Study guide

5.5 Affinity Laws & Parallel/Series Pump/Fan System Curves

PE Mechanical: HVAC and Refrigeration Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Overview, Reference Handbook & Engineering Foundations

1.1 NCEES Exam Specification, CBT Delivery & Reference Handbook Strategy 1.2 Engineering Units, Dimensional Analysis & Physical Property Lookups 1.3 Engineering Economics, Life Cycle Cost Analysis & Equipment Financial Evaluation 1.4 Electrical Foundations, Motor Ratings & Variable Frequency Drives (VFDs)

2 Chapter 2: Thermodynamics & Energy Balances

2.1 First and Second Laws of Thermodynamics & Open/Closed System Energy Balances 2.2 Thermodynamic Cycles: Carnot, Rankine, Brayton & Reversed Carnot Limit 2.3 Gas & Vapor Property Evaluation: Steam Tables, Superheat & Subcooling 2.4 Mass, Energy & Combustion Balances for HVAC Equipment

3 Chapter 3: Psychrometrics, Moist Air Processes & Humidity Equipment

3.1 Psychrometric Properties: DBT, WBT, DPT, RH, Humidity Ratio & Enthalpy 3.2 Chart Reading & Psychrometric Equations at Sea Level vs. Altitude (5,000 ft) 3.3 Basic Psychrometric Processes: Sensible Heating/Cooling, Humidification & Dehumidification 3.4 Mixed Air Calculations & Complex Air Conditioning Cycles (Preheat, Reheat & Bypass) 3.5 Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP) & Coil Bypass Factor 3.6 Humidification & Dehumidification Equipment: Steam, Adiabatic, Desiccant & Low-Temperature Processes

4 Chapter 4: Heat Transfer Principles & Sizing

4.1 Steady-State Conduction & Multilayer Thermal Resistance (R-Value & U-Factor) 4.2 Convective Heat Transfer & Forced/Natural Convection Coefficients 4.3 Radiation Heat Transfer, Surface Emissivity & View Factors 4.4 Overall Heat Transfer Coefficients, Fouling Factors & Transient/Thermal Mass Effects 4.5 Heat Exchanger Analysis: Log Mean Temperature Difference (LMTD) & Effectiveness-NTU (ε-NTU)

5 Chapter 5: Fluid Mechanics & Hydraulic Fundamentals

5.1 Fluid Statics, Incompressible Continuity & Bernoulli Energy Equation 5.2 Pipe Friction, Moody Diagram & Darcy-Weisbach / Hazen-Williams Calculations 5.3 Minor Losses: Equivalent Length, Loss Coefficients (K-factors) & Total System Head 5.4 Pump Sizing, Net Positive Suction Head (NPSHa vs NPSHr) & Cavitation Prevention 5.5 Affinity Laws & Parallel/Series Pump/Fan System Curves

6 Chapter 6: Heating & Cooling Load Calculations

6.1 Outdoor & Indoor Design Conditions (ASHRAE Fundamentals, Climatic Data & Indoor Setpoints) 6.2 Envelope Heat Transmission & Infiltration/Exfiltration Load Methods 6.3 Solar Heat Gain (SHGC), Fenestration & Cooling Load Temperature Difference / Radiant Time Series (CLTD/RTS) 6.4 Internal Heat Gains: Lighting, People, Equipment & Diversity Factors 6.5 Ventilation Loads & Sensible / Latent / Total Cooling Load Synthesis

7 Chapter 7: Refrigeration Principles, Cycles & Cold Storage Applications

7.1 Standard Vapor-Compression Refrigeration Cycle on P-h & T-s Diagrams 7.2 Refrigeration Cycle Performance Metrics: COP, EER, SEER, kW/ton & Ton of Refrigeration 7.3 Cycle Enhancements: Subcooling, Superheating, Liquid-Suction Heat Exchangers & Economizers 7.4 Multi-Stage & Cascade Refrigeration Systems: Intercooling & Flash Gas Removal 7.5 Absorption Refrigeration Cycles: Water-Lithium Bromide & Ammonia-Water Systems 7.6 Food Processing & Cold Storage Refrigeration: Product Load, Pull-Down & Storage Design

