4.4 Overall Heat Transfer Coefficients, Fouling Factors & Transient/Thermal Mass Effects
PE Mechanical: HVAC and Refrigeration Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview, Reference Handbook & Engineering Foundations
1.1 NCEES Exam Specification, CBT Delivery & Reference Handbook Strategy 1.2 Engineering Units, Dimensional Analysis & Physical Property Lookups 1.3 Engineering Economics, Life Cycle Cost Analysis & Equipment Financial Evaluation 1.4 Electrical Foundations, Motor Ratings & Variable Frequency Drives (VFDs)
2 Chapter 2: Thermodynamics & Energy Balances
2.1 First and Second Laws of Thermodynamics & Open/Closed System Energy Balances 2.2 Thermodynamic Cycles: Carnot, Rankine, Brayton & Reversed Carnot Limit 2.3 Gas & Vapor Property Evaluation: Steam Tables, Superheat & Subcooling 2.4 Mass, Energy & Combustion Balances for HVAC Equipment
3 Chapter 3: Psychrometrics, Moist Air Processes & Humidity Equipment
3.1 Psychrometric Properties: DBT, WBT, DPT, RH, Humidity Ratio & Enthalpy 3.2 Chart Reading & Psychrometric Equations at Sea Level vs. Altitude (5,000 ft) 3.3 Basic Psychrometric Processes: Sensible Heating/Cooling, Humidification & Dehumidification 3.4 Mixed Air Calculations & Complex Air Conditioning Cycles (Preheat, Reheat & Bypass) 3.5 Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP) & Coil Bypass Factor 3.6 Humidification & Dehumidification Equipment: Steam, Adiabatic, Desiccant & Low-Temperature Processes
4 Chapter 4: Heat Transfer Principles & Sizing
4.1 Steady-State Conduction & Multilayer Thermal Resistance (R-Value & U-Factor) 4.2 Convective Heat Transfer & Forced/Natural Convection Coefficients 4.3 Radiation Heat Transfer, Surface Emissivity & View Factors 4.4 Overall Heat Transfer Coefficients, Fouling Factors & Transient/Thermal Mass Effects 4.5 Heat Exchanger Analysis: Log Mean Temperature Difference (LMTD) & Effectiveness-NTU (ε-NTU)
5 Chapter 5: Fluid Mechanics & Hydraulic Fundamentals
5.1 Fluid Statics, Incompressible Continuity & Bernoulli Energy Equation 5.2 Pipe Friction, Moody Diagram & Darcy-Weisbach / Hazen-Williams Calculations 5.3 Minor Losses: Equivalent Length, Loss Coefficients (K-factors) & Total System Head 5.4 Pump Sizing, Net Positive Suction Head (NPSHa vs NPSHr) & Cavitation Prevention 5.5 Affinity Laws & Parallel/Series Pump/Fan System Curves
6 Chapter 6: Heating & Cooling Load Calculations
6.1 Outdoor & Indoor Design Conditions (ASHRAE Fundamentals, Climatic Data & Indoor Setpoints) 6.2 Envelope Heat Transmission & Infiltration/Exfiltration Load Methods 6.3 Solar Heat Gain (SHGC), Fenestration & Cooling Load Temperature Difference / Radiant Time Series (CLTD/RTS) 6.4 Internal Heat Gains: Lighting, People, Equipment & Diversity Factors 6.5 Ventilation Loads & Sensible / Latent / Total Cooling Load Synthesis
7 Chapter 7: Refrigeration Principles, Cycles & Cold Storage Applications
7.1 Standard Vapor-Compression Refrigeration Cycle on P-h & T-s Diagrams 7.2 Refrigeration Cycle Performance Metrics: COP, EER, SEER, kW/ton & Ton of Refrigeration 7.3 Cycle Enhancements: Subcooling, Superheating, Liquid-Suction Heat Exchangers & Economizers 7.4 Multi-Stage & Cascade Refrigeration Systems: Intercooling & Flash Gas Removal 7.5 Absorption Refrigeration Cycles: Water-Lithium Bromide & Ammonia-Water Systems 7.6 Food Processing & Cold Storage Refrigeration: Product Load, Pull-Down & Storage Design
8 Chapter 8: Refrigerants, Environmental Regulations & Safety
8.1 Refrigerant Classifications, Nomenclature & Thermodynamic Properties (ASHRAE Standard 34) 8.2 AIM Act, EPA Technology Transitions Sector GWP Limits & Low-GWP Refrigerants (R-32, R-454B) 8.3 Refrigerant Safety Requirements & Machinery Room Design (ASHRAE Standard 15) 8.4 Refrigerant Piping Sizing, Oil Return, Traps & Double Risers
9 Chapter 9: HVAC Equipment & Primary Machinery
