Study guide
5.4 Pump Sizing, Net Positive Suction Head (NPSHa vs NPSHr) & Cavitation Prevention
PE Mechanical: HVAC and Refrigeration Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview, Reference Handbook & Engineering Foundations
1.1 NCEES Exam Specification, CBT Delivery & Reference Handbook Strategy 1.2 Engineering Units, Dimensional Analysis & Physical Property Lookups 1.3 Engineering Economics, Life Cycle Cost Analysis & Equipment Financial Evaluation 1.4 Electrical Foundations, Motor Ratings & Variable Frequency Drives (VFDs)
2 Chapter 2: Thermodynamics & Energy Balances
2.1 First and Second Laws of Thermodynamics & Open/Closed System Energy Balances 2.2 Thermodynamic Cycles: Carnot, Rankine, Brayton & Reversed Carnot Limit 2.3 Gas & Vapor Property Evaluation: Steam Tables, Superheat & Subcooling 2.4 Mass, Energy & Combustion Balances for HVAC Equipment
3 Chapter 3: Psychrometrics, Moist Air Processes & Humidity Equipment
3.1 Psychrometric Properties: DBT, WBT, DPT, RH, Humidity Ratio & Enthalpy 3.2 Chart Reading & Psychrometric Equations at Sea Level vs. Altitude (5,000 ft) 3.3 Basic Psychrometric Processes: Sensible Heating/Cooling, Humidification & Dehumidification 3.4 Mixed Air Calculations & Complex Air Conditioning Cycles (Preheat, Reheat & Bypass) 3.5 Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP) & Coil Bypass Factor 3.6 Humidification & Dehumidification Equipment: Steam, Adiabatic, Desiccant & Low-Temperature Processes
4 Chapter 4: Heat Transfer Principles & Sizing
4.1 Steady-State Conduction & Multilayer Thermal Resistance (R-Value & U-Factor) 4.2 Convective Heat Transfer & Forced/Natural Convection Coefficients 4.3 Radiation Heat Transfer, Surface Emissivity & View Factors 4.4 Overall Heat Transfer Coefficients, Fouling Factors & Transient/Thermal Mass Effects 4.5 Heat Exchanger Analysis: Log Mean Temperature Difference (LMTD) & Effectiveness-NTU (ε-NTU)
5 Chapter 5: Fluid Mechanics & Hydraulic Fundamentals
5.1 Fluid Statics, Incompressible Continuity & Bernoulli Energy Equation 5.2 Pipe Friction, Moody Diagram & Darcy-Weisbach / Hazen-Williams Calculations 5.3 Minor Losses: Equivalent Length, Loss Coefficients (K-factors) & Total System Head 5.4 Pump Sizing, Net Positive Suction Head (NPSHa vs NPSHr) & Cavitation Prevention 5.5 Affinity Laws & Parallel/Series Pump/Fan System Curves
6 Chapter 6: Heating & Cooling Load Calculations
6.1 Outdoor & Indoor Design Conditions (ASHRAE Fundamentals, Climatic Data & Indoor Setpoints) 6.2 Envelope Heat Transmission & Infiltration/Exfiltration Load Methods 6.3 Solar Heat Gain (SHGC), Fenestration & Cooling Load Temperature Difference / Radiant Time Series (CLTD/RTS) 6.4 Internal Heat Gains: Lighting, People, Equipment & Diversity Factors 6.5 Ventilation Loads & Sensible / Latent / Total Cooling Load Synthesis
7 Chapter 7: Refrigeration Principles, Cycles & Cold Storage Applications
7.1 Standard Vapor-Compression Refrigeration Cycle on P-h & T-s Diagrams 7.2 Refrigeration Cycle Performance Metrics: COP, EER, SEER, kW/ton & Ton of Refrigeration 7.3 Cycle Enhancements: Subcooling, Superheating, Liquid-Suction Heat Exchangers & Economizers 7.4 Multi-Stage & Cascade Refrigeration Systems: Intercooling & Flash Gas Removal 7.5 Absorption Refrigeration Cycles: Water-Lithium Bromide & Ammonia-Water Systems 7.6 Food Processing & Cold Storage Refrigeration: Product Load, Pull-Down & Storage Design
8 Chapter 8: Refrigerants, Environmental Regulations & Safety
