Study guide

6.2 Envelope Heat Transmission & Infiltration/Exfiltration Load Methods

PE Mechanical: HVAC and Refrigeration Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Overview, Reference Handbook & Engineering Foundations

1.1 NCEES Exam Specification, CBT Delivery & Reference Handbook Strategy 1.2 Engineering Units, Dimensional Analysis & Physical Property Lookups 1.3 Engineering Economics, Life Cycle Cost Analysis & Equipment Financial Evaluation 1.4 Electrical Foundations, Motor Ratings & Variable Frequency Drives (VFDs)

2 Chapter 2: Thermodynamics & Energy Balances

2.1 First and Second Laws of Thermodynamics & Open/Closed System Energy Balances 2.2 Thermodynamic Cycles: Carnot, Rankine, Brayton & Reversed Carnot Limit 2.3 Gas & Vapor Property Evaluation: Steam Tables, Superheat & Subcooling 2.4 Mass, Energy & Combustion Balances for HVAC Equipment

3 Chapter 3: Psychrometrics, Moist Air Processes & Humidity Equipment

3.1 Psychrometric Properties: DBT, WBT, DPT, RH, Humidity Ratio & Enthalpy 3.2 Chart Reading & Psychrometric Equations at Sea Level vs. Altitude (5,000 ft) 3.3 Basic Psychrometric Processes: Sensible Heating/Cooling, Humidification & Dehumidification 3.4 Mixed Air Calculations & Complex Air Conditioning Cycles (Preheat, Reheat & Bypass) 3.5 Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP) & Coil Bypass Factor 3.6 Humidification & Dehumidification Equipment: Steam, Adiabatic, Desiccant & Low-Temperature Processes

4 Chapter 4: Heat Transfer Principles & Sizing

4.1 Steady-State Conduction & Multilayer Thermal Resistance (R-Value & U-Factor) 4.2 Convective Heat Transfer & Forced/Natural Convection Coefficients 4.3 Radiation Heat Transfer, Surface Emissivity & View Factors 4.4 Overall Heat Transfer Coefficients, Fouling Factors & Transient/Thermal Mass Effects 4.5 Heat Exchanger Analysis: Log Mean Temperature Difference (LMTD) & Effectiveness-NTU (ε-NTU)

5 Chapter 5: Fluid Mechanics & Hydraulic Fundamentals

5.1 Fluid Statics, Incompressible Continuity & Bernoulli Energy Equation 5.2 Pipe Friction, Moody Diagram & Darcy-Weisbach / Hazen-Williams Calculations 5.3 Minor Losses: Equivalent Length, Loss Coefficients (K-factors) & Total System Head 5.4 Pump Sizing, Net Positive Suction Head (NPSHa vs NPSHr) & Cavitation Prevention 5.5 Affinity Laws & Parallel/Series Pump/Fan System Curves

6 Chapter 6: Heating & Cooling Load Calculations

6.1 Outdoor & Indoor Design Conditions (ASHRAE Fundamentals, Climatic Data & Indoor Setpoints) 6.2 Envelope Heat Transmission & Infiltration/Exfiltration Load Methods 6.3 Solar Heat Gain (SHGC), Fenestration & Cooling Load Temperature Difference / Radiant Time Series (CLTD/RTS) 6.4 Internal Heat Gains: Lighting, People, Equipment & Diversity Factors 6.5 Ventilation Loads & Sensible / Latent / Total Cooling Load Synthesis

7 Chapter 7: Refrigeration Principles, Cycles & Cold Storage Applications

7.1 Standard Vapor-Compression Refrigeration Cycle on P-h & T-s Diagrams 7.2 Refrigeration Cycle Performance Metrics: COP, EER, SEER, kW/ton & Ton of Refrigeration 7.3 Cycle Enhancements: Subcooling, Superheating, Liquid-Suction Heat Exchangers & Economizers 7.4 Multi-Stage & Cascade Refrigeration Systems: Intercooling & Flash Gas Removal 7.5 Absorption Refrigeration Cycles: Water-Lithium Bromide & Ammonia-Water Systems 7.6 Food Processing & Cold Storage Refrigeration: Product Load, Pull-Down & Storage Design

8 Chapter 8: Refrigerants, Environmental Regulations & Safety

8.1 Refrigerant Classifications, Nomenclature & Thermodynamic Properties (ASHRAE Standard 34) 8.2 AIM Act, EPA Technology Transitions Sector GWP Limits & Low-GWP Refrigerants (R-32, R-454B) 8.3 Refrigerant Safety Requirements & Machinery Room Design (ASHRAE Standard 15) 8.4 Refrigerant Piping Sizing, Oil Return, Traps & Double Risers

9 Chapter 9: HVAC Equipment & Primary Machinery

9.1 Compressors: Reciprocating, Rotary, Scroll, Screw & Centrifugal 9.2 Condensers: Air-Cooled, Water-Cooled & Evaporative Condensers 9.3 Evaporators & Direct Expansion (DX) vs Liquid Chilling Coils 9.4 Water Chillers: Centrifugal, Screw & Scroll with ASHRAE 90.1 Path A/B IPLV Ratings 9.5 Cooling Towers: Range, Approach, Evaporation, Blowdown & Legionella Control 9.6 Heat Pumps & Variable Refrigerant Flow (VRF): Balance Point, Defrost & Heat Recovery 9.7 Thermal Energy Storage: Full vs. Partial Storage, Chilled Water & Ice Systems

