Study guide

4.5 Heat Exchanger Analysis: Log Mean Temperature Difference (LMTD) & Effectiveness-NTU (ε-NTU)

PE Mechanical: HVAC and Refrigeration Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Overview, Reference Handbook & Engineering Foundations

1.1 NCEES Exam Specification, CBT Delivery & Reference Handbook Strategy 1.2 Engineering Units, Dimensional Analysis & Physical Property Lookups 1.3 Engineering Economics, Life Cycle Cost Analysis & Equipment Financial Evaluation 1.4 Electrical Foundations, Motor Ratings & Variable Frequency Drives (VFDs)

2 Chapter 2: Thermodynamics & Energy Balances

2.1 First and Second Laws of Thermodynamics & Open/Closed System Energy Balances 2.2 Thermodynamic Cycles: Carnot, Rankine, Brayton & Reversed Carnot Limit 2.3 Gas & Vapor Property Evaluation: Steam Tables, Superheat & Subcooling 2.4 Mass, Energy & Combustion Balances for HVAC Equipment

3 Chapter 3: Psychrometrics, Moist Air Processes & Humidity Equipment

3.1 Psychrometric Properties: DBT, WBT, DPT, RH, Humidity Ratio & Enthalpy 3.2 Chart Reading & Psychrometric Equations at Sea Level vs. Altitude (5,000 ft) 3.3 Basic Psychrometric Processes: Sensible Heating/Cooling, Humidification & Dehumidification 3.4 Mixed Air Calculations & Complex Air Conditioning Cycles (Preheat, Reheat & Bypass) 3.5 Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP) & Coil Bypass Factor 3.6 Humidification & Dehumidification Equipment: Steam, Adiabatic, Desiccant & Low-Temperature Processes

4 Chapter 4: Heat Transfer Principles & Sizing

4.1 Steady-State Conduction & Multilayer Thermal Resistance (R-Value & U-Factor) 4.2 Convective Heat Transfer & Forced/Natural Convection Coefficients 4.3 Radiation Heat Transfer, Surface Emissivity & View Factors 4.4 Overall Heat Transfer Coefficients, Fouling Factors & Transient/Thermal Mass Effects 4.5 Heat Exchanger Analysis: Log Mean Temperature Difference (LMTD) & Effectiveness-NTU (ε-NTU)

5 Chapter 5: Fluid Mechanics & Hydraulic Fundamentals

5.1 Fluid Statics, Incompressible Continuity & Bernoulli Energy Equation 5.2 Pipe Friction, Moody Diagram & Darcy-Weisbach / Hazen-Williams Calculations 5.3 Minor Losses: Equivalent Length, Loss Coefficients (K-factors) & Total System Head 5.4 Pump Sizing, Net Positive Suction Head (NPSHa vs NPSHr) & Cavitation Prevention 5.5 Affinity Laws & Parallel/Series Pump/Fan System Curves

6 Chapter 6: Heating & Cooling Load Calculations

6.1 Outdoor & Indoor Design Conditions (ASHRAE Fundamentals, Climatic Data & Indoor Setpoints) 6.2 Envelope Heat Transmission & Infiltration/Exfiltration Load Methods 6.3 Solar Heat Gain (SHGC), Fenestration & Cooling Load Temperature Difference / Radiant Time Series (CLTD/RTS) 6.4 Internal Heat Gains: Lighting, People, Equipment & Diversity Factors 6.5 Ventilation Loads & Sensible / Latent / Total Cooling Load Synthesis

7 Chapter 7: Refrigeration Principles, Cycles & Cold Storage Applications

7.1 Standard Vapor-Compression Refrigeration Cycle on P-h & T-s Diagrams 7.2 Refrigeration Cycle Performance Metrics: COP, EER, SEER, kW/ton & Ton of Refrigeration 7.3 Cycle Enhancements: Subcooling, Superheating, Liquid-Suction Heat Exchangers & Economizers 7.4 Multi-Stage & Cascade Refrigeration Systems: Intercooling & Flash Gas Removal 7.5 Absorption Refrigeration Cycles: Water-Lithium Bromide & Ammonia-Water Systems 7.6 Food Processing & Cold Storage Refrigeration: Product Load, Pull-Down & Storage Design

8 Chapter 8: Refrigerants, Environmental Regulations & Safety

8.1 Refrigerant Classifications, Nomenclature & Thermodynamic Properties (ASHRAE Standard 34) 8.2 AIM Act, EPA Technology Transitions Sector GWP Limits & Low-GWP Refrigerants (R-32, R-454B) 8.3 Refrigerant Safety Requirements & Machinery Room Design (ASHRAE Standard 15) 8.4 Refrigerant Piping Sizing, Oil Return, Traps & Double Risers

9 Chapter 9: HVAC Equipment & Primary Machinery

9.1 Compressors: Reciprocating, Rotary, Scroll, Screw & Centrifugal 9.2 Condensers: Air-Cooled, Water-Cooled & Evaporative Condensers 9.3 Evaporators & Direct Expansion (DX) vs Liquid Chilling Coils 9.4 Water Chillers: Centrifugal, Screw & Scroll with ASHRAE 90.1 Path A/B IPLV Ratings 9.5 Cooling Towers: Range, Approach, Evaporation, Blowdown & Legionella Control 9.6 Heat Pumps & Variable Refrigerant Flow (VRF): Balance Point, Defrost & Heat Recovery 9.7 Thermal Energy Storage: Full vs. Partial Storage, Chilled Water & Ice Systems

10 Chapter 10: Air-Side Systems & Distribution

10.1 Air Handling Units (AHUs), Dedicated Outdoor Air Systems (DOAS) & Fan-Coil Units 10.2 Duct Design Methodologies: Equal Friction, Static Regain & Velocity Reduction 10.3 Duct Fittings, Dynamic Pressure Losses & SMACNA Construction Standards 10.4 Fan Types, Performance Curves, System Effect Factors & Surge/Stall Dynamics 10.5 Variable Air Volume (VAV) Systems, Terminal Boxes & Space Air Diffusion (ADPI) 10.6 Cooling & Heating Coil Selection: Face Velocity, Rows, Circuiting & Freeze Protection

