6.3 Solar Heat Gain (SHGC), Fenestration & Cooling Load Temperature Difference / Radiant Time Series (CLTD/RTS)

PE Mechanical: HVAC and Refrigeration Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Overview, Reference Handbook & Engineering Foundations

1.1 NCEES Exam Specification, CBT Delivery & Reference Handbook Strategy 1.2 Engineering Units, Dimensional Analysis & Physical Property Lookups 1.3 Engineering Economics, Life Cycle Cost Analysis & Equipment Financial Evaluation 1.4 Electrical Foundations, Motor Ratings & Variable Frequency Drives (VFDs)

2 Chapter 2: Thermodynamics & Energy Balances

2.1 First and Second Laws of Thermodynamics & Open/Closed System Energy Balances 2.2 Thermodynamic Cycles: Carnot, Rankine, Brayton & Reversed Carnot Limit 2.3 Gas & Vapor Property Evaluation: Steam Tables, Superheat & Subcooling 2.4 Mass, Energy & Combustion Balances for HVAC Equipment

3 Chapter 3: Psychrometrics, Moist Air Processes & Humidity Equipment

3.1 Psychrometric Properties: DBT, WBT, DPT, RH, Humidity Ratio & Enthalpy 3.2 Chart Reading & Psychrometric Equations at Sea Level vs. Altitude (5,000 ft) 3.3 Basic Psychrometric Processes: Sensible Heating/Cooling, Humidification & Dehumidification 3.4 Mixed Air Calculations & Complex Air Conditioning Cycles (Preheat, Reheat & Bypass) 3.5 Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP) & Coil Bypass Factor 3.6 Humidification & Dehumidification Equipment: Steam, Adiabatic, Desiccant & Low-Temperature Processes

4 Chapter 4: Heat Transfer Principles & Sizing

4.1 Steady-State Conduction & Multilayer Thermal Resistance (R-Value & U-Factor) 4.2 Convective Heat Transfer & Forced/Natural Convection Coefficients 4.3 Radiation Heat Transfer, Surface Emissivity & View Factors 4.4 Overall Heat Transfer Coefficients, Fouling Factors & Transient/Thermal Mass Effects 4.5 Heat Exchanger Analysis: Log Mean Temperature Difference (LMTD) & Effectiveness-NTU (ε-NTU)

5 Chapter 5: Fluid Mechanics & Hydraulic Fundamentals

5.1 Fluid Statics, Incompressible Continuity & Bernoulli Energy Equation 5.2 Pipe Friction, Moody Diagram & Darcy-Weisbach / Hazen-Williams Calculations 5.3 Minor Losses: Equivalent Length, Loss Coefficients (K-factors) & Total System Head 5.4 Pump Sizing, Net Positive Suction Head (NPSHa vs NPSHr) & Cavitation Prevention 5.5 Affinity Laws & Parallel/Series Pump/Fan System Curves

6 Chapter 6: Heating & Cooling Load Calculations

6.1 Outdoor & Indoor Design Conditions (ASHRAE Fundamentals, Climatic Data & Indoor Setpoints) 6.2 Envelope Heat Transmission & Infiltration/Exfiltration Load Methods 6.3 Solar Heat Gain (SHGC), Fenestration & Cooling Load Temperature Difference / Radiant Time Series (CLTD/RTS) 6.4 Internal Heat Gains: Lighting, People, Equipment & Diversity Factors 6.5 Ventilation Loads & Sensible / Latent / Total Cooling Load Synthesis

7 Chapter 7: Refrigeration Principles, Cycles & Cold Storage Applications

7.1 Standard Vapor-Compression Refrigeration Cycle on P-h & T-s Diagrams 7.2 Refrigeration Cycle Performance Metrics: COP, EER, SEER, kW/ton & Ton of Refrigeration 7.3 Cycle Enhancements: Subcooling, Superheating, Liquid-Suction Heat Exchangers & Economizers 7.4 Multi-Stage & Cascade Refrigeration Systems: Intercooling & Flash Gas Removal 7.5 Absorption Refrigeration Cycles: Water-Lithium Bromide & Ammonia-Water Systems 7.6 Food Processing & Cold Storage Refrigeration: Product Load, Pull-Down & Storage Design

8 Chapter 8: Refrigerants, Environmental Regulations & Safety

8.1 Refrigerant Classifications, Nomenclature & Thermodynamic Properties (ASHRAE Standard 34) 8.2 AIM Act, EPA Technology Transitions Sector GWP Limits & Low-GWP Refrigerants (R-32, R-454B) 8.3 Refrigerant Safety Requirements & Machinery Room Design (ASHRAE Standard 15) 8.4 Refrigerant Piping Sizing, Oil Return, Traps & Double Risers