8 Chapter 8: Refrigerants, Environmental Regulations & Safety

8.1 Refrigerant Classifications, Nomenclature & Thermodynamic Properties (ASHRAE Standard 34) 8.2 AIM Act, EPA Technology Transitions Sector GWP Limits & Low-GWP Refrigerants (R-32, R-454B) 8.3 Refrigerant Safety Requirements & Machinery Room Design (ASHRAE Standard 15) 8.4 Refrigerant Piping Sizing, Oil Return, Traps & Double Risers

9 Chapter 9: HVAC Equipment & Primary Machinery

9.1 Compressors: Reciprocating, Rotary, Scroll, Screw & Centrifugal 9.2 Condensers: Air-Cooled, Water-Cooled & Evaporative Condensers 9.3 Evaporators & Direct Expansion (DX) vs Liquid Chilling Coils 9.4 Water Chillers: Centrifugal, Screw & Scroll with ASHRAE 90.1 Path A/B IPLV Ratings 9.5 Cooling Towers: Range, Approach, Evaporation, Blowdown & Legionella Control 9.6 Heat Pumps & Variable Refrigerant Flow (VRF): Balance Point, Defrost & Heat Recovery 9.7 Thermal Energy Storage: Full vs. Partial Storage, Chilled Water & Ice Systems

10 Chapter 10: Air-Side Systems & Distribution

10.1 Air Handling Units (AHUs), Dedicated Outdoor Air Systems (DOAS) & Fan-Coil Units 10.2 Duct Design Methodologies: Equal Friction, Static Regain & Velocity Reduction 10.3 Duct Fittings, Dynamic Pressure Losses & SMACNA Construction Standards 10.4 Fan Types, Performance Curves, System Effect Factors & Surge/Stall Dynamics 10.5 Variable Air Volume (VAV) Systems, Terminal Boxes & Space Air Diffusion (ADPI) 10.6 Cooling & Heating Coil Selection: Face Velocity, Rows, Circuiting & Freeze Protection

11 Chapter 11: Hydronic, Steam & Fuel Distribution and Heating Plant

11.1 Hydronic System Architectures: Primary-Only, Primary-Secondary & Variable Primary Flow (VPF) 11.2 Hydronic Pipe Sizing, Velocity Limits & Closed/Open Expansion Tank Sizing 11.3 Control Valves: 2-Way vs 3-Way, Valve Authority (N), Cv Calculations & Characteristic Curves 11.4 Boilers & Heating Hot Water Systems: Condensing vs Non-Condensing & Water Treatment 11.5 Furnaces & Gas-Fired Heating Equipment: AFUE, Temperature Rise, Combustion Air & Vent Categories 11.6 Steam & Condensate Distribution: Latent Heat, Trap Selection, Flash Steam & Stall 11.7 Fuel Gas & Fuel Oil Piping: Demand, Sizing Method, Pressure Drop & Storage Systems

12 Chapter 12: HVAC Control Concepts, Sensors & Sequences

12.1 Sensors, Actuators & Dampers: Selection, Placement, Fail-Safe Position & Damper Authority 12.2 Control Loops: Proportional Offset, PID Action, Reset Strategies & Standard Sequences

13 Chapter 13: Building Energy, Ventilation & Indoor Environmental Quality Codes

13.1 ASHRAE Standard 62.1: Ventilation Rate Procedure (VRP), Indoor Air Quality Procedure & DCV 13.2 ASHRAE Standard 90.1: Building Energy Envelope, Mechanical Efficiency & Economizer Mandates 13.3 ASHRAE Standard 55: Thermal Environmental Conditions, PMV/PPD & Adaptive Comfort Models 13.4 Energy Recovery Systems: Enthalpy Wheels, Fixed-Plate Exchangers, Heat Pipes & Runaround Loops

14 Chapter 14: Supportive Engineering Knowledge, Life Safety & Operations

14.1 Air Filtration Standards: MERV Ratings (ASHRAE 52.2), HEPA & Gas-Phase Adsorption 14.2 Life Safety Systems: Fire/Smoke Dampers, Stairwell Pressurization (NFPA 92) & Smoke Control (NFPA 90A) 14.3 Acoustical Control & Vibration Isolation in HVAC Systems (NC / RC Criteria)

5.5 Affinity Laws & Parallel/Series Pump/Fan System Curves

Key Takeaways Explain This Topic AI

The Turbomachinery Affinity Laws scale flow linearly with speed (Q2/Q1 = N2/N1), head with speed squared (H2/H1 = (N2/N1)^2), and power with speed cubed (P2/P1 = (N2/N1)^3) at constant impeller diameter.