11 Chapter 11: Hydronic, Steam & Fuel Distribution and Heating Plant

11.1 Hydronic System Architectures: Primary-Only, Primary-Secondary & Variable Primary Flow (VPF) 11.2 Hydronic Pipe Sizing, Velocity Limits & Closed/Open Expansion Tank Sizing 11.3 Control Valves: 2-Way vs 3-Way, Valve Authority (N), Cv Calculations & Characteristic Curves 11.4 Boilers & Heating Hot Water Systems: Condensing vs Non-Condensing & Water Treatment 11.5 Furnaces & Gas-Fired Heating Equipment: AFUE, Temperature Rise, Combustion Air & Vent Categories 11.6 Steam & Condensate Distribution: Latent Heat, Trap Selection, Flash Steam & Stall 11.7 Fuel Gas & Fuel Oil Piping: Demand, Sizing Method, Pressure Drop & Storage Systems

12 Chapter 12: HVAC Control Concepts, Sensors & Sequences

12.1 Sensors, Actuators & Dampers: Selection, Placement, Fail-Safe Position & Damper Authority 12.2 Control Loops: Proportional Offset, PID Action, Reset Strategies & Standard Sequences

13 Chapter 13: Building Energy, Ventilation & Indoor Environmental Quality Codes

13.1 ASHRAE Standard 62.1: Ventilation Rate Procedure (VRP), Indoor Air Quality Procedure & DCV 13.2 ASHRAE Standard 90.1: Building Energy Envelope, Mechanical Efficiency & Economizer Mandates 13.3 ASHRAE Standard 55: Thermal Environmental Conditions, PMV/PPD & Adaptive Comfort Models 13.4 Energy Recovery Systems: Enthalpy Wheels, Fixed-Plate Exchangers, Heat Pipes & Runaround Loops

14 Chapter 14: Supportive Engineering Knowledge, Life Safety & Operations

14.1 Air Filtration Standards: MERV Ratings (ASHRAE 52.2), HEPA & Gas-Phase Adsorption 14.2 Life Safety Systems: Fire/Smoke Dampers, Stairwell Pressurization (NFPA 92) & Smoke Control (NFPA 90A) 14.3 Acoustical Control & Vibration Isolation in HVAC Systems (NC / RC Criteria)

4.5 Heat Exchanger Analysis: Log Mean Temperature Difference (LMTD) & Effectiveness-NTU (ε-NTU)

Key Takeaways Explain This Topic AI

Heat exchangers are governed by the overall energy balance: q ˙ = C h ( T h , i n − T h , o u t ) = C c ( T c , o u t − T c , i n ) \dot{q} = C_h (T_{h,in} - T_{h,out}) = C_c (T_{c,out} - T_{c,in}) q ˙ ​ = C h ​ ( T h , in ​ − T h , o u t ​ ) = C c ​ ( T c , o u t ​ − T c , in ​ ) , where heat capacity rate is C = m ˙ c p C = \dot{m} c_p C = m ˙ c p ​ .

The Log Mean Temperature Difference (LMTD) method calculates heat duty via q ˙ = U A F Δ T l m \dot{q} = U A F \Delta T_{lm} q ˙ ​ = U A F Δ T l m ​ , where Δ T l m = Δ T 1 − Δ T 2 ln ⁡ ( Δ T 1 / Δ T 2 ) \Delta T_{lm} = \frac{\Delta T_1 - \Delta T_2}{\ln(\Delta T_1 / \Delta T_2)} Δ T l m ​ = l n ( Δ T 1 ​ /Δ T 2 ​ ) Δ T 1 ​ − Δ T 2 ​ ​ ; counterflow is thermodynamically superior to parallel flow and can achieve T c , o u t > T h , o u t T_{c,out} > T_{h,out} T c , o u t ​ > T h , o u t ​ .

The LMTD correction factor F ≤ 1.0 F \le 1.0 F ≤ 1.0 accounts for cross-flow and multi-pass shell-and-tube geometry deviations; when F < 0.75 − 0.80 F < 0.75-0.80 F < 0.75 − 0.80 , the design is inefficient and risks temperature cross. For phase-change processes ( C m a x → ∞ C_{max} \to \infty C ma x ​ → ∞ ), F = 1.0 F = 1.0 F = 1.0 identically.

The Effectiveness-NTU ( ε -NTU \varepsilon\text{-NTU} ε -NTU ) method is required when outlet temperatures are unknown; effectiveness is ε = q ˙ q ˙ m a x = q ˙ C m i n ( T h , i n − T c , i n ) \varepsilon = \frac{\dot{q}}{\dot{q}_{max}} = \frac{\dot{q}}{C_{min}(T_{h,in} - T_{c,in})} ε = q ˙ ​ ma x ​ q ˙ ​ ​ = C min ​ ( T h , in ​ − T c , in ​ ) q ˙ ​ ​ , and Number of Transfer Units is NTU = U A C m i n \text{NTU} = \frac{U A}{C_{min}} NTU = C min ​ U A ​ .

For boilers and condensers where one fluid undergoes phase change ( C r = C m i n C m a x = 0 C_r = \frac{C_{min}}{C_{max}} = 0 C r ​ = C ma x ​ C min ​ ​ = 0 ), the effectiveness relationship simplifies to ε = 1 − exp ⁡ ( − NTU ) \varepsilon = 1 - \exp(-\text{NTU}) ε = 1 − exp ( − NTU ) regardless of flow configuration.

Last updated: August 2026

4.5 Heat Exchanger Analysis: Log Mean Temperature Difference (LMTD) & Effectiveness-NTU ( ε -NTU \varepsilon\text{-NTU} ε -NTU )

Heat exchangers transfer thermal energy between two moving fluid streams at different temperatures across a solid conducting boundary. In HVAC and refrigeration systems, heat exchangers include air handling heating/cooling coils, shell-and-tube chiller evaporators and condensers, plate-and-frame waterside economizers, air-to-air energy recovery ventilators (ERVs), and cooling towers. Analyzing heat exchangers requires selecting between two standard analytical approaches:

Log Mean Temperature Difference (LMTD) Method: Preferred for sizing/design problems , where all inlet and outlet fluid temperatures are specified and the required heat transfer surface area ( A A A ) or overall U U U -factor must be determined.

Effectiveness-NTU ( ε -NTU \varepsilon\text{-NTU} ε -NTU ) Method: Preferred for rating/performance problems , where the heat exchanger geometry ( A A A ) and fluid inlet conditions are known, and the outlet temperatures and total heat transfer rate ( q ˙ \dot{q} q ˙ ​ ) must be calculated without iterative solving.

