5.2 Pipe Friction, Moody Diagram & Darcy-Weisbach / Hazen-Williams Calculations
PE Mechanical: HVAC and Refrigeration Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview, Reference Handbook & Engineering Foundations
1.1 NCEES Exam Specification, CBT Delivery & Reference Handbook Strategy 1.2 Engineering Units, Dimensional Analysis & Physical Property Lookups 1.3 Engineering Economics, Life Cycle Cost Analysis & Equipment Financial Evaluation 1.4 Electrical Foundations, Motor Ratings & Variable Frequency Drives (VFDs)
2 Chapter 2: Thermodynamics & Energy Balances
2.1 First and Second Laws of Thermodynamics & Open/Closed System Energy Balances 2.2 Thermodynamic Cycles: Carnot, Rankine, Brayton & Reversed Carnot Limit 2.3 Gas & Vapor Property Evaluation: Steam Tables, Superheat & Subcooling 2.4 Mass, Energy & Combustion Balances for HVAC Equipment
3 Chapter 3: Psychrometrics, Moist Air Processes & Humidity Equipment
3.1 Psychrometric Properties: DBT, WBT, DPT, RH, Humidity Ratio & Enthalpy 3.2 Chart Reading & Psychrometric Equations at Sea Level vs. Altitude (5,000 ft) 3.3 Basic Psychrometric Processes: Sensible Heating/Cooling, Humidification & Dehumidification 3.4 Mixed Air Calculations & Complex Air Conditioning Cycles (Preheat, Reheat & Bypass) 3.5 Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP) & Coil Bypass Factor 3.6 Humidification & Dehumidification Equipment: Steam, Adiabatic, Desiccant & Low-Temperature Processes
4 Chapter 4: Heat Transfer Principles & Sizing
4.1 Steady-State Conduction & Multilayer Thermal Resistance (R-Value & U-Factor) 4.2 Convective Heat Transfer & Forced/Natural Convection Coefficients 4.3 Radiation Heat Transfer, Surface Emissivity & View Factors 4.4 Overall Heat Transfer Coefficients, Fouling Factors & Transient/Thermal Mass Effects 4.5 Heat Exchanger Analysis: Log Mean Temperature Difference (LMTD) & Effectiveness-NTU (ε-NTU)
5 Chapter 5: Fluid Mechanics & Hydraulic Fundamentals
5.1 Fluid Statics, Incompressible Continuity & Bernoulli Energy Equation 5.2 Pipe Friction, Moody Diagram & Darcy-Weisbach / Hazen-Williams Calculations 5.3 Minor Losses: Equivalent Length, Loss Coefficients (K-factors) & Total System Head 5.4 Pump Sizing, Net Positive Suction Head (NPSHa vs NPSHr) & Cavitation Prevention 5.5 Affinity Laws & Parallel/Series Pump/Fan System Curves
6 Chapter 6: Heating & Cooling Load Calculations
6.1 Outdoor & Indoor Design Conditions (ASHRAE Fundamentals, Climatic Data & Indoor Setpoints) 6.2 Envelope Heat Transmission & Infiltration/Exfiltration Load Methods 6.3 Solar Heat Gain (SHGC), Fenestration & Cooling Load Temperature Difference / Radiant Time Series (CLTD/RTS) 6.4 Internal Heat Gains: Lighting, People, Equipment & Diversity Factors 6.5 Ventilation Loads & Sensible / Latent / Total Cooling Load Synthesis
7 Chapter 7: Refrigeration Principles, Cycles & Cold Storage Applications
7.1 Standard Vapor-Compression Refrigeration Cycle on P-h & T-s Diagrams 7.2 Refrigeration Cycle Performance Metrics: COP, EER, SEER, kW/ton & Ton of Refrigeration 7.3 Cycle Enhancements: Subcooling, Superheating, Liquid-Suction Heat Exchangers & Economizers 7.4 Multi-Stage & Cascade Refrigeration Systems: Intercooling & Flash Gas Removal 7.5 Absorption Refrigeration Cycles: Water-Lithium Bromide & Ammonia-Water Systems 7.6 Food Processing & Cold Storage Refrigeration: Product Load, Pull-Down & Storage Design
8 Chapter 8: Refrigerants, Environmental Regulations & Safety
