13.4 Energy Recovery Systems: Enthalpy Wheels, Fixed-Plate Exchangers, Heat Pipes & Runaround Loops
PE Mechanical: HVAC and Refrigeration Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview, Reference Handbook & Engineering Foundations
1.1 NCEES Exam Specification, CBT Delivery & Reference Handbook Strategy 1.2 Engineering Units, Dimensional Analysis & Physical Property Lookups 1.3 Engineering Economics, Life Cycle Cost Analysis & Equipment Financial Evaluation 1.4 Electrical Foundations, Motor Ratings & Variable Frequency Drives (VFDs)
2 Chapter 2: Thermodynamics & Energy Balances
2.1 First and Second Laws of Thermodynamics & Open/Closed System Energy Balances 2.2 Thermodynamic Cycles: Carnot, Rankine, Brayton & Reversed Carnot Limit 2.3 Gas & Vapor Property Evaluation: Steam Tables, Superheat & Subcooling 2.4 Mass, Energy & Combustion Balances for HVAC Equipment
3 Chapter 3: Psychrometrics, Moist Air Processes & Humidity Equipment
3.1 Psychrometric Properties: DBT, WBT, DPT, RH, Humidity Ratio & Enthalpy 3.2 Chart Reading & Psychrometric Equations at Sea Level vs. Altitude (5,000 ft) 3.3 Basic Psychrometric Processes: Sensible Heating/Cooling, Humidification & Dehumidification 3.4 Mixed Air Calculations & Complex Air Conditioning Cycles (Preheat, Reheat & Bypass) 3.5 Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP) & Coil Bypass Factor 3.6 Humidification & Dehumidification Equipment: Steam, Adiabatic, Desiccant & Low-Temperature Processes
4 Chapter 4: Heat Transfer Principles & Sizing
4.1 Steady-State Conduction & Multilayer Thermal Resistance (R-Value & U-Factor) 4.2 Convective Heat Transfer & Forced/Natural Convection Coefficients 4.3 Radiation Heat Transfer, Surface Emissivity & View Factors 4.4 Overall Heat Transfer Coefficients, Fouling Factors & Transient/Thermal Mass Effects 4.5 Heat Exchanger Analysis: Log Mean Temperature Difference (LMTD) & Effectiveness-NTU (ε-NTU)
5 Chapter 5: Fluid Mechanics & Hydraulic Fundamentals
5.1 Fluid Statics, Incompressible Continuity & Bernoulli Energy Equation 5.2 Pipe Friction, Moody Diagram & Darcy-Weisbach / Hazen-Williams Calculations 5.3 Minor Losses: Equivalent Length, Loss Coefficients (K-factors) & Total System Head 5.4 Pump Sizing, Net Positive Suction Head (NPSHa vs NPSHr) & Cavitation Prevention 5.5 Affinity Laws & Parallel/Series Pump/Fan System Curves
6 Chapter 6: Heating & Cooling Load Calculations
6.1 Outdoor & Indoor Design Conditions (ASHRAE Fundamentals, Climatic Data & Indoor Setpoints) 6.2 Envelope Heat Transmission & Infiltration/Exfiltration Load Methods 6.3 Solar Heat Gain (SHGC), Fenestration & Cooling Load Temperature Difference / Radiant Time Series (CLTD/RTS) 6.4 Internal Heat Gains: Lighting, People, Equipment & Diversity Factors 6.5 Ventilation Loads & Sensible / Latent / Total Cooling Load Synthesis
7 Chapter 7: Refrigeration Principles, Cycles & Cold Storage Applications
7.1 Standard Vapor-Compression Refrigeration Cycle on P-h & T-s Diagrams 7.2 Refrigeration Cycle Performance Metrics: COP, EER, SEER, kW/ton & Ton of Refrigeration 7.3 Cycle Enhancements: Subcooling, Superheating, Liquid-Suction Heat Exchangers & Economizers 7.4 Multi-Stage & Cascade Refrigeration Systems: Intercooling & Flash Gas Removal 7.5 Absorption Refrigeration Cycles: Water-Lithium Bromide & Ammonia-Water Systems 7.6 Food Processing & Cold Storage Refrigeration: Product Load, Pull-Down & Storage Design
8 Chapter 8: Refrigerants, Environmental Regulations & Safety
8.1 Refrigerant Classifications, Nomenclature & Thermodynamic Properties (ASHRAE Standard 34) 8.2 AIM Act, EPA Technology Transitions Sector GWP Limits & Low-GWP Refrigerants (R-32, R-454B) 8.3 Refrigerant Safety Requirements & Machinery Room Design (ASHRAE Standard 15) 8.4 Refrigerant Piping Sizing, Oil Return, Traps & Double Risers
