6.4 Internal Heat Gains: Lighting, People, Equipment & Diversity Factors
PE Mechanical: HVAC and Refrigeration Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview, Reference Handbook & Engineering Foundations
1.1 NCEES Exam Specification, CBT Delivery & Reference Handbook Strategy 1.2 Engineering Units, Dimensional Analysis & Physical Property Lookups 1.3 Engineering Economics, Life Cycle Cost Analysis & Equipment Financial Evaluation 1.4 Electrical Foundations, Motor Ratings & Variable Frequency Drives (VFDs)
2 Chapter 2: Thermodynamics & Energy Balances
2.1 First and Second Laws of Thermodynamics & Open/Closed System Energy Balances 2.2 Thermodynamic Cycles: Carnot, Rankine, Brayton & Reversed Carnot Limit 2.3 Gas & Vapor Property Evaluation: Steam Tables, Superheat & Subcooling 2.4 Mass, Energy & Combustion Balances for HVAC Equipment
3 Chapter 3: Psychrometrics, Moist Air Processes & Humidity Equipment
3.1 Psychrometric Properties: DBT, WBT, DPT, RH, Humidity Ratio & Enthalpy 3.2 Chart Reading & Psychrometric Equations at Sea Level vs. Altitude (5,000 ft) 3.3 Basic Psychrometric Processes: Sensible Heating/Cooling, Humidification & Dehumidification 3.4 Mixed Air Calculations & Complex Air Conditioning Cycles (Preheat, Reheat & Bypass) 3.5 Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP) & Coil Bypass Factor 3.6 Humidification & Dehumidification Equipment: Steam, Adiabatic, Desiccant & Low-Temperature Processes
4 Chapter 4: Heat Transfer Principles & Sizing
4.1 Steady-State Conduction & Multilayer Thermal Resistance (R-Value & U-Factor) 4.2 Convective Heat Transfer & Forced/Natural Convection Coefficients 4.3 Radiation Heat Transfer, Surface Emissivity & View Factors 4.4 Overall Heat Transfer Coefficients, Fouling Factors & Transient/Thermal Mass Effects 4.5 Heat Exchanger Analysis: Log Mean Temperature Difference (LMTD) & Effectiveness-NTU (ε-NTU)
5 Chapter 5: Fluid Mechanics & Hydraulic Fundamentals
5.1 Fluid Statics, Incompressible Continuity & Bernoulli Energy Equation 5.2 Pipe Friction, Moody Diagram & Darcy-Weisbach / Hazen-Williams Calculations 5.3 Minor Losses: Equivalent Length, Loss Coefficients (K-factors) & Total System Head 5.4 Pump Sizing, Net Positive Suction Head (NPSHa vs NPSHr) & Cavitation Prevention 5.5 Affinity Laws & Parallel/Series Pump/Fan System Curves
6 Chapter 6: Heating & Cooling Load Calculations
6.1 Outdoor & Indoor Design Conditions (ASHRAE Fundamentals, Climatic Data & Indoor Setpoints) 6.2 Envelope Heat Transmission & Infiltration/Exfiltration Load Methods 6.3 Solar Heat Gain (SHGC), Fenestration & Cooling Load Temperature Difference / Radiant Time Series (CLTD/RTS) 6.4 Internal Heat Gains: Lighting, People, Equipment & Diversity Factors 6.5 Ventilation Loads & Sensible / Latent / Total Cooling Load Synthesis
7 Chapter 7: Refrigeration Principles, Cycles & Cold Storage Applications
7.1 Standard Vapor-Compression Refrigeration Cycle on P-h & T-s Diagrams 7.2 Refrigeration Cycle Performance Metrics: COP, EER, SEER, kW/ton & Ton of Refrigeration 7.3 Cycle Enhancements: Subcooling, Superheating, Liquid-Suction Heat Exchangers & Economizers 7.4 Multi-Stage & Cascade Refrigeration Systems: Intercooling & Flash Gas Removal 7.5 Absorption Refrigeration Cycles: Water-Lithium Bromide & Ammonia-Water Systems 7.6 Food Processing & Cold Storage Refrigeration: Product Load, Pull-Down & Storage Design
8 Chapter 8: Refrigerants, Environmental Regulations & Safety