8.1 Refrigerant Classifications, Nomenclature & Thermodynamic Properties (ASHRAE Standard 34) 8.2 AIM Act, EPA Technology Transitions Sector GWP Limits & Low-GWP Refrigerants (R-32, R-454B) 8.3 Refrigerant Safety Requirements & Machinery Room Design (ASHRAE Standard 15) 8.4 Refrigerant Piping Sizing, Oil Return, Traps & Double Risers
9 Chapter 9: HVAC Equipment & Primary Machinery
9.1 Compressors: Reciprocating, Rotary, Scroll, Screw & Centrifugal 9.2 Condensers: Air-Cooled, Water-Cooled & Evaporative Condensers 9.3 Evaporators & Direct Expansion (DX) vs Liquid Chilling Coils 9.4 Water Chillers: Centrifugal, Screw & Scroll with ASHRAE 90.1 Path A/B IPLV Ratings 9.5 Cooling Towers: Range, Approach, Evaporation, Blowdown & Legionella Control 9.6 Heat Pumps & Variable Refrigerant Flow (VRF): Balance Point, Defrost & Heat Recovery 9.7 Thermal Energy Storage: Full vs. Partial Storage, Chilled Water & Ice Systems
10 Chapter 10: Air-Side Systems & Distribution
10.1 Air Handling Units (AHUs), Dedicated Outdoor Air Systems (DOAS) & Fan-Coil Units 10.2 Duct Design Methodologies: Equal Friction, Static Regain & Velocity Reduction 10.3 Duct Fittings, Dynamic Pressure Losses & SMACNA Construction Standards 10.4 Fan Types, Performance Curves, System Effect Factors & Surge/Stall Dynamics 10.5 Variable Air Volume (VAV) Systems, Terminal Boxes & Space Air Diffusion (ADPI) 10.6 Cooling & Heating Coil Selection: Face Velocity, Rows, Circuiting & Freeze Protection
11 Chapter 11: Hydronic, Steam & Fuel Distribution and Heating Plant
11.1 Hydronic System Architectures: Primary-Only, Primary-Secondary & Variable Primary Flow (VPF) 11.2 Hydronic Pipe Sizing, Velocity Limits & Closed/Open Expansion Tank Sizing 11.3 Control Valves: 2-Way vs 3-Way, Valve Authority (N), Cv Calculations & Characteristic Curves 11.4 Boilers & Heating Hot Water Systems: Condensing vs Non-Condensing & Water Treatment 11.5 Furnaces & Gas-Fired Heating Equipment: AFUE, Temperature Rise, Combustion Air & Vent Categories 11.6 Steam & Condensate Distribution: Latent Heat, Trap Selection, Flash Steam & Stall 11.7 Fuel Gas & Fuel Oil Piping: Demand, Sizing Method, Pressure Drop & Storage Systems
12 Chapter 12: HVAC Control Concepts, Sensors & Sequences
12.1 Sensors, Actuators & Dampers: Selection, Placement, Fail-Safe Position & Damper Authority 12.2 Control Loops: Proportional Offset, PID Action, Reset Strategies & Standard Sequences
13 Chapter 13: Building Energy, Ventilation & Indoor Environmental Quality Codes
13.1 ASHRAE Standard 62.1: Ventilation Rate Procedure (VRP), Indoor Air Quality Procedure & DCV 13.2 ASHRAE Standard 90.1: Building Energy Envelope, Mechanical Efficiency & Economizer Mandates 13.3 ASHRAE Standard 55: Thermal Environmental Conditions, PMV/PPD & Adaptive Comfort Models 13.4 Energy Recovery Systems: Enthalpy Wheels, Fixed-Plate Exchangers, Heat Pipes & Runaround Loops
14 Chapter 14: Supportive Engineering Knowledge, Life Safety & Operations
14.1 Air Filtration Standards: MERV Ratings (ASHRAE 52.2), HEPA & Gas-Phase Adsorption 14.2 Life Safety Systems: Fire/Smoke Dampers, Stairwell Pressurization (NFPA 92) & Smoke Control (NFPA 90A) 14.3 Acoustical Control & Vibration Isolation in HVAC Systems (NC / RC Criteria)
5.4 Pump Sizing, Net Positive Suction Head (NPSHa vs NPSHr) & Cavitation Prevention
Key Takeaways Explain This Topic AI
Water Horsepower (WHP) represents useful hydraulic power: WHP = (Q * H * SG) / 3960; Brake Horsepower (BHP) accounts for pump efficiency: BHP = WHP / eta_pump.