Trimming a pump impeller scales flow linearly with diameter (Q2/Q1 = D2/D1), head with diameter squared (H2/H1 = (D2/D1)^2), and power with diameter cubed (P2/P1 = (D2/D1)^3) for trims up to 15-20%.

For gas/air fans at constant RPM, volumetric airflow (CFM) remains constant regardless of air density, while total pressure and power scale directly and linearly with air density (P2/P1 = rho2/rho1).

Pumps operating in parallel add flow rates at equal head (Q_total = Q_A + Q_B at H); due to parabolic system resistance curves (H = C*Q^2), two identical parallel pumps deliver only 1.25x to 1.40x single pump flow.

Pumps operating in series add head at equal flow rate (H_total = H_A + H_B at Q), making series configurations ideal for steep, high-resistance piping systems.

Last updated: August 2026

5.5 Affinity Laws & Parallel/Series Pump/Fan System Curves

The Affinity Laws (homologous scaling relationships) govern the performance of geometrically similar turbomachinery—including centrifugal pumps, fans, and blowers—under variations in rotational speed, impeller diameter, and fluid density. On the NCEES PE Mechanical exam, affinity law calculations are routinely paired with system resistance curves , Variable Frequency Drive (VFD) energy evaluations, and parallel/series pump combinations .

1. The Affinity Laws for Constant Impeller Diameter (Variable Speed N N N )

When a pump or fan changes rotational speed ( N N N , in RPM \text{RPM} RPM ) while maintaining a fixed impeller diameter and constant fluid density: +-----------------------------------------------------------------------------+

  • | THE ROTATIONAL SPEED AFFINITY LAWS (Constant Diameter D) |
  • +-----------------------------------------------------------------------------+
  • | 1. Volumetric Flow Rate scales linearly with speed: |
  • | Q_2 / Q_1 = N_2 / N_1 |
  • | |
  • | 2. Total Head / Static Pressure scales with speed squared: |
  • | H_2 / H_1 = (N_2 / N_1)^2 or P_2 / P_1 = (N_2 / N_1)^2 |
  • | |
  • | 3. Brake Horsepower (Power) scales with speed CUBED: |
  • | BHP_2 / BHP_1 = (N_2 / N_1)^3 or P_2 / P_1 = (N_2 / N_1)^3 |
  • +-----------------------------------------------------------------------------+
  • The Cubic Power Relationship & VFD Energy Savings

The cubic power law ( BHP ∝ N 3 \text{BHP} \propto N^3 BHP ∝ N 3 ) demonstrates the tremendous energy savings of Variable Frequency Drives (VFDs). If building cooling load drops and a secondary chilled water pump speed is reduced by 20 % 20\% 20% ( N 2 / N 1 = 0.80 N_2 / N_1 = 0.80 N 2 ​ / N 1 ​ = 0.80 ): Flow Rate: Q 2 = 0.80 × Q 1 ( 20 % reduction ) \text{Flow Rate:} \quad Q_2 = 0.80 \times Q_1 \quad (20\% \text{ reduction}) Flow Rate: Q 2 ​ = 0.80 × Q 1 ​ ( 20% reduction ) Head: H 2 = ( 0.80 ) 2 × H 1 = 0.64 × H 1 ( 36 % reduction ) \text{Head:} \quad H_2 = (0.80)^2 \times H_1 = 0.64 \times H_1 \quad (36\% \text{ reduction}) Head: H 2 ​ = ( 0.80 ) 2 × H 1 ​ = 0.64 × H 1 ​ ( 36% reduction ) Power: BHP 2 = ( 0.80 ) 3 × BHP 1 = 0.512 × BHP 1 ( 48.8 % energy reduction! ) \text{Power:} \quad \text{BHP}_2 = (0.80)^3 \times \text{BHP}_1 = 0.512 \times \text{BHP}_1 \quad (48.8\% \text{ energy reduction!}) Power: BHP 2 ​ = ( 0.80 ) 3 × BHP 1 ​ = 0.512 × BHP 1 ​ ( 48.8% energy reduction! )

VFD vs. Throttling Valve: Reducing flow to 80 % 80\% 80% by closing a discharge triple-duty balancing valve keeps the pump running at full 100 % 100\% 100% speed, riding the pump curve up to higher head and consuming approximately 88 % − 92 % 88\% - 92\% 88% − 92% power. Slowing the pump with a VFD drops power consumption to 51.2 % 51.2\% 51.2% , saving over 40 % 40\% 40% more energy.