8.1 Refrigerant Classifications, Nomenclature & Thermodynamic Properties (ASHRAE Standard 34) 8.2 AIM Act, EPA Technology Transitions Sector GWP Limits & Low-GWP Refrigerants (R-32, R-454B) 8.3 Refrigerant Safety Requirements & Machinery Room Design (ASHRAE Standard 15) 8.4 Refrigerant Piping Sizing, Oil Return, Traps & Double Risers
9 Chapter 9: HVAC Equipment & Primary Machinery
9.1 Compressors: Reciprocating, Rotary, Scroll, Screw & Centrifugal 9.2 Condensers: Air-Cooled, Water-Cooled & Evaporative Condensers 9.3 Evaporators & Direct Expansion (DX) vs Liquid Chilling Coils 9.4 Water Chillers: Centrifugal, Screw & Scroll with ASHRAE 90.1 Path A/B IPLV Ratings 9.5 Cooling Towers: Range, Approach, Evaporation, Blowdown & Legionella Control 9.6 Heat Pumps & Variable Refrigerant Flow (VRF): Balance Point, Defrost & Heat Recovery 9.7 Thermal Energy Storage: Full vs. Partial Storage, Chilled Water & Ice Systems
10 Chapter 10: Air-Side Systems & Distribution
10.1 Air Handling Units (AHUs), Dedicated Outdoor Air Systems (DOAS) & Fan-Coil Units 10.2 Duct Design Methodologies: Equal Friction, Static Regain & Velocity Reduction 10.3 Duct Fittings, Dynamic Pressure Losses & SMACNA Construction Standards 10.4 Fan Types, Performance Curves, System Effect Factors & Surge/Stall Dynamics 10.5 Variable Air Volume (VAV) Systems, Terminal Boxes & Space Air Diffusion (ADPI) 10.6 Cooling & Heating Coil Selection: Face Velocity, Rows, Circuiting & Freeze Protection
11 Chapter 11: Hydronic, Steam & Fuel Distribution and Heating Plant
11.1 Hydronic System Architectures: Primary-Only, Primary-Secondary & Variable Primary Flow (VPF) 11.2 Hydronic Pipe Sizing, Velocity Limits & Closed/Open Expansion Tank Sizing 11.3 Control Valves: 2-Way vs 3-Way, Valve Authority (N), Cv Calculations & Characteristic Curves 11.4 Boilers & Heating Hot Water Systems: Condensing vs Non-Condensing & Water Treatment 11.5 Furnaces & Gas-Fired Heating Equipment: AFUE, Temperature Rise, Combustion Air & Vent Categories 11.6 Steam & Condensate Distribution: Latent Heat, Trap Selection, Flash Steam & Stall 11.7 Fuel Gas & Fuel Oil Piping: Demand, Sizing Method, Pressure Drop & Storage Systems
12 Chapter 12: HVAC Control Concepts, Sensors & Sequences
12.1 Sensors, Actuators & Dampers: Selection, Placement, Fail-Safe Position & Damper Authority 12.2 Control Loops: Proportional Offset, PID Action, Reset Strategies & Standard Sequences
13 Chapter 13: Building Energy, Ventilation & Indoor Environmental Quality Codes
13.1 ASHRAE Standard 62.1: Ventilation Rate Procedure (VRP), Indoor Air Quality Procedure & DCV 13.2 ASHRAE Standard 90.1: Building Energy Envelope, Mechanical Efficiency & Economizer Mandates 13.3 ASHRAE Standard 55: Thermal Environmental Conditions, PMV/PPD & Adaptive Comfort Models 13.4 Energy Recovery Systems: Enthalpy Wheels, Fixed-Plate Exchangers, Heat Pipes & Runaround Loops
14 Chapter 14: Supportive Engineering Knowledge, Life Safety & Operations
14.1 Air Filtration Standards: MERV Ratings (ASHRAE 52.2), HEPA & Gas-Phase Adsorption 14.2 Life Safety Systems: Fire/Smoke Dampers, Stairwell Pressurization (NFPA 92) & Smoke Control (NFPA 90A) 14.3 Acoustical Control & Vibration Isolation in HVAC Systems (NC / RC Criteria)
6.4 Internal Heat Gains: Lighting, People, Equipment & Diversity Factors
Key Takeaways Explain This Topic AI
Internal heat gains from occupants, electric lighting, office equipment, and motors constitute the baseline year-round sensible and latent cooling loads in commercial buildings.
