4.1 Steady-State Conduction & Multilayer Thermal Resistance (R-Value & U-Factor)
PE Mechanical: HVAC and Refrigeration Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview, Reference Handbook & Engineering Foundations
1.1 NCEES Exam Specification, CBT Delivery & Reference Handbook Strategy 1.2 Engineering Units, Dimensional Analysis & Physical Property Lookups 1.3 Engineering Economics, Life Cycle Cost Analysis & Equipment Financial Evaluation 1.4 Electrical Foundations, Motor Ratings & Variable Frequency Drives (VFDs)
2 Chapter 2: Thermodynamics & Energy Balances
2.1 First and Second Laws of Thermodynamics & Open/Closed System Energy Balances 2.2 Thermodynamic Cycles: Carnot, Rankine, Brayton & Reversed Carnot Limit 2.3 Gas & Vapor Property Evaluation: Steam Tables, Superheat & Subcooling 2.4 Mass, Energy & Combustion Balances for HVAC Equipment
3 Chapter 3: Psychrometrics, Moist Air Processes & Humidity Equipment
3.1 Psychrometric Properties: DBT, WBT, DPT, RH, Humidity Ratio & Enthalpy 3.2 Chart Reading & Psychrometric Equations at Sea Level vs. Altitude (5,000 ft) 3.3 Basic Psychrometric Processes: Sensible Heating/Cooling, Humidification & Dehumidification 3.4 Mixed Air Calculations & Complex Air Conditioning Cycles (Preheat, Reheat & Bypass) 3.5 Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP) & Coil Bypass Factor 3.6 Humidification & Dehumidification Equipment: Steam, Adiabatic, Desiccant & Low-Temperature Processes
4 Chapter 4: Heat Transfer Principles & Sizing
4.1 Steady-State Conduction & Multilayer Thermal Resistance (R-Value & U-Factor) 4.2 Convective Heat Transfer & Forced/Natural Convection Coefficients 4.3 Radiation Heat Transfer, Surface Emissivity & View Factors 4.4 Overall Heat Transfer Coefficients, Fouling Factors & Transient/Thermal Mass Effects 4.5 Heat Exchanger Analysis: Log Mean Temperature Difference (LMTD) & Effectiveness-NTU (ε-NTU)
5 Chapter 5: Fluid Mechanics & Hydraulic Fundamentals
5.1 Fluid Statics, Incompressible Continuity & Bernoulli Energy Equation 5.2 Pipe Friction, Moody Diagram & Darcy-Weisbach / Hazen-Williams Calculations 5.3 Minor Losses: Equivalent Length, Loss Coefficients (K-factors) & Total System Head 5.4 Pump Sizing, Net Positive Suction Head (NPSHa vs NPSHr) & Cavitation Prevention 5.5 Affinity Laws & Parallel/Series Pump/Fan System Curves
6 Chapter 6: Heating & Cooling Load Calculations
6.1 Outdoor & Indoor Design Conditions (ASHRAE Fundamentals, Climatic Data & Indoor Setpoints) 6.2 Envelope Heat Transmission & Infiltration/Exfiltration Load Methods 6.3 Solar Heat Gain (SHGC), Fenestration & Cooling Load Temperature Difference / Radiant Time Series (CLTD/RTS) 6.4 Internal Heat Gains: Lighting, People, Equipment & Diversity Factors 6.5 Ventilation Loads & Sensible / Latent / Total Cooling Load Synthesis
7 Chapter 7: Refrigeration Principles, Cycles & Cold Storage Applications
7.1 Standard Vapor-Compression Refrigeration Cycle on P-h & T-s Diagrams 7.2 Refrigeration Cycle Performance Metrics: COP, EER, SEER, kW/ton & Ton of Refrigeration 7.3 Cycle Enhancements: Subcooling, Superheating, Liquid-Suction Heat Exchangers & Economizers 7.4 Multi-Stage & Cascade Refrigeration Systems: Intercooling & Flash Gas Removal 7.5 Absorption Refrigeration Cycles: Water-Lithium Bromide & Ammonia-Water Systems 7.6 Food Processing & Cold Storage Refrigeration: Product Load, Pull-Down & Storage Design
8 Chapter 8: Refrigerants, Environmental Regulations & Safety
8.1 Refrigerant Classifications, Nomenclature & Thermodynamic Properties (ASHRAE Standard 34) 8.2 AIM Act, EPA Technology Transitions Sector GWP Limits & Low-GWP Refrigerants (R-32, R-454B) 8.3 Refrigerant Safety Requirements & Machinery Room Design (ASHRAE Standard 15) 8.4 Refrigerant Piping Sizing, Oil Return, Traps & Double Risers
9 Chapter 9: HVAC Equipment & Primary Machinery
9.1 Compressors: Reciprocating, Rotary, Scroll, Screw & Centrifugal 9.2 Condensers: Air-Cooled, Water-Cooled & Evaporative Condensers 9.3 Evaporators & Direct Expansion (DX) vs Liquid Chilling Coils 9.4 Water Chillers: Centrifugal, Screw & Scroll with ASHRAE 90.1 Path A/B IPLV Ratings 9.5 Cooling Towers: Range, Approach, Evaporation, Blowdown & Legionella Control 9.6 Heat Pumps & Variable Refrigerant Flow (VRF): Balance Point, Defrost & Heat Recovery 9.7 Thermal Energy Storage: Full vs. Partial Storage, Chilled Water & Ice Systems
10 Chapter 10: Air-Side Systems & Distribution
10.1 Air Handling Units (AHUs), Dedicated Outdoor Air Systems (DOAS) & Fan-Coil Units 10.2 Duct Design Methodologies: Equal Friction, Static Regain & Velocity Reduction 10.3 Duct Fittings, Dynamic Pressure Losses & SMACNA Construction Standards 10.4 Fan Types, Performance Curves, System Effect Factors & Surge/Stall Dynamics 10.5 Variable Air Volume (VAV) Systems, Terminal Boxes & Space Air Diffusion (ADPI) 10.6 Cooling & Heating Coil Selection: Face Velocity, Rows, Circuiting & Freeze Protection