10 Chapter 10: Air-Side Systems & Distribution

10.1 Air Handling Units (AHUs), Dedicated Outdoor Air Systems (DOAS) & Fan-Coil Units 10.2 Duct Design Methodologies: Equal Friction, Static Regain & Velocity Reduction 10.3 Duct Fittings, Dynamic Pressure Losses & SMACNA Construction Standards 10.4 Fan Types, Performance Curves, System Effect Factors & Surge/Stall Dynamics 10.5 Variable Air Volume (VAV) Systems, Terminal Boxes & Space Air Diffusion (ADPI) 10.6 Cooling & Heating Coil Selection: Face Velocity, Rows, Circuiting & Freeze Protection

11 Chapter 11: Hydronic, Steam & Fuel Distribution and Heating Plant

11.1 Hydronic System Architectures: Primary-Only, Primary-Secondary & Variable Primary Flow (VPF) 11.2 Hydronic Pipe Sizing, Velocity Limits & Closed/Open Expansion Tank Sizing 11.3 Control Valves: 2-Way vs 3-Way, Valve Authority (N), Cv Calculations & Characteristic Curves 11.4 Boilers & Heating Hot Water Systems: Condensing vs Non-Condensing & Water Treatment 11.5 Furnaces & Gas-Fired Heating Equipment: AFUE, Temperature Rise, Combustion Air & Vent Categories 11.6 Steam & Condensate Distribution: Latent Heat, Trap Selection, Flash Steam & Stall 11.7 Fuel Gas & Fuel Oil Piping: Demand, Sizing Method, Pressure Drop & Storage Systems

12 Chapter 12: HVAC Control Concepts, Sensors & Sequences

12.1 Sensors, Actuators & Dampers: Selection, Placement, Fail-Safe Position & Damper Authority 12.2 Control Loops: Proportional Offset, PID Action, Reset Strategies & Standard Sequences

13 Chapter 13: Building Energy, Ventilation & Indoor Environmental Quality Codes

13.1 ASHRAE Standard 62.1: Ventilation Rate Procedure (VRP), Indoor Air Quality Procedure & DCV 13.2 ASHRAE Standard 90.1: Building Energy Envelope, Mechanical Efficiency & Economizer Mandates 13.3 ASHRAE Standard 55: Thermal Environmental Conditions, PMV/PPD & Adaptive Comfort Models 13.4 Energy Recovery Systems: Enthalpy Wheels, Fixed-Plate Exchangers, Heat Pipes & Runaround Loops

14 Chapter 14: Supportive Engineering Knowledge, Life Safety & Operations

14.1 Air Filtration Standards: MERV Ratings (ASHRAE 52.2), HEPA & Gas-Phase Adsorption 14.2 Life Safety Systems: Fire/Smoke Dampers, Stairwell Pressurization (NFPA 92) & Smoke Control (NFPA 90A) 14.3 Acoustical Control & Vibration Isolation in HVAC Systems (NC / RC Criteria)

6.2 Envelope Heat Transmission & Infiltration/Exfiltration Load Methods

Key Takeaways Explain This Topic AI

Steady-state envelope heat transmission obeys Fourier's conduction law: q = U * A * Delta_T, where overall thermal resistance R_total equals the summation of internal/external air film resistances and all intermediate material layers.

Thermal bridging through steel or wood framing significantly increases overall wall U-factors, requiring parallel-path thermal calculations or ASHRAE 90.1 framing correction factors (modified zone method).

Below-grade slab-on-grade heat loss is proportional to exposed perimeter length rather than floor area: q = F_p * P * (T_in - T_out), where F_p is the perimeter heat loss coefficient in Btu/(hr·ft·°F).

Infiltration airflow is calculated via the Air Change Method (CFM = ACH * Volume (ft^3) / 60) or the Crack Method, driven by wind pressure, stack effect (buoyancy), and mechanical ventilation imbalance.

Infiltration introduces direct sensible (q_s = 1.08 * CFM * Delta_T), latent (q_l = 4840 * CFM * Delta_W), and total (q_t = 4.5 * CFM * Delta_h) loads directly into the conditioned zone.

Last updated: August 2026

6.2 Envelope Heat Transmission & Infiltration/Exfiltration Load Methods

Building envelope heat transmission and unconditioned air infiltration represent the primary heating loads during winter design conditions and substantial components of summer sensible cooling loads. Calculating envelope loads requires evaluating the steady-state thermal resistance ( R R R -value) and overall heat transfer coefficient ( U U U -factor) of multi-layer assemblies, accounting for two-dimensional thermal bridging across structural framing members, sizing below-grade and slab-on-grade boundary losses, and quantifying infiltration air volume driven by stack effect, wind velocity, and mechanical room pressurization.