Occupant heat dissipation splits into sensible and latent components based on metabolic activity (met) and space temperature: moderate office work produces ~250 Btu/hr sensible and ~250 Btu/hr latent (500 Btu/hr total per person).
Electric lighting generates heat at 3.412 Btu/(hr·W), with recessed plenum fixtures discharging 20% to 30% of their heat directly into the return air plenum rather than the conditioned room space.
Electric motor heat generation depends on motor location and driven machine location: when both are inside the space, q = (hp * 2545) / eta; when only the motor is in the space, q = hp * 2545 * (1 - eta) / eta; when only the driven load is in the space, q = hp * 2545.
Diversity factors account for the non-coincidence of peak occupant density, lighting usage, and plug loads, allowing central chiller and primary equipment sizing to be smaller than the sum of individual zone peak loads.
Last updated: August 2026
6.4 Internal Heat Gains: Lighting, People, Equipment & Diversity Factors
In modern energy-efficient commercial buildings with highly insulated building envelopes and high-performance glazing, internal heat gains frequently dominate the total cooling load. Internal heat gains originate from four primary sources: building occupants, electric lighting fixtures, office and process plug load equipment, and electric motors/machinery. Unlike external weather loads that reverse direction between summer and winter, internal heat gains generate continuous cooling loads during all occupied hours, reducing winter heating demand while increasing year-round cooling coil loads.
1. Occupant Heat Gain (People)
Human beings generate heat through biological metabolism. Heat is released to the surrounding environment through four simultaneous thermodynamic pathways:
Convection: Heat transfer from skin and clothing to ambient air (Sensible).
Radiation: Longwave radiant heat transfer from outer surface clothing/skin to cooler surrounding room surfaces (Sensible).
Evaporation (Sweating & Respiration): Moisture vapor release from skin and breathing exhalation (Latent phase change: h f g ≈ 1050 Btu/lb h_{fg} \approx 1050\text{ Btu/lb} h f g ≈ 1050 Btu/lb ).
Conduction: Direct physical contact with furniture/flooring (Sensible, negligible). +-----------------------------------------------------------------------------------------+
- | HUMAN THERMAL DISSIPATION PATHWAYS |
- +-----------------------------------------------------------------------------------------+
- | Total Metabolic Rate (M) = Sensible Heat (Convection + Radiation) + Latent Heat (Evap) |
- | |
- | Space DB Effect: At 70°F -> 70% Sensible / 30% Latent |
- | At 75°F -> 50% Sensible / 50% Latent (Standard Office Design) |
- | At 80°F -> 30% Sensible / 70% Latent (Sweating Dominates) |
- +-----------------------------------------------------------------------------------------+
- ASHRAE Standard Occupant Heat Output Table (at 75 ∘ F 75^\circ\text{F} 7 5 ∘ F Indoor Dry-Bulb)
Activity Level & Application Typical Application Total Heat ( q t q_t q t , Btu/hr \text{Btu/hr} Btu/hr ) Sensible Heat ( q s q_s q s , Btu/hr \text{Btu/hr} Btu/hr ) Latent Heat ( q l q_l q l , Btu/hr \text{Btu/hr} Btu/hr ) Metabolic Rate (met)
Seated at Rest Theater, Auditorium, Cinema 350 350 350 210 210 210 140 140 140 0.9 to 1.0 0.9\text{ to }1.0 0.9 to 1.0
Seated, Very Light Work Executive Office, Control Room 400 400 400 230 230 230 170 170 170 1.1 1.1 1.1
Moderate Office Work General Office, Classrooms 450 to 500 450\text{ to }500 450 to 500 250 250 250 200 to 250 200\text{ to }250 200 to 250 1.2 to 1.4 1.2\text{ to }1.4 1.2 to 1.4
Standing, Light Work / Walking Retail Store, Bank, Supermarket 550 550 550 275 275 275 275 275 275 1.5 to 1.7 1.5\text{ to }1.7 1.5 to 1.7
Light Industrial / Assembly Manufacturing Plant, Workshop 750 750 750 375 375 375 375 375 375 2.0 to 2.2 2.0\text{ to }2.2 2.0 to 2.2
Heavy Work / Athletics Gymnasium, Fitness Center 1 , 500 1,500 1 , 500 500 500 500 1 , 000 1,000 1 , 000 4.0 to 5.0 4.0\text{ to }5.0 4.0 to 5.0
Occupant Cooling Load Calculation Formulation q people, sensible = N ⋅ q s , person ⋅ F D ⋅ CLF people q_{\text{people, sensible}} = N \cdot q_{s,\text{person}} \cdot F_D \cdot \text{CLF}_{\text{people}} q people, sensible = N ⋅ q s , person ⋅ F D ⋅ CLF people q people, latent = N ⋅ q l , person ⋅ F D q_{\text{people, latent}} = N \cdot q_{l,\text{person}} \cdot F_D q people, latent = N ⋅ q l , person ⋅ F D