9.1 Compressors: Reciprocating, Rotary, Scroll, Screw & Centrifugal 9.2 Condensers: Air-Cooled, Water-Cooled & Evaporative Condensers 9.3 Evaporators & Direct Expansion (DX) vs Liquid Chilling Coils 9.4 Water Chillers: Centrifugal, Screw & Scroll with ASHRAE 90.1 Path A/B IPLV Ratings 9.5 Cooling Towers: Range, Approach, Evaporation, Blowdown & Legionella Control 9.6 Heat Pumps & Variable Refrigerant Flow (VRF): Balance Point, Defrost & Heat Recovery 9.7 Thermal Energy Storage: Full vs. Partial Storage, Chilled Water & Ice Systems
10 Chapter 10: Air-Side Systems & Distribution
10.1 Air Handling Units (AHUs), Dedicated Outdoor Air Systems (DOAS) & Fan-Coil Units 10.2 Duct Design Methodologies: Equal Friction, Static Regain & Velocity Reduction 10.3 Duct Fittings, Dynamic Pressure Losses & SMACNA Construction Standards 10.4 Fan Types, Performance Curves, System Effect Factors & Surge/Stall Dynamics 10.5 Variable Air Volume (VAV) Systems, Terminal Boxes & Space Air Diffusion (ADPI) 10.6 Cooling & Heating Coil Selection: Face Velocity, Rows, Circuiting & Freeze Protection
11 Chapter 11: Hydronic, Steam & Fuel Distribution and Heating Plant
11.1 Hydronic System Architectures: Primary-Only, Primary-Secondary & Variable Primary Flow (VPF) 11.2 Hydronic Pipe Sizing, Velocity Limits & Closed/Open Expansion Tank Sizing 11.3 Control Valves: 2-Way vs 3-Way, Valve Authority (N), Cv Calculations & Characteristic Curves 11.4 Boilers & Heating Hot Water Systems: Condensing vs Non-Condensing & Water Treatment 11.5 Furnaces & Gas-Fired Heating Equipment: AFUE, Temperature Rise, Combustion Air & Vent Categories 11.6 Steam & Condensate Distribution: Latent Heat, Trap Selection, Flash Steam & Stall 11.7 Fuel Gas & Fuel Oil Piping: Demand, Sizing Method, Pressure Drop & Storage Systems
12 Chapter 12: HVAC Control Concepts, Sensors & Sequences
12.1 Sensors, Actuators & Dampers: Selection, Placement, Fail-Safe Position & Damper Authority 12.2 Control Loops: Proportional Offset, PID Action, Reset Strategies & Standard Sequences
13 Chapter 13: Building Energy, Ventilation & Indoor Environmental Quality Codes
13.1 ASHRAE Standard 62.1: Ventilation Rate Procedure (VRP), Indoor Air Quality Procedure & DCV 13.2 ASHRAE Standard 90.1: Building Energy Envelope, Mechanical Efficiency & Economizer Mandates 13.3 ASHRAE Standard 55: Thermal Environmental Conditions, PMV/PPD & Adaptive Comfort Models 13.4 Energy Recovery Systems: Enthalpy Wheels, Fixed-Plate Exchangers, Heat Pipes & Runaround Loops
14 Chapter 14: Supportive Engineering Knowledge, Life Safety & Operations
14.1 Air Filtration Standards: MERV Ratings (ASHRAE 52.2), HEPA & Gas-Phase Adsorption 14.2 Life Safety Systems: Fire/Smoke Dampers, Stairwell Pressurization (NFPA 92) & Smoke Control (NFPA 90A) 14.3 Acoustical Control & Vibration Isolation in HVAC Systems (NC / RC Criteria)
4.4 Overall Heat Transfer Coefficients, Fouling Factors & Transient/Thermal Mass Effects
Key Takeaways Explain This Topic AI
The overall heat transfer coefficient U U U for tubular heat exchangers incorporates internal/external convection, wall conduction, and inside/outside fouling resistances: 1 U o A o = 1 U i A i = 1 h i A i + R f , i A i + ln ( r o / r i ) 2 π k L + R f , o A o + 1 η o h o A o \frac{1}{U_o A_o} = \frac{1}{U_i A_i} = \frac{1}{h_i A_i} + \frac{R_{f,i}}{A_i} + \frac{\ln(r_o/r_i)}{2 \pi k L} + \frac{R_{f,o}}{A_o} + \frac{1}{\eta_o h_o A_o} U o A o 1 = U i A i 1 = h i A i 1 + A i R f , i + 2 πk L l n ( r o / r i ) + A o R f , o + η o h o A o 1 .
Extended surface (fin) efficiency is η f = tanh ( m L c ) m L c \eta_f = \frac{\tanh(m L_c)}{m L_c} η f = m L c t a n h ( m L c ) where fin parameter m = h P k A c m = \sqrt{\frac{h P}{k A_c}} m = k A c h P ; total surface efficiency is η o = 1 − A f A t ( 1 − η f ) \eta_o = 1 - \frac{A_f}{A_t}(1 - \eta_f) η o = 1 − A t A f ( 1 − η f ) . Fins are placed on the fluid side with the lower convective coefficient (e.g., air side of hydronic coils).
Fouling resistance ( R f R_f R f ) degrades overall U U U -factor over time; for water-cooled chillers, scale buildup increases condensing pressure, increasing compressor power by approximately 2 % 2\% 2% to 3 % 3\% 3% per 0.0001 hr ⋅ ft 2 ⋅ ∘ F/Btu 0.0001\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu} 0.0001 hr ⋅ ft 2 ⋅ ∘ F/Btu fouling factor increase.