1. Steady-State Conduction & Multilayer Thermal Resistance

Under steady-state conditions with one-dimensional heat flow, the thermal transmission rate ( q q q ) through an opaque building component of surface area A A A is expressed by Fourier's law: q = U ⋅ A ⋅ ( T outdoor − T indoor ) = A ⋅ Δ T R total q = U \cdot A \cdot (T_{\text{outdoor}} - T_{\text{indoor}}) = \frac{A \cdot \Delta T}{R_{\text{total}}} q = U ⋅ A ⋅ ( T outdoor ​ − T indoor ​ ) = R total ​ A ⋅ Δ T ​

Where:

q = Heat transfer rate ( Btu/hr ) q = \text{Heat transfer rate } (\text{Btu/hr}) q = Heat transfer rate ( Btu/hr )

U = Overall heat transfer coefficient ( Btu/(hr ⋅ ft 2 ⋅ ∘ F) ) U = \text{Overall heat transfer coefficient } (\text{Btu/(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)}) U = Overall heat transfer coefficient ( Btu/(hr ⋅ ft 2 ⋅ ∘ F) )

A = Net surface area of assembly ( ft 2 ) A = \text{Net surface area of assembly } (\text{ft}^2) A = Net surface area of assembly ( ft 2 )

Δ T = Temperature difference between ambient outdoor air and indoor air ( ∘ F ) \Delta T = \text{Temperature difference between ambient outdoor air and indoor air } ({}^\circ\text{F}) Δ T = Temperature difference between ambient outdoor air and indoor air ( ∘ F )

R total = Total thermal resistance of the composite assembly ( hr ⋅ ft 2 ⋅ ∘ F/Btu ) R_{\text{total}} = \text{Total thermal resistance of the composite assembly } (\text{hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu}) R total ​ = Total thermal resistance of the composite assembly ( hr ⋅ ft 2 ⋅ ∘ F/Btu ) +-----------------------------------------------------------------------------------------+

  • | COMPOSITE MULTI-LAYER WALL THERMAL CIRCUIT |
  • +-----------------------------------------------------------------------------------------+
  • | Outdoor Air (To) Indoor Air (Ti) |
  • | | | |
  • | [R_o] --- [R_ext_finish] --- [R_sheathing] --- [R_insul] --- [R_gyp] --- [R_i] |
  • | (Film Out) (Brick/Siding) (Plywood/OSB) (Cavity) (Drywall) (Film In)
  • +-----------------------------------------------------------------------------------------+
  • Overall Thermal Resistance ( R total R_{\text{total}} R total ​ ) & Series Layer Summation

The total thermal resistance of an unbridged, homogeneous multi-layer assembly is the direct series sum of the individual layer resistances, including the interior ( R i R_i R i ​ ) and exterior ( R o R_o R o ​ ) surface air film resistances: R total = R i + ∑ k = 1 n R k + R o = 1 h i + ∑ k = 1 n x k k k + 1 h o R_{\text{total}} = R_i + \sum_{k=1}^n R_k + R_o = \frac{1}{h_i} + \sum_{k=1}^n \frac{x_k}{k_k} + \frac{1}{h_o} R total ​ = R i ​ + k = 1 ∑ n ​ R k ​ + R o ​ = h i ​ 1 ​ + k = 1 ∑ n ​ k k ​ x k ​ ​ + h o ​ 1 ​ U = 1 R total U = \frac{1}{R_{\text{total}}} U = R total ​ 1 ​

Where:

x k = Thickness of material layer k (inches or feet) x_k = \text{Thickness of material layer } k\text{ (inches or feet)} x k ​ = Thickness of material layer k (inches or feet)

k k = Thermal conductivity of material layer k (Btu ⋅ in./(hr ⋅ ft 2 ⋅ ∘ F) or Btu/(hr ⋅ ft ⋅ ∘ F) ) k_k = \text{Thermal conductivity of material layer } k\text{ (Btu}\cdot\text{in./(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F) or Btu/(hr}\cdot\text{ft}\cdot{}^\circ\text{F)}) k k ​ = Thermal conductivity of material layer k (Btu ⋅ in./(hr ⋅ ft 2 ⋅ ∘ F) or Btu/(hr ⋅ ft ⋅ ∘ F) )

h i , h o = Inside and outside convective/radiative surface film heat transfer coefficients ( Btu/(hr ⋅ ft 2 ⋅ ∘ F) ) h_i, h_o = \text{Inside and outside convective/radiative surface film heat transfer coefficients } (\text{Btu/(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)}) h i ​ , h o ​ = Inside and outside convective/radiative surface film heat transfer coefficients ( Btu/(hr ⋅ ft 2 ⋅ ∘ F) )

Standard Surface Air Film Resistances ( R i R_i R i ​ and R o R_o R o ​ )

Surface Orientation & Heat Flow Direction Surface Emittance ( ε \varepsilon ε ) Winter Condition ( 15 mph wind 15\text{ mph wind} 15 mph wind ) Summer Condition ( 7.5 mph wind 7.5\text{ mph wind} 7.5 mph wind ) Still Air (Indoor)

Exterior Surface (Any Orientation) ε = 0.90 \varepsilon = 0.90 ε = 0.90 R o = 0.17 hr ⋅ ft 2 ⋅ ∘ F/Btu R_o = 0.17\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu} R o ​ = 0.17 hr ⋅ ft 2 ⋅ ∘ F/Btu R o = 0.25 hr ⋅ ft 2 ⋅ ∘ F/Btu R_o = 0.25\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu} R o ​ = 0.25 hr ⋅ ft 2 ⋅ ∘ F/Btu —

Interior Wall (Vertical, Horizontal Flow) ε = 0.90 \varepsilon = 0.90 ε = 0.90 — — R i = 0.68 hr ⋅ ft 2 ⋅ ∘ F/Btu R_i = 0.68\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu} R i ​ = 0.68 hr ⋅ ft 2 ⋅ ∘ F/Btu