9 Chapter 9: HVAC Equipment & Primary Machinery

9.1 Compressors: Reciprocating, Rotary, Scroll, Screw & Centrifugal 9.2 Condensers: Air-Cooled, Water-Cooled & Evaporative Condensers 9.3 Evaporators & Direct Expansion (DX) vs Liquid Chilling Coils 9.4 Water Chillers: Centrifugal, Screw & Scroll with ASHRAE 90.1 Path A/B IPLV Ratings 9.5 Cooling Towers: Range, Approach, Evaporation, Blowdown & Legionella Control 9.6 Heat Pumps & Variable Refrigerant Flow (VRF): Balance Point, Defrost & Heat Recovery 9.7 Thermal Energy Storage: Full vs. Partial Storage, Chilled Water & Ice Systems

10 Chapter 10: Air-Side Systems & Distribution

10.1 Air Handling Units (AHUs), Dedicated Outdoor Air Systems (DOAS) & Fan-Coil Units 10.2 Duct Design Methodologies: Equal Friction, Static Regain & Velocity Reduction 10.3 Duct Fittings, Dynamic Pressure Losses & SMACNA Construction Standards 10.4 Fan Types, Performance Curves, System Effect Factors & Surge/Stall Dynamics 10.5 Variable Air Volume (VAV) Systems, Terminal Boxes & Space Air Diffusion (ADPI) 10.6 Cooling & Heating Coil Selection: Face Velocity, Rows, Circuiting & Freeze Protection

11 Chapter 11: Hydronic, Steam & Fuel Distribution and Heating Plant

11.1 Hydronic System Architectures: Primary-Only, Primary-Secondary & Variable Primary Flow (VPF) 11.2 Hydronic Pipe Sizing, Velocity Limits & Closed/Open Expansion Tank Sizing 11.3 Control Valves: 2-Way vs 3-Way, Valve Authority (N), Cv Calculations & Characteristic Curves 11.4 Boilers & Heating Hot Water Systems: Condensing vs Non-Condensing & Water Treatment 11.5 Furnaces & Gas-Fired Heating Equipment: AFUE, Temperature Rise, Combustion Air & Vent Categories 11.6 Steam & Condensate Distribution: Latent Heat, Trap Selection, Flash Steam & Stall 11.7 Fuel Gas & Fuel Oil Piping: Demand, Sizing Method, Pressure Drop & Storage Systems

12 Chapter 12: HVAC Control Concepts, Sensors & Sequences

12.1 Sensors, Actuators & Dampers: Selection, Placement, Fail-Safe Position & Damper Authority 12.2 Control Loops: Proportional Offset, PID Action, Reset Strategies & Standard Sequences

13 Chapter 13: Building Energy, Ventilation & Indoor Environmental Quality Codes

13.1 ASHRAE Standard 62.1: Ventilation Rate Procedure (VRP), Indoor Air Quality Procedure & DCV 13.2 ASHRAE Standard 90.1: Building Energy Envelope, Mechanical Efficiency & Economizer Mandates 13.3 ASHRAE Standard 55: Thermal Environmental Conditions, PMV/PPD & Adaptive Comfort Models 13.4 Energy Recovery Systems: Enthalpy Wheels, Fixed-Plate Exchangers, Heat Pipes & Runaround Loops

14 Chapter 14: Supportive Engineering Knowledge, Life Safety & Operations

14.1 Air Filtration Standards: MERV Ratings (ASHRAE 52.2), HEPA & Gas-Phase Adsorption 14.2 Life Safety Systems: Fire/Smoke Dampers, Stairwell Pressurization (NFPA 92) & Smoke Control (NFPA 90A) 14.3 Acoustical Control & Vibration Isolation in HVAC Systems (NC / RC Criteria)

6.3 Solar Heat Gain (SHGC), Fenestration & Cooling Load Temperature Difference / Radiant Time Series (CLTD/RTS)

Key Takeaways Explain This Topic AI

Total fenestration heat gain comprises simultaneous thermal conduction and transmitted/absorbed solar radiation: q_fen = U * A * (T_o - T_i) + A * SHGC * IAC * E_t.

The Solar Heat Gain Coefficient (SHGC) represents the fraction of incident solar radiation admitted through a window; legacy Shading Coefficient (SC) relates to SHGC by SHGC ≈ 0.86 * SC.

Sol-air temperature (T_sol-air) combines outdoor dry-bulb temperature, solar absorptance (alpha), incident solar irradiance (I_t), and surface longwave radiation re-radiation to express the fictitious equivalent outdoor temperature driving envelope conduction.