9 Chapter 9: HVAC Equipment & Primary Machinery
9.1 Compressors: Reciprocating, Rotary, Scroll, Screw & Centrifugal 9.2 Condensers: Air-Cooled, Water-Cooled & Evaporative Condensers 9.3 Evaporators & Direct Expansion (DX) vs Liquid Chilling Coils 9.4 Water Chillers: Centrifugal, Screw & Scroll with ASHRAE 90.1 Path A/B IPLV Ratings 9.5 Cooling Towers: Range, Approach, Evaporation, Blowdown & Legionella Control 9.6 Heat Pumps & Variable Refrigerant Flow (VRF): Balance Point, Defrost & Heat Recovery 9.7 Thermal Energy Storage: Full vs. Partial Storage, Chilled Water & Ice Systems
10 Chapter 10: Air-Side Systems & Distribution
10.1 Air Handling Units (AHUs), Dedicated Outdoor Air Systems (DOAS) & Fan-Coil Units 10.2 Duct Design Methodologies: Equal Friction, Static Regain & Velocity Reduction 10.3 Duct Fittings, Dynamic Pressure Losses & SMACNA Construction Standards 10.4 Fan Types, Performance Curves, System Effect Factors & Surge/Stall Dynamics 10.5 Variable Air Volume (VAV) Systems, Terminal Boxes & Space Air Diffusion (ADPI) 10.6 Cooling & Heating Coil Selection: Face Velocity, Rows, Circuiting & Freeze Protection
11 Chapter 11: Hydronic, Steam & Fuel Distribution and Heating Plant
11.1 Hydronic System Architectures: Primary-Only, Primary-Secondary & Variable Primary Flow (VPF) 11.2 Hydronic Pipe Sizing, Velocity Limits & Closed/Open Expansion Tank Sizing 11.3 Control Valves: 2-Way vs 3-Way, Valve Authority (N), Cv Calculations & Characteristic Curves 11.4 Boilers & Heating Hot Water Systems: Condensing vs Non-Condensing & Water Treatment 11.5 Furnaces & Gas-Fired Heating Equipment: AFUE, Temperature Rise, Combustion Air & Vent Categories 11.6 Steam & Condensate Distribution: Latent Heat, Trap Selection, Flash Steam & Stall 11.7 Fuel Gas & Fuel Oil Piping: Demand, Sizing Method, Pressure Drop & Storage Systems
12 Chapter 12: HVAC Control Concepts, Sensors & Sequences
12.1 Sensors, Actuators & Dampers: Selection, Placement, Fail-Safe Position & Damper Authority 12.2 Control Loops: Proportional Offset, PID Action, Reset Strategies & Standard Sequences
13 Chapter 13: Building Energy, Ventilation & Indoor Environmental Quality Codes
13.1 ASHRAE Standard 62.1: Ventilation Rate Procedure (VRP), Indoor Air Quality Procedure & DCV 13.2 ASHRAE Standard 90.1: Building Energy Envelope, Mechanical Efficiency & Economizer Mandates 13.3 ASHRAE Standard 55: Thermal Environmental Conditions, PMV/PPD & Adaptive Comfort Models 13.4 Energy Recovery Systems: Enthalpy Wheels, Fixed-Plate Exchangers, Heat Pipes & Runaround Loops
14 Chapter 14: Supportive Engineering Knowledge, Life Safety & Operations
14.1 Air Filtration Standards: MERV Ratings (ASHRAE 52.2), HEPA & Gas-Phase Adsorption 14.2 Life Safety Systems: Fire/Smoke Dampers, Stairwell Pressurization (NFPA 92) & Smoke Control (NFPA 90A) 14.3 Acoustical Control & Vibration Isolation in HVAC Systems (NC / RC Criteria)
13.4 Energy Recovery Systems: Enthalpy Wheels, Fixed-Plate Exchangers, Heat Pipes & Runaround Loops
Key Takeaways Explain This Topic AI
Air-to-air energy recovery systems transfer sensible heat and/or latent moisture between building exhaust air and incoming outdoor ventilation air, dramatically reducing peak mechanical heating/cooling loads and annual HVAC operating energy.
ASHRAE Standard 90.1 prescriptively mandates Energy Recovery Ventilation (ERV) for fan systems meeting specific design airflow and percent outdoor air thresholds, requiring a minimum 50% enthalpy recovery ratio (ERR) or 60% sensible energy recovery effectiveness.