Interior Ceiling (Horizontal, Upward Flow) ε = 0.90 \varepsilon = 0.90 ε = 0.90 — — R i = 0.61 hr ⋅ ft 2 ⋅ ∘ F/Btu R_i = 0.61\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu} R i ​ = 0.61 hr ⋅ ft 2 ⋅ ∘ F/Btu

Interior Floor (Horizontal, Downward Flow) ε = 0.90 \varepsilon = 0.90 ε = 0.90 — — R i = 0.92 hr ⋅ ft 2 ⋅ ∘ F/Btu R_i = 0.92\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu} R i ​ = 0.92 hr ⋅ ft 2 ⋅ ∘ F/Btu

2. Thermal Bridging & Parallel Heat Flow in Framed Assemblies

Framed envelope assemblies (wood studs, light-gauge steel studs, metal curtain wall mullions) contain high-conductivity structural framing that bridges the low-conductivity cavity insulation. This requires calculating an area-weighted parallel heat flow path. +-----------------------------------------------------------------------------------------+

  • | PARALLEL HEAT PATHS THROUGH FRAMED WALL CAVITY |
  • +-----------------------------------------------------------------------------------------+
  • | Path 1 (Through Stud / Framing): R_path1 = R_i + R_gyp + R_stud + R_sheath + R_o |
  • | Path 2 (Through Insulated Cavity): R_path2 = R_i + R_gyp + R_cavity + R_sheath + R_o |
  • | Area-Weighted Overall U-factor: U_overall = (f_frame * U_path1) + (f_cav * U_path2)|
  • +-----------------------------------------------------------------------------------------+

Area-Weighted Parallel Path Equation U overall = f framing ⋅ U framing + ( 1 − f framing ) ⋅ U cavity = f framing R framing + 1 − f framing R cavity U_{\text{overall}} = f_{\text{framing}} \cdot U_{\text{framing}} + (1 - f_{\text{framing}}) \cdot U_{\text{cavity}} = \frac{f_{\text{framing}}}{R_{\text{framing}}} + \frac{1 - f_{\text{framing}}}{R_{\text{cavity}}} U overall ​ = f framing ​ ⋅ U framing ​ + ( 1 − f framing ​ ) ⋅ U cavity ​ = R framing ​ f framing ​ ​ + R cavity ​ 1 − f framing ​ ​

Where f framing f_{\text{framing}} f framing ​ is the framing fraction (typically 0.15 to 0.25 0.15\text{ to }0.25 0.15 to 0.25 for wood framing at 16 in. 16\text{ in.} 16 in. or 24 in. 24\text{ in.} 24 in. on center, and 0.10 to 0.18 0.10\text{ to }0.18 0.10 to 0.18 for steel stud construction).

Steel Stud Thermal Derating (Modified Zone Method / ASHRAE 90.1)

Steel has a thermal conductivity ( k ≈ 314 Btu ⋅ in./(hr ⋅ ft 2 ⋅ ∘ F) k \approx 314\text{ Btu}\cdot\text{in./(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)} k ≈ 314 Btu ⋅ in./(hr ⋅ ft 2 ⋅ ∘ F) ) over 300 times greater than fiberglass batt insulation ( k ≈ 0.27 k \approx 0.27 k ≈ 0.27 ). Steel studs act as massive thermal shorts, derating cavity insulation effectiveness by 40% to 60% . ASHRAE Standard 90.1 provides effective cavity R R R -values ( R effective R_{\text{effective}} R effective ​ ):

Nominal Cavity Batt Rating Steel Stud Size & Spacing Effective Cavity R R R -Value ( R effective R_{\text{effective}} R effective ​ ) Framing Derating Factor

R-11 2 × 4 (3.5 in.) @ 16 in. OC 2\times 4\text{ (3.5 in.) @ 16 in. OC} 2 × 4 (3.5 in.) @ 16 in. OC R - 5.5 R\text{-}5.5 R - 5.5 50 % 50\% 50%

R-13 2 × 4 (3.5 in.) @ 16 in. OC 2\times 4\text{ (3.5 in.) @ 16 in. OC} 2 × 4 (3.5 in.) @ 16 in. OC R - 6.0 R\text{-}6.0 R - 6.0 46 % 46\% 46%

R-19 2 × 6 (5.5 in.) @ 16 in. OC 2\times 6\text{ (5.5 in.) @ 16 in. OC} 2 × 6 (5.5 in.) @ 16 in. OC R - 7.1 R\text{-}7.1 R - 7.1 37 % 37\% 37%

R-21 2 × 6 (5.5 in.) @ 16 in. OC 2\times 6\text{ (5.5 in.) @ 16 in. OC} 2 × 6 (5.5 in.) @ 16 in. OC R - 7.4 R\text{-}7.4 R - 7.4 35 % 35\% 35%

R-19 2 × 6 (5.5 in.) @ 24 in. OC 2\times 6\text{ (5.5 in.) @ 24 in. OC} 2 × 6 (5.5 in.) @ 24 in. OC R - 8.6 R\text{-}8.6 R - 8.6 45 % 45\% 45%

Design Rule: To meet modern energy codes (ASHRAE Standard 90.1 / IECC), steel-framed walls require continuous exterior insulation (ci) (such as rigid polyisocyanurate or extruded polystyrene) to break the framing thermal bridge.