8.1 Refrigerant Classifications, Nomenclature & Thermodynamic Properties (ASHRAE Standard 34) 8.2 AIM Act, EPA Technology Transitions Sector GWP Limits & Low-GWP Refrigerants (R-32, R-454B) 8.3 Refrigerant Safety Requirements & Machinery Room Design (ASHRAE Standard 15) 8.4 Refrigerant Piping Sizing, Oil Return, Traps & Double Risers
9 Chapter 9: HVAC Equipment & Primary Machinery
9.1 Compressors: Reciprocating, Rotary, Scroll, Screw & Centrifugal 9.2 Condensers: Air-Cooled, Water-Cooled & Evaporative Condensers 9.3 Evaporators & Direct Expansion (DX) vs Liquid Chilling Coils 9.4 Water Chillers: Centrifugal, Screw & Scroll with ASHRAE 90.1 Path A/B IPLV Ratings 9.5 Cooling Towers: Range, Approach, Evaporation, Blowdown & Legionella Control 9.6 Heat Pumps & Variable Refrigerant Flow (VRF): Balance Point, Defrost & Heat Recovery 9.7 Thermal Energy Storage: Full vs. Partial Storage, Chilled Water & Ice Systems
10 Chapter 10: Air-Side Systems & Distribution
10.1 Air Handling Units (AHUs), Dedicated Outdoor Air Systems (DOAS) & Fan-Coil Units 10.2 Duct Design Methodologies: Equal Friction, Static Regain & Velocity Reduction 10.3 Duct Fittings, Dynamic Pressure Losses & SMACNA Construction Standards 10.4 Fan Types, Performance Curves, System Effect Factors & Surge/Stall Dynamics 10.5 Variable Air Volume (VAV) Systems, Terminal Boxes & Space Air Diffusion (ADPI) 10.6 Cooling & Heating Coil Selection: Face Velocity, Rows, Circuiting & Freeze Protection
11 Chapter 11: Hydronic, Steam & Fuel Distribution and Heating Plant
11.1 Hydronic System Architectures: Primary-Only, Primary-Secondary & Variable Primary Flow (VPF) 11.2 Hydronic Pipe Sizing, Velocity Limits & Closed/Open Expansion Tank Sizing 11.3 Control Valves: 2-Way vs 3-Way, Valve Authority (N), Cv Calculations & Characteristic Curves 11.4 Boilers & Heating Hot Water Systems: Condensing vs Non-Condensing & Water Treatment 11.5 Furnaces & Gas-Fired Heating Equipment: AFUE, Temperature Rise, Combustion Air & Vent Categories 11.6 Steam & Condensate Distribution: Latent Heat, Trap Selection, Flash Steam & Stall 11.7 Fuel Gas & Fuel Oil Piping: Demand, Sizing Method, Pressure Drop & Storage Systems
12 Chapter 12: HVAC Control Concepts, Sensors & Sequences
12.1 Sensors, Actuators & Dampers: Selection, Placement, Fail-Safe Position & Damper Authority 12.2 Control Loops: Proportional Offset, PID Action, Reset Strategies & Standard Sequences
13 Chapter 13: Building Energy, Ventilation & Indoor Environmental Quality Codes
13.1 ASHRAE Standard 62.1: Ventilation Rate Procedure (VRP), Indoor Air Quality Procedure & DCV 13.2 ASHRAE Standard 90.1: Building Energy Envelope, Mechanical Efficiency & Economizer Mandates 13.3 ASHRAE Standard 55: Thermal Environmental Conditions, PMV/PPD & Adaptive Comfort Models 13.4 Energy Recovery Systems: Enthalpy Wheels, Fixed-Plate Exchangers, Heat Pipes & Runaround Loops
14 Chapter 14: Supportive Engineering Knowledge, Life Safety & Operations
14.1 Air Filtration Standards: MERV Ratings (ASHRAE 52.2), HEPA & Gas-Phase Adsorption 14.2 Life Safety Systems: Fire/Smoke Dampers, Stairwell Pressurization (NFPA 92) & Smoke Control (NFPA 90A) 14.3 Acoustical Control & Vibration Isolation in HVAC Systems (NC / RC Criteria)
5.2 Pipe Friction, Moody Diagram & Darcy-Weisbach / Hazen-Williams Calculations
Key Takeaways Explain This Topic AI
The Darcy-Weisbach equation (h_f = f * (L/D) * (V^2 / 2g)) is the universal, fundamental equation for fluid friction valid for all fluid types, temperatures, and flow regimes.
Flow regime is determined by the Reynolds number: Re < 2,300 is laminar (f = 64/Re, independent of roughness), 2,300 < Re < 4,000 is transitional, and Re > 4,000 is turbulent.
