6.5 Ventilation Loads & Sensible / Latent / Total Cooling Load Synthesis
PE Mechanical: HVAC and Refrigeration Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview, Reference Handbook & Engineering Foundations
1.1 NCEES Exam Specification, CBT Delivery & Reference Handbook Strategy 1.2 Engineering Units, Dimensional Analysis & Physical Property Lookups 1.3 Engineering Economics, Life Cycle Cost Analysis & Equipment Financial Evaluation 1.4 Electrical Foundations, Motor Ratings & Variable Frequency Drives (VFDs)
2 Chapter 2: Thermodynamics & Energy Balances
2.1 First and Second Laws of Thermodynamics & Open/Closed System Energy Balances 2.2 Thermodynamic Cycles: Carnot, Rankine, Brayton & Reversed Carnot Limit 2.3 Gas & Vapor Property Evaluation: Steam Tables, Superheat & Subcooling 2.4 Mass, Energy & Combustion Balances for HVAC Equipment
3 Chapter 3: Psychrometrics, Moist Air Processes & Humidity Equipment
3.1 Psychrometric Properties: DBT, WBT, DPT, RH, Humidity Ratio & Enthalpy 3.2 Chart Reading & Psychrometric Equations at Sea Level vs. Altitude (5,000 ft) 3.3 Basic Psychrometric Processes: Sensible Heating/Cooling, Humidification & Dehumidification 3.4 Mixed Air Calculations & Complex Air Conditioning Cycles (Preheat, Reheat & Bypass) 3.5 Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP) & Coil Bypass Factor 3.6 Humidification & Dehumidification Equipment: Steam, Adiabatic, Desiccant & Low-Temperature Processes
4 Chapter 4: Heat Transfer Principles & Sizing
4.1 Steady-State Conduction & Multilayer Thermal Resistance (R-Value & U-Factor) 4.2 Convective Heat Transfer & Forced/Natural Convection Coefficients 4.3 Radiation Heat Transfer, Surface Emissivity & View Factors 4.4 Overall Heat Transfer Coefficients, Fouling Factors & Transient/Thermal Mass Effects 4.5 Heat Exchanger Analysis: Log Mean Temperature Difference (LMTD) & Effectiveness-NTU (ε-NTU)
5 Chapter 5: Fluid Mechanics & Hydraulic Fundamentals
5.1 Fluid Statics, Incompressible Continuity & Bernoulli Energy Equation 5.2 Pipe Friction, Moody Diagram & Darcy-Weisbach / Hazen-Williams Calculations 5.3 Minor Losses: Equivalent Length, Loss Coefficients (K-factors) & Total System Head 5.4 Pump Sizing, Net Positive Suction Head (NPSHa vs NPSHr) & Cavitation Prevention 5.5 Affinity Laws & Parallel/Series Pump/Fan System Curves
6 Chapter 6: Heating & Cooling Load Calculations
6.1 Outdoor & Indoor Design Conditions (ASHRAE Fundamentals, Climatic Data & Indoor Setpoints) 6.2 Envelope Heat Transmission & Infiltration/Exfiltration Load Methods 6.3 Solar Heat Gain (SHGC), Fenestration & Cooling Load Temperature Difference / Radiant Time Series (CLTD/RTS) 6.4 Internal Heat Gains: Lighting, People, Equipment & Diversity Factors 6.5 Ventilation Loads & Sensible / Latent / Total Cooling Load Synthesis
7 Chapter 7: Refrigeration Principles, Cycles & Cold Storage Applications
7.1 Standard Vapor-Compression Refrigeration Cycle on P-h & T-s Diagrams 7.2 Refrigeration Cycle Performance Metrics: COP, EER, SEER, kW/ton & Ton of Refrigeration 7.3 Cycle Enhancements: Subcooling, Superheating, Liquid-Suction Heat Exchangers & Economizers 7.4 Multi-Stage & Cascade Refrigeration Systems: Intercooling & Flash Gas Removal 7.5 Absorption Refrigeration Cycles: Water-Lithium Bromide & Ammonia-Water Systems 7.6 Food Processing & Cold Storage Refrigeration: Product Load, Pull-Down & Storage Design
8 Chapter 8: Refrigerants, Environmental Regulations & Safety