3. Below-Grade Envelopes & Slab-on-Grade Heat Losses

Heat transfer from basements and on-grade concrete slabs does not follow simple 1D one-layer equations because ground temperature varies with depth and thermal path length through the earth increases radially. +-----------------------------------------------------------------------------------------+

  • | SLAB-ON-GRADE PERIMETER HEAT FLOW DYNAMICS |
  • +-----------------------------------------------------------------------------------------+
  • | Indoor Space (Ti) |
  • | ============================= |
  • | | Concrete Slab Floor | |
  • | Outside | | Perimeter Length P (ft) |
  • | Air (To) +---------------------------+ |
  • | ~~~~~~~~~ | Perimeter Insulation (R) | |
  • | | +---------------------------+ ===> q = F_p * P * (T_in - T_out) |
  • | | | Ground Heat Paths |
  • | +--------------+ (Curvilinear Earth Flow) |
  • +-----------------------------------------------------------------------------------------+
  • 1. Slab-on-Grade Perimeter Heat Loss Formulation

Concrete slab-on-grade heat loss occurs almost entirely around the exposed perimeter. Sizing is based on the perimeter heat loss coefficient ( F p F_p F p ​ ) and slab perimeter length ( P P P ): q slab = F p ⋅ P ⋅ ( T indoor − T outdoor ) q_{\text{slab}} = F_p \cdot P \cdot (T_{\text{indoor}} - T_{\text{outdoor}}) q slab ​ = F p ​ ⋅ P ⋅ ( T indoor ​ − T outdoor ​ )

Where:

q slab = Slab heating transmission rate ( Btu/hr ) q_{\text{slab}} = \text{Slab heating transmission rate } (\text{Btu/hr}) q slab ​ = Slab heating transmission rate ( Btu/hr )

F p = Perimeter heat loss coefficient ( Btu/(hr ⋅ ft ⋅ ∘ F) ) F_p = \text{Perimeter heat loss coefficient } (\text{Btu/(hr}\cdot\text{ft}\cdot{}^\circ\text{F)}) F p ​ = Perimeter heat loss coefficient ( Btu/(hr ⋅ ft ⋅ ∘ F) )

P = Exposed perimeter length of the slab floor ( ft ) P = \text{Exposed perimeter length of the slab floor } (\text{ft}) P = Exposed perimeter length of the slab floor ( ft )

T indoor − T outdoor = Design dry-bulb temperature difference ( ∘ F ) T_{\text{indoor}} - T_{\text{outdoor}} = \text{Design dry-bulb temperature difference } ({}^\circ\text{F}) T indoor ​ − T outdoor ​ = Design dry-bulb temperature difference ( ∘ F )

Standard F p F_p F p ​ Perimeter Loss Coefficients (ASHRAE 90.1)

Slab Edge Insulation Configuration Unheated Slab F p [Btu/(hr ⋅ ft ⋅ ∘ F)] F_p\text{ [Btu/(hr}\cdot\text{ft}\cdot{}^\circ\text{F)]} F p ​ [Btu/(hr ⋅ ft ⋅ ∘ F)] Heated Slab F p [Btu/(hr ⋅ ft ⋅ ∘ F)] F_p\text{ [Btu/(hr}\cdot\text{ft}\cdot{}^\circ\text{F)]} F p ​ [Btu/(hr ⋅ ft ⋅ ∘ F)]

  • Uninsulated Slab 0.73 0.73 0.73 1.35 1.35 1.35
  • R-5 Perimeter Insulation ( 12 in. 12\text{ in.} 12 in. depth) 0.57 0.57 0.57 0.85 0.85 0.85
  • R-10 Perimeter Insulation ( 24 in. 24\text{ in.} 24 in. depth) 0.54 0.54 0.54 0.78 0.78 0.78
  • R-15 Perimeter Insulation ( 24 in. 24\text{ in.} 24 in. depth) 0.52 0.52 0.52 0.74 0.74 0.74
  • R-20 Fully Insulated Under Slab & Edge 0.46 0.46 0.46 0.62 0.62 0.62
  • 2. Below-Grade Basement Walls & Floors

Below-grade heat transfer is evaluated using depth-averaged U U U -factors ( U avg U_{\text{avg}} U avg ​ ) applied to below-grade wall area ( A bg A_{\text{bg}} A bg ​ ) against ground temperature ( T ground T_{\text{ground}} T ground ​ ): q basement, wall = U bg, wall ⋅ A bg, wall ⋅ ( T indoor − T ground ) q_{\text{basement, wall}} = U_{\text{bg, wall}} \cdot A_{\text{bg, wall}} \cdot (T_{\text{indoor}} - T_{\text{ground}}) q basement, wall ​ = U bg, wall ​ ⋅ A bg, wall ​ ⋅ ( T indoor ​ − T ground ​ ) q basement, floor = U bg, floor ⋅ A floor ⋅ ( T indoor − T ground ) q_{\text{basement, floor}} = U_{\text{bg, floor}} \cdot A_{\text{floor}} \cdot (T_{\text{indoor}} - T_{\text{ground}}) q basement, floor ​ = U bg, floor ​ ⋅ A floor ​ ⋅ ( T indoor ​ − T ground ​ )

4. Infiltration & Exfiltration Load Methodologies

Infiltration is the uncontrolled ingress of outdoor air through cracks, gaps, building envelope joints, and door openings. Exfiltration is the corresponding egress of conditioned air.