11 Chapter 11: Hydronic, Steam & Fuel Distribution and Heating Plant
11.1 Hydronic System Architectures: Primary-Only, Primary-Secondary & Variable Primary Flow (VPF) 11.2 Hydronic Pipe Sizing, Velocity Limits & Closed/Open Expansion Tank Sizing 11.3 Control Valves: 2-Way vs 3-Way, Valve Authority (N), Cv Calculations & Characteristic Curves 11.4 Boilers & Heating Hot Water Systems: Condensing vs Non-Condensing & Water Treatment 11.5 Furnaces & Gas-Fired Heating Equipment: AFUE, Temperature Rise, Combustion Air & Vent Categories 11.6 Steam & Condensate Distribution: Latent Heat, Trap Selection, Flash Steam & Stall 11.7 Fuel Gas & Fuel Oil Piping: Demand, Sizing Method, Pressure Drop & Storage Systems
12 Chapter 12: HVAC Control Concepts, Sensors & Sequences
12.1 Sensors, Actuators & Dampers: Selection, Placement, Fail-Safe Position & Damper Authority 12.2 Control Loops: Proportional Offset, PID Action, Reset Strategies & Standard Sequences
13 Chapter 13: Building Energy, Ventilation & Indoor Environmental Quality Codes
13.1 ASHRAE Standard 62.1: Ventilation Rate Procedure (VRP), Indoor Air Quality Procedure & DCV 13.2 ASHRAE Standard 90.1: Building Energy Envelope, Mechanical Efficiency & Economizer Mandates 13.3 ASHRAE Standard 55: Thermal Environmental Conditions, PMV/PPD & Adaptive Comfort Models 13.4 Energy Recovery Systems: Enthalpy Wheels, Fixed-Plate Exchangers, Heat Pipes & Runaround Loops
14 Chapter 14: Supportive Engineering Knowledge, Life Safety & Operations
14.1 Air Filtration Standards: MERV Ratings (ASHRAE 52.2), HEPA & Gas-Phase Adsorption 14.2 Life Safety Systems: Fire/Smoke Dampers, Stairwell Pressurization (NFPA 92) & Smoke Control (NFPA 90A) 14.3 Acoustical Control & Vibration Isolation in HVAC Systems (NC / RC Criteria)
4.1 Steady-State Conduction & Multilayer Thermal Resistance (R-Value & U-Factor)
Key Takeaways Explain This Topic AI
Fourier's Law governs steady-state conduction in planar geometries: q ˙ = − k A d T d x = k A Δ T L = Δ T R t h \dot{q} = -k A \frac{dT}{dx} = \frac{k A \Delta T}{L} = \frac{\Delta T}{R_{th}} q ˙ = − k A d x d T = L k A Δ T = R t h Δ T , where thermal conductivity k k k is expressed in Btu/(hr ⋅ ft ⋅ ∘ F) \text{Btu/(hr}\cdot\text{ft}\cdot{}^\circ\text{F)} Btu/(hr ⋅ ft ⋅ ∘ F) or W/(m ⋅ K) \text{W/(m}\cdot\text{K)} W/(m ⋅ K) .
Thermal resistance for a flat layer is R = L k R = \frac{L}{k} R = k L in hr ⋅ ft 2 ⋅ ∘ F/Btu \text{hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu} hr ⋅ ft 2 ⋅ ∘ F/Btu ; total thermal resistance for series layers sums linearly: R t o t a l = R i + ∑ L j k j + R o R_{total} = R_i + \sum \frac{L_j}{k_j} + R_o R t o t a l = R i + ∑ k j L j + R o , and the overall U-factor is U = 1 R t o t a l U = \frac{1}{R_{total}} U = R t o t a l 1 .
In parallel heat flow paths (such as wood or steel-framed building assemblies), overall U-factor is area-weighted: U o v e r a l l = ∑ f j U j U_{overall} = \sum f_j U_j U o v er a ll = ∑ f j U j , where f j f_j f j is the area fraction of each path.
Radial conduction through cylindrical walls (pipes, tubes, ductwork) exhibits logarithmic thermal resistance per unit length: R c y l ′ = ln ( r o / r i ) 2 π k R'_{cyl} = \frac{\ln(r_o/r_i)}{2 \pi k} R cy l ′ = 2 πk l n ( r o / r i ) , leading to heat transfer q ˙ ′ = 2 π k ( T i − T o ) ln ( r o / r i ) \dot{q}' = \frac{2 \pi k (T_i - T_o)}{\ln(r_o/r_i)} q ˙ ′ = l n ( r o / r i ) 2 πk ( T i − T o ) .
The critical radius of insulation for a cylinder is r c r = k i n s h o r_{cr} = \frac{k_{ins}}{h_o} r cr = h o k in s ; adding insulation to an outer radius r o < r c r r_o < r_{cr} r o < r cr increases total heat transfer until r o = r c r r_o = r_{cr} r o = r cr , after which further insulation decreases heat loss.
Last updated: August 2026
4.1 Steady-State Conduction & Multilayer Thermal Resistance (R-Value & U-Factor)
Thermal conduction is the transfer of internal thermal energy through microscopic collisions of particles and movement of free electrons within a stationary medium. In HVAC and refrigeration engineering, conduction governs envelope transmission loads (walls, roofs, fenestration, floor slabs), thermal insulation performance, pipe and duct heat gains/losses, and solid-wall thermal barriers in heat exchangers. Analyzing these systems requires evaluating one-dimensional steady-state conduction through planar and radial multi-layered geometries using the thermal resistance network methodology.