The four primary energy recovery device technologies—rotary enthalpy wheels, fixed-plate heat exchangers, heat pipes, and runaround coil loops—differ fundamentally in sensible vs. latent effectiveness, cross-contamination risk (Exhaust Air Transfer Ratio - EATR), and duct proximity constraints.
AHRI Standard 1060 governs thermal effectiveness ratings (epsilon = C_s * Delta_X_s / (C_min * Delta_X_max)); frost mitigation controls (preheat, face-and-bypass, wheel speed modulation) are required when exhaust air drops below freezing in cold outdoor climates.
Last updated: August 2026
13.4 Energy Recovery Systems: Enthalpy Wheels, Fixed-Plate Exchangers, Heat Pipes & Runaround Loops
Outdoor air ventilation represents one of the largest thermal energy loads in modern commercial HVAC systems. In a 100 % 100\% 100% Dedicated Outdoor Air System (DOAS), conditioning raw ambient air requires substantial sensible and latent energy. Energy Recovery Ventilation (ERV) and Heat Recovery Ventilation (HRV) systems capture thermal energy from departing building exhaust air to pre-condition incoming outdoor ventilation air. ASHRAE Standard 90.1 establishes prescriptive mandates for energy recovery based on supply airflow ( CFM \text{CFM} CFM ), percent outdoor air, and local climate zone.
1. Governing Heat Exchanger Thermodynamics & AHRI Standard 1060
AHRI Standard 1060 ( Performance Rating of Air-to-Air Heat Exchangers for Energy Recovery Ventilation Equipment ) defines thermal effectiveness ( ϵ \epsilon ϵ ) across sensible, latent, and total enthalpy domains: +---------------------------------------------------------------------------------------------------------+
- | ENERGY RECOVERY AIRSTREAM CONFIGURATION & NOMENCLATURE |
- +---------------------------------------------------------------------------------------------------------+
- | |
- | Outdoor Air (Supply Inlet: State 1) -------> [ ENERGY RECOVERY ] -------> Leaving Supply (State 2) |
- | (T_s1, W_s1, h_s1, CFM_s) [ EXCHANGER ] (T_s2, W_s2, h_s2) |
- | [ ] |
- | Leaving Exhaust (State 4) <----------------- [ (Sensible/Total)] <------- Exhaust Air (Inlet: State 3)|
- | (T_e2, W_e2, h_e2) (T_e1, W_e1, h_e1, CFM_e) |
- | |
- +---------------------------------------------------------------------------------------------------------+
- AHRI 1060 Thermal Effectiveness Formulations
Sensible Effectiveness ( ϵ s \epsilon_s ϵ s ): ϵ s = m ˙ s ⋅ c p ⋅ ( T s 2 − T s 1 ) C ˙ min ⋅ ( T e 1 − T s 1 ) \epsilon_s = \frac{\dot{m}_s \cdot c_p \cdot (T_{s2} - T_{s1})}{\dot{C}_{\min} \cdot (T_{e1} - T_{s1})} ϵ s = C ˙ m i n ⋅ ( T e 1 − T s 1 ) m ˙ s ⋅ c p ⋅ ( T s 2 − T s 1 )
When supply and exhaust mass flow rates are balanced ( m ˙ s = m ˙ e \dot{m}_s = \dot{m}_e m ˙ s = m ˙ e ): ϵ s = T s 2 − T s 1 T e 1 − T s 1 ⟹ T s 2 = T s 1 + ϵ s ( T e 1 − T s 1 ) \epsilon_s = \frac{T_{s2} - T_{s1}}{T_{e1} - T_{s1}} \implies T_{s2} = T_{s1} + \epsilon_s (T_{e1} - T_{s1}) ϵ s = T e 1 − T s 1 T s 2 − T s 1 ⟹ T s 2 = T s 1 + ϵ s ( T e 1 − T s 1 )
Latent Effectiveness ( ϵ L \epsilon_L ϵ L ): ϵ L = m ˙ s ⋅ ( W s 2 − W s 1 ) m ˙ min ⋅ ( W e 1 − W s 1 ) \epsilon_L = \frac{\dot{m}_s \cdot (W_{s2} - W_{s1})}{\dot{m}_{\min} \cdot (W_{e1} - W_{s1})} ϵ L = m ˙ m i n ⋅ ( W e 1 − W s 1 ) m ˙ s ⋅ ( W s 2 − W s 1 )
When mass flows are balanced: ϵ L = W s 2 − W s 1 W e 1 − W s 1 ⟹ W s 2 = W s 1 + ϵ L ( W e 1 − W s 1 ) \epsilon_L = \frac{W_{s2} - W_{s1}}{W_{e1} - W_{s1}} \implies W_{s2} = W_{s1} + \epsilon_L (W_{e1} - W_{s1}) ϵ L = W e 1 − W s 1 W s 2 − W s 1 ⟹ W s 2 = W s 1 + ϵ L ( W e 1 − W s 1 )
Total (Enthalpy) Effectiveness ( ϵ t \epsilon_t ϵ t ): ϵ t = m ˙ s ⋅ ( h s 2 − h s 1 ) m ˙ min ⋅ ( h e 1 − h s 1 ) \epsilon_t = \frac{\dot{m}_s \cdot (h_{s2} - h_{s1})}{\dot{m}_{\min} \cdot (h_{e1} - h_{s1})} ϵ t = m ˙ m i n ⋅ ( h e 1 − h s 1 ) m ˙ s ⋅ ( h s 2 − h s 1 )