Cavitation occurs when local static pressure at the pump impeller eye drops below the fluid vapor pressure (P_vp), forming vapor bubbles that violently collapse in high-pressure regions.
Net Positive Suction Head Available (NPSHa) is determined solely by the suction piping system: NPSHa = (P_surface,abs / gamma) +/- z_s - h_f,suction - (P_vp / gamma).
For closed deaerators or boiling tanks where liquid is at saturation (P_surface = P_vp), the surface pressure and vapor pressure terms cancel out, leaving NPSHa = z_s - h_f,suction.
To prevent cavitation, design systems so NPSHa >= NPSHr + Margin (where Margin is typically >= 2 to 5 ft or 1.2 * NPSHr); increase NPSHa by raising tank elevation, upsizing suction pipe, or subcooling fluid.
Last updated: August 2026
5.4 Pump Sizing, Net Positive Suction Head (NPSHa vs NPSHr) & Cavitation Prevention
Centrifugal pumps are the primary prime movers in hydronic HVAC systems, circulating chilled water, condenser water, heating hot water, and boiler feedwater. Properly selecting and sizing a pump requires calculating the exact operating flow and total dynamic head, evaluating pump hydraulic efficiency at the Best Efficiency Point (BEP), determining motor horsepower requirements, and verifying Net Positive Suction Head (NPSH) margins to prevent destructive cavitation . Cavitation calculations are among the most frequently tested topics on the PE Mechanical exam.
1. Pump Power & Efficiency Formulations
Centrifugal pumps convert mechanical shaft power supplied by an electric motor into fluid hydraulic energy (static pressure and velocity). +-----------------------------------------------------------------------------+
- | CENTRIFUGAL PUMP ENERGY FLOW & EFFICIENCY LOSS CHAIN |
- +-----------------------------------------------------------------------------+
- | Electrical Input Power (kW) |
- | | |
- | v [Motor Efficiency: eta_motor ~ 90% - 95%] |
- | Brake Horsepower (BHP) = Shaft Power into Pump |
- | | |
- | v [Pump Hydraulic & Mechanical Efficiency: eta_pump ~ 70% - 85%] |
- | Water Horsepower (WHP) = Useful Hydraulic Power in Fluid |
- +-----------------------------------------------------------------------------+
- 1. Water Horsepower (Hydraulic Power, W H P WHP W H P )
Water horsepower is the theoretical power transferred directly into the moving liquid stream: W H P = m ˙ g H 550 g c = Q (GPM) × H (ft) × Specific Gravity (SG) 3960 WHP = \frac{\dot{m} g H}{550 g_c} = \frac{Q\text{ (GPM)} \times H\text{ (ft)} \times \text{Specific Gravity (SG)}}{3960} W H P = 550 g c m ˙ g H = 3960 Q (GPM) × H (ft) × Specific Gravity (SG) In SI Metric Units: P hyd (kW) = ρ g Q H 1000 = γ Q H 1000 = Q (m 3 /s) × Δ P (kPa) 1 \text{In SI Metric Units:} \quad P_{\text{hyd}}\text{ (kW)} = \frac{\rho g Q H}{1000} = \frac{\gamma Q H}{1000} = \frac{Q\text{ (m}^3\text{/s)} \times \Delta P\text{ (kPa)}}{1} In SI Metric Units: P hyd (kW) = 1000 ρ g Q H = 1000 γ Q H = 1 Q (m 3 /s) × Δ P (kPa)
2. Brake Horsepower (Shaft Power, B H P BHP B H P )
Brake horsepower is the actual mechanical power required at the pump input shaft, accounting for internal impeller friction, recirculation losses, and bearing/seal drag: B H P = W H P η pump = Q (GPM) × H (ft) × SG 3960 × η pump BHP = \frac{WHP}{\eta_{\text{pump}}} = \frac{Q\text{ (GPM)} \times H\text{ (ft)} \times \text{SG}}{3960 \times \eta_{\text{pump}}} B H P = η pump W H P = 3960 × η pump Q (GPM) × H (ft) × SG