1. Flow Classifications & Temperature Profiles +-----------------------------------------------------------------------------------------+

  • | HEAT EXCHANGER FLOW CONFIGURATIONS AND TEMPERATURE PROFILES |
  • +-----------------------------------------------------------------------------------------+
  • | PARALLEL FLOW (Co-Current): COUNTER FLOW (Counter-Current): |
  • | Hot: T_h,in ================> T_h,out Hot: T_h,in ================> T_h,out |
  • | Cold: T_c,in ================> T_c,out Cold: T_c,out <================ T_c,in |
  • | |
  • | Temp ^ Temp ^ |
  • | | T_h,in | T_h,in |
  • | | \ | \ |
  • | | \---------> T_h,out | \---------> T_h,out |
  • | | ------- T_c,out | / |
  • | | /---------> | T_c,out <--/ |
  • | | / | \ |
  • | | T_c,in | \<--------- T_c,in |
  • | +-------------------------> Area +-------------------------> Area |
  • | Limit: T_c,out CANNOT exceed T_h,out! Advantage: T_c,out CAN EXCEED T_h,out! |
  • +-----------------------------------------------------------------------------------------+
  • Primary Flow Configurations

Counter-Flow (Counter-Current): Fluids flow in opposite directions. Counter-flow provides the highest theoretical thermal efficiency and the maximum effective mean temperature difference. Crucially, counter-flow allows the cold fluid outlet temperature to exceed the hot fluid outlet temperature ( T c , o u t > T h , o u t T_{c,out} > T_{h,out} T c , o u t ​ > T h , o u t ​ ).

Parallel-Flow (Co-Current): Fluids flow in the same direction. Parallel-flow has the lowest thermal efficiency; the cold fluid outlet temperature can never exceed the hot fluid outlet temperature ( T c , o u t < T h , o u t T_{c,out} < T_{h,out} T c , o u t ​ < T h , o u t ​ ).

Cross-Flow: Fluids flow perpendicular to each other (e.g., air flowing across finned hydronic tubes in AHUs). Categorized as unmixed/unmixed (both streams channeled by fins/tubes), mixed/unmixed (one stream mixes freely in the plenum), or mixed/mixed .

Shell-and-Tube: One fluid flows inside tubes while the other flows across baffles inside the outer shell (designated by TEMA standards, such as 1-shell pass, 2-tube passes or 2-shell passes, 4-tube passes).

2. Heat Capacity Rates & Overall Energy Balance

Under steady-state adiabatic conditions (neglecting heat loss from the outer shell to surroundings): q ˙ = m ˙ h c p , h ( T h , i n − T h , o u t ) = m ˙ c c p , c ( T c , o u t − T c , i n ) \dot{q} = \dot{m}_h c_{p,h} (T_{h,in} - T_{h,out}) = \dot{m}_c c_{p,c} (T_{c,out} - T_{c,in}) q ˙ ​ = m ˙ h ​ c p , h ​ ( T h , in ​ − T h , o u t ​ ) = m ˙ c ​ c p , c ​ ( T c , o u t ​ − T c , in ​ )

Defining the heat capacity rate ( C C C ) for hot and cold streams: C h = m ˙ h c p , h and C c = m ˙ c c p , c [ Btu hr ⋅ ∘ F or W K ] C_h = \dot{m}_h c_{p,h} \quad \text{and} \quad C_c = \dot{m}_c c_{p,c} \quad \left[\frac{\text{Btu}}{\text{hr}\cdot{}^\circ\text{F}} \text{ or } \frac{\text{W}}{\text{K}}\right] C h ​ = m ˙ h ​ c p , h ​ and C c ​ = m ˙ c ​ c p , c ​ [ hr ⋅ ∘ F Btu ​ or K W ​ ] q ˙ = C h ( T h , i n − T h , o u t ) = C c ( T c , o u t − T c , i n ) \dot{q} = C_h (T_{h,in} - T_{h,out}) = C_c (T_{c,out} - T_{c,in}) q ˙ ​ = C h ​ ( T h , in ​ − T h , o u t ​ ) = C c ​ ( T c , o u t ​ − T c , in ​ )

Capacity Rate Extremes & Capacity Ratio ( C r C_r C r ​ ) C m i n = min ⁡ ( C h , C c ) and C m a x = max ⁡ ( C h , C c ) C_{min} = \min(C_h, C_c) \quad \text{and} \quad C_{max} = \max(C_h, C_c) C min ​ = min ( C h ​ , C c ​ ) and C ma x ​ = max ( C h ​ , C c ​ ) C r = C m i n C m a x ( 0 ≤ C r ≤ 1.0 ) C_r = \frac{C_{min}}{C_{max}} \quad (0 \le C_r \le 1.0) C r ​ = C ma x ​ C min ​ ​ ( 0 ≤ C r ​ ≤ 1.0 )

Pure Phase Change (Boilers & Condensers): For an evaporating or condensing fluid (such as steam or refrigerant), phase change occurs at constant temperature ( c p → ∞ c_p \to \infty c p ​ → ∞ ), meaning C m a x → ∞ C_{max} \to \infty C ma x ​ → ∞ and the capacity ratio is identically C r = 0 C_r = 0 C r ​ = 0 .

Balanced Flow: When hot and cold mass capacity rates are equal ( C h = C c C_h = C_c C h ​ = C c ​ ), C r = 1.0 C_r = 1.0 C r ​ = 1.0 .