1. Fourier's Law of Conduction & Planar Heat Flow
Conduction is governed by Fourier's Law , which states that the local heat flux is directly proportional to the negative temperature gradient along the direction of heat flow: q ′ ′ = q ˙ A = − k d T d x q'' = \frac{\dot{q}}{A} = -k \frac{dT}{dx} q ′′ = A q ˙ = − k d x d T
Where:
q ˙ = heat transfer rate ( Btu/hr or W ) \dot{q} = \text{heat transfer rate } (\text{Btu/hr or W}) q ˙ = heat transfer rate ( Btu/hr or W )
q ′ ′ = heat flux ( Btu/(hr ⋅ ft 2 ) or W/m 2 ) q'' = \text{heat flux } (\text{Btu/(hr}\cdot\text{ft}^2) \text{ or W/m}^2) q ′′ = heat flux ( Btu/(hr ⋅ ft 2 ) or W/m 2 )
A = cross-sectional area normal to heat flow ( ft 2 or m 2 ) A = \text{cross-sectional area normal to heat flow } (\text{ft}^2 \text{ or m}^2) A = cross-sectional area normal to heat flow ( ft 2 or m 2 )
k = thermal conductivity of the material ( Btu/(hr ⋅ ft ⋅ ∘ F) or W/(m ⋅ K) ) k = \text{thermal conductivity of the material } (\text{Btu/(hr}\cdot\text{ft}\cdot{}^\circ\text{F)} \text{ or W/(m}\cdot\text{K)}) k = thermal conductivity of the material ( Btu/(hr ⋅ ft ⋅ ∘ F) or W/(m ⋅ K) )
d T d x = temperature gradient in the direction of heat flow ( ∘ F/ft or ∘ C/m ) \frac{dT}{dx} = \text{temperature gradient in the direction of heat flow } ({}^\circ\text{F/ft or } {}^\circ\text{C/m}) d x d T = temperature gradient in the direction of heat flow ( ∘ F/ft or ∘ C/m ) +-----------------------------------------------------------------------------------------+
- | ONE-DIMENSIONAL STEADY-STATE CONDUCTION THROUGH A PLANE SLAB |
- +-----------------------------------------------------------------------------------------+
- | T_1 (Hot Surface) |
- | |=========================| |
- | | | ---> Heat Flow: q_dot = k * A * (T_1 - T_2) / L |
- | | Material Thickness L | |
- | | Conductivity: k | ---> Thermal Resistance: R_th = L / (k * A) |
- | | | |
- | |=========================| |
- | T_2 (Cold Surface) |
- +-----------------------------------------------------------------------------------------+
Integrating Fourier's law for a homogeneous planar slab of uniform thickness L L L with fixed surface temperatures T 1 T_1 T 1 and T 2 T_2 T 2 ( T 1 > T 2 T_1 > T_2 T 1 > T 2 ) under steady-state conditions with constant thermal conductivity: q ˙ = k A ( T 1 − T 2 ) L = T 1 − T 2 R t h \dot{q} = \frac{k A (T_1 - T_2)}{L} = \frac{T_1 - T_2}{R_{th}} q ˙ = L k A ( T 1 − T 2 ) = R t h T 1 − T 2
Thermal Resistance ( R t h R_{th} R t h ) and Unit Thermal Resistance ( R R R -Value)
In mechanical engineering, the electrical-thermal analogy represents temperature difference Δ T \Delta T Δ T as voltage potential, heat rate q ˙ \dot{q} q ˙ as electric current, and thermal resistance R t h R_{th} R t h as electrical resistance: R t h = L k A [ hr ⋅ ∘ F Btu or K W ] R_{th} = \frac{L}{k A} \quad \left[\frac{\text{hr}\cdot{}^\circ\text{F}}{\text{Btu}} \text{ or } \frac{\text{K}}{\text{W}}\right] R t h = k A L [ Btu hr ⋅ ∘ F or W K ]
In building envelope and architectural engineering, resistance is normalized per unit area and termed the R R R -value ( R R R ): R = R t h × A = L k = L ⋅ r [ hr ⋅ ft 2 ⋅ ∘ F Btu ] R = R_{th} \times A = \frac{L}{k} = L \cdot r \quad \left[\frac{\text{hr}\cdot\text{ft}^2\cdot{}^\circ\text{F}}{\text{Btu}}\right] R = R t h × A = k L = L ⋅ r [ Btu hr ⋅ ft 2 ⋅ ∘ F ]
Where r = 1 / k r = 1/k r = 1/ k is the thermal resistivity per unit thickness (expressed in hr ⋅ ft ⋅ ∘ F/Btu \text{hr}\cdot\text{ft}\cdot{}^\circ\text{F/Btu} hr ⋅ ft ⋅ ∘ F/Btu or commonly as R R R -value per inch: hr ⋅ ft 2 ⋅ ∘ F/(Btu ⋅ in.) \text{hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/(Btu}\cdot\text{in.)} hr ⋅ ft 2 ⋅ ∘ F/(Btu ⋅ in.) ). When thickness L i n L_{in} L in is in inches and thermal conductivity k k k is in Btu/(hr ⋅ ft ⋅ ∘ F) \text{Btu/(hr}\cdot\text{ft}\cdot{}^\circ\text{F)} Btu/(hr ⋅ ft ⋅ ∘ F) : R = L i n / 12 k = L i n 12 k R = \frac{L_{in} / 12}{k} = \frac{L_{in}}{12 k} R = k L in /12 = 12 k L in
2. Multilayer Planar Assemblies & Overall Heat Transmission ( U U U -Factor)
Building envelopes and duct/pipe insulation assemblies consist of multiple material layers in series, bounded by interior and exterior air boundary layers (convection/radiation air films). +-----------------------------------------------------------------------------------------+
- | SERIES THERMAL RESISTANCE NETWORK (BUILDING ENVELOPE) |
- +-----------------------------------------------------------------------------------------+
- | T_inside o---[ R_i ]---o---[ R_1 ]---o---[ R_2 ]---o---[ R_3 ]---o---[ R_o ]---o T_outside
- | Air Film Gypsum Insulation Sheathing Air Film |
- | |
- | Total Resistance: R_total = R_i + R_1 + R_2 + R_3 + R_o |
- | Overall Heat Transmission Coefficient: U = 1 / R_total |
- +-----------------------------------------------------------------------------------------+
- Series Thermal Resistance Summation
For n n n plane layers in series bounded by fluid environments with internal convective film coefficient h i h_i h i and external film coefficient h o h_o h o : R t o t a l = R i + ∑ j = 1 n R j + R o = 1 h i + ∑ j = 1 n L j k j + 1 h o R_{total} = R_i + \sum_{j=1}^n R_j + R_o = \frac{1}{h_i} + \sum_{j=1}^n \frac{L_j}{k_j} + \frac{1}{h_o} R t o t a l = R i + j = 1 ∑ n R j + R o = h i 1 + j = 1 ∑ n k j L j + h o 1
Where:
R i = 1 h i = inside surface air film resistance ( hr ⋅ ft 2 ⋅ ∘ F/Btu ) R_i = \frac{1}{h_i} = \text{inside surface air film resistance } (\text{hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu}) R i = h i 1 = inside surface air film resistance ( hr ⋅ ft 2 ⋅ ∘ F/Btu )
R o = 1 h o = outside surface air film resistance ( hr ⋅ ft 2 ⋅ ∘ F/Btu ) R_o = \frac{1}{h_o} = \text{outside surface air film resistance } (\text{hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu}) R o = h o 1 = outside surface air film resistance ( hr ⋅ ft 2 ⋅ ∘ F/Btu )