When mass flows are balanced: ϵ t = h s 2 − h s 1 h e 1 − h s 1 ⟹ h s 2 = h s 1 + ϵ t ( h e 1 − h s 1 ) \epsilon_t = \frac{h_{s2} - h_{s1}}{h_{e1} - h_{s1}} \implies h_{s2} = h_{s1} + \epsilon_t (h_{e1} - h_{s1}) ϵ t = h e 1 − h s 1 h s 2 − h s 1 ⟹ h s 2 = h s 1 + ϵ t ( h e 1 − h s 1 )
Where:
T = Dry-bulb temperature ( ∘ F ) T = \text{Dry-bulb temperature } (^\circ\text{F}) T = Dry-bulb temperature ( ∘ F )
W = Humidity ratio ( lbm water / lbm dry air or grains/lbm ) W = \text{Humidity ratio } (\text{lbm}_{\text{water}}/\text{lbm}_{\text{dry air}} \text{ or } \text{grains/lbm}) W = Humidity ratio ( lbm water / lbm dry air or grains/lbm )
h = Enthalpy ( Btu/lbm dry air ) h = \text{Enthalpy } (\text{Btu/lbm}_{\text{dry air}}) h = Enthalpy ( Btu/lbm dry air )
C ˙ min = min ( m ˙ s c p , m ˙ e c p ) = Minimum heat capacity rate \dot{C}_{\min} = \min(\dot{m}_s c_p, \dot{m}_e c_p) = \text{Minimum heat capacity rate} C ˙ m i n = min ( m ˙ s c p , m ˙ e c p ) = Minimum heat capacity rate
Psychrometric Energy Transfer Rates Q ˙ total = 4.5 ⋅ CFM ⋅ ∣ h s 1 − h s 2 ∣ ( Btu/h ) \dot{Q}_{\text{total}} = 4.5 \cdot \text{CFM} \cdot |h_{s1} - h_{s2}| \quad (\text{Btu/h}) Q ˙ total = 4.5 ⋅ CFM ⋅ ∣ h s 1 − h s 2 ∣ ( Btu/h ) Q ˙ sensible = 1.08 ⋅ CFM ⋅ ∣ T s 1 − T s 2 ∣ ( Btu/h ) \dot{Q}_{\text{sensible}} = 1.08 \cdot \text{CFM} \cdot |T_{s1} - T_{s2}| \quad (\text{Btu/h}) Q ˙ sensible = 1.08 ⋅ CFM ⋅ ∣ T s 1 − T s 2 ∣ ( Btu/h ) Q ˙ latent = 4 , 840 ⋅ CFM ⋅ ∣ W s 1 − W s 2 ∣ ( Btu/h ) \dot{Q}_{\text{latent}} = 4,840 \cdot \text{CFM} \cdot |W_{s1} - W_{s2}| \quad (\text{Btu/h}) Q ˙ latent = 4 , 840 ⋅ CFM ⋅ ∣ W s 1 − W s 2 ∣ ( Btu/h )
2. Comparison of Energy Recovery Device Technologies
Four primary heat exchanger architectures are utilized in commercial HVAC engineering: +---------------------------------------------------------------------------------------------------------+
- | COMPARATIVE MATRIX OF ENERGY RECOVERY TECHNOLOGIES |
- +---------------------+-------------------+-------------------+-------------------+-----------------------+
- | FEATURE | ROTARY WHEEL | FIXED-PLATE | HEAT PIPES | RUNAROUND COIL LOOP |
- +---------------------+-------------------+-------------------+-------------------+-----------------------+
- | Energy Transferred | Total (Sensible + | Sensible or Total | Sensible Only | Sensible Only |
- | | Latent Moisture) | (Membrane Plate) | (Phase change DX) | (Water/Glycol loop) |
- +---------------------+-------------------+-------------------+-------------------+-----------------------+
- | Typical Sensible Eff| 65% – 80% | 60% – 78% | 45% – 65% | 45% – 60% |
- +---------------------+-------------------+-------------------+-------------------+-----------------------+
- | Typical Latent Eff | 60% – 75% | 0% (Metal) to | 0% | 0% |
- | | | 55% (Membrane) | | |
- +---------------------+-------------------+-------------------+-------------------+-----------------------+
- | Cross-Contamination | Low (EATR 1-3% | Zero (EATR = 0%) | Zero (EATR = 0%) | Absolutely Zero |
- | (EATR Risk) | with purge seal) | | | (EATR = 0.0%) |
- +---------------------+-------------------+-------------------+-------------------+-----------------------+
- | Duct Proximity | Adjacent Airstreams| Adjacent Airstreams| Adjacent Airstreams| Remote Airstreams |
- | Requirement | Required | Required | Required | Permitted (Any dist) |
- +---------------------+-------------------+-------------------+-------------------+-----------------------+
- | Moving Parts | Yes (Motor/Belt) | No | No (Passive) | Yes (Hydronic Pump) |
- +---------------------+-------------------+-------------------+-------------------+-----------------------+
- | Ideal Application | DOAS, Schools, | Commercial Office,| Laboratories, ORs,| Hazardous Lab Exhaust,|