Maximum Theoretical Heat Transfer Rate ( q ˙ m a x \dot{q}_{max} q ˙ ​ ma x ​ )

The absolute thermodynamic maximum heat transfer rate achievable in an infinitely long counter-flow heat exchanger is limited by the fluid stream with the smaller capacity rate ( C m i n C_{min} C min ​ ), which undergoes the maximum possible temperature difference ( T h , i n − T c , i n T_{h,in} - T_{c,in} T h , in ​ − T c , in ​ ): q ˙ m a x = C m i n ( T h , i n − T c , i n ) \dot{q}_{max} = C_{min} (T_{h,in} - T_{c,in}) q ˙ ​ ma x ​ = C min ​ ( T h , in ​ − T c , in ​ )

3. Log Mean Temperature Difference (LMTD) Method

The fundamental heat transfer rate equation using the LMTD method is: q ˙ = U A F Δ T l m \dot{q} = U A F \Delta T_{lm} q ˙ ​ = U A F Δ T l m ​

Where:

U = overall heat transfer coefficient ( Btu/(hr ⋅ ft 2 ⋅ ∘ F) or W/(m 2 ⋅ K) ) U = \text{overall heat transfer coefficient } (\text{Btu/(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)} \text{or W/(m}^2\cdot\text{K)}) U = overall heat transfer coefficient ( Btu/(hr ⋅ ft 2 ⋅ ∘ F) or W/(m 2 ⋅ K) )

A = total heat transfer surface area ( ft 2 or m 2 ) A = \text{total heat transfer surface area } (\text{ft}^2 \text{ or m}^2) A = total heat transfer surface area ( ft 2 or m 2 )

F = LMTD geometry correction factor ( F = 1.0 for true pure counter-flow or parallel-flow ) F = \text{LMTD geometry correction factor } (F = 1.0 \text{ for true pure counter-flow or parallel-flow}) F = LMTD geometry correction factor ( F = 1.0 for true pure counter-flow or parallel-flow )

Δ T l m = Log Mean Temperature Difference ( ∘ F or ∘ C ) \Delta T_{lm} = \text{Log Mean Temperature Difference } ({}^\circ\text{F or } {}^\circ\text{C}) Δ T l m ​ = Log Mean Temperature Difference ( ∘ F or ∘ C )

Definition of Δ T l m \Delta T_{lm} Δ T l m ​ Δ T l m = Δ T 1 − Δ T 2 ln ⁡ ( Δ T 1 Δ T 2 ) \Delta T_{lm} = \frac{\Delta T_1 - \Delta T_2}{\ln\left(\frac{\Delta T_1}{\Delta T_2}\right)} Δ T l m ​ = ln ( Δ T 2 ​ Δ T 1 ​ ​ ) Δ T 1 ​ − Δ T 2 ​ ​

Where the terminal temperature differences Δ T 1 \Delta T_1 Δ T 1 ​ and Δ T 2 \Delta T_2 Δ T 2 ​ are defined based on flow orientation:

Flow Configuration Terminal Difference Δ T 1 \Delta T_1 Δ T 1 ​ Terminal Difference Δ T 2 \Delta T_2 Δ T 2 ​

Counter-Flow Δ T 1 = T h , i n − T c , o u t \Delta T_1 = T_{h,in} - T_{c,out} Δ T 1 ​ = T h , in ​ − T c , o u t ​ Δ T 2 = T h , o u t − T c , i n \Delta T_2 = T_{h,out} - T_{c,in} Δ T 2 ​ = T h , o u t ​ − T c , in ​

Parallel-Flow Δ T 1 = T h , i n − T c , i n \Delta T_1 = T_{h,in} - T_{c,in} Δ T 1 ​ = T h , in ​ − T c , in ​ Δ T 2 = T h , o u t − T c , o u t \Delta T_2 = T_{h,out} - T_{c,out} Δ T 2 ​ = T h , o u t ​ − T c , o u t ​

Special Balanced Case ( Δ T 1 = Δ T 2 \Delta T_1 = \Delta T_2 Δ T 1 ​ = Δ T 2 ​ ): When Δ T 1 = Δ T 2 \Delta T_1 = \Delta T_2 Δ T 1 ​ = Δ T 2 ​ (which occurs in counterflow when C h = C c C_h = C_c C h ​ = C c ​ ), Δ T 1 − Δ T 2 ln ⁡ ( Δ T 1 / Δ T 2 ) \frac{\Delta T_1 - \Delta T_2}{\ln(\Delta T_1 / \Delta T_2)} l n ( Δ T 1 ​ /Δ T 2 ​ ) Δ T 1 ​ − Δ T 2 ​ ​ yields the indeterminate form 0 / 0 0/0 0/0 . Applying L'Hôpital's Rule confirms that Δ T l m = Δ T 1 = Δ T 2 \Delta T_{lm} = \Delta T_1 = \Delta T_2 Δ T l m ​ = Δ T 1 ​ = Δ T 2 ​ .

Loading diagram... Counter-Flow Terminal Temperature Differences

4. LMTD Correction Factor ( F F F ) for Complex Geometries

For multi-pass shell-and-tube heat exchangers and cross-flow coils, flow paths deviate from pure counter-flow, reducing the effective mean temperature difference ( F ≤ 1.0 F \le 1.0 F ≤ 1.0 ). +-----------------------------------------------------------------------------------------+

  • | LMTD CORRECTION FACTOR DIMENSIONLESS PARAMETERS (P and R) |
  • +-----------------------------------------------------------------------------------------+
  • | Temperature Effectiveness P: P = (t_out - t_in) / (T_in - t_in) |
  • | Capacity Rate Ratio R: R = (T_in - T_out) / (t_out - t_in) = C_tube / C_shell |
  • | |
  • | Where: T = Shell-side fluid temperatures (T_in, T_out) |
  • | t = Tube-side fluid temperatures (t_in, t_out) |
  • +-----------------------------------------------------------------------------------------+
  • Analytical Form for 1-Shell Pass, 2 n 2n 2 n -Tube Passes

For a standard 1-shell-pass, 2-tube-pass (or 4, 6 tube passes) shell-and-tube exchanger: F = R 2 + 1 ln ⁡ ( 1 − P 1 − P R ) ( R − 1 ) ln ⁡ ( 2 − P ( R + 1 − R 2 + 1 ) 2 − P ( R + 1 + R 2 + 1 ) ) F = \frac{\sqrt{R^2 + 1} \ln\left(\frac{1 - P}{1 - P R}\right)}{(R - 1) \ln\left(\frac{2 - P(R + 1 - \sqrt{R^2 + 1})}{2 - P(R + 1 + \sqrt{R^2 + 1})}\right)} F = ( R − 1 ) ln ( 2 − P ( R + 1 + R 2 + 1 ​ ) 2 − P ( R + 1 − R 2 + 1 ​ ) ​ ) R 2 + 1 ​ ln ( 1 − PR 1 − P ​ ) ​

Critical Design Rules for F F F on the PE Exam

The F ≥ 0.75 − 0.80 F \ge 0.75-0.80 F ≥ 0.75 − 0.80 Threshold: In professional HVAC engineering, heat exchangers are never selected with F < 0.75 F < 0.75 F < 0.75 . Low F F F values indicate severe temperature cross and steep performance drops where tiny changes in fluid flow cause large capacity losses. If F < 0.75 F < 0.75 F < 0.75 , add more shell passes in series (e.g., switch to a 2-shell-pass, 4-tube-pass exchanger).