3. Electrical Motor Input Power ( P elec P_{\text{elec}} P elec )
The electrical power drawn from the building electrical distribution grid: P elec (kW) = B H P × 0.7457 η motor = Q (GPM) × H (ft) × SG × 0.7457 3960 × η pump × η motor P_{\text{elec}}\text{ (kW)} = \frac{BHP \times 0.7457}{\eta_{\text{motor}}} = \frac{Q\text{ (GPM)} \times H\text{ (ft)} \times \text{SG} \times 0.7457}{3960 \times \eta_{\text{pump}} \times \eta_{\text{motor}}} P elec (kW) = η motor B H P × 0.7457 = 3960 × η pump × η motor Q (GPM) × H (ft) × SG × 0.7457
2. Centrifugal Pump Performance Curves & BEP
Centrifugal pump performance is defined by characteristic curves provided by manufacturers for specific impeller diameters and rotational speeds. Head H (ft) Efficiency eta (%)
- BHP (hp) NPSHr (ft)
- ^
- | ======================================\ Head Curve (H vs Q)
- | \
- | +--- BEP ---+ \
- | / (Best Eff) \ \ <--- Efficiency Curve (eta vs Q)
- | / \=======\
- | / \
- | / BHP Curve \
- | ==========+============================+===> (BHP vs Q)
- | /
- | / NPSHr Curve
- | +=============================================> (NPSHr vs Q)
- +--------------------------------------------------------> Flow Q (GPM)
Best Efficiency Point (BEP): The flow rate and head where the pump operates at peak mechanical/hydraulic efficiency. Operating within the Preferred Operating Region (POR) ( 70 % to 120 % 70\% \text{ to } 120\% 70% to 120% of BEP) minimizes shaft deflection, bearing wear, noise, and vibration.
Shutoff Head ( H 0 H_0 H 0 ): The total head produced by the pump at zero volumetric discharge flow ( Q = 0 Q = 0 Q = 0 ). Running continuously at shutoff overheats and vaporizes the fluid inside the casing.
3. Physics of Cavitation
Cavitation is a destructive two-phase hydraulic phenomenon occurring when localized static pressure inside the pump casing drops below the liquid's saturation vapor pressure ( P v p P_{vp} P v p ) at the operating temperature. +-----------------------------------------------------------------------------+
- | THE TWO PHASES OF PUMP CAVITATION |
- +-----------------------------------------------------------------------------+
- | PHASE 1: VAPOR BUBBLE FORMATION (Impeller Eye / Low Pressure Area) |
- | - Liquid enters suction eye; accelerates around leading vane edge. |
- | - Local static pressure drops: P_local < P_vapor. |
- | - Liquid flashes instantly into thousands of microscopic vapor bubbles. |
- | |
- | PHASE 2: VIOLENT BUBBLE COLLAPSE (Impeller Vane Discharge / High Pressure) |
- | - Fluid travels into high-pressure outer volute passages: P_local > P_vp. |
- | - Vapor bubbles collapse asymmetrically at supersonic speeds. |
- | - Micro-jets strike metal surfaces with impact pressures > 100,000 psi. |
- | - Results: Severe pitting, erosion, gravel rattling noise, failed seals. |
- +-----------------------------------------------------------------------------+
- 4. Net Positive Suction Head: NPSHa vs. NPSHr
To prevent cavitation, the total suction head available in the piping system must exceed the suction head required by the pump impeller.
Net Positive Suction Head Available ( NPSHa \text{NPSHa} NPSHa )
NPSHa \text{NPSHa} NPSHa is a property of the suction piping installation . It measures the net stagnation pressure above vapor pressure at the pump suction centerline: NPSHa = P surface, abs γ ± z s − h f , suction − P v p γ \text{NPSHa} = \frac{P_{\text{surface, abs}}}{\gamma} \pm z_s - h_{f,\text{suction}} - \frac{P_{vp}}{\gamma} NPSHa = γ P surface, abs ± z s − h f , suction − γ P v p