- | | High-density Occ. | Cleanrooms | Wrap-around Dehum.| Industrial Retrofit |
- +---------------------+-------------------+-------------------+-------------------+-----------------------+
- 1. Rotary Enthalpy Wheels
A porous aluminum or polymer matrix coated with a desiccant (such as silica gel or 3 A ˚ 3\text{Å} 3 A ˚ molecular sieve ) slowly rotates between counter-flowing supply and exhaust airstreams at 15 15 15 to 30 RPM 30\text{ RPM} 30 RPM . As it passes through the warm/humid airstream, the matrix absorbs heat and moisture, which it transfers to the cooler/drier airstream. A purge sector with positive supply-to-exhaust pressure differential ( Δ P sup > Δ P exh \Delta P_{\text{sup}} > \Delta P_{\text{exh}} Δ P sup > Δ P exh ) flushes entrained exhaust air back into the exhaust duct, keeping carryover below 1 % 1\% 1% .
2. Fixed-Plate Exchangers
Consists of alternating thin plates forming isolated cross-flow or counter-flow air channels. When constructed of aluminum or polypropylene, it transfers sensible heat only. When constructed of polymeric semi-permeable membranes (water-vapor permeable), it functions as an energy recovery plate , transferring both sensible heat and latent moisture with zero liquid or gas bypass.
3. Heat Pipe Heat Exchangers
Sealed tubes charged with a phase-change working fluid (e.g., R-134a or methanol) with an internal capillary wick. Heat from the warm airstream evaporates liquid refrigerant at the bottom, vapor travels to the cold airstream where it condenses and releases latent heat, and capillary action/gravity returns the liquid. Used in wrap-around coil configurations around a cooling coil to provide passive free reheat and enhanced dehumidification.
4. Runaround Coil Loops
Comprises two standard hydronic finned-tube coils—one in the exhaust duct and one in the supply duct—connected by a closed hydronic piping loop circulating a water-glycol mixture driven by a small pump. Its defining advantage is that the supply and exhaust ducts do not need to be adjacent (can be hundreds of feet apart, or on different floors), making it the mandatory choice for hazardous Class 4 laboratory exhaust systems where cross-contamination must be zero.
3. Leakage Metrics: EATR & OACF
To ensure air quality, AHRI Standard 1060 defines two critical leakage parameters: +---------------------------------------------------------------------------------------------------------+
- | AIR LEAKAGE METRICS IN ROTARY ENERGY RECOVERY |
- +---------------------------------------------------------------------------------------------------------+
- | |
- | 1. Exhaust Air Transfer Ratio (EATR): |
- | Measures the fraction of exhaust air recirculated into the supply air: |
- | |
- | EATR = (C_s2 - C_s1) / (C_e1 - C_s1) * 100% |
- | |
- | Where C is the concentration of an inert tracer gas (e.g., SF6). Target: EATR < 1% to 3%. |
- | |
- | 2. Outdoor Air Correction Factor (OACF): |
- | Ratio of outdoor entering airflow to supply leaving airflow: |
- | |
- | OACF = CFM_s1 / CFM_s2 |
- | |
- | - OACF > 1.0 : Outdoor supply air leaks into the exhaust airstream (proper fan arrangement). |
- | - OACF < 1.0 : Exhaust air leaks into the supply airstream (dangerous condition). |
- | |
- +---------------------------------------------------------------------------------------------------------+
- Fan Arrangement for Minimum Cross-Contamination
To prevent contaminant transfer in rotary wheels, the supply blower must be located downstream (draw-through) of the wheel and the exhaust blower must be located downstream (draw-through) , ensuring the supply plenum is at a higher static pressure than the exhaust plenum ( P supply > P exhaust P_{\text{supply}} > P_{\text{exhaust}} P supply > P exhaust ).