Phase Change Equivalence ( F = 1.0 F = 1.0 F = 1.0 ): When one fluid is condensing or boiling ( C r = 0 C_r = 0 C r ​ = 0 , R = 0 R = 0 R = 0 or R → ∞ R \to \infty R → ∞ ), F = 1.00 F = 1.00 F = 1.00 for all heat exchanger configurations (shell-and-tube, cross-flow, etc.).

5. The Effectiveness-NTU ( ε -NTU \varepsilon\text{-NTU} ε -NTU ) Method

When sizing an existing heat exchanger with known surface area A A A and entering fluid conditions, solving via LMTD requires tedious iterations because outlet temperatures appear inside logarithms. The ε -NTU \varepsilon\text{-NTU} ε -NTU method provides direct, explicit closed-form solutions.

1. Heat Exchanger Effectiveness ( ε \varepsilon ε )

Effectiveness is the ratio of actual heat transfer rate q ˙ \dot{q} q ˙ ​ to the maximum theoretical heat transfer rate q ˙ m a x \dot{q}_{max} q ˙ ​ ma x ​ : ε = q ˙ q ˙ m a x = C h ( T h , i n − T h , o u t ) C m i n ( T h , i n − T c , i n ) = C c ( T c , o u t − T c , i n ) C m i n ( T h , i n − T c , i n ) \varepsilon = \frac{\dot{q}}{\dot{q}_{max}} = \frac{C_h (T_{h,in} - T_{h,out})}{C_{min}(T_{h,in} - T_{c,in})} = \frac{C_c (T_{c,out} - T_{c,in})}{C_{min}(T_{h,in} - T_{c,in})} ε = q ˙ ​ ma x ​ q ˙ ​ ​ = C min ​ ( T h , in ​ − T c , in ​ ) C h ​ ( T h , in ​ − T h , o u t ​ ) ​ = C min ​ ( T h , in ​ − T c , in ​ ) C c ​ ( T c , o u t ​ − T c , in ​ ) ​

Once ε \varepsilon ε is known, total heat transfer is calculated immediately: q ˙ = ε q ˙ m a x = ε C m i n ( T h , i n − T c , i n ) \dot{q} = \varepsilon \dot{q}_{max} = \varepsilon C_{min} (T_{h,in} - T_{c,in}) q ˙ ​ = ε q ˙ ​ ma x ​ = ε C min ​ ( T h , in ​ − T c , in ​ )

Fluid outlet temperatures follow directly: T h , o u t = T h , i n − q ˙ C h and T c , o u t = T c , i n + q ˙ C c T_{h,out} = T_{h,in} - \frac{\dot{q}}{C_h} \quad \text{and} \quad T_{c,out} = T_{c,in} + \frac{\dot{q}}{C_c} T h , o u t ​ = T h , in ​ − C h ​ q ˙ ​ ​ and T c , o u t ​ = T c , in ​ + C c ​ q ˙ ​ ​

2. Number of Transfer Units ( NTU \text{NTU} NTU )

NTU \text{NTU} NTU is a dimensionless measure of the physical heat transfer size of the exchanger: NTU = U A C m i n \text{NTU} = \frac{U A}{C_{min}} NTU = C min ​ U A ​

Summary of Analytical ε -NTU \varepsilon\text{-NTU} ε -NTU Formulas (NCEES Reference Handbook)

Flow Geometry Effectiveness Formula ε = f ( NTU , C r ) \varepsilon = f(\text{NTU}, C_r) ε = f ( NTU , C r ​ ) NTU \text{NTU} NTU Formula NTU = f ( ε , C r ) \text{NTU} = f(\varepsilon, C_r) NTU = f ( ε , C r ​ )

Pure Counter-Flow ( C r < 1 C_r < 1 C r ​ < 1 ) ε = 1 − exp ⁡ [ − NTU ( 1 − C r ) ] 1 − C r exp ⁡ [ − NTU ( 1 − C r ) ] \varepsilon = \frac{1 - \exp[-\text{NTU}(1 - C_r)]}{1 - C_r \exp[-\text{NTU}(1 - C_r)]} ε = 1 − C r ​ e x p [ − NTU ( 1 − C r ​ )] 1 − e x p [ − NTU ( 1 − C r ​ )] ​ NTU = 1 C r − 1 ln ⁡ ( ε − 1 ε C r − 1 ) \text{NTU} = \frac{1}{C_r - 1} \ln\left(\frac{\varepsilon - 1}{\varepsilon C_r - 1}\right) NTU = C r ​ − 1 1 ​ ln ( ε C r ​ − 1 ε − 1 ​ )

Pure Counter-Flow ( C r = 1 C_r = 1 C r ​ = 1 ) ε = NTU 1 + NTU \varepsilon = \frac{\text{NTU}}{1 + \text{NTU}} ε = 1 + NTU NTU ​ NTU = ε 1 − ε \text{NTU} = \frac{\varepsilon}{1 - \varepsilon} NTU = 1 − ε ε ​

Parallel-Flow (Any C r C_r C r ​ ) ε = 1 − exp ⁡ [ − NTU ( 1 + C r ) ] 1 + C r \varepsilon = \frac{1 - \exp[-\text{NTU}(1 + C_r)]}{1 + C_r} ε = 1 + C r ​ 1 − e x p [ − NTU ( 1 + C r ​ )] ​ NTU = − ln ⁡ [ 1 − ε ( 1 + C r ) ] 1 + C r \text{NTU} = -\frac{\ln[1 - \varepsilon(1 + C_r)]}{1 + C_r} NTU = − 1 + C r ​ l n [ 1 − ε ( 1 + C r ​ )] ​

Any Exchanger with C r = 0 C_r = 0 C r ​ = 0 (Boiler/Condenser) ε = 1 − exp ⁡ ( − NTU ) \varepsilon = 1 - \exp(-\text{NTU}) ε = 1 − exp ( − NTU ) NTU = − ln ⁡ ( 1 − ε ) \text{NTU} = -\ln(1 - \varepsilon) NTU = − ln ( 1 − ε )