The Lumped Capacitance Model is valid only when the Biot number Bi = h L c k < 0.10 \text{Bi} = \frac{h L_c}{k} < 0.10 Bi = k h L c < 0.10 , indicating uniform internal temperature; the transient thermal response follows T ( t ) − T ∞ T 0 − T ∞ = exp ( − t / τ ) \frac{T(t) - T_\infty}{T_0 - T_\infty} = \exp(-t / \tau) T 0 − T ∞ T ( t ) − T ∞ = exp ( − t / τ ) where thermal time constant τ = ρ V c p h A s \tau = \frac{\rho V c_p}{h A_s} τ = h A s ρ V c p .
For Bi ≥ 0.10 \text{Bi} \ge 0.10 Bi ≥ 0.10 , internal temperature gradients are significant, requiring spatial transient solutions governed by the Fourier number Fo = α t L c 2 \text{Fo} = \frac{\alpha t}{L_c^2} Fo = L c 2 α t where thermal diffusivity is α = k ρ c p \alpha = \frac{k}{\rho c_p} α = ρ c p k .
Last updated: August 2026
4.4 Overall Heat Transfer Coefficients, Fouling Factors & Transient/Thermal Mass Effects
In real-world HVAC equipment—such as shell-and-tube water chillers, finned-tube cooling coils, plate-and-frame heat exchangers, and boiler firetubes—heat flows across multi-component thermal barriers involving convection, conduction, surface extended fins, and fouling scale deposits. Furthermore, equipment startup, thermostat cycling, and building envelope thermal storage exhibit time-dependent transient heat transfer . Mastering the complete overall heat transfer coefficient formulation and transient lumped capacitance criteria is essential for the PE Mechanical exam.
1. Overall Heat Transfer Coefficient Formulation ( U U U )
The steady-state heat transfer rate across any composite thermal barrier is expressed in terms of the overall heat transfer coefficient ( U U U ) and a defined reference area A A A : q ˙ = U A Δ T = U i A i Δ T = U o A o Δ T = Δ T R t o t a l \dot{q} = U A \Delta T = U_i A_i \Delta T = U_o A_o \Delta T = \frac{\Delta T}{R_{total}} q ˙ = U A Δ T = U i A i Δ T = U o A o Δ T = R t o t a l Δ T
Where:
U i = overall heat transfer coefficient based on inside surface area A i [ Btu/(hr ⋅ ft 2 ⋅ ∘ F) or W/(m 2 ⋅ K) ] U_i = \text{overall heat transfer coefficient based on inside surface area } A_i \quad [\text{Btu/(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)} \text{ or W/(m}^2\cdot\text{K)}] U i = overall heat transfer coefficient based on inside surface area A i [ Btu/(hr ⋅ ft 2 ⋅ ∘ F) or W/(m 2 ⋅ K) ]
U o = overall heat transfer coefficient based on outside surface area A o [ Btu/(hr ⋅ ft 2 ⋅ ∘ F) or W/(m 2 ⋅ K) ] U_o = \text{overall heat transfer coefficient based on outside surface area } A_o \quad [\text{Btu/(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)} \text{ or W/(m}^2\cdot\text{K)}] U o = overall heat transfer coefficient based on outside surface area A o [ Btu/(hr ⋅ ft 2 ⋅ ∘ F) or W/(m 2 ⋅ K) ]
Because heat rate q ˙ \dot{q} q ˙ is identical regardless of reference datum: U i A i = U o A o = 1 R t o t a l U_i A_i = U_o A_o = \frac{1}{R_{total}} U i A i = U o A o = R t o t a l 1 +-----------------------------------------------------------------------------------------+
- | COMPREHENSIVE THERMAL RESISTANCE NETWORK FOR A TUBULAR HEAT EXCHANGER |
- +-----------------------------------------------------------------------------------------+
| T_hot o---[ 1/(h_i A_i) ]---[ R_fi/A_i ]---[ ln(r_o/r_i)/(2 pi k L) ]---[ R_fo/A_o ]---[ 1/(eta_o h_o A_o) ]---o T_cold
- | Inside Inside Tube Wall Conduction Outside Outside Finned Surface |
- | Convection Fouling Fouling Convection |
- +-----------------------------------------------------------------------------------------+
- General Resistance Equation for Finned Tubes