Driving Physical Forces for Infiltration

Wind Pressure (Velocity Head): Δ P wind = C p ⋅ ρ air ⋅ V wind 2 2 g c \Delta P_{\text{wind}} = C_p \cdot \frac{\rho_{\text{air}} \cdot V_{\text{wind}}^2}{2 g_c} Δ P wind ​ = C p ​ ⋅ 2 g c ​ ρ air ​ ⋅ V wind 2 ​ ​ Wind creates positive pressure on the windward facade (causing infiltration) and negative suction pressure on the leeward and sidewall facades (causing exfiltration).

Stack Effect (Thermal Buoyancy): Δ P stack = ρ 0 ( g g c ) h ( T indoor − T outdoor T outdoor ) \Delta P_{\text{stack}} = \rho_0 \left(\frac{g}{g_c}\right) h \left(\frac{T_{\text{indoor}} - T_{\text{outdoor}}}{T_{\text{outdoor}}}\right) Δ P stack ​ = ρ 0 ​ ( g c ​ g ​ ) h ( T outdoor ​ T indoor ​ − T outdoor ​ ​ ) During winter ( T indoor > T outdoor T_{\text{indoor}} > T_{\text{outdoor}} T indoor ​ > T outdoor ​ ), warm air rises inside the building, creating negative pressure and infiltration at the ground level, and positive pressure and exfiltration at upper levels. The height where internal and external pressures equalize is the Neutral Pressure Level (NPL) .

Mechanical Imbalance: Exhaust air flow in excess of supply/ventilation air creates net negative building pressure, accelerating infiltration. +-----------------------------------------------------------------------------------------+

  • | WINTER STACK EFFECT & INFILTRATION PRESSURE PROFILE |
  • +-----------------------------------------------------------------------------------------+
  • | Top of Building (Z = H): P_in > P_out --> EXFILTRATION (Positive Pressure) |
  • | | |
  • | Neutral Pressure Level (NPL): P_in = P_out --> ZERO FLOW |
  • | | |
  • | Base of Building (Z = 0): P_in < P_out --> INFILTRATION (Negative Suction) |
  • +-----------------------------------------------------------------------------------------+
  • Infiltration Volumetric Airflow Calculation Methods
  • 1. Air Change Method

Used widely for general commercial and residential room load estimation: CFM inf = ACH × Volume ( ft 3 ) 60 min/hr \text{CFM}_{\text{inf}} = \frac{\text{ACH} \times \text{Volume }(\text{ft}^3)}{60\text{ min/hr}} CFM inf ​ = 60 min/hr ACH × Volume ( ft 3 ) ​

Where ACH \text{ACH} ACH is Air Changes per Hour ( 0.1 to 0.3 ACH 0.1\text{ to }0.3\text{ ACH} 0.1 to 0.3 ACH for tight commercial construction; 0.5 to 1.0 ACH 0.5\text{ to }1.0\text{ ACH} 0.5 to 1.0 ACH for loose/older construction).

2. Crack Length Method

Based on fluid flow through window and door perimeter gaps: CFM inf = K ⋅ L ⋅ ( Δ P ) n \text{CFM}_{\text{inf}} = K \cdot L \cdot (\Delta P)^n CFM inf ​ = K ⋅ L ⋅ ( Δ P ) n

Where L L L is total crack length in feet, K K K is crack flow coefficient, and n n n is flow exponent ( 0.5 ≤ n ≤ 0.7 0.5 \le n \le 0.7 0.5 ≤ n ≤ 0.7 ).

5. Infiltration Heating & Cooling Load Synthesis

Infiltration air enters directly into the occupied space without passing through the central cooling/heating coil. It must be treated as a direct room sensible and latent load. +-----------------------------------------------------------------------------------------+

  • | INFILTRATION PSYCHROMETRIC LOAD EQUATIONS (STANDARD SEA-LEVEL AIR) |
  • +-----------------------------------------------------------------------------------------+
  • | Sensible Load: q_s = 1.08 * CFM_inf * (T_outdoor - T_indoor) |
  • | Latent Load: q_l = 4840 * CFM_inf * (W_outdoor - W_indoor) |
  • | Total Load: q_t = 4.5 * CFM_inf * (h_outdoor - h_indoor) |
  • +-----------------------------------------------------------------------------------------+

Winter Heating Infiltration: Both Δ T = ( T o − T i ) \Delta T = (T_o - T_i) Δ T = ( T o ​ − T i ​ ) and Δ W = ( W o − W i ) \Delta W = (W_o - W_i) Δ W = ( W o ​ − W i ​ ) are negative, imposing direct sensible and humidification (latent) heating loads on the zone terminal units.

Summer Cooling Infiltration: Hot, humid air entering the room adds to the zone Sensible Heat Ratio (RSHR) and requires coil dehumidification.

6. NCEES Reference Handbook Navigation Tactics

Envelope Transmission Formulas: Search "Thermal Resistance" or "Heat Transmission" to find steady-state conduction formulas ( U = 1 / R total U = 1/R_{\text{total}} U = 1/ R total ​ ) and typical material thermal conductivity ( k k k ) tables.

Slab-on-Grade Coefficients: Search "Slab-on-Grade" or "F_p" to locate the perimeter heat loss formula and coefficient table.

Air Change Method: Search "Infiltration" or "Air Changes" to locate air change rate tables and conversion formulas.