Where:
N = Number of occupants in the space N = \text{Number of occupants in the space} N = Number of occupants in the space
q s , person , q l , person = Sensible and latent heat dissipation rates per person ( Btu/hr ) q_{s,\text{person}}, q_{l,\text{person}} = \text{Sensible and latent heat dissipation rates per person } (\text{Btu/hr}) q s , person , q l , person = Sensible and latent heat dissipation rates per person ( Btu/hr )
F D = Occupant Diversity Factor ( 0.7 to 1.0 ) F_D = \text{Occupant Diversity Factor } (0.7\text{ to }1.0) F D = Occupant Diversity Factor ( 0.7 to 1.0 )
CLF people = Cooling Load Factor for people (accounts for radiant thermal storage, ≈ 1.0 for 24-hr operation) \text{CLF}_{\text{people}} = \text{Cooling Load Factor for people (accounts for radiant thermal storage, } \approx 1.0\text{ for 24-hr operation)} CLF people = Cooling Load Factor for people (accounts for radiant thermal storage, ≈ 1.0 for 24-hr operation)
2. Electric Lighting Heat Gains
All electrical energy supplied to interior lighting fixtures is ultimately converted entirely into thermal heat energy ( 100 % 100\% 100% conservation of energy). Light photons emitted by the fixtures strike walls, floors, and furniture where they are absorbed and degraded into thermal heat.
General Lighting Heat Gain Formulation q light = W installed × 3.412 ( Btu/hr Watt ) × F u × F s a × CLF light q_{\text{light}} = W_{\text{installed}} \times 3.412\left(\frac{\text{Btu/hr}}{\text{Watt}}\right) \times F_u \times F_{sa} \times \text{CLF}_{\text{light}} q light = W installed × 3.412 ( Watt Btu/hr ) × F u × F s a × CLF light
Where:
W installed = Total connected lighting electrical power (Watts) or Area ( ft 2 ) × LPD ( W/ft 2 ) W_{\text{installed}} = \text{Total connected lighting electrical power (Watts) or Area } (\text{ft}^2) \times \text{LPD } (\text{W/ft}^2) W installed = Total connected lighting electrical power (Watts) or Area ( ft 2 ) × LPD ( W/ft 2 )
3.412 = Conversion constant ( 1 Watt = 3.41214 Btu/hr ) 3.412 = \text{Conversion constant } (1\text{ Watt} = 3.41214\text{ Btu/hr}) 3.412 = Conversion constant ( 1 Watt = 3.41214 Btu/hr )
F u = Lighting Use Factor (fraction of installed lights energized during peak load, typically 0.85 to 1.0 ) F_u = \text{Lighting Use Factor (fraction of installed lights energized during peak load, typically } 0.85\text{ to }1.0) F u = Lighting Use Factor (fraction of installed lights energized during peak load, typically 0.85 to 1.0 )
F s a = Special Allowance Factor (Ballast or LED driver power multiplier: 1.0 for direct LED, 1.15 for fluorescent/HID) F_{sa} = \text{Special Allowance Factor (Ballast or LED driver power multiplier: } 1.0\text{ for direct LED, } 1.15\text{ for fluorescent/HID)} F s a = Special Allowance Factor (Ballast or LED driver power multiplier: 1.0 for direct LED, 1.15 for fluorescent/HID)
CLF light = Cooling Load Factor for lighting (accounting for thermal mass storage delay) \text{CLF}_{\text{light}} = \text{Cooling Load Factor for lighting (accounting for thermal mass storage delay)} CLF light = Cooling Load Factor for lighting (accounting for thermal mass storage delay) +-----------------------------------------------------------------------------------------+
- | LIGHTING HEAT SPLIT: ROOM SPACE VS. RETURN AIR PLENUM |
- +-----------------------------------------------------------------------------------------+
- | Recessed Fixture in Dropped Ceiling: |
- | |
- | +---------------------------------------+ <-- Floor Slab Above |
- | | RETURN AIR PLENUM (T_plenum > T_room) | |
- | | q_plenum = (1 - F_space) * q_light | --> Heat goes to central return air |
- | +================[ FIXTURE ]============+ <-- Acoustic Ceiling Tile |
- | | | |
- | | CONDITIONED ROOM SPACE (T_room = 75°F)| |
- | | q_space = F_space * q_light | --> Heat goes directly into zone CFM |
- | +---------------------------------------+ |
- +-----------------------------------------------------------------------------------------+
- Space vs. Return Air Plenum Heat Fraction ( F space F_{\text{space}} F space )
When lighting fixtures are recessed into a suspended return air plenum:
Heat to Room Space ( q room q_{\text{room}} q room ): F space ≈ 0.70 to 0.80 F_{\text{space}} \approx 0.70\text{ to }0.80 F space ≈ 0.70 to 0.80 enters the conditioned space directly.