Expanding the total thermal resistance network across a cylindrical tube of length L L L , inner radius r i r_i r i , outer radius r o r_o r o , with extended fins on the exterior surface: 1 U o A o = 1 h i A i + R f , i A i + ln ( r o / r i ) 2 π k L + R f , o A o + 1 η o h o A o \frac{1}{U_o A_o} = \frac{1}{h_i A_i} + \frac{R_{f,i}}{A_i} + \frac{\ln(r_o / r_i)}{2 \pi k L} + \frac{R_{f,o}}{A_o} + \frac{1}{\eta_o h_o A_o} U o A o 1 = h i A i 1 + A i R f , i + 2 πk L ln ( r o / r i ) + A o R f , o + η o h o A o 1
Multiplying through by outside reference area A o A_o A o gives the outside overall U U U -factor ( U o U_o U o ): 1 U o = 1 h i ( A o A i ) + R f , i ( A o A i ) + r o ln ( r o / r i ) k + R f , o + 1 η o h o \frac{1}{U_o} = \frac{1}{h_i} \left(\frac{A_o}{A_i}\right) + R_{f,i} \left(\frac{A_o}{A_i}\right) + \frac{r_o \ln(r_o / r_i)}{k} + R_{f,o} + \frac{1}{\eta_o h_o} U o 1 = h i 1 ( A i A o ) + R f , i ( A i A o ) + k r o ln ( r o / r i ) + R f , o + η o h o 1
Where:
h i , h o = inside and outside convective heat transfer coefficients ( Btu/(hr ⋅ ft 2 ⋅ ∘ F) ) h_i, h_o = \text{inside and outside convective heat transfer coefficients } (\text{Btu/(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)}) h i , h o = inside and outside convective heat transfer coefficients ( Btu/(hr ⋅ ft 2 ⋅ ∘ F) )
R f , i , R f , o = inside and outside fouling factors ( hr ⋅ ft 2 ⋅ ∘ F/Btu ) R_{f,i}, R_{f,o} = \text{inside and outside fouling factors } (\text{hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu}) R f , i , R f , o = inside and outside fouling factors ( hr ⋅ ft 2 ⋅ ∘ F/Btu )
k = tube wall material thermal conductivity ( Btu/(hr ⋅ ft ⋅ ∘ F) ) k = \text{tube wall material thermal conductivity } (\text{Btu/(hr}\cdot\text{ft}\cdot{}^\circ\text{F)}) k = tube wall material thermal conductivity ( Btu/(hr ⋅ ft ⋅ ∘ F) )
η o = overall surface temperature efficiency of the finned array \eta_o = \text{overall surface temperature efficiency of the finned array} η o = overall surface temperature efficiency of the finned array
For thin-walled bare planar heat exchanger plates ( A i ≈ A o = A A_i \approx A_o = A A i ≈ A o = A , thickness t t t , no fins): 1 U = 1 h i + R f , i + t k + R f , o + 1 h o \frac{1}{U} = \frac{1}{h_i} + R_{f,i} + \frac{t}{k} + R_{f,o} + \frac{1}{h_o} U 1 = h i 1 + R f , i + k t + R f , o + h o 1
2. Extended Surfaces (Fins) & Surface Temperature Efficiency
In gas-to-liquid heat exchangers (such as hydronic cooling coils and air-cooled condensers), the air-side convective coefficient is much lower than the liquid-side coefficient ( h a i r ≈ 10 − 20 Btu/(hr ⋅ ft 2 ⋅ ∘ F) h_{air} \approx 10-20\text{ Btu/(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)} h ai r ≈ 10 − 20 Btu/(hr ⋅ ft 2 ⋅ ∘ F) vs h w a t e r ≈ 800 − 1500 Btu/(hr ⋅ ft 2 ⋅ ∘ F) h_{water} \approx 800-1500\text{ Btu/(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)} h w a t er ≈ 800 − 1500 Btu/(hr ⋅ ft 2 ⋅ ∘ F) ). To balance thermal resistances, thin aluminum fins are attached to the outside of the copper tubes to multiply the effective surface area ( A o ≫ A i A_o \gg A_i A o ≫ A i ). +-----------------------------------------------------------------------------------------+
- | FIN TEMPERATURE PROFILE AND EFFICIENCY |
- +-----------------------------------------------------------------------------------------+
- | Fin Base: Temp T_b |
- | | |
- | |=========\ |
- | | \ |
- | | \-----> Temp drops along fin: T(x) |
- | | Convective heat loss to surrounding air (T_inf) |
- | | \ |
- | | \========= Fin Tip: Temp T_L |
- | +------------------------------> Fin Length L |
- | Fin Efficiency: eta_f = Actual Heat Transfer / Ideal Heat Transfer (if fin was at T_b) |