Cross-Flow (Both Streams Unmixed) ε = 1 − exp ⁡ [ 1 C r NTU 0.22 ( exp ⁡ ( − C r NTU 0.78 ) − 1 ) ] \varepsilon = 1 - \exp\left[\frac{1}{C_r} \text{NTU}^{0.22} \left(\exp(-C_r \text{NTU}^{0.78}) - 1\right)\right] ε = 1 − exp [ C r ​ 1 ​ NTU 0.22 ( exp ( − C r ​ NTU 0.78 ) − 1 ) ] Numerical / Chart lookup

Cross-Flow ( C m a x C_{max} C ma x ​ Mixed, C m i n C_{min} C min ​ Unmixed) ε = 1 C r [ 1 − exp ⁡ ( − C r ( 1 − e − NTU ) ) ] \varepsilon = \frac{1}{C_r}\left[1 - \exp\left(-C_r (1 - e^{-\text{NTU}})\right)\right] ε = C r ​ 1 ​ [ 1 − exp ( − C r ​ ( 1 − e − NTU ) ) ] NTU = − ln ⁡ [ 1 + 1 C r ln ⁡ ( 1 − ε C r ) ] \text{NTU} = -\ln\left[1 + \frac{1}{C_r}\ln(1 - \varepsilon C_r)\right] NTU = − ln [ 1 + C r ​ 1 ​ ln ( 1 − ε C r ​ ) ]

1-Shell Pass, 2-Tube Passes ε 1 = 2 [ 1 + C r + 1 + C r 2 ( 1 + e − NTU 1 + C r 2 1 − e − NTU 1 + C r 2 ) ] − 1 \varepsilon_1 = 2\left[1 + C_r + \sqrt{1 + C_r^2}\left(\frac{1 + e^{-\text{NTU}\sqrt{1+C_r^2}}}{1 - e^{-\text{NTU}\sqrt{1+C_r^2}}}\right)\right]^{-1} ε 1 ​ = 2 [ 1 + C r ​ + 1 + C r 2 ​ ​ ( 1 − e − NTU 1 + C r 2 ​ ​ 1 + e − NTU 1 + C r 2 ​ ​ ​ ) ] − 1 NTU = − 1 1 + C r 2 ln ⁡ ( 2 ε − 1 − C r − 1 + C r 2 2 ε − 1 − C r + 1 + C r 2 ) \text{NTU} = -\frac{1}{\sqrt{1+C_r^2}} \ln\left(\frac{\frac{2}{\varepsilon} - 1 - C_r - \sqrt{1+C_r^2}}{\frac{2}{\varepsilon} - 1 - C_r + \sqrt{1+C_r^2}}\right) NTU = − 1 + C r 2 ​ ​ 1 ​ ln ( ε 2 ​ − 1 − C r ​ + 1 + C r 2 ​ ​ ε 2 ​ − 1 − C r ​ − 1 + C r 2 ​ ​ ​ )

  • 6. Step-by-Step Worked Example 1: Sizing a Plate-and-Frame Waterside Economizer (LMTD)
  • Problem Statement

A plate-and-frame heat exchanger serves as a waterside economizer (free cooling) in a central chiller plant. The system cools 200.0 GPM 200.0\text{ GPM} 200.0 GPM of building chilled water from T h , i n = 56.0 ∘ F T_{h,in} = 56.0^\circ\text{F} T h , in ​ = 56. 0 ∘ F down to T h , o u t = 44.0 ∘ F T_{h,out} = 44.0^\circ\text{F} T h , o u t ​ = 44. 0 ∘ F using cold tower water entering at T c , i n = 38.0 ∘ F T_{c,in} = 38.0^\circ\text{F} T c , in ​ = 38. 0 ∘ F with a flow rate of 250.0 GPM 250.0\text{ GPM} 250.0 GPM .

Fluid properties:

Standard water specific heat: c p = 1.000 Btu/(lbm ⋅ ∘ F) c_p = 1.000\text{ Btu/(lbm}\cdot{}^\circ\text{F)} c p ​ = 1.000 Btu/(lbm ⋅ ∘ F)

Chilled water multiplier: C h = 500 × 200.0 GPM = 100 , 000 Btu/(hr ⋅ ∘ F) C_h = 500 \times 200.0\text{ GPM} = 100,000\text{ Btu/(hr}\cdot{}^\circ\text{F)} C h ​ = 500 × 200.0 GPM = 100 , 000 Btu/(hr ⋅ ∘ F)

Tower water multiplier: C c = 500 × 250.0 GPM = 125 , 000 Btu/(hr ⋅ ∘ F) C_c = 500 \times 250.0\text{ GPM} = 125,000\text{ Btu/(hr}\cdot{}^\circ\text{F)} C c ​ = 500 × 250.0 GPM = 125 , 000 Btu/(hr ⋅ ∘ F)

Heat exchanger overall heat transfer coefficient: U = 450.0 Btu/(hr ⋅ ft 2 ⋅ ∘ F) U = 450.0\text{ Btu/(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)} U = 450.0 Btu/(hr ⋅ ft 2 ⋅ ∘ F)

True counter-flow configuration ( F = 1.00 F = 1.00 F = 1.00 )

Calculate:

  • Total heat duty q ˙ \dot{q} q ˙ ​ ( Btu/hr \text{Btu/hr} Btu/hr and Tons of Refrigeration)
  • Leaving cooling tower water temperature T c , o u t T_{c,out} T c , o u t ​ ( ∘ F {}^\circ\text{F} ∘ F )
  • Counter-flow Log Mean Temperature Difference Δ T l m \Delta T_{lm} Δ T l m ​ ( ∘ F {}^\circ\text{F} ∘ F )
  • Required heat transfer plate surface area A A A ( ft 2 \text{ft}^2 ft 2 )
  • Solution Steps