8.1 Refrigerant Classifications, Nomenclature & Thermodynamic Properties (ASHRAE Standard 34) 8.2 AIM Act, EPA Technology Transitions Sector GWP Limits & Low-GWP Refrigerants (R-32, R-454B) 8.3 Refrigerant Safety Requirements & Machinery Room Design (ASHRAE Standard 15) 8.4 Refrigerant Piping Sizing, Oil Return, Traps & Double Risers
9 Chapter 9: HVAC Equipment & Primary Machinery
9.1 Compressors: Reciprocating, Rotary, Scroll, Screw & Centrifugal 9.2 Condensers: Air-Cooled, Water-Cooled & Evaporative Condensers 9.3 Evaporators & Direct Expansion (DX) vs Liquid Chilling Coils 9.4 Water Chillers: Centrifugal, Screw & Scroll with ASHRAE 90.1 Path A/B IPLV Ratings 9.5 Cooling Towers: Range, Approach, Evaporation, Blowdown & Legionella Control 9.6 Heat Pumps & Variable Refrigerant Flow (VRF): Balance Point, Defrost & Heat Recovery 9.7 Thermal Energy Storage: Full vs. Partial Storage, Chilled Water & Ice Systems
10 Chapter 10: Air-Side Systems & Distribution
10.1 Air Handling Units (AHUs), Dedicated Outdoor Air Systems (DOAS) & Fan-Coil Units 10.2 Duct Design Methodologies: Equal Friction, Static Regain & Velocity Reduction 10.3 Duct Fittings, Dynamic Pressure Losses & SMACNA Construction Standards 10.4 Fan Types, Performance Curves, System Effect Factors & Surge/Stall Dynamics 10.5 Variable Air Volume (VAV) Systems, Terminal Boxes & Space Air Diffusion (ADPI) 10.6 Cooling & Heating Coil Selection: Face Velocity, Rows, Circuiting & Freeze Protection
11 Chapter 11: Hydronic, Steam & Fuel Distribution and Heating Plant
11.1 Hydronic System Architectures: Primary-Only, Primary-Secondary & Variable Primary Flow (VPF) 11.2 Hydronic Pipe Sizing, Velocity Limits & Closed/Open Expansion Tank Sizing 11.3 Control Valves: 2-Way vs 3-Way, Valve Authority (N), Cv Calculations & Characteristic Curves 11.4 Boilers & Heating Hot Water Systems: Condensing vs Non-Condensing & Water Treatment 11.5 Furnaces & Gas-Fired Heating Equipment: AFUE, Temperature Rise, Combustion Air & Vent Categories 11.6 Steam & Condensate Distribution: Latent Heat, Trap Selection, Flash Steam & Stall 11.7 Fuel Gas & Fuel Oil Piping: Demand, Sizing Method, Pressure Drop & Storage Systems
12 Chapter 12: HVAC Control Concepts, Sensors & Sequences
12.1 Sensors, Actuators & Dampers: Selection, Placement, Fail-Safe Position & Damper Authority 12.2 Control Loops: Proportional Offset, PID Action, Reset Strategies & Standard Sequences
13 Chapter 13: Building Energy, Ventilation & Indoor Environmental Quality Codes
13.1 ASHRAE Standard 62.1: Ventilation Rate Procedure (VRP), Indoor Air Quality Procedure & DCV 13.2 ASHRAE Standard 90.1: Building Energy Envelope, Mechanical Efficiency & Economizer Mandates 13.3 ASHRAE Standard 55: Thermal Environmental Conditions, PMV/PPD & Adaptive Comfort Models 13.4 Energy Recovery Systems: Enthalpy Wheels, Fixed-Plate Exchangers, Heat Pipes & Runaround Loops
14 Chapter 14: Supportive Engineering Knowledge, Life Safety & Operations
14.1 Air Filtration Standards: MERV Ratings (ASHRAE 52.2), HEPA & Gas-Phase Adsorption 14.2 Life Safety Systems: Fire/Smoke Dampers, Stairwell Pressurization (NFPA 92) & Smoke Control (NFPA 90A) 14.3 Acoustical Control & Vibration Isolation in HVAC Systems (NC / RC Criteria)
6.5 Ventilation Loads & Sensible / Latent / Total Cooling Load Synthesis
Key Takeaways Explain This Topic AI
ASHRAE Standard 62.1-2022 Ventilation Rate Procedure defines breathing zone outdoor airflow as V_bz = R_p * P_z + R_a * A_z, corrected by zone air distribution effectiveness E_z to find zone outdoor airflow V_oz.