- +-----------------------------------------------------------------------------------------+
- Fin Parameter ( m m m ) & Straight Fin Efficiency ( η f \eta_f η f )
As heat conducts along a fin, convection continuously dissipates energy into the airstream, causing the fin temperature to drop from the base temperature T b T_b T b toward fluid temperature T ∞ T_\infty T ∞ . For a straight rectangular fin of length L L L , thickness t t t , perimeter P P P , and cross-sectional area A c A_c A c : m = h P k A c = h ( 2 w + 2 t ) k ( w ⋅ t ) ≈ 2 h k t m = \sqrt{\frac{h P}{k A_c}} = \sqrt{\frac{h (2w + 2t)}{k (w \cdot t)}} \approx \sqrt{\frac{2 h}{k t}} m = k A c h P = k ( w ⋅ t ) h ( 2 w + 2 t ) ≈ k t 2 h
For an adiabatic (insulated) tip fin, the fin efficiency ( η f \eta_f η f ) is: η f = q ˙ a c t u a l q ˙ i d e a l = tanh ( m L ) m L \eta_f = \frac{\dot{q}_{actual}}{\dot{q}_{ideal}} = \frac{\tanh(m L)}{m L} η f = q ˙ i d e a l q ˙ a c t u a l = m L tanh ( m L )
When accounting for convective heat loss from the tip, use the corrected fin length L c = L + t 2 L_c = L + \frac{t}{2} L c = L + 2 t : η f = tanh ( m L c ) m L c \eta_f = \frac{\tanh(m L_c)}{m L_c} η f = m L c tanh ( m L c )
Total Extended Surface Efficiency ( η o \eta_o η o )
An HVAC coil exterior surface consists of unfinned tube area ( A u A_u A u ) at base temperature T b T_b T b (efficiency = 1.0 = 1.0 = 1.0 ) and fin area ( A f A_f A f ) at efficiency η f \eta_f η f . The total outside area is A t = A u + A f A_t = A_u + A_f A t = A u + A f . The overall surface efficiency is: η o = A u ( 1.0 ) + A f η f A t = ( A t − A f ) + A f η f A t = 1 − A f A t ( 1 − η f ) \eta_o = \frac{A_u(1.0) + A_f \eta_f}{A_t} = \frac{(A_t - A_f) + A_f \eta_f}{A_t} = 1 - \frac{A_f}{A_t}(1 - \eta_f) η o = A t A u ( 1.0 ) + A f η f = A t ( A t − A f ) + A f η f = 1 − A t A f ( 1 − η f )
3. Fouling Factors (Thermal Resistances)
During operation, mineral scaling (calcium carbonate), biological growth (algae/biofilms), particulate sedimentation, and corrosion deposit an insulating layer on heat exchanger surfaces.
Typical Design Fouling Factors (TEMA & AHRI Standards)
Fluid Stream Application / Source Standard Fouling Resistance R f R_f R f [hr ⋅ ft 2 ⋅ ∘ F/Btu] \text{[hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu]} [hr ⋅ ft 2 ⋅ ∘ F/Btu]
Clean Closed-Loop Chilled Water Closed treated hydronic system 0.00010 0.00010 0.00010
Treated Boiler Heating Water Closed hydronic loop ( < 160 ∘ F <160^\circ\text{F} < 16 0 ∘ F ) 0.00010 0.00010 0.00010
- Open Cooling Tower Water Open evaporative cooling loop 0.00020 − 0.00030 0.00020 - 0.00030 0.00020 − 0.00030
- Untreated River / Well Water Once-through condensing 0.00100 − 0.00200 0.00100 - 0.00200 0.00100 − 0.00200
- Refrigerants (CFC, HCFC, HFC) Clean vapor/liquid condensing 0.00010 0.00010 0.00010
- Compressed Air / Clean Gas HVAC airstreams 0.00020 0.00020 0.00020
- Heavy Fuel Oil / Steam Exhaust Industrial process 0.00100 − 0.00500 0.00100 - 0.00500 0.00100 − 0.00500
- Impact on Water Chiller Performance
In a centrifugal water chiller, cooling tower water flows through condenser tubes. As scale deposits increase R f , i R_{f,i} R f , i :
Overall U U U -factor drops, requiring a higher temperature difference Δ T \Delta T Δ T to reject heat.
Chiller condensing pressure and saturated condensing temperature ( T c o n d T_{cond} T co n d ) rise.
Compressor lift increases, increasing compressor electrical consumption by approximately 2 % 2\% 2% to 3 % 3\% 3% per 0.0001 hr ⋅ ft 2 ⋅ ∘ F/Btu 0.0001\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu} 0.0001 hr ⋅ ft 2 ⋅ ∘ F/Btu increase in fouling resistance.