2. Impeller Trimming Laws (Constant Speed N N N )

When a pump impeller is physically machined (trimmed) on a lathe to reduce its outer diameter ( D 1 → D 2 D_1 \rightarrow D_2 D 1 ​ → D 2 ​ ) at constant rotational speed (valid for moderate trims up to 15 % − 20 % 15\% - 20\% 15% − 20% of original diameter): Q 2 Q 1 = D 2 D 1 , H 2 H 1 = ( D 2 D 1 ) 2 , BHP 2 BHP 1 = ( D 2 D 1 ) 3 \frac{Q_2}{Q_1} = \frac{D_2}{D_1}, \quad \frac{H_2}{H_1} = \left( \frac{D_2}{D_1} \right)^2, \quad \frac{\text{BHP}_2}{\text{BHP}_1} = \left( \frac{D_2}{D_1} \right)^3 Q 1 ​ Q 2 ​ ​ = D 1 ​ D 2 ​ ​ , H 1 ​ H 2 ​ ​ = ( D 1 ​ D 2 ​ ​ ) 2 , BHP 1 ​ BHP 2 ​ ​ = ( D 1 ​ D 2 ​ ​ ) 3

Combined Speed and Diameter Scaling

If both rotational speed and impeller diameter vary simultaneously: Q 2 Q 1 = ( N 2 N 1 ) ( D 2 D 1 ) \frac{Q_2}{Q_1} = \left( \frac{N_2}{N_1} \right) \left( \frac{D_2}{D_1} \right) Q 1 ​ Q 2 ​ ​ = ( N 1 ​ N 2 ​ ​ ) ( D 1 ​ D 2 ​ ​ ) H 2 H 1 = ( N 2 N 1 ) 2 ( D 2 D 1 ) 2 \frac{H_2}{H_1} = \left( \frac{N_2}{N_1} \right)^2 \left( \frac{D_2}{D_1} \right)^2 H 1 ​ H 2 ​ ​ = ( N 1 ​ N 2 ​ ​ ) 2 ( D 1 ​ D 2 ​ ​ ) 2 BHP 2 BHP 1 = ( N 2 N 1 ) 3 ( D 2 D 1 ) 3 \frac{\text{BHP}_2}{\text{BHP}_1} = \left( \frac{N_2}{N_1} \right)^3 \left( \frac{D_2}{D_1} \right)^3 BHP 1 ​ BHP 2 ​ ​ = ( N 1 ​ N 2 ​ ​ ) 3 ( D 1 ​ D 2 ​ ​ ) 3

3. Gas Density Variations in Fans & Air Handling Systems

Unlike incompressible hydronic water circuits, air handling systems operate across varying air densities due to elevation (altitude) and temperature.

Fan Performance at Variable Air Density (Constant RPM & Duct Geometry)

Volumetric Airflow ( Q Q Q , in CFM \text{CFM} CFM ) is INDEPENDENT of density: A fan is a constant-volume machine. At fixed RPM, it displaces the exact same geometric volume of air regardless of density: Q 2 = Q 1 ( CFM 2 = CFM 1 ) Q_2 = Q_1 \quad (\text{CFM}_2 = \text{CFM}_1) Q 2 ​ = Q 1 ​ ( CFM 2 ​ = CFM 1 ​ )

Mass Flow Rate ( m ˙ \dot{m} m ˙ ) scales directly with density: m ˙ 2 = m ˙ 1 ( ρ 2 ρ 1 ) \dot{m}_2 = \dot{m}_1 \left( \frac{\rho_2}{\rho_1} \right) m ˙ 2 ​ = m ˙ 1 ​ ( ρ 1 ​ ρ 2 ​ ​ )