In the fully rough turbulent zone on the Moody diagram, friction factor f depends entirely on relative roughness (epsilon/D) and is independent of Reynolds number.
The Haaland equation provides an explicit, non-iterative approximation of the implicit Colebrook formula accurate to within 1.5% across the entire turbulent regime.
The Hazen-Williams equation is an empirical method strictly limited to clean water at ambient temperatures (40°F to 75°F); it must NEVER be used for glycol solutions, steam, or high-temperature water.
Last updated: August 2026
5.2 Pipe Friction, Moody Diagram & Darcy-Weisbach / Hazen-Williams Calculations
Accurate calculation of frictional pressure drop in piping networks is essential for sizing hydronic pumps, selecting pipe diameters, and ensuring balanced distribution across HVAC coils, chillers, cooling towers, and boilers. Frictional head loss represents the continuous conversion of mechanical flow energy into internal thermal energy due to fluid shear stress along the conduit walls and turbulent momentum exchange. The NCEES PE Mechanical exam tests both the universal Darcy-Weisbach method (and the associated Moody chart) and the empirical Hazen-Williams formulation.
1. Flow Regimes & Reynolds Number ( R e Re R e )
The flow regime inside a circular conduit is dictated by the dimensionless Reynolds Number ( R e Re R e ), which quantifies the ratio of inertial forces to viscous forces: R e = ρ V D μ = V D ν Re = \frac{\rho V D}{\mu} = \frac{V D}{\nu} R e = μ ρ V D = ν V D
Where:
- ρ \rho ρ : Fluid density ( lbm/ft 3 \text{lbm/ft}^3 lbm/ft 3 or kg/m 3 \text{kg/m}^3 kg/m 3 )
- V V V : Average flow velocity ( ft/s \text{ft/s} ft/s or m/s \text{m/s} m/s )
- D D D : Internal pipe diameter ( ft \text{ft} ft or m \text{m} m )
μ \mu μ : Dynamic (absolute) viscosity ( lbm/(ft ⋅ s) \text{lbm/(ft}\cdot\text{s)} lbm/(ft ⋅ s) or Pa ⋅ s \text{Pa}\cdot\text{s} Pa ⋅ s ; 1 cP = 6.7197 × 10 − 4 lbm/(ft ⋅ s) 1\text{ cP} = 6.7197 \times 10^{-4}\text{ lbm/(ft}\cdot\text{s)} 1 cP = 6.7197 × 1 0 − 4 lbm/(ft ⋅ s) )
ν = μ / ρ \nu = \mu / \rho ν = μ / ρ : Kinematic viscosity ( ft 2 / s \text{ft}^2/\text{s} ft 2 / s or m 2 / s \text{m}^2/\text{s} m 2 / s ; 1 cSt = 1.0764 × 10 − 5 ft 2 / s 1\text{ cSt} = 1.0764 \times 10^{-5}\text{ ft}^2/\text{s} 1 cSt = 1.0764 × 1 0 − 5 ft 2 / s )
Practical GPM Shortcut Formulation for Water at 60 ∘ F 60^\circ\text{F} 6 0 ∘ F
For liquid water at standard conditions ( ρ = 62.37 lbm/ft 3 \rho = 62.37\text{ lbm/ft}^3 ρ = 62.37 lbm/ft 3 , ν = 1.217 × 10 − 5 ft 2 / s \nu = 1.217 \times 10^{-5}\text{ ft}^2/\text{s} ν = 1.217 × 1 0 − 5 ft 2 / s ), with flow rate Q Q Q in GPM \text{GPM} GPM and internal diameter d d d in inches \text{inches} inches : R e ≈ 3160 × Q (GPM) d (inches) × ν (cSt) ≈ 3790 × Q (GPM) d (inches) Re \approx \frac{3160 \times Q\text{ (GPM)}}{d\text{ (inches)} \times \nu\text{ (cSt)}} \approx \frac{3790 \times Q\text{ (GPM)}}{d\text{ (inches)}} R e ≈ d (inches) × ν (cSt) 3160 × Q (GPM) ≈ d (inches) 3790 × Q (GPM)
Flow Regime Boundaries
Laminar Flow ( R e < 2300 Re < 2300 R e < 2300 ): Fluid particles travel along smooth, parallel streamlines. Viscous forces dominate; momentum exchange is purely molecular. Friction factor depends solely on R e Re R e and is completely independent of pipe wall roughness ϵ \epsilon ϵ .
