least one critical VAV box damper opens to 90 % 90\% 90% to 95 % 95\% 95% .
Energy Impact: Reducing duct static pressure from 1.5 in. wg 1.5\text{ in. wg} 1.5 in. wg down to 0.8 in. wg 0.8\text{ in. wg} 0.8 in. wg during part-load hours slashes central fan electrical consumption by 30 % 30\% 30% to 50 % 50\% 50% while eliminating high-pressure duct hiss.
6. Worked Example: VAV Box Mixed Air & ADPI Point Evaluation
Problem: A Series Fan-Powered Terminal Unit (FPU) serves a corner conference room. The terminal fan delivers a constant airflow of 1 , 200 CFM 1,200\text{ CFM} 1 , 200 CFM to four ceiling diffusers. Primary cold air is supplied at 55.0 ∘ F 55.0^\circ\text{F} 55. 0 ∘ F ( h p = 23.22 Btu/lbm h_p = 23.22\text{ Btu/lbm} h p = 23.22 Btu/lbm ). Ceiling plenum return air is at 76.0 ∘ F 76.0^\circ\text{F} 76. 0 ∘ F ( h plenum = 28.50 Btu/lbm h_{\text{plenum}} = 28.50\text{ Btu/lbm} h plenum = 28.50 Btu/lbm ). The room thermostat setpoint is T c = 74.0 ∘ F T_c = 74.0^\circ\text{F} T c = 74. 0 ∘ F .
Part A: When the room sensible cooling load is 16 , 200 Btu/hr 16,200\text{ Btu/hr} 16 , 200 Btu/hr , calculate:
The required supply air temperature ( T supply T_{\text{supply}} T supply ) delivered by the terminal unit.
The required primary airflow rate ( CFM primary \text{CFM}_{\text{primary}} CFM primary ) and induced plenum airflow rate ( CFM plenum \text{CFM}_{\text{plenum}} CFM plenum ).
Part B: In the occupied zone, air velocity and temperature are measured at two locations:
Point 1: T 1 = 72.0 ∘ F T_1 = 72.0^\circ\text{F} T 1 = 72. 0 ∘ F , V 1 = 45 FPM V_1 = 45\text{ FPM} V 1 = 45 FPM
Point 2: T 2 = 69.5 ∘ F T_2 = 69.5^\circ\text{F} T 2 = 69. 5 ∘ F , V 2 = 80 FPM V_2 = 80\text{ FPM} V 2 = 80 FPM Calculate the Effective Draft Temperature ( θ \theta θ ) for each point and determine whether each point satisfies the ADPI thermal comfort criteria.
Step-by-Step Solution:
Part A: Calculate supply temperature and primary airflow: Q ˙ s = 1.08 × CFM total × ( T room − T supply ) \dot{Q}_s = 1.08 \times \text{CFM}_{\text{total}} \times (T_{\text{room}} - T_{\text{supply}}) Q ˙ s = 1.08 × CFM total × ( T room − T supply ) 16 , 200 Btu/hr = 1.08 × 1 , 200 CFM × ( 74.0 ∘ F − T supply ) 16,200\text{ Btu/hr} = 1.08 \times 1,200\text{ CFM} \times (74.0^\circ\text{F} - T_{\text{supply}}) 16 , 200 Btu/hr = 1.08 × 1 , 200 CFM × ( 74. 0 ∘ F − T supply ) 16 , 200 = 1 , 296 × ( 74.0 − T supply ) 16,200 = 1,296 \times (74.0 - T_{\text{supply}}) 16 , 200 = 1 , 296 × ( 74.0 − T supply ) 74.0 − T supply = 16 , 200 1 , 296 = 12.50 ∘ F 74.0 - T_{\text{supply}} = \frac{16,200}{1,296} = 12.50^\circ\text{F} 74.0 − T supply = 1 , 296 16 , 200 = 12.5 0 ∘ F T supply = 74.0 ∘ F − 12.50 ∘ F = 61.50 ∘ F T_{\text{supply}} = 74.0^\circ\text{F} - 12.50^\circ\text{F} = 61.50^\circ\text{F} T supply = 74. 0 ∘ F − 12.5 0 ∘ F = 61.5 0 ∘ F