Loading diagram... Impact of Tube Scale Fouling on Chiller Lift & Compressor Power
4. Transient Heat Conduction & Lumped Capacitance Method
When thermal boundary conditions change abruptly (e.g., thermostat temperature setback, hot water pipe startup, refrigerated food pull-down), temperature varies with both location and time: T = T ( x , y , z , t ) T = T(x, y, z, t) T = T ( x , y , z , t ) . +-----------------------------------------------------------------------------------------+
- | LUMPED CAPACITANCE VALIDITY CRITERION: BIOT NUMBER Bi < 0.10 |
- +-----------------------------------------------------------------------------------------+
- | Biot Number: Bi = (h * L_c) / k_solid where L_c = Volume / Surface Area |
- | |
- | Case A: Bi < 0.10 (Lumped Capacitance Valid) Case B: Bi >= 0.10 (Spatial Gradients) |
- | Conduction resistance << Convection Conduction resistance is significant |
- | Solid temperature is uniform: T(t) only T = T(x, t) requires Fourier / Heisler |
- | +---------------------------------------+ +-------------------------------------+ |
- | | T_solid = constant across volume | | T_center > T_surface (steep curve) | |
- | +---------------------------------------+ +-------------------------------------+ |
- +-----------------------------------------------------------------------------------------+
- The Biot Number Criterion ( Bi \text{Bi} Bi )
The Biot number evaluates whether internal conduction resistance within the solid is negligible compared to external surface convection resistance: Bi = R c o n d R c o n v = L c / ( k s A s ) 1 / ( h A s ) = h L c k s \text{Bi} = \frac{R_{cond}}{R_{conv}} = \frac{L_c / (k_s A_s)}{1 / (h A_s)} = \frac{h L_c}{k_s} Bi = R co n v R co n d = 1/ ( h A s ) L c / ( k s A s ) = k s h L c
Where:
h = convective heat transfer coefficient ( Btu/(hr ⋅ ft 2 ⋅ ∘ F) ) h = \text{convective heat transfer coefficient } (\text{Btu/(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)}) h = convective heat transfer coefficient ( Btu/(hr ⋅ ft 2 ⋅ ∘ F) )
k s = thermal conductivity of the solid material ( Btu/(hr ⋅ ft ⋅ ∘ F) ) k_s = \text{thermal conductivity of the solid material } (\text{Btu/(hr}\cdot\text{ft}\cdot{}^\circ\text{F)}) k s = thermal conductivity of the solid material ( Btu/(hr ⋅ ft ⋅ ∘ F) )
L c = V A s = characteristic length of the solid ( ft ) L_c = \frac{V}{A_s} = \text{characteristic length of the solid } (\text{ft}) L c = A s V = characteristic length of the solid ( ft ) :
Plane slab of thickness 2 L 2L 2 L (exposed both sides): L c = 2 L A 2 A = L L_c = \frac{2L A}{2A} = L L c = 2 A 2 L A = L
Long cylinder of radius r o r_o r o : L c = π r o 2 L 2 π r o L = r o 2 L_c = \frac{\pi r_o^2 L}{2 \pi r_o L} = \frac{r_o}{2} L c = 2 π r o L π r o 2 L = 2 r o
Sphere of radius r o r_o r o : L c = 4 3 π r o 3 4 π r o 2 = r o 3 L_c = \frac{\frac{4}{3}\pi r_o^3}{4 \pi r_o^2} = \frac{r_o}{3} L c = 4 π r o 2 3 4 π r o 3 = 3 r o
Governing Rule for Lumped Capacitance: If Bi < 0.10 \mathbf{\text{Bi} < 0.10} Bi < 0.10 , temperature gradients inside the body are negligible ( < 5 % <5\% < 5% error). The body can be treated as a single uniform "lumped" temperature T ( t ) T(t) T ( t ) .
Lumped Capacitance Formulation & Thermal Time Constant ( τ \tau τ )
Performing an energy balance equating rate of internal energy change to surface convection: ρ V c p d T d t = − h A s ( T − T ∞ ) \rho V c_p \frac{dT}{dt} = -h A_s (T - T_\infty) ρ V c p d t d T = − h A s ( T − T ∞ )
Separating variables and integrating from initial temperature T ( 0 ) = T 0 T(0) = T_0 T ( 0 ) = T 0 at t = 0 t = 0 t = 0 : T ( t ) − T ∞ T 0 − T ∞ = exp ( − h A s ρ V c p t ) = exp ( − t τ ) = e − t / τ \frac{T(t) - T_\infty}{T_0 - T_\infty} = \exp\left(-\frac{h A_s}{\rho V c_p} t\right) = \exp\left(-\frac{t}{\tau}\right) = e^{-t / \tau} T 0 − T ∞ T ( t ) − T ∞ = exp ( − ρ V c p h A s t ) = exp ( − τ t ) = e − t / τ
Where τ \tau τ is the thermal time constant of the system: τ = R t h C t h = ( 1 h A s ) ( ρ V c p ) = ρ V c p h A s = ρ c p L c h [ hours or seconds ] \tau = R_{th} C_{th} = \left(\frac{1}{h A_s}\right)(\rho V c_p) = \frac{\rho V c_p}{h A_s} = \frac{\rho c_p L_c}{h} \quad [\text{hours or seconds}] τ = R t h C t h = ( h A s 1 ) ( ρ V c p ) = h A s ρ V c p = h ρ c p L c [ hours or seconds ]
At t = 1 τ t = 1\tau t = 1 τ : T ( t ) T(t) T ( t ) has completed 63.2 % 63.2\% 63.2% of its total temperature change.
At t = 3 τ t = 3\tau t = 3 τ : T ( t ) T(t) T ( t ) has completed 95.0 % 95.0\% 95.0% of change.
At t = 5 τ t = 5\tau t = 5 τ : T ( t ) T(t) T ( t ) has completed 99.3 % 99.3\% 99.3% of change (essentially steady-state).
Spatial Transient Conduction ( Bi ≥ 0.10 \text{Bi} \ge 0.10 Bi ≥ 0.10 ) & Fourier Number ( Fo \text{Fo} Fo )
When Bi ≥ 0.10 \text{Bi} \ge 0.10 Bi ≥ 0.10 , internal temperature varies with spatial position, governed by the dimensionless Fourier number : Fo = α t L c 2 \text{Fo} = \frac{\alpha t}{L_c^2} Fo = L c 2 α t
Where α = k ρ c p \alpha = \frac{k}{\rho c_p} α = ρ c p k is the material's thermal diffusivity ( ft 2 / hr \text{ft}^2/\text{hr} ft 2 / hr or m 2 / s \text{m}^2/\text{s} m 2 / s ). For Fo > 0.2 \text{Fo} > 0.2 Fo > 0.2 , one-term approximate analytical solutions or Heisler charts provide exact temperature profiles.