Transition Zone ( 2300 ≤ R e ≤ 4000 2300 \le Re \le 4000 2300 ≤ R e ≤ 4000 ): Flow alternates unpredictably between laminar bursts and turbulent eddies. Engineering calculations in this zone are inherently uncertain; designers generally avoid operating in this regime.
Turbulent Flow ( R e > 4000 Re > 4000 R e > 4000 ): Chaotic 3D velocity fluctuations and turbulent eddies dominate momentum transfer. Friction factor is governed by both Reynolds number R e Re R e and relative pipe roughness ϵ / D \epsilon / D ϵ / D .
2. The Darcy-Weisbach Equation & Moody Diagram
The Darcy-Weisbach equation is the universally applicable, theoretically sound relationship for frictional head loss in any closed conduit carrying any single-phase fluid: h f = f L D V 2 2 g h_f = f \frac{L}{D} \frac{V^2}{2g} h f = f D L 2 g V 2 Δ P f = ρ g g c h f = f L D ρ V 2 2 g c \Delta P_f = \rho \frac{g}{g_c} h_f = f \frac{L}{D} \frac{\rho V^2}{2 g_c} Δ P f = ρ g c g h f = f D L 2 g c ρ V 2
Where:
h f h_f h f : Frictional head loss ( ft of fluid column \text{ft of fluid column} ft of fluid column )
Δ P f \Delta P_f Δ P f : Frictional pressure drop ( lbf/ft 2 \text{lbf/ft}^2 lbf/ft 2 or psi \text{psi} psi , where psi = Δ P f / 144 \text{psi} = \Delta P_f / 144 psi = Δ P f /144 )
f f f : Darcy (Moody) friction factor (dimensionless; note that Fanning friction factor f Fanning = f / 4 f_{\text{Fanning}} = f / 4 f Fanning = f /4 )
- L L L : Length of pipe ( ft \text{ft} ft )
- D D D : Internal pipe diameter ( ft \text{ft} ft )
- V V V : Average flow velocity ( ft/s \text{ft/s} ft/s )
- g g g : Acceleration due to gravity ( 32.174 ft/s 2 32.174\text{ ft/s}^2 32.174 ft/s 2 )
Determining the Friction Factor ( f f f ) +-----------------------------------------------------------------------------------------+
- | MOODY DIAGRAM SCHEMATIC OVERVIEW |
- +-----------------------------------------------------------------------------------------+
- | Friction Relative Roughness|
- | Factor f epsilon / D|
- | 0.10 +----+---------------------------------------------------------------+ 0.05 |
- | | | Laminar Flow: f = 64 / Re | |
- | |\ +-------------------+ | 0.02 |
- | | \ | Transition | |
- | 0.04 | \ | Zone | 0.005 |
- | | \ | ======+ | |
- | 0.02 | \ | Smooth Pipe Line ======= | 0.001 |
- | | \ | ================ | 0.0001 |
- | 0.01 +------+-----------------+-----------------+-------------------------+ Smooth |
- | 10^3 10^4 10^5 10^6 10^8 |
- | Reynolds Number (Re) |
- +-----------------------------------------------------------------------------------------+
Laminar Flow Regime ( R e < 2300 Re < 2300 R e < 2300 ): f = 64 R e f = \frac{64}{Re} f = R e 64
Turbulent Smooth Pipe Regime (Blasius Equation for 4000 < R e < 10 5 4000 < Re < 10^5 4000 < R e < 1 0 5 ): f = 0.3164 R e 0.25 f = \frac{0.3164}{Re^{0.25}} f = R e 0.25 0.3164
General Turbulent Regime (Colebrook Implicit Equation): 1 f = − 2.0 log 10 ( ϵ / D 3.7 + 2.51 R e f ) \frac{1}{\sqrt{f}} = -2.0 \log_{10} \left( \frac{\epsilon / D}{3.7} + \frac{2.51}{Re \sqrt{f}} \right) f 1 = − 2.0 lo g 10 ( 3.7 ϵ / D + R e f 2.51 )