Outdoor ventilation air introduced at the central air handling unit does NOT impose a load on the occupied space; it acts as a primary load on the central cooling and heating coils.
The Room Sensible Heat Ratio (RSHR = q_s,space / q_total,space) establishes the slope of the space conditioning process line on the psychrometric chart, governing required supply air temperature and apparatus dew point (ADP).
Required supply airflow is determined strictly by the room sensible heat load and temperature differential: CFM_supply = q_s,space / (1.08 * (T_room - T_supply)).
Mixed air properties represent mass-weighted averages of outdoor air and return air: T_mix = (CFM_oa * T_oa + CFM_ra * T_ra) / CFM_supply, with total cooling coil tonnage calculated via q_total = 4.5 * CFM_supply * (h_mix - h_leaving).
Last updated: August 2026
6.5 Ventilation Loads & Sensible / Latent / Total Cooling Load Synthesis
The final phase of load calculations synthesizes all individual load components—envelope transmission, fenestration conduction, solar radiation, lighting, occupants, plug loads, and outdoor ventilation air—into a unified psychrometric system analysis. Correctly synthesizing these loads allows the mechanical engineer to determine required supply airflow ( CFM supply \text{CFM}_{\text{supply}} CFM supply ), establish the supply air temperature ( T supply T_{\text{supply}} T supply ) and apparatus dew point (ADP), evaluate mixed air properties ( T mix , W mix , h mix T_{\text{mix}}, W_{\text{mix}}, h_{\text{mix}} T mix , W mix , h mix ), and size central cooling and heating coils in Tons of Refrigeration (TR) or MBH.
1. ASHRAE Standard 62.1 Ventilation Rate Procedure (VRP)
Outdoor air must be continuously introduced to occupied spaces to dilute bioeffluents, volatile organic compounds (VOCs), and off-gassing from building materials. +-----------------------------------------------------------------------------------------+
- | ASHRAE 62.1 VENTILATION RATE PROCEDURE (VRP) FLOWCHART |
- +-----------------------------------------------------------------------------------------+
- | 1. Breathing Zone Outdoor Airflow: V_bz = (R_p * P_z) + (R_a * A_z) |
- | | |
- | 2. Zone Outdoor Airflow: V_oz = V_bz / E_z |
- | | |
- | 3. Multi-Zone System Efficiency: E_v = 1 + X_s - Z_p (or tabular lookup) |
- | | |
- | 4. Total System Outdoor Air Intake: V_ot = V_ou / E_v |
- +-----------------------------------------------------------------------------------------+
1. Breathing Zone Outdoor Airflow ( V b z V_{bz} V b z ) V b z = R p ⋅ P z + R a ⋅ A z V_{bz} = R_p \cdot P_z + R_a \cdot A_z V b z = R p ⋅ P z + R a ⋅ A z
Where:
R p = Outdoor airflow rate per person ( CFM/person, typically 5 to 10 CFM/person ) R_p = \text{Outdoor airflow rate per person } (\text{CFM/person, typically } 5\text{ to }10\text{ CFM/person}) R p = Outdoor airflow rate per person ( CFM/person, typically 5 to 10 CFM/person )
P z = Design zone population (occupants) P_z = \text{Design zone population (occupants)} P z = Design zone population (occupants)
R a = Outdoor airflow rate per unit area ( CFM/ft 2 , typically 0.06 to 0.12 CFM/ft 2 ) R_a = \text{Outdoor airflow rate per unit area } (\text{CFM/ft}^2\text{, typically } 0.06\text{ to }0.12\text{ CFM/ft}^2) R a = Outdoor airflow rate per unit area ( CFM/ft 2 , typically 0.06 to 0.12 CFM/ft 2 )
A z = Zone floor area ( ft 2 ) A_z = \text{Zone floor area } (\text{ft}^2) A z = Zone floor area ( ft 2 )
2. Zone Outdoor Airflow ( V o z V_{oz} V oz ) V o z = V b z E z V_{oz} = \frac{V_{bz}}{E_z} V oz = E z V b z
Where E z E_z E z is the Zone Air Distribution Effectiveness :
E z = 1.0 E_z = 1.0 E z = 1.0 : Ceiling supply of cool air; or floor supply of warm air ( T supply < T room + 15 ∘ F T_{\text{supply}} < T_{\text{room}} + 15^\circ\text{F} T supply < T room + 1 5 ∘ F ).