Heat to Return Air Plenum ( q plenum q_{\text{plenum}} q plenum ): 1 − F space ≈ 0.20 to 0.30 1 - F_{\text{space}} \approx 0.20\text{ to }0.30 1 − F space ≈ 0.20 to 0.30 is carried directly by return air back to the air handling unit. This fraction increases the mixed air temperature ( T mix T_{\text{mix}} T mix ) at the central cooling coil but does not increase the required zone supply airflow ( CFM supply \text{CFM}_{\text{supply}} CFM supply ).
3. Plug Loads & Office Equipment
Plug loads include computers, monitors, printers, copiers, servers, and laboratory equipment. Using the manufacturer's maximum nameplate power rating severely overestimates cooling loads because equipment operates at idle or partial load states for the majority of the working day.
Sensible Equipment Heat Gain Equation q equip = P operating × 3.412 ( Btu/hr Watt ) = W nameplate × F use × 3.412 q_{\text{equip}} = P_{\text{operating}} \times 3.412\left(\frac{\text{Btu/hr}}{\text{Watt}}\right) = W_{\text{nameplate}} \times F_{\text{use}} \times 3.412 q equip = P operating × 3.412 ( Watt Btu/hr ) = W nameplate × F use × 3.412
Representative Commercial Equipment Heat Gains
Equipment Type Typical Nameplate Rating Actual Continuous Operating Heat ( W W W ) Heat Output ( Btu/hr \text{Btu/hr} Btu/hr )
Desktop Computer + Dual Monitors 350 W 350\text{ W} 350 W 120 to 160 W 120\text{ to }160\text{ W} 120 to 160 W 410 to 550 Btu/hr 410\text{ to }550\text{ Btu/hr} 410 to 550 Btu/hr
Laptop Computer (Docked) 90 W 90\text{ W} 90 W 30 to 50 W 30\text{ to }50\text{ W} 30 to 50 W 100 to 170 Btu/hr 100\text{ to }170\text{ Btu/hr} 100 to 170 Btu/hr
Floor-Standing Office Laser Copier 1 , 500 W 1,500\text{ W} 1 , 500 W 350 to 500 W 350\text{ to }500\text{ W} 350 to 500 W 1 , 200 to 1 , 700 Btu/hr 1,200\text{ to }1,700\text{ Btu/hr} 1 , 200 to 1 , 700 Btu/hr
Small Network Server (per 1U chassis) 500 W 500\text{ W} 500 W 350 to 450 W 350\text{ to }450\text{ W} 350 to 450 W 1 , 200 to 1 , 535 Btu/hr 1,200\text{ to }1,535\text{ Btu/hr} 1 , 200 to 1 , 535 Btu/hr
Coffee Maker (Brewing / Warmer) 1 , 200 W / 150 W 1,200\text{ W / } 150\text{ W} 1 , 200 W / 150 W 150 W (average) 150\text{ W (average)} 150 W (average) 510 Btu/hr (sensible) + latent 510\text{ Btu/hr (sensible) + latent} 510 Btu/hr (sensible) + latent
4. Electric Motors & Machinery Heat Gains
Electric motors drive fans, pumps, compressors, and industrial machines. Sizing motor heat gains requires evaluating whether the motor itself, the driven machine, or both are physically located inside the conditioned space. +-----------------------------------------------------------------------------------------+
- | THE THREE CANONICAL MOTOR HEAT DISSIPATION CONFIGURATIONS |
- +-----------------------------------------------------------------------------------------+
- | Case 1: Motor IN Space, Driven Machine IN Space |
- | q = (hp * 2,545) / eta |
- | |
- | Case 2: Motor IN Space, Driven Machine OUTSIDE Space |