Static & Total Pressure ( P P P , in in. w.g. \text{in. w.g.} in. w.g. ) scale directly with density: P 2 = P 1 ( ρ 2 ρ 1 ) P_2 = P_1 \left( \frac{\rho_2}{\rho_1} \right) P 2 ​ = P 1 ​ ( ρ 1 ​ ρ 2 ​ ​ )

Fan Brake Horsepower ( BHP \text{BHP} BHP ) scales directly with density: BHP 2 = BHP 1 ( ρ 2 ρ 1 ) \text{BHP}_2 = \text{BHP}_1 \left( \frac{\rho_2}{\rho_1} \right) BHP 2 ​ = BHP 1 ​ ( ρ 1 ​ ρ 2 ​ ​ ) +-----------------------------------------------------------------------------+

  • | AIR DENSITY DERATING SUMMARY (Denver 5,000 ft vs Sea Level) |
  • +-----------------------------------------------------------------------------+
  • | Parameter Sea Level (rho = 0.075) Denver (rho = 0.0624) |
  • | Volumetric Flow (CFM) 10,000 CFM 10,000 CFM (No Change)|
  • | Total Pressure (in. w.g.) 2.50 in. w.g. 2.08 in. w.g. (-16.8%)|
  • | Fan Power (BHP) 5.00 hp 4.16 hp (-16.8%)|
  • | Thermal Sensible Heat (q_s) 1.08 * CFM * Delta_T 0.90 * CFM * Delta_T |
  • +-----------------------------------------------------------------------------+

4. Parallel vs. Series Pump Configurations

When multiple pumps are piped together, their combined characteristic curve is constructed by summing individual pump curves according to hydraulic topology. +-----------------------------------------------------------------------------------------+

  • | PARALLEL VS. SERIES PUMP COMBINATIONS |
  • +-----------------------------------------------------------------------------------------+
  • | PARALLEL CONFIGURATION (Common Headers): |
  • | |
  • | +---[ Pump A ]---+ |
  • | --->| |---> Combined Flow: Q_total = Q_A + Q_B at identical Head H |
  • | +---[ Pump B ]---+ |
  • | |
  • | - Curve Construction: Add flows horizontally (Q_total = 2 * Q_single at each H) |
  • | - Purpose: Increase volumetric flow rate in low-resistance / flat system curves |
  • | |
  • | SERIES CONFIGURATION (Booster in Line): |
  • | |
  • | --->[ Pump A ]---->[ Pump B ]---> Combined Head: H_total = H_A + H_B at flow Q |
  • | |
  • | - Curve Construction: Add heads vertically (H_total = 2 * H_single at each Q) |
  • | - Purpose: Increase total pressure / head in high-resistance / steep system curves |
  • +-----------------------------------------------------------------------------------------+
  • The Parallel Pump Diminishing Returns Phenomenon

A common engineering misconception is that adding an identical second pump in parallel doubles the total system flow rate ( Q parallel = 2 × Q single Q_{\text{parallel}} = 2 \times Q_{\text{single}} Q parallel ​ = 2 × Q single ​ ). This is false in real piping networks! Head (ft)

  • ^
  • | / System Curve: H = C * Q^2 (Steep Parabola)
  • | /
  • | Combined /
  • | Parallel / <--- Operating Point 2 (Two Pumps: Q_total)
  • | Curve / Q_total ~ 1.25x to 1.40x Q_single
  • | Single ========+===/=========
  • | Pump / |
  • | Curve / |
  • | ========+/==========+==================
  • | / | |
  • | / | Operating Point 1 (Single Pump: Q_single)
  • +---+---------+-----------+-----------------------------> Flow Q (GPM)
  • 0 Q_single Q_total (NOT 2 * Q_single!)

Because the system friction curve rises quadratically ( H sys ∝ Q 2 H_{\text{sys}} \propto Q^2 H sys ​ ∝ Q 2 ), operating two identical pumps in parallel increases system flow by only 25 % to 40 % 25\% \text{ to } 40\% 25% to 40% (typically Q parallel ≈ 1.25 to 1.40 × Q single Q_{\text{parallel}} \approx 1.25 \text{ to } 1.40 \times Q_{\text{single}} Q parallel ​ ≈ 1.25 to 1.40 × Q single ​ ), while each individual pump delivers less than its single-pump design flow ( Q each = Q total / 2 Q_{\text{each}} = Q_{\text{total}} / 2 Q each ​ = Q total ​ /2 ) at a higher head.