Haaland Equation (Explicit Approximation of Colebrook): Because the Colebrook equation requires iterative root-finding, S.E. Haaland developed an explicit formulation accurate to within 1.5 % 1.5\% 1.5% of Colebrook across 4000 ≤ R e ≤ 10 8 4000 \le Re \le 10^8 4000 ≤ R e ≤ 1 0 8 and 10 − 6 ≤ ϵ / D ≤ 0.05 10^{-6} \le \epsilon/D \le 0.05 1 0 − 6 ≤ ϵ / D ≤ 0.05 : 1 f = − 1.8 log 10 [ ( ϵ / D 3.7 ) 1.11 + 6.9 R e ] \frac{1}{\sqrt{f}} = -1.8 \log_{10} \left[ \left( \frac{\epsilon / D}{3.7} \right)^{1.11} + \frac{6.9}{Re} \right] f 1 = − 1.8 lo g 10 [ ( 3.7 ϵ / D ) 1.11 + R e 6.9 ] f = ( − 1.8 log 10 [ ( ϵ / D 3.7 ) 1.11 + 6.9 R e ] ) − 2 f = \left( -1.8 \log_{10} \left[ \left( \frac{\epsilon / D}{3.7} \right)^{1.11} + \frac{6.9}{Re} \right] \right)^{-2} f = ( − 1.8 lo g 10 [ ( 3.7 ϵ / D ) 1.11 + R e 6.9 ] ) − 2
Fully Rough / Wholly Turbulent Regime (Right Plateau of Moody Chart): At very high Reynolds numbers, the laminar viscous sublayer becomes thinner than the surface asperities ϵ \epsilon ϵ . In this regime, friction is entirely independent of R e Re R e and depends solely on relative roughness: 1 f = − 2.0 log 10 ( ϵ / D 3.7 ) = 1.14 − 2.0 log 10 ( ϵ D ) \frac{1}{\sqrt{f}} = -2.0 \log_{10} \left( \frac{\epsilon / D}{3.7} \right) = 1.14 - 2.0 \log_{10}\left(\frac{\epsilon}{D}\right) f 1 = − 2.0 lo g 10 ( 3.7 ϵ / D ) = 1.14 − 2.0 lo g 10 ( D ϵ )
Pipe Absolute Roughness Values ( ϵ \epsilon ϵ )
Pipe Material Absolute Roughness ϵ \epsilon ϵ (feet) Absolute Roughness ϵ \epsilon ϵ (mm) Description / Typical Usage
Drawn Copper / Brass / Plastic (PVC/PEX) 0.000005 ft 0.000005\text{ ft} 0.000005 ft ( 5 × 10 − 6 5 \times 10^{-6} 5 × 1 0 − 6 ) 0.0015 mm 0.0015\text{ mm} 0.0015 mm Smooth tubing, domestic water, refrigerant lines
Commercial Steel / Wrought Iron (Sch 40/80) 0.00015 ft 0.00015\text{ ft} 0.00015 ft ( 1.5 × 10 − 4 1.5 \times 10^{-4} 1.5 × 1 0 − 4 ) 0.045 mm 0.045\text{ mm} 0.045 mm Standard hydronic heating/cooling piping
Galvanized Steel Duct / Pipe 0.0005 ft 0.0005\text{ ft} 0.0005 ft ( 5.0 × 10 − 4 5.0 \times 10^{-4} 5.0 × 1 0 − 4 ) 0.15 mm 0.15\text{ mm} 0.15 mm Condenser water lines, air distribution ducts
Cast Iron (Uncoated) 0.00085 ft 0.00085\text{ ft} 0.00085 ft ( 8.5 × 10 − 4 8.5 \times 10^{-4} 8.5 × 1 0 − 4 ) 0.26 mm 0.26\text{ mm} 0.26 mm Legacy municipal mains, steam condensate
Ductile Iron (Cement-Mortar Lined) 0.000082 ft 0.000082\text{ ft} 0.000082 ft ( 8.2 × 10 − 5 8.2 \times 10^{-5} 8.2 × 1 0 − 5 ) 0.025 mm 0.025\text{ mm} 0.025 mm Buried chilled water distribution infrastructure
3. The Hazen-Williams Empirical Method (Water Only)
The Hazen-Williams equation is an empirical formulation widely used in civil fire protection (NFPA 13) and domestic plumbing design. It relates water flow rate to friction loss without calculating Reynolds numbers or reading the Moody diagram.