Now, perform a sensible energy balance across the series mixing plenum ( T supply = 61.50 ∘ F T_{\text{supply}} = 61.50^\circ\text{F} T supply = 61.5 0 ∘ F ): T supply = CFM p ⋅ T p + CFM plenum ⋅ T plenum CFM total T_{\text{supply}} = \frac{\text{CFM}_p \cdot T_p + \text{CFM}_{\text{plenum}} \cdot T_{\text{plenum}}}{\text{CFM}_{\text{total}}} T supply = CFM total CFM p ⋅ T p + CFM plenum ⋅ T plenum 61.50 = CFM p × 55.0 + ( 1 , 200 − CFM p ) × 76.0 1 , 200 61.50 = \frac{\text{CFM}_p \times 55.0 + (1,200 - \text{CFM}_p) \times 76.0}{1,200} 61.50 = 1 , 200 CFM p × 55.0 + ( 1 , 200 − CFM p ) × 76.0 61.50 × 1 , 200 = 55.0 ⋅ CFM p + 91 , 200 − 76.0 ⋅ CFM p 61.50 \times 1,200 = 55.0 \cdot \text{CFM}_p + 91,200 - 76.0 \cdot \text{CFM}_p 61.50 × 1 , 200 = 55.0 ⋅ CFM p + 91 , 200 − 76.0 ⋅ CFM p 73 , 800 = 91 , 200 − 21.0 ⋅ CFM p 73,800 = 91,200 - 21.0 \cdot \text{CFM}_p 73 , 800 = 91 , 200 − 21.0 ⋅ CFM p 21.0 ⋅ CFM p = 91 , 200 − 73 , 800 = 17 , 400 21.0 \cdot \text{CFM}_p = 91,200 - 73,800 = 17,400 21.0 ⋅ CFM p = 91 , 200 − 73 , 800 = 17 , 400 CFM p = 17 , 400 21.0 = 828.57 CFM ≈ 829 CFM \text{CFM}_p = \frac{17,400}{21.0} = 828.57\text{ CFM} \approx 829\text{ CFM} CFM p = 21.0 17 , 400 = 828.57 CFM ≈ 829 CFM CFM plenum = 1 , 200 − 829 = 371 CFM \text{CFM}_{\text{plenum}} = 1,200 - 829 = 371\text{ CFM} CFM plenum = 1 , 200 − 829 = 371 CFM
Part B: Evaluate Effective Draft Temperatures (theta): Effective Draft Temperature Formula: θ = ( T x − T c ) − 0.07 ( V x − 30 ) \text{Effective Draft Temperature Formula: } \theta = (T_x - T_c) - 0.07 (V_x - 30) Effective Draft Temperature Formula: θ = ( T x − T c ) − 0.07 ( V x − 30 )
Point 1 ( T 1 = 72.0 ∘ F T_1 = 72.0^\circ\text{F} T 1 = 72. 0 ∘ F , V 1 = 45 FPM V_1 = 45\text{ FPM} V 1 = 45 FPM ): θ 1 = ( 72.0 − 74.0 ) − 0.07 ( 45 − 30 ) = − 2.0 − 0.07 ( 15 ) = − 2.0 − 1.05 = − 3.05 ∘ F \theta_1 = (72.0 - 74.0) - 0.07(45 - 30) = -2.0 - 0.07(15) = -2.0 - 1.05 = -3.05^\circ\text{F} θ 1 = ( 72.0 − 74.0 ) − 0.07 ( 45 − 30 ) = − 2.0 − 0.07 ( 15 ) = − 2.0 − 1.05 = − 3.0 5 ∘ F
θ 1 = − 3.05 ∘ F \theta_1 = -3.05^\circ\text{F} θ 1 = − 3.0 5 ∘ F (Fails comfort threshold − 3.0 ∘ F ≤ θ ≤ + 2.0 ∘ F -3.0^\circ\text{F} \le \theta \le +2.0^\circ\text{F} − 3. 0 ∘ F ≤ θ ≤ + 2. 0 ∘ F ; slight cold draft).
V 1 = 45 FPM < 70 FPM V_1 = 45\text{ FPM} < 70\text{ FPM} V 1 = 45 FPM < 70 FPM (Velocity acceptable).
Conclusion for Point 1: FAILS ADPI criteria due to draft.
Point 2 ( T 2 = 69.5 ∘ F T_2 = 69.5^\circ\text{F} T 2 = 69. 5 ∘ F , V 2 = 80 FPM V_2 = 80\text{ FPM} V 2 = 80 FPM ): θ 2 = ( 69.5 − 74.0 ) − 0.07 ( 80 − 30 ) = − 4.5 − 0.07 ( 50 ) = − 4.5 − 3.50 = − 8.00 ∘ F \theta_2 = (69.5 - 74.0) - 0.07(80 - 30) = -4.5 - 0.07(50) = -4.5 - 3.50 = -8.00^\circ\text{F} θ 2 = ( 69.5 − 74.0 ) − 0.07 ( 80 − 30 ) = − 4.5 − 0.07 ( 50 ) = − 4.5 − 3.50 = − 8.0 0 ∘ F
θ 2 = − 8.00 ∘ F \theta_2 = -8.00^\circ\text{F} θ 2 = − 8.0 0 ∘ F (Severe cold draft failure).
V 2 = 80 FPM > 70 FPM V_2 = 80\text{ FPM} > 70\text{ FPM} V 2 = 80 FPM > 70 FPM (Velocity exceeds maximum comfort limit).
Conclusion for Point 2: FAILS ADPI criteria.
7. NCEES Reference Handbook Navigation & Exam Tips
Effective Draft Temperature: Look in the Space Air Diffusion section of the Mechanical Reference Handbook for θ = ( T x − T c ) − 0.07 ( V x − 30 ) \theta = (T_x - T_c) - 0.07(V_x - 30) θ = ( T x − T c ) − 0.07 ( V x − 30 ) .
ADPI Criteria: Remember that a test point passes if and only if − 3.0 ∘ F ≤ θ ≤ + 2.0 ∘ F -3.0^\circ\text{F} \le \theta \le +2.0^\circ\text{F} − 3. 0 ∘ F ≤ θ ≤ + 2. 0 ∘ F AND V x ≤ 70 FPM V_x \le 70\text{ FPM} V x ≤ 70 FPM .
Coanda Throw Rule: For diffusers with surface attachment (Coanda), catalog throw values are approximately 1.4 × 1.4\times 1.4 × to 1.5 × 1.5\times 1.5 × longer than for non-attached (free jet) discharge.