  • 5. Worked Engineering Examples
  • Worked Example 1: Fan Affinity Laws & Speed Reduction

A supply air fan currently operates at N 1 = 1750 RPM N_1 = 1750\text{ RPM} N 1 ​ = 1750 RPM , delivering Q 1 = 12 , 000 CFM Q_1 = 12,000\text{ CFM} Q 1 ​ = 12 , 000 CFM against a total static pressure of P 1 = 2.50 in. w.g. P_1 = 2.50\text{ in. w.g.} P 1 ​ = 2.50 in. w.g. with a motor shaft power of BHP 1 = 7.50 hp \text{BHP}_1 = 7.50\text{ hp} BHP 1 ​ = 7.50 hp . A building balance requires reducing the airflow to Q 2 = 9 , 600 CFM Q_2 = 9,600\text{ CFM} Q 2 ​ = 9 , 600 CFM . Assuming constant duct configuration and standard air density:

What is the required new fan speed ( N 2 N_2 N 2 ​ )?

What is the new fan static pressure ( P 2 P_2 P 2 ​ )?

What is the new Brake Horsepower ( BHP 2 \text{BHP}_2 BHP 2 ​ )?

Step 1: Determine speed ratio from flow affinity law: N 2 N 1 = Q 2 Q 1 = 9 , 600 CFM 12 , 000 CFM = 0.80 \frac{N_2}{N_1} = \frac{Q_2}{Q_1} = \frac{9,600\text{ CFM}}{12,000\text{ CFM}} = 0.80 N 1 ​ N 2 ​ ​ = Q 1 ​ Q 2 ​ ​ = 12 , 000 CFM 9 , 600 CFM ​ = 0.80 N 2 = 0.80 × 1750 RPM = 1400 RPM N_2 = 0.80 \times 1750\text{ RPM} = 1400\text{ RPM} N 2 ​ = 0.80 × 1750 RPM = 1400 RPM

Step 2: Calculate new static pressure using the squared law: P 2 = P 1 ( N 2 N 1 ) 2 = 2.50 in. w.g. × ( 0.80 ) 2 = 2.50 × 0.64 = 1.60 in. w.g. P_2 = P_1 \left( \frac{N_2}{N_1} \right)^2 = 2.50\text{ in. w.g.} \times (0.80)^2 = 2.50 \times 0.64 = 1.60\text{ in. w.g.} P 2 ​ = P 1 ​ ( N 1 ​ N 2 ​ ​ ) 2 = 2.50 in. w.g. × ( 0.80 ) 2 = 2.50 × 0.64 = 1.60 in. w.g.

Step 3: Calculate new Brake Horsepower using the cubic law: BHP 2 = BHP 1 ( N 2 N 1 ) 3 = 7.50 hp × ( 0.80 ) 3 = 7.50 × 0.512 = 3.84 hp \text{BHP}_2 = \text{BHP}_1 \left( \frac{N_2}{N_1} \right)^3 = 7.50\text{ hp} \times (0.80)^3 = 7.50 \times 0.512 = 3.84\text{ hp} BHP 2 ​ = BHP 1 ​ ( N 1 ​ N 2 ​ ​ ) 3 = 7.50 hp × ( 0.80 ) 3 = 7.50 × 0.512 = 3.84 hp

Worked Example 2: Mathematical Parallel Pump Operating Point

A closed chilled water loop has a system curve defined by H sys = 0.00024 Q 2 H_{\text{sys}} = 0.00024 Q^2 H sys ​ = 0.00024 Q 2 (where H H H is in feet and Q Q Q is in GPM \text{GPM} GPM ). A single pump has a characteristic curve H p = 80 − 0.00008 Q p 2 H_p = 80 - 0.00008 Q_p^2 H p ​ = 80 − 0.00008 Q p 2 ​ .

Find the operating point ( Q 1 , H 1 ) (Q_1, H_1) ( Q 1 ​ , H 1 ​ ) with one pump running.

Find the total system operating point ( Q total , H total ) (Q_{\text{total}}, H_{\text{total}}) ( Q total ​ , H total ​ ) when two identical pumps operate in parallel.