- | q = hp * 2,545 * (1 - eta) / eta = Motor Inefficiency Heat |
- | |
- | Case 3: Motor OUTSIDE Space, Driven Machine IN Space |
- | q = hp * 2,545 = Mechanical Work Converted to Heat |
- +-----------------------------------------------------------------------------------------+
- Mathematical Formulation of the Three Motor Cases
Case 1: Motor IN Space, Machine IN Space (e.g., AHU supply fan inside conditioned air stream, indoor machine tool):
All electrical power input to the motor ( P in = P brake / η P_{\text{in}} = P_{\text{brake}} / \eta P in = P brake / η ) degrades into heat within the space: q motor = P hp × 2544.43 η motor = P hp × 2545 η motor ( Btu/hr ) q_{\text{motor}} = \frac{P_{\text{hp}} \times 2544.43}{\eta_{\text{motor}}} = \frac{P_{\text{hp}} \times 2545}{\eta_{\text{motor}}}\quad (\text{Btu/hr}) q motor = η motor P hp × 2544.43 = η motor P hp × 2545 ( Btu/hr )
Case 2: Motor IN Space, Machine OUTSIDE Space (e.g., exhaust fan motor inside conditioned room driving rooftop impeller via shaft):
Only the motor electrical and magnetic losses ( P in − P shaft P_{\text{in}} - P_{\text{shaft}} P in − P shaft ) remain in the space: q motor = P hp × 2545 × ( 1 − η motor η motor ) ( Btu/hr ) q_{\text{motor}} = P_{\text{hp}} \times 2545 \times \left(\frac{1 - \eta_{\text{motor}}}{\eta_{\text{motor}}}\right)\quad (\text{Btu/hr}) q motor = P hp × 2545 × ( η motor 1 − η motor ) ( Btu/hr )
Case 3: Motor OUTSIDE Space, Machine IN Space (e.g., outdoor motor driving an indoor chilled water pump):
The motor losses are rejected to the outdoors, but the useful shaft work delivered to the indoor fluid/machine degrades into friction/viscous heat: q motor = P hp × 2545 ( Btu/hr ) q_{\text{motor}} = P_{\text{hp}} \times 2545\quad (\text{Btu/hr}) q motor = P hp × 2545 ( Btu/hr )
Where:
P hp = Brake horsepower delivered to the driven load ( hp ) P_{\text{hp}} = \text{Brake horsepower delivered to the driven load } (\text{hp}) P hp = Brake horsepower delivered to the driven load ( hp )
η motor = Full-load electric motor efficiency (decimal, 0.80 to 0.95 ) \eta_{\text{motor}} = \text{Full-load electric motor efficiency (decimal, } 0.80\text{ to }0.95) η motor = Full-load electric motor efficiency (decimal, 0.80 to 0.95 )
2545 = Conversion constant ( 1 hp = 2544.43 Btu/hr = 745.7 Watts ) 2545 = \text{Conversion constant } (1\text{ hp} = 2544.43\text{ Btu/hr} = 745.7\text{ Watts}) 2545 = Conversion constant ( 1 hp = 2544.43 Btu/hr = 745.7 Watts )
5. Diversity Factors & Block Load Synthesis
In multi-room facilities, not all internal loads peak simultaneously. Occupants move between offices and conference rooms; lights are switched off in vacant areas; and computers cycle power.
Space Peak Load vs. Block (Coincident) Peak Load
Space (Zone) Peak Load: Sized using a diversity factor F D = 1.0 F_D = 1.0 F D = 1.0 (worst-case individual peak) to ensure terminal VAV boxes, ductwork, and zone coils can meet individual room maximums.