Step 1: Calculate total heat duty q ˙ \dot{q} q ˙ ​ q ˙ = C h ( T h , i n − T h , o u t ) = 100 , 000 Btu/(hr ⋅ ∘ F) × ( 56.0 ∘ F − 44.0 ∘ F ) = 100 , 000 × 12.0 = 1 , 200 , 000 Btu/hr \dot{q} = C_h (T_{h,in} - T_{h,out}) = 100,000\text{ Btu/(hr}\cdot{}^\circ\text{F)} \times (56.0^\circ\text{F} - 44.0^\circ\text{F}) = 100,000 \times 12.0 = 1,200,000\text{ Btu/hr} q ˙ ​ = C h ​ ( T h , in ​ − T h , o u t ​ ) = 100 , 000 Btu/(hr ⋅ ∘ F) × ( 56. 0 ∘ F − 44. 0 ∘ F ) = 100 , 000 × 12.0 = 1 , 200 , 000 Btu/hr Cooling Capacity = 1 , 200 , 000 Btu/hr 12 , 000 Btu/(hr ⋅ Ton) = 100.0 Tons \text{Cooling Capacity} = \frac{1,200,000\text{ Btu/hr}}{12,000\text{ Btu/(hr}\cdot\text{Ton)}} = 100.0\text{ Tons} Cooling Capacity = 12 , 000 Btu/(hr ⋅ Ton) 1 , 200 , 000 Btu/hr ​ = 100.0 Tons

Step 2: Calculate leaving cooling tower water temperature T c , o u t T_{c,out} T c , o u t ​ q ˙ = C c ( T c , o u t − T c , i n ) ⟹ T c , o u t = T c , i n + q ˙ C c \dot{q} = C_c (T_{c,out} - T_{c,in}) \implies T_{c,out} = T_{c,in} + \frac{\dot{q}}{C_c} q ˙ ​ = C c ​ ( T c , o u t ​ − T c , in ​ ) ⟹ T c , o u t ​ = T c , in ​ + C c ​ q ˙ ​ ​ T c , o u t = 38.0 ∘ F + 1 , 200 , 000 Btu/hr 125 , 000 Btu/(hr ⋅ ∘ F) = 38.0 + 9.60 = 47.60 ∘ F T_{c,out} = 38.0^\circ\text{F} + \frac{1,200,000\text{ Btu/hr}}{125,000\text{ Btu/(hr}\cdot{}^\circ\text{F)}} = 38.0 + 9.60 = 47.60^\circ\text{F} T c , o u t ​ = 38. 0 ∘ F + 125 , 000 Btu/(hr ⋅ ∘ F) 1 , 200 , 000 Btu/hr ​ = 38.0 + 9.60 = 47.6 0 ∘ F

Notice that T c , o u t = 47.60 ∘ F > T h , o u t = 44.0 ∘ F T_{c,out} = 47.60^\circ\text{F} > T_{h,out} = 44.0^\circ\text{F} T c , o u t ​ = 47.6 0 ∘ F > T h , o u t ​ = 44. 0 ∘ F (temperature cross, demonstrating counterflow capability).

Step 3: Calculate counter-flow LMTD Δ T 1 = T h , i n − T c , o u t = 56.0 ∘ F − 47.60 ∘ F = 8.40 ∘ F \Delta T_1 = T_{h,in} - T_{c,out} = 56.0^\circ\text{F} - 47.60^\circ\text{F} = 8.40^\circ\text{F} Δ T 1 ​ = T h , in ​ − T c , o u t ​ = 56. 0 ∘ F − 47.6 0 ∘ F = 8.4 0 ∘ F Δ T 2 = T h , o u t − T c , i n = 44.0 ∘ F − 38.0 ∘ F = 6.00 ∘ F \Delta T_2 = T_{h,out} - T_{c,in} = 44.0^\circ\text{F} - 38.0^\circ\text{F} = 6.00^\circ\text{F} Δ T 2 ​ = T h , o u t ​ − T c , in ​ = 44. 0 ∘ F − 38. 0 ∘ F = 6.0 0 ∘ F Δ T l m = Δ T 1 − Δ T 2 ln ⁡ ( Δ T 1 / Δ T 2 ) = 8.40 − 6.00 ln ⁡ ( 8.40 / 6.00 ) = 2.40 ln ⁡ ( 1.400 ) = 2.40 0.33647 = 7.133 ∘ F \Delta T_{lm} = \frac{\Delta T_1 - \Delta T_2}{\ln(\Delta T_1 / \Delta T_2)} = \frac{8.40 - 6.00}{\ln(8.40 / 6.00)} = \frac{2.40}{\ln(1.400)} = \frac{2.40}{0.33647} = 7.133^\circ\text{F} Δ T l m ​ = ln ( Δ T 1 ​ /Δ T 2 ​ ) Δ T 1 ​ − Δ T 2 ​ ​ = ln ( 8.40/6.00 ) 8.40 − 6.00 ​ = ln ( 1.400 ) 2.40 ​ = 0.33647 2.40 ​ = 7.13 3 ∘ F

Step 4: Calculate required plate surface area A A A q ˙ = U A F Δ T l m ⟹ A = q ˙ U F Δ T l m \dot{q} = U A F \Delta T_{lm} \implies A = \frac{\dot{q}}{U F \Delta T_{lm}} q ˙ ​ = U A F Δ T l m ​ ⟹ A = U F Δ T l m ​ q ˙ ​ ​ A = 1 , 200 , 000 Btu/hr 450.0 Btu/(hr ⋅ ft 2 ⋅ ∘ F) × 1.00 × 7.133 ∘ F = 1 , 200 , 000 3 , 209.85 = 373.85 ft 2 A = \frac{1,200,000\text{ Btu/hr}}{450.0\text{ Btu/(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)} \times 1.00 \times 7.133^\circ\text{F}} = \frac{1,200,000}{3,209.85} = 373.85\text{ ft}^2 A = 450.0 Btu/(hr ⋅ ft 2 ⋅ ∘ F) × 1.00 × 7.13 3 ∘ F 1 , 200 , 000 Btu/hr ​ = 3 , 209.85 1 , 200 , 000 ​ = 373.85 ft 2

7. Step-by-Step Worked Example 2: Rating an Air-to-Air Energy Recovery Ventilator ( ε -NTU \varepsilon\text{-NTU} ε -NTU )

Problem Statement

An air-to-air fixed plate energy recovery ventilator (ERV, counter-flow arrangement) handles an outdoor fresh airstream ( 3 , 000 CFM 3,000\text{ CFM} 3 , 000 CFM , T c , i n = 10.0 ∘ F T_{c,in} = 10.0^\circ\text{F} T c , in ​ = 10. 0 ∘ F ) and an building exhaust airstream ( 3 , 000 CFM 3,000\text{ CFM} 3 , 000 CFM , T h , i n = 72.0 ∘ F T_{h,in} = 72.0^\circ\text{F} T h , in ​ = 72. 0 ∘ F ). Standard air properties apply ( C s = 1.08 Btu/(hr ⋅ CFM ⋅ ∘ F) C_s = 1.08\text{ Btu/(hr}\cdot\text{CFM}\cdot{}^\circ\text{F)} C s ​ = 1.08 Btu/(hr ⋅ CFM ⋅ ∘ F) ). The total heat transfer surface area is A = 1200.0 ft 2 A = 1200.0\text{ ft}^2 A = 1200.0 ft 2 and the overall U U U -factor is U = 2.70 Btu/(hr ⋅ ft 2 ⋅ ∘ F) U = 2.70\text{ Btu/(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)} U = 2.70 Btu/(hr ⋅ ft 2 ⋅ ∘ F) .