Step 1: Single Pump Operating Point: H p = H sys ⟹ 80 − 0.00008 Q 1 2 = 0.00024 Q 1 2 H_p = H_{\text{sys}} \implies 80 - 0.00008 Q_1^2 = 0.00024 Q_1^2 H p ​ = H sys ​ ⟹ 80 − 0.00008 Q 1 2 ​ = 0.00024 Q 1 2 ​ 80 = 0.00032 Q 1 2 ⟹ Q 1 2 = 80 0.00032 = 250 , 000 80 = 0.00032 Q_1^2 \implies Q_1^2 = \frac{80}{0.00032} = 250,000 80 = 0.00032 Q 1 2 ​ ⟹ Q 1 2 ​ = 0.00032 80 ​ = 250 , 000 Q 1 = 250 , 000 = 500 GPM Q_1 = \sqrt{250,000} = 500\text{ GPM} Q 1 ​ = 250 , 000 ​ = 500 GPM H 1 = 0.00024 × ( 500 ) 2 = 60.0 ft H_1 = 0.00024 \times (500)^2 = 60.0\text{ ft} H 1 ​ = 0.00024 × ( 500 ) 2 = 60.0 ft

Step 2: Two Pumps in Parallel: In parallel, each pump delivers half the total flow: Q p = Q total / 2 Q_p = Q_{\text{total}} / 2 Q p ​ = Q total ​ /2 . H p , parallel = 80 − 0.00008 ( Q total 2 ) 2 = 80 − 0.00002 Q total 2 H_{p,\text{parallel}} = 80 - 0.00008 \left( \frac{Q_{\text{total}}}{2} \right)^2 = 80 - 0.00002 Q_{\text{total}}^2 H p , parallel ​ = 80 − 0.00008 ( 2 Q total ​ ​ ) 2 = 80 − 0.00002 Q total 2 ​

Equating parallel pump head to system head: 80 − 0.00002 Q total 2 = 0.00024 Q total 2 80 - 0.00002 Q_{\text{total}}^2 = 0.00024 Q_{\text{total}}^2 80 − 0.00002 Q total 2 ​ = 0.00024 Q total 2 ​ 80 = 0.00026 Q total 2 ⟹ Q total 2 = 80 0.00026 = 307 , 692 80 = 0.00026 Q_{\text{total}}^2 \implies Q_{\text{total}}^2 = \frac{80}{0.00026} = 307,692 80 = 0.00026 Q total 2 ​ ⟹ Q total 2 ​ = 0.00026 80 ​ = 307 , 692 Q total = 307 , 692 = 554.7 GPM ≈ 555 GPM Q_{\text{total}} = \sqrt{307,692} = 554.7\text{ GPM} \approx 555\text{ GPM} Q total ​ = 307 , 692 ​ = 554.7 GPM ≈ 555 GPM H total = 0.00024 × ( 554.7 ) 2 = 73.8 ft H_{\text{total}} = 0.00024 \times (554.7)^2 = 73.8\text{ ft} H total ​ = 0.00024 × ( 554.7 ) 2 = 73.8 ft Flow Increase Ratio = 554.7 GPM 500 GPM = 1.109 ( Only an 11 % increase in flow, NOT 100 % ! ) \text{Flow Increase Ratio} = \frac{554.7\text{ GPM}}{500\text{ GPM}} = 1.109 \quad (\text{Only an } 11\% \text{ increase in flow, NOT } 100\%!) Flow Increase Ratio = 500 GPM 554.7 GPM ​ = 1.109 ( Only an 11% increase in flow, NOT 100% !)

6. NCEES Reference Handbook Navigation & Exam Tips

Affinity Laws Location: In the Reference Handbook under Fluid Mechanics → \rightarrow → Turbomachinery → \rightarrow → Affinity Laws .

Static Head Affinity Trap: The Affinity Laws ( H ∝ N 2 H \propto N^2 H ∝ N 2 ) scale the pump curve itself , but they do NOT represent the operating point trajectory if the system has static head ( H static ≠ 0 H_{\text{static}} \ne 0 H static ​  = 0 ). If static head exists, the operating point must be calculated by finding the intersection of the scaled pump curve and the system curve ( H = H static + C Q 2 H = H_{\text{static}} + C Q^2 H = H static ​ + C Q 2 ).