The Cooling Load Temperature Difference (CLTD) method accounts for thermal mass time lag and solar radiation, requiring corrections for indoor temperature setpoint (78°F) and mean outdoor daily temperature (T_o,m = T_peak - DR/2).

The Radiant Time Series (RTS) method separates instantaneous heat gains into convective portions (which become immediate cooling load) and radiant portions (which are absorbed by room thermal mass and converted to cooling load over 24 hours via Radiant Time Factors).

Last updated: August 2026

6.3 Solar Heat Gain (SHGC), Fenestration & Cooling Load Temperature Difference / Radiant Time Series (CLTD/RTS)

Solar radiation passing through fenestration and striking opaque exterior envelope surfaces represents one of the largest and most dynamic components of building cooling loads. Unlike steady-state winter heating calculations, cooling load calculations must account for the dual nature of solar radiation: direct optical transmission through glazing, and transient thermal storage within opaque building materials. Engineering methods developed by ASHRAE—including the traditional Cooling Load Temperature Difference (CLTD / SCL / CLF) method and the modern Radiant Time Series (RTS) method—translate instantaneous thermal heat gains into actual cooling loads experienced by the air conditioning system.

1. Fenestration Heat Transfer & Solar Optics

Heat gain through glazed fenestration assemblies (windows, curtain walls, skylights) consists of two concurrent, independent heat transfer mechanisms:

Conductive/Convective Heat Transmission: Driven by the dry-bulb temperature difference across the glass.

Solar Radiation Heat Gain: Driven by direct beam, diffuse sky, and ground-reflected solar irradiance striking the glass surface. +-----------------------------------------------------------------------------------------+

  • | FENESTRATION TOTAL HEAT GAIN MECHANISMS |
  • +-----------------------------------------------------------------------------------------+
  • | Incident Solar Irradiance (E_t) |
  • | | |
  • | +---> [Reflected Outward] (rho * E_t) |
  • | | |
  • | +---> [Directly Transmitted] (tau * E_t) -----------------------------> Room Space |
  • | | | |
  • | +---> [Absorbed in Glass] (alpha * E_t) --+-> [Inward Re-radiation/Conv] --->+ |
  • | +-> [Outward Re-radiation/Conv] |
  • | |
  • | Conduction Across Glass: q_cond = U * A * (T_outdoor - T_indoor) |
  • +-----------------------------------------------------------------------------------------+

Total Fenestration Heat Gain Equation q fen = q conduction + q solar q_{\text{fen}} = q_{\text{conduction}} + q_{\text{solar}} q fen ​ = q conduction ​ + q solar ​ q fen = U ⋅ A ⋅ ( T outdoor − T indoor ) + A ⋅ SHGC ⋅ IAC ⋅ E t q_{\text{fen}} = U \cdot A \cdot (T_{\text{outdoor}} - T_{\text{indoor}}) + A \cdot \text{SHGC} \cdot \text{IAC} \cdot E_t q fen ​ = U ⋅ A ⋅ ( T outdoor ​ − T indoor ​ ) + A ⋅ SHGC ⋅ IAC ⋅ E t ​

Where:

q fen = Total instantaneous fenestration heat gain ( Btu/hr ) q_{\text{fen}} = \text{Total instantaneous fenestration heat gain } (\text{Btu/hr}) q fen ​ = Total instantaneous fenestration heat gain ( Btu/hr )

U = Overall fenestration assembly U -factor, including frame ( Btu/(hr ⋅ ft 2 ⋅ ∘ F) ) U = \text{Overall fenestration assembly } U\text{-factor, including frame } (\text{Btu/(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)}) U = Overall fenestration assembly U -factor, including frame ( Btu/(hr ⋅ ft 2 ⋅ ∘ F) )

A = Total fenestration gross area ( ft 2 ) A = \text{Total fenestration gross area } (\text{ft}^2) A = Total fenestration gross area ( ft 2 )

SHGC = Solar Heat Gain Coefficient of the glazing assembly (dimensionless, 0.0 to 1.0 ) \text{SHGC} = \text{Solar Heat Gain Coefficient of the glazing assembly (dimensionless, } 0.0\text{ to }1.0) SHGC = Solar Heat Gain Coefficient of the glazing assembly (dimensionless, 0.0 to 1.0 )

IAC = Interior Attenuation Coefficient (accounting for interior blinds, shades, or drapes) \text{IAC} = \text{Interior Attenuation Coefficient (accounting for interior blinds, shades, or drapes)} IAC = Interior Attenuation Coefficient (accounting for interior blinds, shades, or drapes)

E t = Total incident solar irradiance on the surface ( Btu/(hr ⋅ ft 2 ) ) E_t = \text{Total incident solar irradiance on the surface } (\text{Btu/(hr}\cdot\text{ft}^2)) E t ​ = Total incident solar irradiance on the surface ( Btu/(hr ⋅ ft 2 ))

Solar Heat Gain Coefficient (SHGC) vs. Legacy Shading Coefficient (SC)

SHGC: Defined as the fraction of incident solar radiation admitted through a window, both via direct transmission and inward release of absorbed heat: SHGC = τ + N i α \text{SHGC} = \tau + N_i \alpha SHGC = τ + N i ​ α .