Hazen-Williams Head Loss Formulas (IP Units) h f = 0.002083 ⋅ L ⋅ ( 100 C ) 1.852 ⋅ Q 1.852 d 4.8655 h_f = 0.002083 \cdot L \cdot \left( \frac{100}{C} \right)^{1.852} \cdot \frac{Q^{1.852}}{d^{4.8655}} h f = 0.002083 ⋅ L ⋅ ( C 100 ) 1.852 ⋅ d 4.8655 Q 1.852 Δ P per 100 ft = 4.52 ⋅ Q 1.852 C 1.852 ⋅ d 4.8655 \Delta P_{\text{per 100 ft}} = \frac{4.52 \cdot Q^{1.852}}{C^{1.852} \cdot d^{4.8655}} Δ P per 100 ft = C 1.852 ⋅ d 4.8655 4.52 ⋅ Q 1.852
Where:
h f h_f h f : Head loss ( ft of water \text{ft of water} ft of water )
Δ P per 100 ft \Delta P_{\text{per 100 ft}} Δ P per 100 ft : Pressure loss per 100 ft of pipe ( psi/100 ft \text{psi/100 ft} psi/100 ft )
- L L L : Total equivalent pipe length ( ft \text{ft} ft )
- Q Q Q : Volumetric water flow rate ( GPM \text{GPM} GPM )
- d d d : Inside pipe diameter ( inches \text{inches} inches )
- C C C : Hazen-Williams roughness coefficient (higher C C C = smoother pipe = lower friction)
- Hazen-Williams Roughness Coefficients ( C C C )
- Pipe Material Design C C C -Factor NFPA 13 / Plumbing Standard
- Plastic (PVC, CPVC, PEX, HDPE) 150 150 150 Extremely smooth, non-corroding
- Drawn Copper / Brass Tubing 140 − 150 140 - 150 140 − 150 New smooth metallic tubing
- New Commercial Steel (Schedule 40/10) 130 − 140 130 - 140 130 − 140 Clean new hydronic steel pipe
- Standard Welded Steel (Aged/Design) 120 120 120 Standard design value for steel pipe networks
- Cast Iron (New) 130 130 130 New cast iron distribution mains
- Cast Iron (Aged / Corroded / 20+ yrs) 100 100 100 Unlined, tuberculated legacy piping
- Critical Engineering Limitations of Hazen-Williams
Warning
When Hazen-Williams CANNOT Be Used on the PE Exam:
Non-Water Fluids: Glycol mixtures (ethylene/propylene glycol), oils, and liquid refrigerants MUST use Darcy-Weisbach because Hazen-Williams embeds standard water viscosity.
Non-Standard Water Temperatures: Water temperatures significantly above 75 ∘ F 75^\circ\text{F} 7 5 ∘ F (e.g., heating hot water at 180 ∘ F 180^\circ\text{F} 18 0 ∘ F or boiler feedwater at 220 ∘ F 220^\circ\text{F} 22 0 ∘ F ) have much lower viscosity, causing Hazen-Williams to overestimate head loss by 20 % − 35 % 20\% - 35\% 20% − 35% .
Laminar Flow: Hazen-Williams is completely invalid for R e < 4000 Re < 4000 R e < 4000 .
Air & Steam Distribution: Gases must always be evaluated using Darcy-Weisbach or dedicated compressibility charts.
4. Hydraulic Diameter for Non-Circular Conduits
For fluid flow through non-circular passages—such as rectangular HVAC ducts, flat-oval ductwork, or annular spaces in double-pipe heat exchangers—the characteristic dimension in R e Re R e and Darcy-Weisbach is replaced by the Hydraulic Diameter ( D h D_h D h ): D h = 4 A P wetted D_h = \frac{4 A}{P_{\text{wetted}}} D h = P wetted 4 A
Where:
A A A : Cross-sectional flow area ( ft 2 \text{ft}^2 ft 2 or in. 2 \text{in.}^2 in. 2 )
P wetted P_{\text{wetted}} P wetted : Wetted perimeter in direct contact with the moving fluid ( ft \text{ft} ft or in. \text{in.} in. )
Standard Geometry Hydraulic Diameters +-----------------------------------------------------------------------------+