4. Frost Formation & Low-Temperature Freeze Protection
In severe winter conditions, moisture in the warm exhaust airstream condenses on the cold exchanger surface. If the heat exchanger surface temperature drops below 32 ∘ F 32^\circ\text{F} 3 2 ∘ F ( 0 ∘ C 0^\circ\text{C} 0 ∘ C ), condensation freezes into frost, blocking airflow and causing fan overload.
Theoretical Frost Threshold Temperature
The outdoor air temperature at which frost begins to form ( T frost,oa T_{\text{frost,oa}} T frost,oa ) is derived by setting the leaving exhaust air surface temperature to 32 ∘ F 32^\circ\text{F} 3 2 ∘ F : T frost,oa = 32 ∘ F − ( 1 − ϵ s ) ⋅ T e 1 ϵ s T_{\text{frost,oa}} = \frac{32^\circ\text{F} - (1 - \epsilon_s) \cdot T_{e1}}{\epsilon_s} T frost,oa = ϵ s 3 2 ∘ F − ( 1 − ϵ s ) ⋅ T e 1
Where T e 1 T_{e1} T e 1 is indoor return/exhaust air dry-bulb temperature (typically 70 ∘ F 70^\circ\text{F} 7 0 ∘ F ).
Example Frost Threshold Calculation
For an ERV with ϵ s = 0.75 \epsilon_s = 0.75 ϵ s = 0.75 and indoor exhaust at T e 1 = 70 ∘ F T_{e1} = 70^\circ\text{F} T e 1 = 7 0 ∘ F : T frost,oa = 32 − ( 1 − 0.75 ) ( 70 ) 0.75 = 32 − ( 0.25 × 70 ) 0.75 = 32 − 17.5 0.75 = 14.5 0.75 = 19.33 ∘ F T_{\text{frost,oa}} = \frac{32 - (1 - 0.75)(70)}{0.75} = \frac{32 - (0.25 \times 70)}{0.75} = \frac{32 - 17.5}{0.75} = \frac{14.5}{0.75} = \mathbf{19.33^\circ\text{F}} T frost,oa = 0.75 32 − ( 1 − 0.75 ) ( 70 ) = 0.75 32 − ( 0.25 × 70 ) = 0.75 32 − 17.5 = 0.75 14.5 = 19.3 3 ∘ F
When outdoor air drops below 19.3 ∘ F 19.3^\circ\text{F} 19. 3 ∘ F , frost protection controls must engage.
Frost Mitigation Control Strategies
Preheat Coil: A hydronic or electric preheat coil warms entering outdoor air to just above T frost,oa T_{\text{frost,oa}} T frost,oa (e.g., to 25 ∘ F 25^\circ\text{F} 2 5 ∘ F ), preventing frost while maintaining full energy recovery.
Variable Speed Wheel Modulation: Slowing the wheel rotation speed (from 20 RPM 20\text{ RPM} 20 RPM down to 1 − 3 RPM 1-3\text{ RPM} 1 − 3 RPM ) reduces sensible effectiveness, elevating the leaving exhaust temperature above 32 ∘ F 32^\circ\text{F} 3 2 ∘ F .
Face and Bypass Dampers: Bypasses a portion of outdoor air around the core, reducing thermal loading and raising exhaust surface temperature.
Timed Exhaust Defrost: Shuts off the outdoor air damper periodically, allowing warm exhaust air to thaw the heat exchanger matrix.
- 5. Worked Engineering Calculation: Dedicated Outdoor Air Enthalpy Wheel Sizing
- Problem Statement
A 100 % 100\% 100% Dedicated Outdoor Air System (DOAS) delivers 8 , 000 CFM 8,000\text{ CFM} 8 , 000 CFM of conditioned outdoor air to an office building. An enthalpy wheel provides total energy recovery with rated sensible effectiveness ϵ s = 0.72 \epsilon_s = 0.72 ϵ s = 0.72 and latent effectiveness ϵ L = 0.68 \epsilon_L = 0.68 ϵ L = 0.68 . Exhaust air mass flow equals supply air mass flow.