Building Thermal Mass Dynamics (Decrement Factor & Time Lag)
In high-thermal-mass building envelopes (concrete, masonry, adobe):
Decrement Factor ( f f f ): Ratio of the inside surface peak temperature fluctuation to the outside ambient sol-air peak temperature fluctuation ( f < 1.0 f < 1.0 f < 1.0 ). High thermal mass damps outdoor temperature swings.
Time Lag ( ϕ \phi ϕ ): Time delay (in hours) between the peak outdoor sol-air temperature and the resulting peak indoor cooling load, shifting peak cooling demand to late evening off-peak hours.
- 5. Step-by-Step Worked Example: Condenser Tube Sizing & Fouling Derating
- Problem Statement
A water-cooled shell-and-tube refrigeration condenser uses copper tubes ( k = 225 Btu/(hr ⋅ ft ⋅ ∘ F) k = 225\text{ Btu/(hr}\cdot\text{ft}\cdot{}^\circ\text{F)} k = 225 Btu/(hr ⋅ ft ⋅ ∘ F) ) with outer diameter D o = 0.750 in. = 0.06250 ft D_o = 0.750\text{ in.} = 0.06250\text{ ft} D o = 0.750 in. = 0.06250 ft and inner diameter D i = 0.652 in. = 0.05433 ft D_i = 0.652\text{ in.} = 0.05433\text{ ft} D i = 0.652 in. = 0.05433 ft .
Operating parameters:
Saturated refrigerant condensing on shell outside: h o = 1200.0 Btu/(hr ⋅ ft 2 ⋅ ∘ F) h_o = 1200.0\text{ Btu/(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)} h o = 1200.0 Btu/(hr ⋅ ft 2 ⋅ ∘ F)
Cooling tower water flowing inside tubes: h i = 850.0 Btu/(hr ⋅ ft 2 ⋅ ∘ F) h_i = 850.0\text{ Btu/(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)} h i = 850.0 Btu/(hr ⋅ ft 2 ⋅ ∘ F)
Inside tube fouling factor (cooling tower scale): R f , i = 0.00050 hr ⋅ ft 2 ⋅ ∘ F/Btu R_{f,i} = 0.00050\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu} R f , i = 0.00050 hr ⋅ ft 2 ⋅ ∘ F/Btu
- Outside fouling factor (clean condensing refrigerant): R f , o = 0.0 R_{f,o} = 0.0 R f , o = 0.0
- Bare smooth tubes (no fins, η o = 1.0 \eta_o = 1.0 η o = 1.0 )
Calculate:
- Ratio of outer-to-inner surface area ( A o / A i A_o / A_i A o / A i )
- Clean overall heat transfer coefficient based on outside area ( U o , c l e a n U_{o,clean} U o , c l e an )
Fouled overall heat transfer coefficient based on outside area ( U o , f o u l e d U_{o,fouled} U o , f o u l e d )
- Percentage reduction in heat transfer capacity caused by water-side tube fouling
- Solution Steps
Step 1: Calculate area ratio and radii r o = 0.06250 2 = 0.03125 ft , r i = 0.05433 2 = 0.027165 ft r_o = \frac{0.06250}{2} = 0.03125\text{ ft}, \quad r_i = \frac{0.05433}{2} = 0.027165\text{ ft} r o = 2 0.06250 = 0.03125 ft , r i = 2 0.05433 = 0.027165 ft A o A i = π D o L π D i L = D o D i = 0.750 in. 0.652 in. = 1.1503 \frac{A_o}{A_i} = \frac{\pi D_o L}{\pi D_i L} = \frac{D_o}{D_i} = \frac{0.750\text{ in.}}{0.652\text{ in.}} = 1.1503 A i A o = π D i L π D o L = D i D o = 0.652 in. 0.750 in. = 1.1503
Step 2: Calculate individual resistance components based on outside area A o A_o A o
Inside Convection Resistance per unit A o A_o A o : R c o n v , i = 1 h i ( A o A i ) = 1 850.0 × 1.1503 = 0.0011765 × 1.1503 = 0.0013533 hr ⋅ ft 2 ⋅ ∘ F/Btu R_{conv,i} = \frac{1}{h_i} \left(\frac{A_o}{A_i}\right) = \frac{1}{850.0} \times 1.1503 = 0.0011765 \times 1.1503 = 0.0013533\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu} R co n v , i = h i 1 ( A i A o ) = 850.0 1 × 1.1503 = 0.0011765 × 1.1503 = 0.0013533 hr ⋅ ft 2 ⋅ ∘ F/Btu