Shading Coefficient (SC): Legacy metric defined as the ratio of solar heat gain through a given glazing to that through standard 1/8-inch clear double-strength sheet glass (DSA, SHGC ref = 0.86 \text{SHGC}_{\text{ref}} = 0.86 SHGC ref ​ = 0.86 to 0.87 0.87 0.87 ). SHGC = SC × 0.86 ⟺ SC = SHGC 0.86 ≈ 1.163 × SHGC \text{SHGC} = \text{SC} \times 0.86 \quad \iff \quad \text{SC} = \frac{\text{SHGC}}{0.86} \approx 1.163 \times \text{SHGC} SHGC = SC × 0.86 ⟺ SC = 0.86 SHGC ​ ≈ 1.163 × SHGC

Fenestration Shading & Overhang Geometry

External architectural shading devices (horizontal overhangs, vertical fins) block direct solar beam radiation during high sun angles. The Projection Factor (PF) characterizes horizontal overhang depth: PF = B H \text{PF} = \frac{B}{H} PF = H B ​

Where B B B is the horizontal overhang projection width (ft) and H H H is the vertical distance from the window sill to the bottom of the overhang (ft).

2. Sol-Air Temperature ( T s o l - a i r T_{sol\text{-}air} T so l - ai r ​ )

Solar radiation striking opaque exterior walls and roofs increases surface temperature significantly above ambient air dry-bulb temperature. The Sol-Air Temperature ( T s o l - a i r T_{sol\text{-}air} T so l - ai r ​ ) is a fictitious outdoor air temperature that, in the absence of all radiation exchanges, would produce the same total rate of heat transmission into the surface as the combined actual outdoor air temperature, incident solar radiation, and longwave radiant exchange with the sky and surroundings.

Sol-Air Temperature Derivation

Balancing heat flux at the exterior surface: q / A = h o ( T o − T s ) + α I t − ε Δ R = h o ( T s o l - a i r − T s ) q/A = h_o (T_o - T_s) + \alpha I_t - \varepsilon \Delta R = h_o (T_{sol\text{-}air} - T_s) q / A = h o ​ ( T o ​ − T s ​ ) + α I t ​ − ε Δ R = h o ​ ( T so l - ai r ​ − T s ​ ) T s o l - a i r = T o + α ⋅ I t h o − ε ⋅ Δ R h o T_{sol\text{-}air} = T_o + \frac{\alpha \cdot I_t}{h_o} - \frac{\varepsilon \cdot \Delta R}{h_o} T so l - ai r ​ = T o ​ + h o ​ α ⋅ I t ​ ​ − h o ​ ε ⋅ Δ R ​

Where:

T o = Outdoor ambient dry-bulb temperature ( ∘ F ) T_o = \text{Outdoor ambient dry-bulb temperature } ({}^\circ\text{F}) T o ​ = Outdoor ambient dry-bulb temperature ( ∘ F )

α = Surface solar absorptance (dimensionless, 0.2 for bright white to 0.95 for black asphalt/tar) \alpha = \text{Surface solar absorptance (dimensionless, } 0.2\text{ for bright white to }0.95\text{ for black asphalt/tar)} α = Surface solar absorptance (dimensionless, 0.2 for bright white to 0.95 for black asphalt/tar)

I t = Total incident solar radiation (direct + diffuse) ( Btu/(hr ⋅ ft 2 ) ) I_t = \text{Total incident solar radiation (direct + diffuse) } (\text{Btu/(hr}\cdot\text{ft}^2)) I t ​ = Total incident solar radiation (direct + diffuse) ( Btu/(hr ⋅ ft 2 ))

h o = Exterior surface combined convective and radiative heat transfer coefficient ( ≈ 3.0 Btu/(hr ⋅ ft 2 ⋅ ∘ F) ) h_o = \text{Exterior surface combined convective and radiative heat transfer coefficient } (\approx 3.0\text{ Btu/(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)}) h o ​ = Exterior surface combined convective and radiative heat transfer coefficient ( ≈ 3.0 Btu/(hr ⋅ ft 2 ⋅ ∘ F) )