Calculate:

Heat capacity rates C h C_h C h ​ and C c C_c C c ​ , capacity ratio C r C_r C r ​ , and maximum possible heat transfer q ˙ m a x \dot{q}_{max} q ˙ ​ ma x ​

  • Number of Transfer Units ( NTU \text{NTU} NTU )
  • Exchanger effectiveness ε \varepsilon ε
  • Actual heat recovery rate q ˙ \dot{q} q ˙ ​ ( Btu/hr \text{Btu/hr} Btu/hr )
  • Supply air temperature delivered to the building ( T c , o u t T_{c,out} T c , o u t ​ )
  • Solution Steps

Step 1: Calculate heat capacity rates and q ˙ m a x \dot{q}_{max} q ˙ ​ ma x ​ C h = C c = 1.08 × 3 , 000 CFM = 3 , 240 Btu/(hr ⋅ ∘ F) C_h = C_c = 1.08 \times 3,000\text{ CFM} = 3,240\text{ Btu/(hr}\cdot{}^\circ\text{F)} C h ​ = C c ​ = 1.08 × 3 , 000 CFM = 3 , 240 Btu/(hr ⋅ ∘ F) C m i n = C m a x = 3 , 240 Btu/(hr ⋅ ∘ F) ⟹ C r = C m i n C m a x = 1.00 C_{min} = C_{max} = 3,240\text{ Btu/(hr}\cdot{}^\circ\text{F)} \implies C_r = \frac{C_{min}}{C_{max}} = 1.00 C min ​ = C ma x ​ = 3 , 240 Btu/(hr ⋅ ∘ F) ⟹ C r ​ = C ma x ​ C min ​ ​ = 1.00 q ˙ m a x = C m i n ( T h , i n − T c , i n ) = 3 , 240 × ( 72.0 ∘ F − 10.0 ∘ F ) = 3 , 240 × 62.0 = 200 , 880 Btu/hr \dot{q}_{max} = C_{min} (T_{h,in} - T_{c,in}) = 3,240 \times (72.0^\circ\text{F} - 10.0^\circ\text{F}) = 3,240 \times 62.0 = 200,880\text{ Btu/hr} q ˙ ​ ma x ​ = C min ​ ( T h , in ​ − T c , in ​ ) = 3 , 240 × ( 72. 0 ∘ F − 10. 0 ∘ F ) = 3 , 240 × 62.0 = 200 , 880 Btu/hr

Step 2: Calculate Number of Transfer Units ( NTU \text{NTU} NTU ) NTU = U A C m i n = 2.70 Btu/(hr ⋅ ft 2 ⋅ ∘ F) × 1200.0 ft 2 3 , 240 Btu/(hr ⋅ ∘ F) = 3 , 240 3 , 240 = 1.00 \text{NTU} = \frac{U A}{C_{min}} = \frac{2.70\text{ Btu/(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)} \times 1200.0\text{ ft}^2}{3,240\text{ Btu/(hr}\cdot{}^\circ\text{F)}} = \frac{3,240}{3,240} = 1.00 NTU = C min ​ U A ​ = 3 , 240 Btu/(hr ⋅ ∘ F) 2.70 Btu/(hr ⋅ ft 2 ⋅ ∘ F) × 1200.0 ft 2 ​ = 3 , 240 3 , 240 ​ = 1.00

Step 3: Calculate effectiveness ε \varepsilon ε for counter-flow with C r = 1.0 C_r = 1.0 C r ​ = 1.0 ε = NTU 1 + NTU = 1.00 1 + 1.00 = 1.00 2.00 = 0.500 ( 50.0 % effectiveness ) \varepsilon = \frac{\text{NTU}}{1 + \text{NTU}} = \frac{1.00}{1 + 1.00} = \frac{1.00}{2.00} = 0.500 \quad (50.0\%\text{ effectiveness}) ε = 1 + NTU NTU ​ = 1 + 1.00 1.00 ​ = 2.00 1.00 ​ = 0.500 ( 50.0% effectiveness )

Step 4: Calculate actual heat transfer rate q ˙ \dot{q} q ˙ ​ q ˙ = ε q ˙ m a x = 0.500 × 200 , 880 Btu/hr = 100 , 440 Btu/hr \dot{q} = \varepsilon \dot{q}_{max} = 0.500 \times 200,880\text{ Btu/hr} = 100,440\text{ Btu/hr} q ˙ ​ = ε q ˙ ​ ma x ​ = 0.500 × 200 , 880 Btu/hr = 100 , 440 Btu/hr

Step 5: Calculate delivered supply air temperature T c , o u t T_{c,out} T c , o u t ​ T c , o u t = T c , i n + q ˙ C c = 10.0 ∘ F + 100 , 440 Btu/hr 3 , 240 Btu/(hr ⋅ ∘ F) = 10.0 + 31.0 = 41.0 ∘ F T_{c,out} = T_{c,in} + \frac{\dot{q}}{C_c} = 10.0^\circ\text{F} + \frac{100,440\text{ Btu/hr}}{3,240\text{ Btu/(hr}\cdot{}^\circ\text{F)}} = 10.0 + 31.0 = 41.0^\circ\text{F} T c , o u t ​ = T c , in ​ + C c ​ q ˙ ​ ​ = 10. 0 ∘ F + 3 , 240 Btu/(hr ⋅ ∘ F) 100 , 440 Btu/hr ​ = 10.0 + 31.0 = 41. 0 ∘ F

The ERV preheats incoming outdoor ventilation air from 10 ∘ F 10^\circ\text{F} 1 0 ∘ F to 41 ∘ F 41^\circ\text{F} 4 1 ∘ F for zero heating fuel expenditure.