L j = thickness of layer j ( ft ) L_j = \text{thickness of layer } j\text{ } (\text{ft}) L j = thickness of layer j ( ft )
k j = thermal conductivity of layer j ( Btu/(hr ⋅ ft ⋅ ∘ F) ) k_j = \text{thermal conductivity of layer } j\text{ } (\text{Btu/(hr}\cdot\text{ft}\cdot{}^\circ\text{F)}) k j = thermal conductivity of layer j ( Btu/(hr ⋅ ft ⋅ ∘ F) )
Overall Heat Transmission Coefficient ( U U U -Factor)
The overall heat transfer coefficient U U U is the mathematical inverse of the total area-normalized thermal resistance: U = 1 R t o t a l = 1 R i + ∑ L j k j + R o [ Btu hr ⋅ ft 2 ⋅ ∘ F ] U = \frac{1}{R_{total}} = \frac{1}{R_i + \sum \frac{L_j}{k_j} + R_o} \quad \left[\frac{\text{Btu}}{\text{hr}\cdot\text{ft}^2\cdot{}^\circ\text{F}}\right] U = R t o t a l 1 = R i + ∑ k j L j + R o 1 [ hr ⋅ ft 2 ⋅ ∘ F Btu ]
The steady-state heat transmission through an assembly of gross surface area A A A exposed to interior air temperature T i n T_{in} T in and exterior air temperature T o u t T_{out} T o u t is: q ˙ = U A ( T i n − T o u t ) = A ( T i n − T o u t ) R t o t a l \dot{q} = U A (T_{in} - T_{out}) = \frac{A (T_{in} - T_{out})}{R_{total}} q ˙ = U A ( T in − T o u t ) = R t o t a l A ( T in − T o u t )
Interface Temperature Derivation
Under steady-state conditions, the heat flux q ′ ′ = q ˙ / A q'' = \dot{q}/A q ′′ = q ˙ / A is constant through every consecutive layer in a series network. The temperature at any internal interface x x x between layer m m m and layer m + 1 m+1 m + 1 is determined from: q ′ ′ = T i n − T x R i n → x = T x − T o u t R x → o u t = T i n − T o u t R t o t a l q'' = \frac{T_{in} - T_x}{R_{in \to x}} = \frac{T_x - T_{out}}{R_{x \to out}} = \frac{T_{in} - T_{out}}{R_{total}} q ′′ = R in → x T in − T x = R x → o u t T x − T o u t = R t o t a l T in − T o u t T x = T i n − q ′ ′ ⋅ R i n → x = T i n − ( T i n − T o u t ) ( R i n → x R t o t a l ) T_x = T_{in} - q'' \cdot R_{in \to x} = T_{in} - (T_{in} - T_{out}) \left(\frac{R_{in \to x}}{R_{total}}\right) T x = T in − q ′′ ⋅ R in → x = T in − ( T in − T o u t ) ( R t o t a l R in → x )
3. Parallel Paths, Framing Factors & Thermal Bridging
Real-world wall and roof assemblies are non-homogeneous because structural framing members (wood studs, light-gauge steel studs, concrete columns) penetrate the insulation cavity, creating parallel heat flow paths with differing thermal resistances. +-----------------------------------------------------------------------------------------+
- | PARALLEL HEAT CONDUCTION THROUGH FRAMED WALL CAVITY |
- +-----------------------------------------------------------------------------------------+
- | Path A (Stud Path, f_frame = 15-25%): |
- | T_in o---[ R_i ]---[ R_gyp ]---[ R_stud ]---[ R_sheath ]---[ R_clad ]---[ R_o ]---o T_out
- | |
- | Path B (Cavity Path, f_cav = 75-85%): |
- | T_in o---[ R_i ]---[ R_gyp ]---[ R_insul ]---[ R_sheath ]---[ R_clad ]---[ R_o ]---o T_out
- | |
- | Overall Area-Weighted U-Factor: U_overall = (f_frame * U_stud) + (f_cav * U_cav) |
- +-----------------------------------------------------------------------------------------+
- ASHRAE Parallel Path Method (Wood-Framed Assemblies)
For assemblies with materials of moderate thermal conductivity (such as wood studs where k w o o d ≈ 0.08 Btu/(hr ⋅ ft ⋅ ∘ F) k_{wood} \approx 0.08\text{ Btu/(hr}\cdot\text{ft}\cdot{}^\circ\text{F)} k w oo d ≈ 0.08 Btu/(hr ⋅ ft ⋅ ∘ F) ), heat flows predominantly perpendicular to the wall surface. The area-weighted overall U U U -factor is: U o v e r a l l = f f r a m e U f r a m e + f c a v i t y U c a v i t y = f f r a m e ( 1 R f r a m e , t o t a l ) + ( 1 − f f r a m e ) ( 1 R c a v i t y , t o t a l ) U_{overall} = f_{frame} U_{frame} + f_{cavity} U_{cavity} = f_{frame} \left(\frac{1}{R_{frame,total}}\right) + (1 - f_{frame}) \left(\frac{1}{R_{cavity,total}}\right) U o v er a ll = f f r am e U f r am e + f c a v i t y U c a v i t y = f f r am e ( R f r am e , t o t a l 1 ) + ( 1 − f f r am e ) ( R c a v i t y , t o t a l 1 )
Where:
f f r a m e = framing factor (fraction of wall area occupied by framing, typically 0.15 to 0.25 ) f_{frame} = \text{framing factor (fraction of wall area occupied by framing, typically } 0.15\text{ to }0.25) f f r am e = framing factor (fraction of wall area occupied by framing, typically 0.15 to 0.25 )
f c a v i t y = 1 − f f r a m e = cavity area fraction occupied by insulation f_{cavity} = 1 - f_{frame} = \text{cavity area fraction occupied by insulation} f c a v i t y = 1 − f f r am e = cavity area fraction occupied by insulation
R f r a m e , t o t a l = total series resistance along the stud/framing path R_{frame,total} = \text{total series resistance along the stud/framing path} R f r am e , t o t a l = total series resistance along the stud/framing path
R c a v i t y , t o t a l = total series resistance along the insulated cavity path R_{cavity,total} = \text{total series resistance along the insulated cavity path} R c a v i t y , t o t a l = total series resistance along the insulated cavity path
Effective Resistance of Parallel Assemblies
The effective assembly R R R -value ( R e f f R_{eff} R e ff ) is the reciprocal of the area-weighted U U U -factor: R e f f = 1 U o v e r a l l = 1 f f r a m e U f r a m e + ( 1 − f f r a m e ) U c a v i t y R_{eff} = \frac{1}{U_{overall}} = \frac{1}{f_{frame} U_{frame} + (1 - f_{frame}) U_{cavity}} R e ff = U o v er a ll 1 = f f r am e U f r am e + ( 1 − f f r am e ) U c a v i t y 1
Critical Exam Rule — Never Average R R R -Values Directly: Thermal resistances in parallel cannot be averaged linearly. Always convert each parallel path to its individual U U U -factor ( U = 1 / R U = 1/R U = 1/ R ), calculate the area-weighted average U o v e r a l l U_{overall} U o v er a ll , and take the reciprocal to find R e f f R_{eff} R e ff . Direct averaging of R R R -values overestimates thermal performance by up to 40%.