  • 7. Worked Computational Examples
  • Example 1: Multilayer Steel-Stud Wall U-Factor with Thermal Bridging

An exterior wall assembly consists of the following series layers from outside to inside:

Exterior air film ( R o = 0.17 hr ⋅ ft 2 ⋅ ∘ F/Btu R_o = 0.17\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu} R o ​ = 0.17 hr ⋅ ft 2 ⋅ ∘ F/Btu )

4-inch face brick ( k = 9.0 Btu ⋅ in./(hr ⋅ ft 2 ⋅ ∘ F) k = 9.0\text{ Btu}\cdot\text{in./(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)} k = 9.0 Btu ⋅ in./(hr ⋅ ft 2 ⋅ ∘ F) , R 1 = 4 / 9.0 = 0.44 hr ⋅ ft 2 ⋅ ∘ F/Btu R_1 = 4 / 9.0 = 0.44\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu} R 1 ​ = 4/9.0 = 0.44 hr ⋅ ft 2 ⋅ ∘ F/Btu )

1-inch continuous extruded polystyrene (XPS) rigid board ( R 2 = 5.00 hr ⋅ ft 2 ⋅ ∘ F/Btu R_2 = 5.00\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu} R 2 ​ = 5.00 hr ⋅ ft 2 ⋅ ∘ F/Btu )

5/8-inch exterior gypsum sheathing ( R 3 = 0.56 hr ⋅ ft 2 ⋅ ∘ F/Btu R_3 = 0.56\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu} R 3 ​ = 0.56 hr ⋅ ft 2 ⋅ ∘ F/Btu )

2 × 6 2\times 6 2 × 6 light-gauge steel studs at 16 in. 16\text{ in.} 16 in. on center with nominal R-19 fiberglass batt cavity insulation. Per ASHRAE Standard 90.1, the effective cavity resistance is R effective = 7.10 hr ⋅ ft 2 ⋅ ∘ F/Btu R_{\text{effective}} = 7.10\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu} R effective ​ = 7.10 hr ⋅ ft 2 ⋅ ∘ F/Btu .

5/8-inch interior gypsum wallboard ( R 4 = 0.56 hr ⋅ ft 2 ⋅ ∘ F/Btu R_4 = 0.56\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu} R 4 ​ = 0.56 hr ⋅ ft 2 ⋅ ∘ F/Btu )

Interior air film ( R i = 0.68 hr ⋅ ft 2 ⋅ ∘ F/Btu R_i = 0.68\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu} R i ​ = 0.68 hr ⋅ ft 2 ⋅ ∘ F/Btu )

Calculate: (a) The overall assembly U U U -factor with thermal bridging, and (b) The total winter heat loss through a 3 , 000 ft 2 3,000\text{ ft}^2 3 , 000 ft 2 wall if T indoor = 70 ∘ F T_{\text{indoor}} = 70^\circ\text{F} T indoor ​ = 7 0 ∘ F and T outdoor = 10 ∘ F T_{\text{outdoor}} = 10^\circ\text{F} T outdoor ​ = 1 0 ∘ F .

Solution:

Sum all series resistances using the derated effective cavity resistance: R total = R o + R 1 + R 2 + R 3 + R effective + R 4 + R i R_{\text{total}} = R_o + R_1 + R_2 + R_3 + R_{\text{effective}} + R_4 + R_i R total ​ = R o ​ + R 1 ​ + R 2 ​ + R 3 ​ + R effective ​ + R 4 ​ + R i ​ R total = 0.17 + 0.44 + 5.00 + 0.56 + 7.10 + 0.56 + 0.68 = 14.51 hr ⋅ ft 2 ⋅ ∘ F/Btu R_{\text{total}} = 0.17 + 0.44 + 5.00 + 0.56 + 7.10 + 0.56 + 0.68 = 14.51\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu} R total ​ = 0.17 + 0.44 + 5.00 + 0.56 + 7.10 + 0.56 + 0.68 = 14.51 hr ⋅ ft 2 ⋅ ∘ F/Btu

Calculate overall U U U -factor: U = 1 R total = 1 14.51 = 0.0689 Btu/(hr ⋅ ft 2 ⋅ ∘ F) U = \frac{1}{R_{\text{total}}} = \frac{1}{14.51} = 0.0689\text{ Btu/(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)} U = R total ​ 1 ​ = 14.51 1 ​ = 0.0689 Btu/(hr ⋅ ft 2 ⋅ ∘ F)

Calculate total winter steady-state transmission heat loss: Δ T = 70 − 10 = 60 ∘ F \Delta T = 70 - 10 = 60^\circ\text{F} Δ T = 70 − 10 = 6 0 ∘ F q = U ⋅ A ⋅ Δ T = 0.0689 × 3 , 000 ft 2 × 60 ∘ F = 12 , 402 Btu/hr q = U \cdot A \cdot \Delta T = 0.0689 \times 3,000\text{ ft}^2 \times 60^\circ\text{F} = 12,402\text{ Btu/hr} q = U ⋅ A ⋅ Δ T = 0.0689 × 3 , 000 ft 2 × 6 0 ∘ F = 12 , 402 Btu/hr

(Note: If thermal bridging were ignored and nominal R-19 were used without derating, R total = 26.41 R_{\text{total}} = 26.41 R total ​ = 26.41 , giving q = 6 , 815 Btu/hr q = 6,815\text{ Btu/hr} q = 6 , 815 Btu/hr —an underestimation of 45%!)