Tube Wall Conduction Resistance per unit A o A_o A o : R c o n d = r o ln ( r o / r i ) k = 0.03125 × ln ( 0.750 / 0.652 ) 225 = 0.03125 × 0.14002 225 = 0.00001945 hr ⋅ ft 2 ⋅ ∘ F/Btu R_{cond} = \frac{r_o \ln(r_o / r_i)}{k} = \frac{0.03125 \times \ln(0.750 / 0.652)}{225} = \frac{0.03125 \times 0.14002}{225} = 0.00001945\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu} R co n d = k r o ln ( r o / r i ) = 225 0.03125 × ln ( 0.750/0.652 ) = 225 0.03125 × 0.14002 = 0.00001945 hr ⋅ ft 2 ⋅ ∘ F/Btu
Outside Convection Resistance per unit A o A_o A o : R c o n v , o = 1 h o = 1 1200.0 = 0.0008333 hr ⋅ ft 2 ⋅ ∘ F/Btu R_{conv,o} = \frac{1}{h_o} = \frac{1}{1200.0} = 0.0008333\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu} R co n v , o = h o 1 = 1200.0 1 = 0.0008333 hr ⋅ ft 2 ⋅ ∘ F/Btu
Step 3: Calculate clean overall U U U -factor ( U o , c l e a n U_{o,clean} U o , c l e an ) R c l e a n , t o t a l = R c o n v , i + R c o n d + R c o n v , o R_{clean,total} = R_{conv,i} + R_{cond} + R_{conv,o} R c l e an , t o t a l = R co n v , i + R co n d + R co n v , o R c l e a n , t o t a l = 0.0013533 + 0.0000195 + 0.0008333 = 0.0022061 hr ⋅ ft 2 ⋅ ∘ F/Btu R_{clean,total} = 0.0013533 + 0.0000195 + 0.0008333 = 0.0022061\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu} R c l e an , t o t a l = 0.0013533 + 0.0000195 + 0.0008333 = 0.0022061 hr ⋅ ft 2 ⋅ ∘ F/Btu U o , c l e a n = 1 R c l e a n , t o t a l = 1 0.0022061 = 453.29 Btu/(hr ⋅ ft 2 ⋅ ∘ F) U_{o,clean} = \frac{1}{R_{clean,total}} = \frac{1}{0.0022061} = 453.29\text{ Btu/(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)} U o , c l e an = R c l e an , t o t a l 1 = 0.0022061 1 = 453.29 Btu/(hr ⋅ ft 2 ⋅ ∘ F)
Step 4: Calculate fouled overall U U U -factor ( U o , f o u l e d U_{o,fouled} U o , f o u l e d ) Inside fouling resistance per unit outside area: R f , i , o = R f , i ( A o A i ) = 0.00050 × 1.1503 = 0.0005752 hr ⋅ ft 2 ⋅ ∘ F/Btu R_{f,i,o} = R_{f,i} \left(\frac{A_o}{A_i}\right) = 0.00050 \times 1.1503 = 0.0005752\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu} R f , i , o = R f , i ( A i A o ) = 0.00050 × 1.1503 = 0.0005752 hr ⋅ ft 2 ⋅ ∘ F/Btu R f o u l e d , t o t a l = R c l e a n , t o t a l + R f , i , o = 0.0022061 + 0.0005752 = 0.0027813 hr ⋅ ft 2 ⋅ ∘ F/Btu R_{fouled,total} = R_{clean,total} + R_{f,i,o} = 0.0022061 + 0.0005752 = 0.0027813\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu} R f o u l e d , t o t a l = R c l e an , t o t a l + R f , i , o = 0.0022061 + 0.0005752 = 0.0027813 hr ⋅ ft 2 ⋅ ∘ F/Btu U o , f o u l e d = 1 R f o u l e d , t o t a l = 1 0.0027813 = 359.54 Btu/(hr ⋅ ft 2 ⋅ ∘ F) U_{o,fouled} = \frac{1}{R_{fouled,total}} = \frac{1}{0.0027813} = 359.54\text{ Btu/(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)} U o , f o u l e d = R f o u l e d , t o t a l 1 = 0.0027813 1 = 359.54 Btu/(hr ⋅ ft 2 ⋅ ∘ F)
Step 5: Calculate percentage reduction in heat transfer capacity % Reduction = U o , c l e a n − U o , f o u l e d U o , c l e a n × 100 % = 453.29 − 359.54 453.29 × 100 % = 93.75 453.29 × 100 % = 20.68 % \%\text{ Reduction} = \frac{U_{o,clean} - U_{o,fouled}}{U_{o,clean}} \times 100\% = \frac{453.29 - 359.54}{453.29} \times 100\% = \frac{93.75}{453.29} \times 100\% = 20.68\% % Reduction = U o , c l e an U o , c l e an − U o , f o u l e d × 100% = 453.29 453.29 − 359.54 × 100% = 453.29 93.75 × 100% = 20.68%
Water-side scale buildup of R f , i = 0.00050 R_{f,i} = 0.00050 R f , i = 0.00050 reduces the condenser heat rejection capability by over 20.7 % 20.7\% 20.7% , demanding higher water flow rates and increasing chiller operating costs.