Metal Framing & Thermal Bridging (ASHRAE Zone / Modified Zone Method)
Because structural steel has an extremely high thermal conductivity ( k s t e e l ≈ 26 − 30 Btu/(hr ⋅ ft ⋅ ∘ F) k_{steel} \approx 26-30\text{ Btu/(hr}\cdot\text{ft}\cdot{}^\circ\text{F)} k s t ee l ≈ 26 − 30 Btu/(hr ⋅ ft ⋅ ∘ F) vs k f i b e r g l a s s ≈ 0.025 Btu/(hr ⋅ ft ⋅ ∘ F) k_{fiberglass} \approx 0.025\text{ Btu/(hr}\cdot\text{ft}\cdot{}^\circ\text{F)} k f ib er g l a ss ≈ 0.025 Btu/(hr ⋅ ft ⋅ ∘ F) , a ratio greater than 1,000:1), light-gauge steel studs create severe two-dimensional thermal bridges that short-circuit cavity insulation. Standard R-13 or R-19 fiberglass cavity insulation between steel studs at 16 inches on center delivers an effective cavity performance of only R-6.0 to R-7.1. ASHRAE Standard 90.1 mandates the use of continuous exterior insulation ( c . i . c.i. c . i . ) on steel-framed walls to mitigate thermal bridging.
Loading diagram... Thermal Bridging vs Continuous Insulation Flux Distribution
4. Radial Conduction: Cylindrical & Spherical Geometries
In piping, chilled water lines, steam headers, and cylindrical ducts, the cross-sectional area normal to heat flow varies continuously with radius ( A ( r ) = 2 π r L A(r) = 2 \pi r L A ( r ) = 2 π r L ). +-----------------------------------------------------------------------------------------+
- | RADIAL STEADY-STATE CONDUCTION IN A HOLLOW CYLINDER (PIPE WITH INSULATION) |
- +-----------------------------------------------------------------------------------------+
- | Outer Surface: Radius r_o, Temp T_o |
- | /---------------------------------\ |
- | / Insulation Layer (k_ins) \ |
- | | /-------------------\ | |
- | | / Pipe Wall (k_p) \ | |
- | | | /------------\ | | |
- | | | / Fluid T_i \ | | |
- | | | | Inner Radius: | | | |
- | | | | r_i | | | |
- | | | \ / | | |
- | | | \------------/ | | |
- | | \ / | |
- | | \-------------------/ | |
- | \ / |
- | \---------------------------------/ |
- +-----------------------------------------------------------------------------------------+
- Cylindrical Conduction Equation Derivation
Applying Fourier's Law at radius r r r for a cylinder of axial length L L L : q ˙ = − k A ( r ) d T d r = − k ( 2 π r L ) d T d r \dot{q} = -k A(r) \frac{dT}{dr} = -k (2 \pi r L) \frac{dT}{dr} q ˙ = − k A ( r ) d r d T = − k ( 2 π r L ) d r d T
Separating variables and integrating from inner radius r i r_i r i (at T i T_i T i ) to outer radius r o r_o r o (at T o T_o T o ): q ˙ ∫ r i r o d r r = − 2 π k L ∫ T i T o d T ⟹ q ˙ ln ( r o r i ) = 2 π k L ( T i − T o ) \dot{q} \int_{r_i}^{r_o} \frac{dr}{r} = -2 \pi k L \int_{T_i}^{T_o} dT \implies \dot{q} \ln\left(\frac{r_o}{r_i}\right) = 2 \pi k L (T_i - T_o) q ˙ ∫ r i r o r d r = − 2 πk L ∫ T i T o d T ⟹ q ˙ ln ( r i r o ) = 2 πk L ( T i − T o ) q ˙ = 2 π k L ( T i − T o ) ln ( r o / r i ) = T i − T o R t h , c y l \dot{q} = \frac{2 \pi k L (T_i - T_o)}{\ln(r_o / r_i)} = \frac{T_i - T_o}{R_{th,cyl}} q ˙ = ln ( r o / r i ) 2 πk L ( T i − T o ) = R t h , cy l T i − T o
Cylindrical Thermal Resistance
The total thermal resistance for a cylindrical shell of length L L L is: R t h , c y l = ln ( r o / r i ) 2 π k L [ hr ⋅ ∘ F Btu ] R_{th,cyl} = \frac{\ln(r_o / r_i)}{2 \pi k L} \quad \left[\frac{\text{hr}\cdot{}^\circ\text{F}}{\text{Btu}}\right] R t h , cy l = 2 πk L ln ( r o / r i ) [ Btu hr ⋅ ∘ F ]
Expressed as resistance per unit linear foot of pipe length ( R t h ′ = R t h ⋅ L R'_{th} = R_{th} \cdot L R t h ′ = R t h ⋅ L ): R t h , c y l ′ = ln ( r o / r i ) 2 π k [ hr ⋅ ft ⋅ ∘ F Btu ] R'_{th,cyl} = \frac{\ln(r_o / r_i)}{2 \pi k} \quad \left[\frac{\text{hr}\cdot\text{ft}\cdot{}^\circ\text{F}}{\text{Btu}}\right] R t h , cy l ′ = 2 πk ln ( r o / r i ) [ Btu hr ⋅ ft ⋅ ∘ F ]
Multilayer Insulated Pipe Network
For a pipe with inside convection h i h_i h i , pipe wall ( r 1 → r 2 , k p r_1 \to r_2, k_p r 1 → r 2 , k p ), insulation layer ( r 2 → r 3 , k i n s r_2 \to r_3, k_{ins} r 2 → r 3 , k in s ), and outer surface convection/radiation h o h_o h o : q ˙ ′ = T ∞ , i − T ∞ , o R t o t a l ′ \dot{q}' = \frac{T_{\infty,i} - T_{\infty,o}}{R'_{total}} q ˙ ′ = R t o t a l ′ T ∞ , i − T ∞ , o R t o t a l ′ = 1 2 π r 1 h i + ln ( r 2 / r 1 ) 2 π k p + ln ( r 3 / r 2 ) 2 π k i n s + 1 2 π r 3 h o R'_{total} = \frac{1}{2 \pi r_1 h_i} + \frac{\ln(r_2 / r_1)}{2 \pi k_p} + \frac{\ln(r_3 / r_2)}{2 \pi k_{ins}} + \frac{1}{2 \pi r_3 h_o} R t o t a l ′ = 2 π r 1 h i 1 + 2 π k p ln ( r 2 / r 1 ) + 2 π k in s ln ( r 3 / r 2 ) + 2 π r 3 h o 1
Spherical Conduction Equation
For a hollow sphere of inner radius r 1 r_1 r 1 and outer radius r 2 r_2 r 2 (such as cryogenic storage tanks or spherical expansion vessels): q ˙ = 4 π k r 1 r 2 ( T 1 − T 2 ) r 2 − r 1 ⟹ R t h , s p h e r e = r 2 − r 1 4 π k r 1 r 2 \dot{q} = \frac{4 \pi k r_1 r_2 (T_1 - T_2)}{r_2 - r_1} \quad \implies \quad R_{th,sphere} = \frac{r_2 - r_1}{4 \pi k r_1 r_2} q ˙ = r 2 − r 1 4 πk r 1 r 2 ( T 1 − T 2 ) ⟹ R t h , s p h ere = 4 πk r 1 r 2 r 2 − r 1
5. Critical Radius of Insulation
Adding insulation to a flat plane always increases conduction resistance without altering the surface area, continuously reducing heat loss. However, adding insulation to a cylindrical pipe produces two competing physical effects:
Conduction Resistance Increases: As insulation thickness increases ( r o ↑ r_o \uparrow r o ↑ ), radial conduction resistance R c o n d = ln ( r o / r i ) 2 π k L R_{cond} = \frac{\ln(r_o/r_i)}{2 \pi k L} R co n d = 2 πk L l n ( r o / r i ) increases logarithmically.