Central Block Load: Sized using the Coincident Peak Diversity Factor ( D < 1.0 D < 1.0 D < 1.0 ) to size the central air handling units, chillers, and cooling towers. +-----------------------------------------------------------------------------------------+
- | DIVERSITY FACTOR (D) = Coincident Building Peak Load / Sum of Individual Zone Peaks |
- +-----------------------------------------------------------------------------------------+
- | Office Buildings: D_people = 0.70 to 0.85 | D_lights = 0.85 to 0.95 |
- | Hotels / Apartments: D_people = 0.50 to 0.70 | D_plug = 0.50 to 0.75 |
+-----------------------------------------------------------------------------------------+ Q chiller, design = D envelope Q envelope, sum + D people Q people, sum + D lights Q lights, sum + D plug Q plug, sum + Q ventilation Q_{\text{chiller, design}} = D_{\text{envelope}} Q_{\text{envelope, sum}} + D_{\text{people}} Q_{\text{people, sum}} + D_{\text{lights}} Q_{\text{lights, sum}} + D_{\text{plug}} Q_{\text{plug, sum}} + Q_{\text{ventilation}} Q chiller, design = D envelope Q envelope, sum + D people Q people, sum + D lights Q lights, sum + D plug Q plug, sum + Q ventilation
6. NCEES Reference Handbook Navigation Tactics
Occupant Heat Gains: Search "Rates of Heat Gain from Occupants" or "Metabolic Rate" in Section 7 (HVAC & Refrigeration Applications) to find the table of sensible and latent heat outputs for seated, office, walking, and athletic activities.
Motor Heat Gain Formulas: Search "Heat Gain from Electric Motors" to find the exact three-case equations relating brake horsepower ( P hp P_{\text{hp}} P hp ), motor efficiency ( η \eta η ), and heat output.
Lighting Heat Multipliers: Search "Lighting Heat Gain" to locate the 3.412 3.412 3.412 conversion constant and special ballast allowance factor ( F s a F_{sa} F s a ).
- 7. Worked Computational Examples
- Example 1: Large Training Facility Internal Cooling Load
A corporate training room ( 2 , 500 ft 2 2,500\text{ ft}^2 2 , 500 ft 2 ) has an occupancy of 60 seated students engaged in light computer training. The following design parameters are specified:
Occupant heat dissipation: q s = 240 Btu/hr q_s = 240\text{ Btu/hr} q s = 240 Btu/hr , q l = 210 Btu/hr q_l = 210\text{ Btu/hr} q l = 210 Btu/hr per person.
Lighting: Recessed LED fixtures with total installed power of 1 , 800 Watts 1,800\text{ Watts} 1 , 800 Watts . 25% of lighting heat is extracted directly into the return air plenum.
Plug loads: 60 laptops at 40 Watts 40\text{ Watts} 40 Watts actual operating power each, plus one instructor workstation and projector totaling 450 Watts 450\text{ Watts} 450 Watts .
Diversity factor for training occupancy: F D = 0.90 F_D = 0.90 F D = 0.90 .
Calculate: (a) Space sensible internal cooling load, (b) Space latent internal cooling load, (c) Total space internal cooling load, and (d) Heat rejected to the return air plenum.
Solution:
Calculate occupant heat gains: q people, sensible = 60 × 240 Btu/hr × 0.90 = 12 , 960 Btu/hr q_{\text{people, sensible}} = 60 \times 240\text{ Btu/hr} \times 0.90 = 12,960\text{ Btu/hr} q people, sensible = 60 × 240 Btu/hr × 0.90 = 12 , 960 Btu/hr q people, latent = 60 × 210 Btu/hr × 0.90 = 11 , 340 Btu/hr q_{\text{people, latent}} = 60 \times 210\text{ Btu/hr} \times 0.90 = 11,340\text{ Btu/hr} q people, latent = 60 × 210 Btu/hr × 0.90 = 11 , 340 Btu/hr