Example 2: Infiltration & Slab-on-Grade Combined Heating Load

A standalone commercial building in Columbus, OH has the following characteristics:

Building floor plan: 100 ft × 60 ft 100\text{ ft} \times 60\text{ ft} 100 ft × 60 ft rectangle ( A floor = 6 , 000 ft 2 A_{\text{floor}} = 6,000\text{ ft}^2 A floor ​ = 6 , 000 ft 2 , ceiling height 12 ft 12\text{ ft} 12 ft ).

Unheated concrete slab-on-grade floor with R-10 perimeter insulation ( F p = 0.54 Btu/(hr ⋅ ft ⋅ ∘ F) F_p = 0.54\text{ Btu/(hr}\cdot\text{ft}\cdot{}^\circ\text{F)} F p ​ = 0.54 Btu/(hr ⋅ ft ⋅ ∘ F) ).

Infiltration rate: 0.35 ACH 0.35\text{ ACH} 0.35 ACH .

Indoor winter design conditions: 70 ∘ F 70^\circ\text{F} 7 0 ∘ F DB, 30 % RH 30\%\text{ RH} 30% RH ( W i = 0.00470 lb w / lb d a W_i = 0.00470\text{ lb}_w/\text{lb}_{da} W i ​ = 0.00470 lb w ​ / lb d a ​ ).

Outdoor winter design conditions (99.6%): 2 ∘ F 2^\circ\text{F} 2 ∘ F DB, 80 % RH 80\%\text{ RH} 80% RH ( W o = 0.00085 lb w / lb d a W_o = 0.00085\text{ lb}_w/\text{lb}_{da} W o ​ = 0.00085 lb w ​ / lb d a ​ ).

Calculate: (a) The perimeter slab-on-grade heat loss, (b) Infiltration volumetric airflow, (c) Infiltration sensible heating load, and (d) Infiltration humidification (latent) heating load.

Solution:

Slab-on-grade perimeter heat loss: P = 2 × ( 100 + 60 ) = 320 ft P = 2 \times (100 + 60) = 320\text{ ft} P = 2 × ( 100 + 60 ) = 320 ft Δ T = 70 − 2 = 68 ∘ F \Delta T = 70 - 2 = 68^\circ\text{F} Δ T = 70 − 2 = 6 8 ∘ F q slab = F p ⋅ P ⋅ Δ T = 0.54 × 320 × 68 = 11 , 750.4 Btu/hr q_{\text{slab}} = F_p \cdot P \cdot \Delta T = 0.54 \times 320 \times 68 = 11,750.4\text{ Btu/hr} q slab ​ = F p ​ ⋅ P ⋅ Δ T = 0.54 × 320 × 68 = 11 , 750.4 Btu/hr

Infiltration volumetric airflow: Volume = 6 , 000 ft 2 × 12 ft = 72 , 000 ft 3 \text{Volume } = 6,000\text{ ft}^2 \times 12\text{ ft} = 72,000\text{ ft}^3 Volume = 6 , 000 ft 2 × 12 ft = 72 , 000 ft 3 CFM inf = 0.35 × 72 , 000 ft 3 60 min/hr = 420 CFM \text{CFM}_{\text{inf}} = \frac{0.35 \times 72,000\text{ ft}^3}{60\text{ min/hr}} = 420\text{ CFM} CFM inf ​ = 60 min/hr 0.35 × 72 , 000 ft 3 ​ = 420 CFM

Infiltration sensible heating load: q s , inf = 1.08 × CFM inf × ( T i − T o ) = 1.08 × 420 × 68 = 30 , 844.8 Btu/hr q_{s,\text{inf}} = 1.08 \times \text{CFM}_{\text{inf}} \times (T_i - T_o) = 1.08 \times 420 \times 68 = 30,844.8\text{ Btu/hr} q s , inf ​ = 1.08 × CFM inf ​ × ( T i ​ − T o ​ ) = 1.08 × 420 × 68 = 30 , 844.8 Btu/hr

Infiltration latent (humidification) heating load: Δ W = 0.00470 − 0.00085 = 0.00385 lb w / lb d a \Delta W = 0.00470 - 0.00085 = 0.00385\text{ lb}_w/\text{lb}_{da} Δ W = 0.00470 − 0.00085 = 0.00385 lb w ​ / lb d a ​ q l , inf = 4840 × CFM inf × Δ W = 4840 × 420 × 0.00385 = 7 , 826.3 Btu/hr q_{l,\text{inf}} = 4840 \times \text{CFM}_{\text{inf}} \times \Delta W = 4840 \times 420 \times 0.00385 = 7,826.3\text{ Btu/hr} q l , inf ​ = 4840 × CFM inf ​ × Δ W = 4840 × 420 × 0.00385 = 7 , 826.3 Btu/hr

Total combined zone heating load from slab edge and infiltration: q total = 11 , 750.4 + 30 , 844.8 + 7 , 826.3 = 50 , 421.5 Btu/hr = 50.42 MBH q_{\text{total}} = 11,750.4 + 30,844.8 + 7,826.3 = 50,421.5\text{ Btu/hr} = 50.42\text{ MBH} q total ​ = 11 , 750.4 + 30 , 844.8 + 7 , 826.3 = 50 , 421.5 Btu/hr = 50.42 MBH