Convection Surface Area Increases: As outer radius expands ( r o ↑ r_o \uparrow r o ↑ ), outer convective surface area A o = 2 π r o L A_o = 2 \pi r_o L A o = 2 π r o L increases, decreasing external surface convective resistance R c o n v = 1 2 π r o L h o R_{conv} = \frac{1}{2 \pi r_o L h_o} R co n v = 2 π r o L h o 1 linearly. +-----------------------------------------------------------------------------------------+
- | THERMAL RESISTANCE VS. OUTER INSULATION RADIUS (CYLINDER) |
- +-----------------------------------------------------------------------------------------+
- | Resistance |
- | ^ |
- | | Total Resistance R_tot (Minimum at r_cr) |
- | | \ / |
- | | \ / |
- | | \--------------/ <--- r_cr = k_ins / h_o (Max Heat Loss) |
- | | . ' ` . |
- | | . ' ` . Convection Resistance: R_conv ~ 1/r_o |
- | | . ' ` . |
- | +-----------------------------------------------------> Outer Radius r_o |
- | 0 r_pipe r_cr |
- +-----------------------------------------------------------------------------------------+
- Mathematical Derivation of r c r r_{cr} r cr
To find the outer radius r o r_o r o that minimizes total thermal resistance R t o t a l ′ R'_{total} R t o t a l ′ per unit length: R t o t a l ′ = ln ( r o / r i ) 2 π k i n s + 1 2 π r o h o R'_{total} = \frac{\ln(r_o / r_i)}{2 \pi k_{ins}} + \frac{1}{2 \pi r_o h_o} R t o t a l ′ = 2 π k in s ln ( r o / r i ) + 2 π r o h o 1
Differentiating with respect to r o r_o r o and setting the derivative to zero: d R t o t a l ′ d r o = 1 2 π k i n s r o − 1 2 π h o r o 2 = 0 \frac{d R'_{total}}{d r_o} = \frac{1}{2 \pi k_{ins} r_o} - \frac{1}{2 \pi h_o r_o^2} = 0 d r o d R t o t a l ′ = 2 π k in s r o 1 − 2 π h o r o 2 1 = 0 1 k i n s r o = 1 h o r o 2 ⟹ r o = k i n s h o \frac{1}{k_{ins} r_o} = \frac{1}{h_o r_o^2} \implies r_o = \frac{k_{ins}}{h_o} k in s r o 1 = h o r o 2 1 ⟹ r o = h o k in s r c r , c y l = k i n s h o r_{cr,cyl} = \frac{k_{ins}}{h_o} r cr , cy l = h o k in s
For a spherical vessel, the critical radius is: r c r , s p h e r e = 2 k i n s h o r_{cr,sphere} = \frac{2 k_{ins}}{h_o} r cr , s p h ere = h o 2 k in s
Practical Engineering Implications on the PE Exam
Small Diameter Tubing / Electrical Wires: For small refrigeration capillary tubes or electrical wires ( r b a r e < r c r r_{bare} < r_{cr} r ba re < r cr ), adding thin insulation increases heat dissipation, keeping electrical wires cooler.
Building HVAC Piping: For standard HVAC chilled water or steam pipes, the bare pipe outer radius r b a r e r_{bare} r ba re is typically much larger than r c r r_{cr} r cr (e.g., for fiberglass insulation with k = 0.025 Btu/(hr ⋅ ft ⋅ ∘ F) k = 0.025\text{ Btu/(hr}\cdot\text{ft}\cdot{}^\circ\text{F)} k = 0.025 Btu/(hr ⋅ ft ⋅ ∘ F) and h o = 1.5 Btu/(hr ⋅ ft 2 ⋅ ∘ F) h_o = 1.5\text{ Btu/(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)} h o = 1.5 Btu/(hr ⋅ ft 2 ⋅ ∘ F) , r c r = 0.025 / 1.5 = 0.0167 ft = 0.20 in. r_{cr} = 0.025 / 1.5 = 0.0167\text{ ft} = 0.20\text{ in.} r cr = 0.025/1.5 = 0.0167 ft = 0.20 in. ). Since standard pipes have r o > 0.20 in. r_o > 0.20\text{ in.} r o > 0.20 in. , adding insulation always reduces heat loss.