Calculate lighting heat gains: q light, total = 1 , 800 W × 3.412 Btu/(hr ⋅ W) = 6 , 141.6 Btu/hr q_{\text{light, total}} = 1,800\text{ W} \times 3.412\text{ Btu/(hr}\cdot\text{W)} = 6,141.6\text{ Btu/hr} q light, total = 1 , 800 W × 3.412 Btu/(hr ⋅ W) = 6 , 141.6 Btu/hr q light, room = 6 , 141.6 × ( 1 − 0.25 ) = 6 , 141.6 × 0.75 = 4 , 606.2 Btu/hr q_{\text{light, room}} = 6,141.6 \times (1 - 0.25) = 6,141.6 \times 0.75 = 4,606.2\text{ Btu/hr} q light, room = 6 , 141.6 × ( 1 − 0.25 ) = 6 , 141.6 × 0.75 = 4 , 606.2 Btu/hr q light, plenum = 6 , 141.6 × 0.25 = 1 , 535.4 Btu/hr q_{\text{light, plenum}} = 6,141.6 \times 0.25 = 1,535.4\text{ Btu/hr} q light, plenum = 6 , 141.6 × 0.25 = 1 , 535.4 Btu/hr
Calculate plug load equipment heat gains (100% sensible): W plug = ( 60 × 40 W ) + 450 W = 2 , 400 + 450 = 2 , 850 Watts W_{\text{plug}} = (60 \times 40\text{ W}) + 450\text{ W} = 2,400 + 450 = 2,850\text{ Watts} W plug = ( 60 × 40 W ) + 450 W = 2 , 400 + 450 = 2 , 850 Watts q plug = 2 , 850 W × 3.412 Btu/(hr ⋅ W) = 9 , 724.2 Btu/hr q_{\text{plug}} = 2,850\text{ W} \times 3.412\text{ Btu/(hr}\cdot\text{W)} = 9,724.2\text{ Btu/hr} q plug = 2 , 850 W × 3.412 Btu/(hr ⋅ W) = 9 , 724.2 Btu/hr
Synthesize space loads: q space, sensible = 12 , 960 + 4 , 606.2 + 9 , 724.2 = 27 , 290.4 Btu/hr q_{\text{space, sensible}} = 12,960 + 4,606.2 + 9,724.2 = 27,290.4\text{ Btu/hr} q space, sensible = 12 , 960 + 4 , 606.2 + 9 , 724.2 = 27 , 290.4 Btu/hr q space, latent = 11 , 340.0 Btu/hr q_{\text{space, latent}} = 11,340.0\text{ Btu/hr} q space, latent = 11 , 340.0 Btu/hr q space, total = 27 , 290.4 + 11 , 340.0 = 38 , 630.4 Btu/hr = 3.219 Tons q_{\text{space, total}} = 27,290.4 + 11,340.0 = 38,630.4\text{ Btu/hr} = 3.219\text{ Tons} q space, total = 27 , 290.4 + 11 , 340.0 = 38 , 630.4 Btu/hr = 3.219 Tons
Heat to return air plenum: q plenum = 1 , 535.4 Btu/hr q_{\text{plenum}} = 1,535.4\text{ Btu/hr} q plenum = 1 , 535.4 Btu/hr
Example 2: Mechanical Room Motor Heat Dissipation (Case 2)
A commercial mechanical equipment room houses a 25 hp 25\text{ hp} 25 hp continuous exhaust fan motor operating at full load with an efficiency of η = 91.0 % \eta = 91.0\% η = 91.0% . The motor is mounted inside the conditioned mechanical room, but its drive shaft passes through an exterior partition wall to rotate the fan impeller located outside in the ambient air stream.
Calculate: The sensible heat dissipation rate into the mechanical room from the motor.
Solution:
Identify the appropriate motor case:
The motor is located inside the room, while the driven machine (fan impeller and moving air stream) is outside the room (Case 2).
Apply the Case 2 heat dissipation formula: q = P hp × 2545 × ( 1 − η motor η motor ) q = P_{\text{hp}} \times 2545 \times \left(\frac{1 - \eta_{\text{motor}}}{\eta_{\text{motor}}}\right) q = P hp × 2545 × ( η motor 1 − η motor ) q = 25 hp × 2545 ( Btu/hr hp ) × ( 1 − 0.910 0.910 ) q = 25\text{ hp} \times 2545\left(\frac{\text{Btu/hr}}{\text{hp}}\right) \times \left(\frac{1 - 0.910}{0.910}\right) q = 25 hp × 2545 ( hp Btu/hr ) × ( 0.910 1 − 0.910 ) q = 63 , 625 × ( 0.090 0.910 ) = 63 , 625 × 0.09890 = 6 , 292.6 Btu/hr q = 63,625 \times \left(\frac{0.090}{0.910}\right) = 63,625 \times 0.09890 = 6,292.6\text{ Btu/hr} q = 63 , 625 × ( 0.910 0.090 ) = 63 , 625 × 0.09890 = 6 , 292.6 Btu/hr
(Note: If the fan impeller were also located inside the room (Case 1), the heat dissipation would be q = 63 , 625 / 0.910 = 69 , 917.6 Btu/hr q = 63,625 / 0.910 = 69,917.6\text{ Btu/hr} q = 63 , 625/0.910 = 69 , 917.6 Btu/hr —over 11 times higher!)