ε = Surface hemispherical thermal emittance ( ≈ 0.90 for most building materials) \varepsilon = \text{Surface hemispherical thermal emittance } (\approx 0.90\text{ for most building materials)} ε = Surface hemispherical thermal emittance ( ≈ 0.90 for most building materials)

Δ R = Longwave radiation correction factor between surface and sky ( Btu/(hr ⋅ ft 2 ) ) \Delta R = \text{Longwave radiation correction factor between surface and sky } (\text{Btu/(hr}\cdot\text{ft}^2)) Δ R = Longwave radiation correction factor between surface and sky ( Btu/(hr ⋅ ft 2 ))

Horizontal Roofs: Δ R ≈ 20 Btu/(hr ⋅ ft 2 ) \Delta R \approx 20\text{ Btu/(hr}\cdot\text{ft}^2) Δ R ≈ 20 Btu/(hr ⋅ ft 2 ) (giving ε Δ R h o ≈ 7 ∘ F \frac{\varepsilon \Delta R}{h_o} \approx 7^\circ\text{F} h o ​ ε Δ R ​ ≈ 7 ∘ F for horizontal surfaces facing open sky)

Vertical Walls: Δ R = 0 Btu/(hr ⋅ ft 2 ) \Delta R = 0\text{ Btu/(hr}\cdot\text{ft}^2) Δ R = 0 Btu/(hr ⋅ ft 2 ) (assuming ground and surroundings are at air temperature, giving ε Δ R h o = 0 ∘ F \frac{\varepsilon \Delta R}{h_o} = 0^\circ\text{F} h o ​ ε Δ R ​ = 0 ∘ F ) +-----------------------------------------------------------------------------------------+

  • | SOL-AIR TEMPERATURE PRACTICAL SHORTCUT FORMULAS (h_o = 3.0 Btu/hr-ft²-°F) |
  • +-----------------------------------------------------------------------------------------+
  • | Horizontal Flat Roofs: T_sol-air = T_o + (alpha * I_t / 3.0) - 7°F |
  • | Vertical Exterior Walls: T_sol-air = T_o + (alpha * I_t / 3.0) |
  • +-----------------------------------------------------------------------------------------+
  • 3. Cooling Load Temperature Difference (CLTD) Method

The CLTD / SCL / CLF method is a simplified hand-calculation procedure that accounts for the transient thermal storage and time-delay effects of building envelope assemblies without requiring complex differential equations.

1. Opaque Roofs and Walls Cooling Load q envelope = U ⋅ A ⋅ CLTD corrected q_{\text{envelope}} = U \cdot A \cdot \text{CLTD}_{\text{corrected}} q envelope ​ = U ⋅ A ⋅ CLTD corrected ​

Where CLTD corrected \text{CLTD}_{\text{corrected}} CLTD corrected ​ modifies tabular baseline CLTD values (which are tabulated for standard conditions: T indoor = 78 ∘ F T_{\text{indoor}} = 78^\circ\text{F} T indoor ​ = 7 8 ∘ F , maximum outdoor temperature T o , max = 95 ∘ F T_{o,\text{max}} = 95^\circ\text{F} T o , max ​ = 9 5 ∘ F , daily range D R = 21 ∘ F DR = 21^\circ\text{F} D R = 2 1 ∘ F ): CLTD corrected = CLTD table + ( 78 − T indoor ) + ( T o , m − 85 ) \text{CLTD}_{\text{corrected}} = \text{CLTD}_{\text{table}} + (78 - T_{\text{indoor}}) + (T_{o,m} - 85) CLTD corrected ​ = CLTD table ​ + ( 78 − T indoor ​ ) + ( T o , m ​ − 85 )

Where the mean outdoor daily temperature T o , m T_{o,m} T o , m ​ is: T o , m = T o , max − D R 2 T_{o,m} = T_{o,\text{max}} - \frac{DR}{2} T o , m ​ = T o , max ​ − 2 D R ​

2. Glazing Conduction & Solar Load via CLTD and SCL q glazing, conduction = U ⋅ A ⋅ CLTD corr, glass q_{\text{glazing, conduction}} = U \cdot A \cdot \text{CLTD}_{\text{corr, glass}} q glazing, conduction ​ = U ⋅ A ⋅ CLTD corr, glass ​ q glazing, solar = A ⋅ SC ⋅ SCL q_{\text{glazing, solar}} = A \cdot \text{SC} \cdot \text{SCL} q glazing, solar ​ = A ⋅ SC ⋅ SCL

Where SCL \text{SCL} SCL is the Solar Cooling Load factor (in Btu/(hr ⋅ ft 2 ) \text{Btu/(hr}\cdot\text{ft}^2) Btu/(hr ⋅ ft 2 ) ), accounting for solar intensity, latitude, orientation, and room thermal storage mass. +-----------------------------------------------------------------------------------------+