Where:
P surface, abs P_{\text{surface, abs}} P surface, abs : Absolute pressure at the liquid supply surface ( psia × 144 / γ \text{psia} \times 144 / \gamma psia × 144/ γ ; for open atmospheric tanks at sea level, P atm = 14.696 psia = 33.93 ft of water P_{\text{atm}} = 14.696\text{ psia} = 33.93\text{ ft of water} P atm = 14.696 psia = 33.93 ft of water )
- + z s +z_s + z s : Static liquid head above pump suction centerline ( Flooded Suction , positive head)
- − z s -z_s − z s : Static liquid elevation below pump suction centerline ( Suction Lift , negative head)
h f , suction h_{f,\text{suction}} h f , suction : Total friction and minor head losses in the suction piping from tank to pump suction flange ( ft \text{ft} ft )
P v p P_{vp} P v p : Fluid saturation vapor pressure at operating temperature ( psia × 144 / γ \text{psia} \times 144 / \gamma psia × 144/ γ , in ft of water \text{ft of water} ft of water ) CASE A: Open Basin (Flooded Suction) CASE B: Open Sump (Suction Lift)
- P_atm P_atm
- ~~~~~ v ~~~~~ v
- | | | |
- | | +z_s (Water level ABOVE pump) | |
- | | | | -z_s (Water level BELOW pump)
- +---+ | |
- | +---+
- | Suction Pipe (h_f,s) | Suction Line (h_f,s)
- v v
- +------+ +------+
- | PUMP | | PUMP |
- +------+ +------+
- NPSHa = h_atm + z_s - h_f,s - h_vp NPSHa = h_atm - z_s - h_f,s - h_vp
- Special Case: Closed Saturated Storage Tanks (Boiler Deaerators)
When liquid is stored in a closed vessel at its boiling / saturation temperature (e.g., a boiler deaerator or condensate receiver), the pressure on the liquid surface equals the fluid vapor pressure ( P surface, abs = P v p P_{\text{surface, abs}} = P_{vp} P surface, abs = P v p ): P surface, abs γ − P v p γ = 0 \frac{P_{\text{surface, abs}}}{\gamma} - \frac{P_{vp}}{\gamma} = 0 γ P surface, abs − γ P v p = 0 NPSHa saturated vessel = z s − h f , suction \text{NPSHa}_{\text{saturated vessel}} = z_s - h_{f,\text{suction}} NPSHa saturated vessel = z s − h f , suction
Exam Key Insight: For boiling or saturated liquid tanks, atmospheric pressure provides ZERO contribution to NPSHa. The available suction head is generated exclusively by the physical elevation of the tank above the pump ( z s z_s z s ) minus the suction pipe friction loss ( h f , suction h_{f,\text{suction}} h f , suction ). This is why boiler feed deaerators are always elevated 15 to 30 feet above the boiler feed pumps!
5. Water Vapor Pressure & Physical Properties Table
Accurate NPSHa calculations require looking up saturation vapor pressure P v p P_{vp} P v p and density at fluid operating temperature.
Water Temp ( ∘ F ^\circ\text{F} ∘ F ) Vapor Pressure P v p P_{vp} P v p ( psia \text{psia} psia ) Vapor Pressure Head h v p h_{vp} h v p ( ft H 2 O \text{ft H}_2\text{O} ft H 2 O ) Density ρ \rho ρ ( lbm/ft 3 \text{lbm/ft}^3 lbm/ft 3 ) Specific Gravity ( SG \text{SG} SG )
40 ∘ F 40^\circ\text{F} 4 0 ∘ F 0.1217 psia 0.1217\text{ psia} 0.1217 psia 0.281 ft 0.281\text{ ft} 0.281 ft 62.42 lbm/ft 3 62.42\text{ lbm/ft}^3 62.42 lbm/ft 3 1.000 1.000 1.000
60 ∘ F 60^\circ\text{F} 6 0 ∘ F 0.2563 psia 0.2563\text{ psia} 0.2563 psia 0.592 ft 0.592\text{ ft} 0.592 ft 62.37 lbm/ft 3 62.37\text{ lbm/ft}^3 62.37 lbm/ft 3 0.999 0.999 0.999