Summer Design Outdoor Air (State 1): T s 1 = 95.0 ∘ F DB T_{s1} = 95.0^\circ\text{F DB} T s 1 = 95. 0 ∘ F DB , W s 1 = 0.0160 lbm w / lbm d a W_{s1} = 0.0160\text{ lbm}_{w}/\text{lbm}_{da} W s 1 = 0.0160 lbm w / lbm d a ( 112.0 gr/lb 112.0\text{ gr/lb} 112.0 gr/lb ), h s 1 = 40.5 Btu/lbm h_{s1} = 40.5\text{ Btu/lbm} h s 1 = 40.5 Btu/lbm .
Indoor Exhaust Air (State 3): T e 1 = 75.0 ∘ F DB T_{e1} = 75.0^\circ\text{F DB} T e 1 = 75. 0 ∘ F DB , W e 1 = 0.0090 lbm w / lbm d a W_{e1} = 0.0090\text{ lbm}_{w}/\text{lbm}_{da} W e 1 = 0.0090 lbm w / lbm d a ( 63.0 gr/lb 63.0\text{ gr/lb} 63.0 gr/lb ), h e 1 = 28.2 Btu/lbm h_{e1} = 28.2\text{ Btu/lbm} h e 1 = 28.2 Btu/lbm .
Calculate:
Leaving supply air dry-bulb temperature ( T s 2 T_{s2} T s 2 ) and humidity ratio ( W s 2 W_{s2} W s 2 ).
Leaving supply air enthalpy ( h s 2 h_{s2} h s 2 ).
Sensible cooling load reduction ( Btu/h \text{Btu/h} Btu/h ).
Latent cooling load reduction ( Btu/h \text{Btu/h} Btu/h ).
Total cooling capacity avoided (in Tons \text{Tons} Tons of refrigeration).
Step-by-Step Solution
1. Leaving Supply Air Properties ( T s 2 , W s 2 T_{s2}, W_{s2} T s 2 , W s 2 ):
Leaving Dry-Bulb Temperature: T s 2 = T s 1 − ϵ s ( T s 1 − T e 1 ) = 95.0 − 0.72 × ( 95.0 − 75.0 ) = 95.0 − 0.72 ( 20.0 ) = 95.0 − 14.4 = 80.6 ∘ F DB T_{s2} = T_{s1} - \epsilon_s (T_{s1} - T_{e1}) = 95.0 - 0.72 \times (95.0 - 75.0) = 95.0 - 0.72(20.0) = 95.0 - 14.4 = \mathbf{80.6^\circ\text{F DB}} T s 2 = T s 1 − ϵ s ( T s 1 − T e 1 ) = 95.0 − 0.72 × ( 95.0 − 75.0 ) = 95.0 − 0.72 ( 20.0 ) = 95.0 − 14.4 = 80. 6 ∘ F DB
Leaving Humidity Ratio: W s 2 = W s 1 − ϵ L ( W s 1 − W e 1 ) = 0.0160 − 0.68 × ( 0.0160 − 0.0090 ) = 0.0160 − 0.68 ( 0.0070 ) = 0.0160 − 0.00476 = 0.01124 lbm w / lbm d a W_{s2} = W_{s1} - \epsilon_L (W_{s1} - W_{e1}) = 0.0160 - 0.68 \times (0.0160 - 0.0090) = 0.0160 - 0.68(0.0070) = 0.0160 - 0.00476 = \mathbf{0.01124\text{ lbm}_w/\text{lbm}_{da}} W s 2 = W s 1 − ϵ L ( W s 1 − W e 1 ) = 0.0160 − 0.68 × ( 0.0160 − 0.0090 ) = 0.0160 − 0.68 ( 0.0070 ) = 0.0160 − 0.00476 = 0.01124 lbm w / lbm da
In grains: W s 2 = 0.01124 × 7 , 000 = 78.68 gr/lb W_{s2} = 0.01124 \times 7,000 = 78.68\text{ gr/lb} W s 2 = 0.01124 × 7 , 000 = 78.68 gr/lb .