- 6. Standard Building Material Properties & Air Film Resistances
- Typical Material Thermal Properties (ASHRAE Fundamentals Reference)
Material Layer Thickness ( L L L ) Conductivity k k k [Btu/(hr ⋅ ft ⋅ ∘ F)] \text{[Btu/(hr}\cdot\text{ft}\cdot{}^\circ\text{F)]} [Btu/(hr ⋅ ft ⋅ ∘ F)] Density ρ \rho ρ [lbm/ft 3 ] \text{[lbm/ft}^3\text{]} [lbm/ft 3 ] Standard R R R -Value [hr ⋅ ft 2 ⋅ ∘ F/Btu] \text{[hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu]} [hr ⋅ ft 2 ⋅ ∘ F/Btu]
Interior Gypsum Board 0.50 in. 0.50\text{ in.} 0.50 in. 0.092 0.092 0.092 50.0 50.0 50.0 R − 0.45 R-0.45 R − 0.45
Fiberglass Batt (2x4 Cavity) 3.50 in. 3.50\text{ in.} 3.50 in. 0.0224 0.0224 0.0224 0.8 0.8 0.8 R − 13.0 R-13.0 R − 13.0
Fiberglass Batt (2x6 Cavity) 5.50 in. 5.50\text{ in.} 5.50 in. 0.0241 0.0241 0.0241 0.8 0.8 0.8 R − 19.0 R-19.0 R − 19.0
Extruded Polystyrene (XPS) 1.00 in. 1.00\text{ in.} 1.00 in. 0.0167 0.0167 0.0167 2.0 2.0 2.0 R − 5.00 R-5.00 R − 5.00
Polyisocyanurate (Foil-Faced) 1.00 in. 1.00\text{ in.} 1.00 in. 0.0128 0.0128 0.0128 2.0 2.0 2.0 R − 6.50 R-6.50 R − 6.50
Expanded Polystyrene (EPS) 1.00 in. 1.00\text{ in.} 1.00 in. 0.0208 0.0208 0.0208 1.5 1.5 1.5 R − 4.00 R-4.00 R − 4.00
Plywood / OSB Sheathing 0.50 in. 0.50\text{ in.} 0.50 in. 0.0750 0.0750 0.0750 34.0 34.0 34.0 R − 0.56 R-0.56 R − 0.56
Face Brick 3.50 in. 3.50\text{ in.} 3.50 in. 0.7500 0.7500 0.7500 120.0 120.0 120.0 R − 0.39 R-0.39 R − 0.39
Poured Concrete 8.00 in. 8.00\text{ in.} 8.00 in. 1.0400 1.0400 1.0400 140.0 140.0 140.0 R − 0.64 R-0.64 R − 0.64
Wood Stud (2x4 Douglas Fir) 3.50 in. 3.50\text{ in.} 3.50 in. 0.0800 0.0800 0.0800 32.0 32.0 32.0 R − 3.65 R-3.65 R − 3.65
ASHRAE Standard Surface Air Film Resistances ( R i R_i R i and R o R_o R o )
Surface Position & Heat Flow Direction Emissivity ( ε \varepsilon ε ) Air Film Condition Film Resistance R R R [hr ⋅ ft 2 ⋅ ∘ F/Btu] \text{[hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu]} [hr ⋅ ft 2 ⋅ ∘ F/Btu]
Vertical Surface (Walls), Horizontal Flow 0.90 0.90 0.90 (non-reflective) Still Air (Indoor) R i = 0.68 R_i = 0.68 R i = 0.68
Horizontal Surface (Ceilings), Upward Flow 0.90 0.90 0.90 Still Air (Indoor) R i = 0.61 R_i = 0.61 R i = 0.61
Horizontal Surface (Floors), Downward Flow 0.90 0.90 0.90 Still Air (Indoor) R i = 0.92 R_i = 0.92 R i = 0.92
Any Orientation (Winter Exterior) Any 15 mph Wind 15\text{ mph Wind} 15 mph Wind R o = 0.17 R_o = 0.17 R o = 0.17
Any Orientation (Summer Exterior) Any 7.5 mph Wind 7.5\text{ mph Wind} 7.5 mph Wind R o = 0.25 R_o = 0.25 R o = 0.25
- 7. Step-by-Step Worked Example: Multilayer Framed Exterior Wall
- Problem Statement
An exterior wall assembly of a commercial office building in Chicago ( 400 ft 2 400\text{ ft}^2 400 ft 2 gross area) consists of the following layers from inside to outside:
Inside air film ( R i = 0.68 hr ⋅ ft 2 ⋅ ∘ F/Btu R_i = 0.68\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu} R i = 0.68 hr ⋅ ft 2 ⋅ ∘ F/Btu )
1 / 2 -in. 1/2\text{-in.} 1/2 -in. gypsum wallboard ( R = 0.45 R = 0.45 R = 0.45 )
2 × 4 2\times4 2 × 4 wood framing at 16 in. 16\text{ in.} 16 in. on center ( 3.5 in. 3.5\text{ in.} 3.5 in. depth):
- Cavity path: R − 13.0 R-13.0 R − 13.0 fiberglass batt
- Stud path: 2 × 4 2\times4 2 × 4 wood studs ( R = 3.65 R = 3.65 R = 3.65 )
Framing factor: f f r a m e = 20 % f_{frame} = 20\% f f r am e = 20% ( 0.20 0.20 0.20 ), f c a v i t y = 80 % f_{cavity} = 80\% f c a v i t y = 80% ( 0.80 0.80 0.80 )
- 1 / 2 -in. 1/2\text{-in.} 1/2 -in. OSB sheathing ( R = 0.56 R = 0.56 R = 0.56 )
- 1.0 -in. 1.0\text{-in.} 1.0 -in. continuous XPS rigid insulation ( R = 5.00 R = 5.00 R = 5.00 )
- 1.0 -in. 1.0\text{-in.} 1.0 -in. unventilated non-reflective air space ( R = 1.00 R = 1.00 R = 1.00 )
- 3.5 -in. 3.5\text{-in.} 3.5 -in. clay face brick ( R = 0.39 R = 0.39 R = 0.39 )
- Outside winter air film ( 15 mph wind 15\text{ mph wind} 15 mph wind , R o = 0.17 R_o = 0.17 R o = 0.17 )
Calculate:
Total thermal resistance along the cavity path ( R c a v R_{cav} R c a v ) and stud path ( R s t u d R_{stud} R s t u d )
Individual U U U -factors for cavity and stud paths
Overall area-weighted U U U -factor ( U o v e r a l l U_{overall} U o v er a ll ) and effective assembly R R R -value ( R e f f R_{eff} R e ff )
Total steady-state winter heat loss rate q ˙ \dot{q} q ˙ when T i n = 70.0 ∘ F T_{in} = 70.0^\circ\text{F} T in = 70. 0 ∘ F and T o u t = 0.0 ∘ F T_{out} = 0.0^\circ\text{F} T o u t = 0. 0 ∘ F
- Temperature at the interior face of the continuous XPS insulation