85 ∘ F 85^\circ\text{F} 8 5 ∘ F 0.5960 psia 0.5960\text{ psia} 0.5960 psia 1.380 ft 1.380\text{ ft} 1.380 ft 62.17 lbm/ft 3 62.17\text{ lbm/ft}^3 62.17 lbm/ft 3 0.996 0.996 0.996
95 ∘ F 95^\circ\text{F} 9 5 ∘ F (Tower Water) 0.8160 psia 0.8160\text{ psia} 0.8160 psia 1.890 ft 1.890\text{ ft} 1.890 ft 62.06 lbm/ft 3 62.06\text{ lbm/ft}^3 62.06 lbm/ft 3 0.995 0.995 0.995
140 ∘ F 140^\circ\text{F} 14 0 ∘ F (Heating Water) 2.892 psia 2.892\text{ psia} 2.892 psia 6.770 ft 6.770\text{ ft} 6.770 ft 61.38 lbm/ft 3 61.38\text{ lbm/ft}^3 61.38 lbm/ft 3 0.984 0.984 0.984
180 ∘ F 180^\circ\text{F} 18 0 ∘ F 7.515 psia 7.515\text{ psia} 7.515 psia 17.84 ft 17.84\text{ ft} 17.84 ft 60.57 lbm/ft 3 60.57\text{ lbm/ft}^3 60.57 lbm/ft 3 0.971 0.971 0.971
212 ∘ F 212^\circ\text{F} 21 2 ∘ F (Boiling/Sea Lvl) 14.696 psia 14.696\text{ psia} 14.696 psia 35.38 ft 35.38\text{ ft} 35.38 ft 59.83 lbm/ft 3 59.83\text{ lbm/ft}^3 59.83 lbm/ft 3 0.959 0.959 0.959
225 ∘ F 225^\circ\text{F} 22 5 ∘ F (Deaerator) 18.95 psia 18.95\text{ psia} 18.95 psia 45.71 ft 45.71\text{ ft} 45.71 ft 59.70 lbm/ft 3 59.70\text{ lbm/ft}^3 59.70 lbm/ft 3 0.956 0.956 0.956
Cavitation Margin & Prevention Strategies Cavitation Margin = NPSHa − NPSHr ≥ 2.0 to 5.0 ft ( or NPSHa ≥ 1.2 × NPSHr ) \text{Cavitation Margin} = \text{NPSHa} - \text{NPSHr} \ge 2.0\text{ to }5.0\text{ ft} \quad (\text{or } \text{NPSHa} \ge 1.2 \times \text{NPSHr}) Cavitation Margin = NPSHa − NPSHr ≥ 2.0 to 5.0 ft ( or NPSHa ≥ 1.2 × NPSHr )
Practical Engineering Methods to Prevent Cavitation:
Upsize Suction Piping Diameter: Drops velocity ( V ∝ D − 2 V \propto D^{-2} V ∝ D − 2 ) and dramatically reduces friction losses ( h f ∝ D − 5 h_f \propto D^{-5} h f ∝ D − 5 ). Never use suction pipe smaller than the pump suction nozzle.
Shorten Suction Line Length & Eliminate Fittings: Locate pump as close to supply vessel as possible; replace restrictive globe valves with full-port butterfly or gate valves.
Elevate Supply Vessel / Lower Pump: Increases static head + z s +z_s + z s .
Subcool the Fluid: Lowering fluid temperature drops vapor pressure P v p P_{vp} P v p exponentially.
Select a Lower-NPSHr Pump: Use a larger impeller eye diameter, lower operational RPM ( 1150 RPM 1150\text{ RPM} 1150 RPM vs 1750 RPM 1750\text{ RPM} 1750 RPM ), or double-suction impeller design.
- 6. Worked Engineering Examples
- Worked Example 1: Condenser Water Pump Power & NPSHa Calculation
A cooling tower condenser water pump delivers Q = 900 GPM Q = 900\text{ GPM} Q = 900 GPM of water against H = 75 ft H = 75\text{ ft} H = 75 ft total dynamic head. The water temperature is 95 ∘ F 95^\circ\text{F} 9 5 ∘ F ( P v p = 0.816 psia P_{vp} = 0.816\text{ psia} P v p = 0.816 psia , ρ = 62.06 lbm/ft 3 \rho = 62.06\text{ lbm/ft}^3 ρ = 62.06 lbm/ft 3 , SG = 0.995 \text{SG} = 0.995 SG = 0.995 ). Pump efficiency is η p = 82 % \eta_p = 82\% η p = 82% and motor efficiency is η m = 94.5 % \eta_m = 94.5\% η m = 94.5% . The pump operates at sea level ( P atm = 14.696 psia = 34.10 ft H 2 O P_{\text{atm}} = 14.696\text{ psia} = 34.10\text{ ft H}_2\text{O} P atm = 14.696 psia = 34.10 ft H 2 O ) with flooded suction from the tower basin located z s = 4.5 ft z_s = 4.5\text{ ft} z s = 4.5 ft above the pump centerline. Suction piping losses total h f , suction = 2.1 ft h_{f,\text{suction}} = 2.1\text{ ft} h f , suction = 2.1 ft , and the pump requires NPSHr = 17.5 ft \text{NPSHr} = 17.5\text{ ft} NPSHr = 17.5 ft .