2. Leaving Supply Enthalpy ( h s 2 h_{s2} h s 2 ):
Psychrometric approximation: h = 0.240 T + W ( 1061 + 0.444 T ) h = 0.240 T + W(1061 + 0.444 T) h = 0.240 T + W ( 1061 + 0.444 T ) h s 2 = ( 0.240 × 80.6 ) + 0.01124 × [ 1061 + ( 0.444 × 80.6 ) ] = 19.344 + 0.01124 × [ 1096.79 ] = 19.344 + 12.328 = 31.67 Btu/lbm h_{s2} = (0.240 \times 80.6) + 0.01124 \times [1061 + (0.444 \times 80.6)] = 19.344 + 0.01124 \times [1096.79] = 19.344 + 12.328 = \mathbf{31.67\text{ Btu/lbm}} h s 2 = ( 0.240 × 80.6 ) + 0.01124 × [ 1061 + ( 0.444 × 80.6 )] = 19.344 + 0.01124 × [ 1096.79 ] = 19.344 + 12.328 = 31.67 Btu/lbm
3. Sensible Heat Reduction: Q ˙ sensible = 1.08 × CFM × ( T s 1 − T s 2 ) = 1.08 × 8 , 000 × ( 95.0 − 80.6 ) = 8 , 640 × 14.4 = 124 , 416 Btu/h \dot{Q}_{\text{sensible}} = 1.08 \times \text{CFM} \times (T_{s1} - T_{s2}) = 1.08 \times 8,000 \times (95.0 - 80.6) = 8,640 \times 14.4 = \mathbf{124,416\text{ Btu/h}} Q ˙ sensible = 1.08 × CFM × ( T s 1 − T s 2 ) = 1.08 × 8 , 000 × ( 95.0 − 80.6 ) = 8 , 640 × 14.4 = 124 , 416 Btu/h
4. Latent Heat Reduction: Q ˙ latent = 4 , 840 × CFM × ( W s 1 − W s 2 ) = 4 , 840 × 8 , 000 × ( 0.0160 − 0.01124 ) = 38 , 720 , 000 × 0.00476 = 184 , 307 Btu/h \dot{Q}_{\text{latent}} = 4,840 \times \text{CFM} \times (W_{s1} - W_{s2}) = 4,840 \times 8,000 \times (0.0160 - 0.01124) = 38,720,000 \times 0.00476 = \mathbf{184,307\text{ Btu/h}} Q ˙ latent = 4 , 840 × CFM × ( W s 1 − W s 2 ) = 4 , 840 × 8 , 000 × ( 0.0160 − 0.01124 ) = 38 , 720 , 000 × 0.00476 = 184 , 307 Btu/h
5. Total Avoided Cooling Capacity: Q ˙ total = Q ˙ sensible + Q ˙ latent = 124 , 416 + 184 , 307 = 308 , 723 Btu/h \dot{Q}_{\text{total}} = \dot{Q}_{\text{sensible}} + \dot{Q}_{\text{latent}} = 124,416 + 184,307 = 308,723\text{ Btu/h} Q ˙ total = Q ˙ sensible + Q ˙ latent = 124 , 416 + 184 , 307 = 308 , 723 Btu/h Tons of Avoided Cooling = 308 , 723 Btu/h 12 , 000 Btu/(h ⋅ Ton) = 25.73 Tons \text{Tons of Avoided Cooling} = \frac{308,723\text{ Btu/h}}{12,000\text{ Btu/(h}\cdot\text{Ton)}} = \mathbf{25.73\text{ Tons}} Tons of Avoided Cooling = 12 , 000 Btu/(h ⋅ Ton) 308 , 723 Btu/h = 25.73 Tons
Engineering Summary: The enthalpy wheel reduces the peak chiller sizing required for outdoor air treatment from 32.8 Tons 32.8\text{ Tons} 32.8 Tons down to 7.1 Tons 7.1\text{ Tons} 7.1 Tons , saving 25.73 Tons 25.73\text{ Tons} 25.73 Tons ( 78.4 % 78.4\% 78.4% ) of peak refrigeration capacity.
6. NCEES Reference Handbook Navigation Strategies
AHRI 1060 Effectiveness Equations: Search "Energy Recovery" or "Effectiveness" under HVAC to find the sensible, latent, and total effectiveness equations.
Psychrometric Equations: Search "Sensible Heat Rate" ( q s = 1.08 ⋅ CFM ⋅ Δ T q_s = 1.08 \cdot \text{CFM} \cdot \Delta T q s = 1.08 ⋅ CFM ⋅ Δ T ), "Total Heat Rate" ( q t = 4.5 ⋅ CFM ⋅ Δ h q_t = 4.5 \cdot \text{CFM} \cdot \Delta h q t = 4.5 ⋅ CFM ⋅ Δ h ), and "Latent Heat Rate" ( q L = 4840 ⋅ CFM ⋅ Δ W q_L = 4840 \cdot \text{CFM} \cdot \Delta W q L = 4840 ⋅ CFM ⋅ Δ W ).
Psychrometric Charts: Locate the ASHRAE Psychrometric Chart No. 1 ( 32 ∘ F 32^\circ\text{F} 3 2 ∘ F to 120 ∘ F 120^\circ\text{F} 12 0 ∘ F ) to determine enthalpy and humidity ratios from dry-bulb and wet-bulb temperatures.