  • | THERMAL MASS TIME LAG & DAMPING EFFECT |
  • +-----------------------------------------------------------------------------------------+
  • | Peak Solar Irradiance on Roof occurs at Solar Noon (12:00 PM) |
  • | - Light Metal Roof (Low Mass): Peak Cooling Load occurs at 1:00 PM (1-hr lag) |
  • | - Heavy Concrete Roof (High Mass): Peak Cooling Load occurs at 6:00 PM (6-hr lag) |
  • | *Thermal mass shifts the peak hour and flattens (damps) peak cooling demand! |
  • +-----------------------------------------------------------------------------------------+
  • 4. Radiant Time Series (RTS) Method & Periodic Response Factors

The Radiant Time Series (RTS) method is the modern ASHRAE standard for non-residential cooling load calculations. It replaces older transfer function techniques by separating heat gains into convective and radiant components.

1. Convective vs. Radiant Heat Gain Split

All heat gains entering a space are partitioned into two distinct physical fractions:

Convective Heat Gain ( f c f_c f c ​ ): Heat transferred directly to room air by convection. Becomes instantaneous cooling load immediately.

Radiant Heat Gain ( f r = 1 − f c f_r = 1 - f_c f r ​ = 1 − f c ​ ): Radiant energy (longwave and shortwave) that passes through air without heating it, striking interior surfaces (floor, partitions, furniture) where it is absorbed and stored.

Heat Gain Source Convective Fraction ( f c f_c f c ​ ) Radiant Fraction ( f r f_r f r ​ ) Primary Heat Mechanism

Fenestration Solar (without blinds) 0.00 0.00 0.00 1.00 1.00 1.00 Shortwave radiation absorbed by floor/furniture

  • Fenestration Solar (with internal blinds) 0.37 0.37 0.37 0.63 0.63 0.63 Blind convection + diffuse radiation
  • Fenestration Conduction 1.00 1.00 1.00 0.00 0.00 0.00 Direct indoor glass surface air convection
  • Opaque Exterior Walls & Roofs 0.00 0.00 0.00 1.00 1.00 1.00 Interior surface radiation exchange

Recessed Fluorescent / LED Lighting 0.30 to 0.50 0.30\text{ to }0.50 0.30 to 0.50 0.50 to 0.70 0.50\text{ to }0.70 0.50 to 0.70 Radiation to room surfaces + ceiling plenum air

Occupants (People) 0.60 to 0.70 0.60\text{ to }0.70 0.60 to 0.70 0.30 to 0.40 0.30\text{ to }0.40 0.30 to 0.40 Convection from skin/clothing + body radiation

Plug Loads & Computers 0.70 to 0.85 0.70\text{ to }0.85 0.70 to 0.85 0.15 to 0.30 0.15\text{ to }0.30 0.15 to 0.30 Internal cooling fan convection + warm casing

  • Infiltration Air 1.00 1.00 1.00 0.00 0.00 0.00 Pure convective air mixing (100% instant)
  • 2. Conduction Time Series Factors (CTSF)

For opaque walls and roofs, the 24-hour conduction heat gain ( q e , θ q_{e,\theta} q e , θ ​ ) at hour θ \theta θ is calculated from historical sol-air temperatures using Conduction Time Series Factors ( c j c_j c j ​ ): q e , θ = A ∑ j = 0 23 c j ⋅ U ⋅ ( T s o l - a i r , θ − j − T indoor ) q_{e,\theta} = A \sum_{j=0}^{23} c_j \cdot U \cdot \left(T_{sol\text{-}air,\theta - j} - T_{\text{indoor}}\right) q e , θ ​ = A j = 0 ∑ 23 ​ c j ​ ⋅ U ⋅ ( T so l - ai r , θ − j ​ − T indoor ​ )

Where ∑ j = 0 23 c j = 1.00 \sum_{j=0}^{23} c_j = 1.00 ∑ j = 0 23 ​ c j ​ = 1.00 . The series factors c j c_j c j ​ define the precise thermal damping and time delay of the assembly mass.