- | HYDRAULIC DIAMETERS FOR COMMON HVAC GEOMETRIES |
- +-----------------------------------------------------------------------------+
- | 1. Rectangular Duct (Width a, Height b): |
- | Area A = a * b |
- | Perimeter P = 2 * (a + b) |
- | D_h = (4 * a * b) / [2 * (a + b)] = (2 * a * b) / (a + b) |
- | |
- | 2. Annular Space (Outer Pipe ID = D_i, Inner Pipe OD = d_o): |
- | Area A = (pi / 4) * (D_i^2 - d_o^2) |
- | Perimeter P = pi * (D_i + d_o) |
- | D_h = [4 * (pi/4) * (D_i^2 - d_o^2)] / [pi * (D_i + d_o)] = D_i - d_o |
- +-----------------------------------------------------------------------------+
- 5. Worked Engineering Examples
- Worked Example 1: Darcy-Weisbach Friction Loss with Haaland Equation
Chilled water at 45 ∘ F 45^\circ\text{F} 4 5 ∘ F (density ρ = 62.42 lbm/ft 3 \rho = 62.42\text{ lbm/ft}^3 ρ = 62.42 lbm/ft 3 , kinematic viscosity ν = 1.54 × 10 − 5 ft 2 / s \nu = 1.54 \times 10^{-5}\text{ ft}^2/\text{s} ν = 1.54 × 1 0 − 5 ft 2 / s ) flows through L = 300 ft L = 300\text{ ft} L = 300 ft of 4-inch Schedule 40 commercial steel pipe ( D = 4.026 in. = 0.3355 ft D = 4.026\text{ in.} = 0.3355\text{ ft} D = 4.026 in. = 0.3355 ft , absolute roughness ϵ = 0.00015 ft \epsilon = 0.00015\text{ ft} ϵ = 0.00015 ft ) at a volumetric flow rate of Q = 200 GPM Q = 200\text{ GPM} Q = 200 GPM . Calculate the Darcy friction factor f f f , the friction head loss h f h_f h f , and the frictional pressure drop Δ P f \Delta P_f Δ P f in psi \text{psi} psi . Given:
- Fluid: Water at 45°F (rho = 62.42 lbm/ft3, nu = 1.54 x 10^-5 ft2/s)
- Pipe: 4" Sch 40 Steel (D = 0.3355 ft, epsilon = 0.00015 ft, L = 300 ft)
- Flow: Q = 200 GPM
Step 1: Calculate flow area and velocity: A = π 4 D 2 = π 4 ( 0.3355 ft ) 2 = 0.08841 ft 2 A = \frac{\pi}{4} D^2 = \frac{\pi}{4} (0.3355\text{ ft})^2 = 0.08841\text{ ft}^2 A = 4 π D 2 = 4 π ( 0.3355 ft ) 2 = 0.08841 ft 2 Q = 200 GPM × 0.002228 ft 3 / ( s ⋅ GPM ) = 0.4456 ft 3 / s Q = 200\text{ GPM} \times 0.002228\text{ ft}^3/(\text{s}\cdot\text{GPM}) = 0.4456\text{ ft}^3/\text{s} Q = 200 GPM × 0.002228 ft 3 / ( s ⋅ GPM ) = 0.4456 ft 3 / s V = Q A = 0.4456 ft 3 / s 0.08841 ft 2 = 5.040 ft/s V = \frac{Q}{A} = \frac{0.4456\text{ ft}^3/\text{s}}{0.08841\text{ ft}^2} = 5.040\text{ ft/s} V = A Q = 0.08841 ft 2 0.4456 ft 3 / s = 5.040 ft/s
Step 2: Calculate Reynolds number and relative roughness: R e = V D ν = 5.040 ft/s × 0.3355 ft 1.54 × 10 − 5 ft 2 / s = 109 , 802 ≈ 1.10 × 10 5 ( Turbulent ) Re = \frac{V D}{\nu} = \frac{5.040\text{ ft/s} \times 0.3355\text{ ft}}{1.54 \times 10^{-5}\text{ ft}^2/\text{s}} = 109,802 \approx 1.10 \times 10^5 \quad (\text{Turbulent}) R e = ν V D = 1.54 × 1 0 − 5 ft 2 / s 5.040 ft/s × 0.3355 ft = 109 , 802 ≈ 1.10 × 1 0 5 ( Turbulent ) ϵ D = 0.00015 ft 0.3355 ft = 0.0004471 \frac{\epsilon}{D} = \frac{0.00015\text{ ft}}{0.3355\text{ ft}} = 0.0004471 D ϵ = 0.3355 ft 0.00015 ft = 0.0004471