Calculate:
- Water Horsepower ( W H P WHP W H P )
- Brake Horsepower ( B H P BHP B H P )
- Electrical Input Power ( P elec P_{\text{elec}} P elec in kW \text{kW} kW )
- Available Net Positive Suction Head ( NPSHa \text{NPSHa} NPSHa ) and cavitation margin
Step 1: Calculate WHP, BHP, and Electrical kW: W H P = Q × H × SG 3960 = 900 GPM × 75 ft × 0.995 3960 = 67 , 162.5 3960 = 16.96 hp WHP = \frac{Q \times H \times \text{SG}}{3960} = \frac{900\text{ GPM} \times 75\text{ ft} \times 0.995}{3960} = \frac{67,162.5}{3960} = 16.96\text{ hp} W H P = 3960 Q × H × SG = 3960 900 GPM × 75 ft × 0.995 = 3960 67 , 162.5 = 16.96 hp B H P = W H P η p = 16.96 hp 0.82 = 20.68 hp BHP = \frac{WHP}{\eta_p} = \frac{16.96\text{ hp}}{0.82} = 20.68\text{ hp} B H P = η p W H P = 0.82 16.96 hp = 20.68 hp P elec = B H P × 0.7457 η m = 20.68 hp × 0.7457 0.945 = 16.32 kW P_{\text{elec}} = \frac{BHP \times 0.7457}{\eta_m} = \frac{20.68\text{ hp} \times 0.7457}{0.945} = 16.32\text{ kW} P elec = η m B H P × 0.7457 = 0.945 20.68 hp × 0.7457 = 16.32 kW
Step 2: Calculate NPSHa: h atm = 14.696 psia × 144 62.06 lbm/ft 3 = 34.10 ft h_{\text{atm}} = \frac{14.696\text{ psia} \times 144}{62.06\text{ lbm/ft}^3} = 34.10\text{ ft} h atm = 62.06 lbm/ft 3 14.696 psia × 144 = 34.10 ft h v p = 0.816 psia × 144 62.06 lbm/ft 3 = 1.89 ft h_{vp} = \frac{0.816\text{ psia} \times 144}{62.06\text{ lbm/ft}^3} = 1.89\text{ ft} h v p = 62.06 lbm/ft 3 0.816 psia × 144 = 1.89 ft NPSHa = h atm + z s − h f , suction − h v p \text{NPSHa} = h_{\text{atm}} + z_s - h_{f,\text{suction}} - h_{vp} NPSHa = h atm + z s − h f , suction − h v p NPSHa = 34.10 ft + 4.50 ft − 2.10 ft − 1.89 ft = 34.61 ft \text{NPSHa} = 34.10\text{ ft} + 4.50\text{ ft} - 2.10\text{ ft} - 1.89\text{ ft} = 34.61\text{ ft} NPSHa = 34.10 ft + 4.50 ft − 2.10 ft − 1.89 ft = 34.61 ft
Step 3: Evaluate cavitation margin: Margin = NPSHa − NPSHr = 34.61 ft − 17.50 ft = 17.11 ft \text{Margin} = \text{NPSHa} - \text{NPSHr} = 34.61\text{ ft} - 17.50\text{ ft} = 17.11\text{ ft} Margin = NPSHa − NPSHr = 34.61 ft − 17.50 ft = 17.11 ft
Since 17.11 ft > 5.0 ft 17.11\text{ ft} > 5.0\text{ ft} 17.11 ft > 5.0 ft , the pump operates safely with zero risk of cavitation.
7. NCEES Reference Handbook Navigation & Exam Tips
Pump Power Formulas: Found under Fluid Mechanics → \rightarrow → Turbomachinery / Pumps . Remember the conversion constant 3960 3960 3960 is derived from 550 ft ⋅ lbf/s × 60 s/min / 8.337 lbm/gal = 3960 550\text{ ft}\cdot\text{lbf/s} \times 60\text{ s/min} / 8.337\text{ lbm/gal} = 3960 550 ft ⋅ lbf/s × 60 s/min /8.337 lbm/gal = 3960 .
Steam Tables for Vapor Pressure: If the problem gives water at an elevated temperature (such as 180 ∘ F 180^\circ\text{F} 18 0 ∘ F or 225 ∘ F 225^\circ\text{F} 22 5 ∘ F ), jump directly to the Thermodynamics → \rightarrow → Saturated Steam Temperature Table to look up P sat P_{\text{sat}} P sat in psia \text{psia} psia .