3. Radiant Time Factors (RTF)

Radiant heat gains ( q r , θ q_{r,\theta} q r , θ ​ ) generated across the preceding 24 hours are converted into hourly cooling loads ( Q r , θ Q_{r,\theta} Q r , θ ​ ) using zone Radiant Time Factors ( r j r_j r j ​ ): Q r , θ = ∑ j = 0 23 r j ⋅ q r , θ − j Q_{r,\theta} = \sum_{j=0}^{23} r_j \cdot q_{r,\theta - j} Q r , θ ​ = j = 0 ∑ 23 ​ r j ​ ⋅ q r , θ − j ​

Where ∑ j = 0 23 r j = 1.00 \sum_{j=0}^{23} r_j = 1.00 ∑ j = 0 23 ​ r j ​ = 1.00 . Total zone sensible cooling load ( Q sensible , θ Q_{\text{sensible},\theta} Q sensible , θ ​ ) at hour θ \theta θ is the sum of the instantaneous convective gains and the radiant cooling load: Q sensible , θ = q convective , θ + Q r , θ Q_{\text{sensible},\theta} = q_{\text{convective},\theta} + Q_{r,\theta} Q sensible , θ ​ = q convective , θ ​ + Q r , θ ​

5. NCEES Reference Handbook Navigation Tactics

Fenestration Formulas: Search "Fenestration" or "SHGC" in Section 7 (HVAC & Refrigeration Applications) to find the overall window heat gain equation and typical U U U -factors and SHGC \text{SHGC} SHGC values for double-pane low-e glass.

Sol-Air Temperature: Search "Sol-Air" to access the exact equation T s o l - a i r = T o + ( α I t / h o ) − ( ε Δ R / h o ) T_{sol\text{-}air} = T_o + (\alpha I_t / h_o) - (\varepsilon \Delta R / h_o) T so l - ai r ​ = T o ​ + ( α I t ​ / h o ​ ) − ( ε Δ R / h o ​ ) .

CLTD Table Adjustments: Search "CLTD" to find the temperature correction formula CLTD corr = CLTD + ( 78 − T i ) + ( T o , m − 85 ) \text{CLTD}_{\text{corr}} = \text{CLTD} + (78 - T_i) + (T_{o,m} - 85) CLTD corr ​ = CLTD + ( 78 − T i ​ ) + ( T o , m ​ − 85 ) .

  • 6. Worked Computational Examples
  • Example 1: Sol-Air Temperature Calculation for a Flat Commercial Roof

A dark-colored, flat asphalt membrane roof (solar absorptance α = 0.90 \alpha = 0.90 α = 0.90 , emittance ε = 0.90 \varepsilon = 0.90 ε = 0.90 ) is exposed to peak solar radiation at solar noon in Phoenix, AZ. The following conditions apply:

Outdoor dry-bulb temperature: T o = 104 ∘ F T_o = 104^\circ\text{F} T o ​ = 10 4 ∘ F

Total incident solar radiation: I t = 310 Btu/(hr ⋅ ft 2 ) I_t = 310\text{ Btu/(hr}\cdot\text{ft}^2) I t ​ = 310 Btu/(hr ⋅ ft 2 )

Outside convective heat transfer coefficient: h o = 3.0 Btu/(hr ⋅ ft 2 ⋅ ∘ F) h_o = 3.0\text{ Btu/(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)} h o ​ = 3.0 Btu/(hr ⋅ ft 2 ⋅ ∘ F)

Longwave roof radiation correction factor: Δ R = 20 Btu/(hr ⋅ ft 2 ) \Delta R = 20\text{ Btu/(hr}\cdot\text{ft}^2) Δ R = 20 Btu/(hr ⋅ ft 2 )

Calculate: (a) The sol-air temperature of the dark roof, and (b) The sol-air temperature if the roof is retrofitted with a bright white "cool roof" elastomeric coating having α = 0.25 \alpha = 0.25 α = 0.25 .

Solution:

Sol-air temperature for the dark asphalt roof: T s o l - a i r = T o + α ⋅ I t h o − ε ⋅ Δ R h o T_{sol\text{-}air} = T_o + \frac{\alpha \cdot I_t}{h_o} - \frac{\varepsilon \cdot \Delta R}{h_o} T so l - ai r ​ = T o ​ + h o ​ α ⋅ I t ​ ​ − h o ​ ε ⋅ Δ R ​ T s o l - a i r = 104 + 0.90 × 310 3.0 − 0.90 × 20 3.0 T_{sol\text{-}air} = 104 + \frac{0.90 \times 310}{3.0} - \frac{0.90 \times 20}{3.0} T so l - ai r ​ = 104 + 3.0 0.90 × 310 ​ − 3.0 0.90 × 20 ​ T s o l - a i r = 104 + 93.0 − 6.0 = 191.0 ∘ F T_{sol\text{-}air} = 104 + 93.0 - 6.0 = 191.0^\circ\text{F} T so l - ai r ​ = 104 + 93.0 − 6.0 = 191. 0 ∘ F