Step 3: Calculate friction factor f f f using the Haaland equation: 1 f = − 1.8 log 10 [ ( 0.0004471 3.7 ) 1.11 + 6.9 109 , 802 ] \frac{1}{\sqrt{f}} = -1.8 \log_{10} \left[ \left( \frac{0.0004471}{3.7} \right)^{1.11} + \frac{6.9}{109,802} \right] f 1 = − 1.8 lo g 10 [ ( 3.7 0.0004471 ) 1.11 + 109 , 802 6.9 ] ( 0.0004471 3.7 ) 1.11 = ( 0.00012084 ) 1.11 = 4.400 × 10 − 5 \left( \frac{0.0004471}{3.7} \right)^{1.11} = (0.00012084)^{1.11} = 4.400 \times 10^{-5} ( 3.7 0.0004471 ) 1.11 = ( 0.00012084 ) 1.11 = 4.400 × 1 0 − 5 6.9 109 , 802 = 6.284 × 10 − 5 \frac{6.9}{109,802} = 6.284 \times 10^{-5} 109 , 802 6.9 = 6.284 × 1 0 − 5 Sum = 4.400 × 10 − 5 + 6.284 × 10 − 5 = 1.0684 × 10 − 4 \text{Sum} = 4.400 \times 10^{-5} + 6.284 \times 10^{-5} = 1.0684 \times 10^{-4} Sum = 4.400 × 1 0 − 5 + 6.284 × 1 0 − 5 = 1.0684 × 1 0 − 4 log 10 ( 1.0684 × 10 − 4 ) = − 3.9713 \log_{10}(1.0684 \times 10^{-4}) = -3.9713 lo g 10 ( 1.0684 × 1 0 − 4 ) = − 3.9713 1 f = − 1.8 × ( − 3.9713 ) = 7.1483 ⟹ f = 0.13989 ⟹ f = 0.01957 ≈ 0.0196 \frac{1}{\sqrt{f}} = -1.8 \times (-3.9713) = 7.1483 \implies \sqrt{f} = 0.13989 \implies f = 0.01957 \approx 0.0196 f 1 = − 1.8 × ( − 3.9713 ) = 7.1483 ⟹ f = 0.13989 ⟹ f = 0.01957 ≈ 0.0196
Step 4: Calculate head loss and pressure drop: h f = f L D V 2 2 g = 0.01957 × ( 300 ft 0.3355 ft ) × ( ( 5.040 ft/s ) 2 2 × 32.174 ft/s 2 ) h_f = f \frac{L}{D} \frac{V^2}{2g} = 0.01957 \times \left( \frac{300\text{ ft}}{0.3355\text{ ft}} \right) \times \left( \frac{(5.040\text{ ft/s})^2}{2 \times 32.174\text{ ft/s}^2} \right) h f = f D L 2 g V 2 = 0.01957 × ( 0.3355 ft 300 ft ) × ( 2 × 32.174 ft/s 2 ( 5.040 ft/s ) 2 ) h f = 0.01957 × 894.19 × 0.39474 ft = 6.908 ft ≈ 6.91 ft h_f = 0.01957 \times 894.19 \times 0.39474\text{ ft} = 6.908\text{ ft} \approx 6.91\text{ ft} h f = 0.01957 × 894.19 × 0.39474 ft = 6.908 ft ≈ 6.91 ft Δ P f = ρ h f 144 = 62.42 lbm/ft 3 × 6.908 ft 144 in. 2 / ft 2 = 2.994 psi ≈ 3.00 psi \Delta P_f = \frac{\rho h_f}{144} = \frac{62.42\text{ lbm/ft}^3 \times 6.908\text{ ft}}{144\text{ in.}^2/\text{ft}^2} = 2.994\text{ psi} \approx 3.00\text{ psi} Δ P f = 144 ρ h f = 144 in. 2 / ft 2 62.42 lbm/ft 3 × 6.908 ft = 2.994 psi ≈ 3.00 psi
6. NCEES Reference Handbook Navigation & Exam Tips
Moody Diagram Location: In the Reference Handbook under Fluid Mechanics → \rightarrow → Friction Factor / Moody Chart . To read the chart, first calculate relative roughness ϵ / D \epsilon/D ϵ / D on the right vertical axis, follow the curve to the calculated Reynolds number on the horizontal axis, and read f f f on the left vertical axis.
Haaland Formula in Handbook: The explicit Haaland equation is listed under Fluid Mechanics → \rightarrow → Colebrook & Haaland Equations . Using this formula on your TI-36X Pro or Casio fx-115ES is significantly faster and more accurate than visually interpolating the Moody chart.
Nominal vs. Actual Pipe Diameters: Always use actual internal diameter (e.g., 4.026 in. 4.026\text{ in.} 4.026 in. for 4-inch Schedule 40 steel, 3.068 in. 3.068\text{ in.} 3.068 in. for 3-inch Schedule 40) rather than nominal diameter ( 4.00 in. 4.00\text{ in.} 4.00 in. or 3.00 in. 3.00\text{ in.} 3.00 in. ). Because diameter appears to the 5th power ( D 5 D^5 D 5 ) in pressure drop formulas, small diameter discrepancies create massive errors.