- Solution Steps
Step 1: Calculate resistance of continuous layers R c o n t = R i + R g y p + R o s b + R x p s + R a i r + R b r i c k + R o R_{cont} = R_i + R_{gyp} + R_{osb} + R_{xps} + R_{air} + R_{brick} + R_o R co n t = R i + R g y p + R os b + R x p s + R ai r + R b r i c k + R o R c o n t = 0.68 + 0.45 + 0.56 + 5.00 + 1.00 + 0.39 + 0.17 = 8.25 hr ⋅ ft 2 ⋅ ∘ F/Btu R_{cont} = 0.68 + 0.45 + 0.56 + 5.00 + 1.00 + 0.39 + 0.17 = 8.25\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu} R co n t = 0.68 + 0.45 + 0.56 + 5.00 + 1.00 + 0.39 + 0.17 = 8.25 hr ⋅ ft 2 ⋅ ∘ F/Btu
Step 2: Calculate total path resistances and individual U U U -factors
Cavity Path: R c a v , t o t a l = R c o n t + R i n s u l = 8.25 + 13.00 = 21.25 hr ⋅ ft 2 ⋅ ∘ F/Btu R_{cav,total} = R_{cont} + R_{insul} = 8.25 + 13.00 = 21.25\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu} R c a v , t o t a l = R co n t + R in s u l = 8.25 + 13.00 = 21.25 hr ⋅ ft 2 ⋅ ∘ F/Btu U c a v = 1 R c a v , t o t a l = 1 21.25 = 0.04706 Btu/(hr ⋅ ft 2 ⋅ ∘ F) U_{cav} = \frac{1}{R_{cav,total}} = \frac{1}{21.25} = 0.04706\text{ Btu/(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)} U c a v = R c a v , t o t a l 1 = 21.25 1 = 0.04706 Btu/(hr ⋅ ft 2 ⋅ ∘ F)
Stud Path: R s t u d , t o t a l = R c o n t + R s t u d = 8.25 + 3.65 = 11.90 hr ⋅ ft 2 ⋅ ∘ F/Btu R_{stud,total} = R_{cont} + R_{stud} = 8.25 + 3.65 = 11.90\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu} R s t u d , t o t a l = R co n t + R s t u d = 8.25 + 3.65 = 11.90 hr ⋅ ft 2 ⋅ ∘ F/Btu U s t u d = 1 R s t u d , t o t a l = 1 11.90 = 0.08403 Btu/(hr ⋅ ft 2 ⋅ ∘ F) U_{stud} = \frac{1}{R_{stud,total}} = \frac{1}{11.90} = 0.08403\text{ Btu/(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)} U s t u d = R s t u d , t o t a l 1 = 11.90 1 = 0.08403 Btu/(hr ⋅ ft 2 ⋅ ∘ F)
Step 3: Calculate area-weighted overall U U U -factor and effective R R R -value U o v e r a l l = ( 1 − f f r a m e ) U c a v + f f r a m e U s t u d = ( 0.80 × 0.04706 ) + ( 0.20 × 0.08403 ) U_{overall} = (1 - f_{frame}) U_{cav} + f_{frame} U_{stud} = (0.80 \times 0.04706) + (0.20 \times 0.08403) U o v er a ll = ( 1 − f f r am e ) U c a v + f f r am e U s t u d = ( 0.80 × 0.04706 ) + ( 0.20 × 0.08403 ) U o v e r a l l = 0.03765 + 0.01681 = 0.05446 Btu/(hr ⋅ ft 2 ⋅ ∘ F) U_{overall} = 0.03765 + 0.01681 = 0.05446\text{ Btu/(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)} U o v er a ll = 0.03765 + 0.01681 = 0.05446 Btu/(hr ⋅ ft 2 ⋅ ∘ F) R e f f = 1 U o v e r a l l = 1 0.05446 = 18.36 hr ⋅ ft 2 ⋅ ∘ F/Btu R_{eff} = \frac{1}{U_{overall}} = \frac{1}{0.05446} = 18.36\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu} R e ff = U o v er a ll 1 = 0.05446 1 = 18.36 hr ⋅ ft 2 ⋅ ∘ F/Btu
Step 4: Calculate total heat loss rate q ˙ \dot{q} q ˙ q ˙ = U o v e r a l l A ( T i n − T o u t ) = 0.05446 × 400 × ( 70.0 − 0.0 ) = 0.05446 × 400 × 70.0 = 1524.9 Btu/hr \dot{q} = U_{overall} A (T_{in} - T_{out}) = 0.05446 \times 400 \times (70.0 - 0.0) = 0.05446 \times 400 \times 70.0 = 1524.9\text{ Btu/hr} q ˙ = U o v er a ll A ( T in − T o u t ) = 0.05446 × 400 × ( 70.0 − 0.0 ) = 0.05446 × 400 × 70.0 = 1524.9 Btu/hr
Step 5: Calculate temperature at interior face of continuous XPS insulation Along the predominant cavity path ( q c a v ′ ′ = U c a v Δ T = 0.04706 × 70.0 = 3.294 Btu/(hr ⋅ ft 2 ) q''_{cav} = U_{cav} \Delta T = 0.04706 \times 70.0 = 3.294\text{ Btu/(hr}\cdot\text{ft}^2) q c a v ′′ = U c a v Δ T = 0.04706 × 70.0 = 3.294 Btu/(hr ⋅ ft 2 ) ):
Resistance from indoor air to the interior face of XPS: R i n → X P S = R i + R g y p + R c a v + R o s b = 0.68 + 0.45 + 13.00 + 0.56 = 14.69 hr ⋅ ft 2 ⋅ ∘ F/Btu R_{in \to XPS} = R_i + R_{gyp} + R_{cav} + R_{osb} = 0.68 + 0.45 + 13.00 + 0.56 = 14.69\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu} R in → XPS = R i + R g y p + R c a v + R os b = 0.68 + 0.45 + 13.00 + 0.56 = 14.69 hr ⋅ ft 2 ⋅ ∘ F/Btu T X P S , i n t = T i n − q c a v ′ ′ ⋅ R i n → X P S = 70.0 − ( 3.294 × 14.69 ) = 70.0 − 48.39 = 21.61 ∘ F T_{XPS,int} = T_{in} - q''_{cav} \cdot R_{in \to XPS} = 70.0 - (3.294 \times 14.69) = 70.0 - 48.39 = 21.61^\circ\text{F} T XPS , in t = T in − q c a v ′′ ⋅ R in → XPS = 70.0 − ( 3.294 × 14.69 ) = 70.0 − 48.39 = 21.6 1 ∘ F
This confirms that without sufficient continuous exterior insulation, the cavity condensation plane remains well below the indoor dew point ( 37 ∘ F ~37^\circ\text{F} 3 7 ∘ F at 50 % RH 50\%\text{ RH} 50% RH ), validating ASHRAE building science guidelines.