Sol-air temperature for the white "cool roof": T s o l - a i r , cool = 104 + 0.25 × 310 3.0 − 0.90 × 20 3.0 T_{sol\text{-}air,\text{cool}} = 104 + \frac{0.25 \times 310}{3.0} - \frac{0.90 \times 20}{3.0} T so l - ai r , cool ​ = 104 + 3.0 0.25 × 310 ​ − 3.0 0.90 × 20 ​ T s o l - a i r , cool = 104 + 25.83 − 6.0 = 123.83 ∘ F T_{sol\text{-}air,\text{cool}} = 104 + 25.83 - 6.0 = 123.83^\circ\text{F} T so l - ai r , cool ​ = 104 + 25.83 − 6.0 = 123.8 3 ∘ F

Conclusion: Retrofitting with a high-albedo cool roof reduces the effective driving temperature difference across the roof by 67.2 ∘ F 67.2^\circ\text{F} 67. 2 ∘ F , drastically reducing roof conductive heat gain.

Example 2: Peak Fenestration Cooling Load Calculation

A west-facing office window assembly has a total area of 250 ft 2 250\text{ ft}^2 250 ft 2 . The fenestration consists of double-pane low-e tinted glazing with the following properties:

Overall assembly U U U -factor: U = 0.35 Btu/(hr ⋅ ft 2 ⋅ ∘ F) U = 0.35\text{ Btu/(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)} U = 0.35 Btu/(hr ⋅ ft 2 ⋅ ∘ F)

  • Solar Heat Gain Coefficient: SHGC = 0.38 \text{SHGC} = 0.38 SHGC = 0.38
  • Interior mini-blinds with an Interior Attenuation Coefficient: IAC = 0.70 \text{IAC} = 0.70 IAC = 0.70
  • Outdoor design dry-bulb: T o = 96 ∘ F T_o = 96^\circ\text{F} T o ​ = 9 6 ∘ F
  • Indoor design setpoint: T i = 74 ∘ F T_i = 74^\circ\text{F} T i ​ = 7 4 ∘ F

Peak 4:00 PM incident solar irradiance on west facade: E t = 215 Btu/(hr ⋅ ft 2 ) E_t = 215\text{ Btu/(hr}\cdot\text{ft}^2) E t ​ = 215 Btu/(hr ⋅ ft 2 )

Calculate: (a) Fenestration conductive heat gain, (b) Fenestration solar radiation heat gain, and (c) Total instantaneous peak fenestration heat gain.

Solution:

Calculate conductive heat gain: q cond = U ⋅ A ⋅ ( T o − T i ) = 0.35 × 250 ft 2 × ( 96 − 74 ) ∘ F = 0.35 × 250 × 22 = 1 , 925 Btu/hr q_{\text{cond}} = U \cdot A \cdot (T_o - T_i) = 0.35 \times 250\text{ ft}^2 \times (96 - 74)^\circ\text{F} = 0.35 \times 250 \times 22 = 1,925\text{ Btu/hr} q cond ​ = U ⋅ A ⋅ ( T o ​ − T i ​ ) = 0.35 × 250 ft 2 × ( 96 − 74 ) ∘ F = 0.35 × 250 × 22 = 1 , 925 Btu/hr

Calculate solar radiation heat gain: q solar = A ⋅ SHGC ⋅ IAC ⋅ E t = 250 ft 2 × 0.38 × 0.70 × 215 Btu/(hr ⋅ ft 2 ) q_{\text{solar}} = A \cdot \text{SHGC} \cdot \text{IAC} \cdot E_t = 250\text{ ft}^2 \times 0.38 \times 0.70 \times 215\text{ Btu/(hr}\cdot\text{ft}^2) q solar ​ = A ⋅ SHGC ⋅ IAC ⋅ E t ​ = 250 ft 2 × 0.38 × 0.70 × 215 Btu/(hr ⋅ ft 2 ) q solar = 250 × 0.266 × 215 = 14 , 297.5 Btu/hr q_{\text{solar}} = 250 \times 0.266 \times 215 = 14,297.5\text{ Btu/hr} q solar ​ = 250 × 0.266 × 215 = 14 , 297.5 Btu/hr

Calculate total instantaneous fenestration heat gain: q fen = q cond + q solar = 1 , 925 + 14 , 297.5 = 16 , 222.5 Btu/hr = 1.352 Tons q_{\text{fen}} = q_{\text{cond}} + q_{\text{solar}} = 1,925 + 14,297.5 = 16,222.5\text{ Btu/hr} = 1.352\text{ Tons} q fen ​ = q cond ​ + q solar ​ = 1 , 925 + 14 , 297.5 = 16 , 222.5 Btu/hr = 1.352 Tons

(Notice that solar radiation accounts for 88.1% of the total window cooling load!)