E z = 0.8 E_z = 0.8 E z = 0.8 : Ceiling supply of warm air with ceiling return ( T supply > T room T_{\text{supply}} > T_{\text{room}} T supply > T room ), due to thermal stratification and short-circuiting.
2. Ventilation Load Allocation: Coil Load vs. Space Load
A critical distinction on the PE Mechanical exam is the physical location where outdoor air enters the building:
Outdoor Air Introduced at Central AHU (Ventilation): Outdoor air mixes with return air in the mixing plenum before passing across the central cooling/heating coil. This air is conditioned before entering the room. Therefore, ventilation outdoor air is a central coil load, NOT a direct space load .
Uncontrolled Infiltration Across Envelope: Outdoor air leaks directly into the room through cracks and doors without conditioning. Therefore, infiltration is a direct space sensible and latent load . +-----------------------------------------------------------------------------------------+
- | SPACE LOAD VS. CENTRAL COIL LOAD MATRIX |
- +-----------------------------------------------------------------------------------------+
- | LOAD COMPONENT | IMPOSES LOAD ON SPACE? | IMPOSES LOAD ON COIL? |
- | -------------------------------------- | ---------------------- | --------------------- |
- | Envelope Conduction (Walls/Roofs) | YES (Sensible) | YES (Sensible) |
- | Window Solar Radiation (SHGC) | YES (Sensible) | YES (Sensible) |
- | Lighting (Room Fraction) | YES (Sensible) | YES (Sensible) |
- | Lighting (Plenum Fraction) | NO | YES (Sensible) |
- | People (Occupants) | YES (Sensible+Latent) | YES (Sensible+Latent) |
- | Equipment & Plug Loads | YES (Sensible) | YES (Sensible) |
- | Envelope Infiltration | YES (Sensible+Latent) | YES (Sensible+Latent) |
- | Central Ventilation Outdoor Air | NO | YES (Sensible+Latent) |
- | Supply Fan Motor Heat | NO | YES (Sensible) |
- | Return Air Duct Heat Gain | NO | YES (Sensible) |
- +-----------------------------------------------------------------------------------------+
- 3. Sensible Heat Ratios & Supply Airflow Sizing
Psychrometric load synthesis establishes the operating state points connecting room conditions, mixed air conditions, and coil leaving conditions. +-----------------------------------------------------------------------------------------+
- | PSYCHROMETRIC LOAD PROCESS LINES (RSHR VS. GSHR) |
- +-----------------------------------------------------------------------------------------+
- | Humidity Ratio (W) |
- | ^ |
- | | (O) Outdoor Air State |
- | | . |
- | | . |
- | | (M) Mixed Air State |
- | | / . |
- | | / . |
- | | / . |
- | | / (R) Room Air State (75°F, 50% RH) |
- | | / . |
- | | / . <--- Room Sensible Heat Ratio (RSHR) Slope |
- | | / . |
- | | (S) Supply Air State (55°F DB) |
- | | . |
- | | (ADP) Apparatus Dew Point |
- | +--------------------------------------------------------------------> Dry Bulb (T) |
- +-----------------------------------------------------------------------------------------+
- 1. Room Sensible Heat Ratio (RSHR)
The slope of the state line between supply air ( S S S ) and room air ( R R R ) is governed by the space loads: RSHR = q space, sensible q space, sensible + q space, latent = q s s q s t \text{RSHR} = \frac{q_{\text{space, sensible}}}{q_{\text{space, sensible}} + q_{\text{space, latent}}} = \frac{q_{ss}}{q_{st}} RSHR = q space, sensible + q space, latent q space, sensible = q s t q ss
2. Grand Sensible Heat Ratio (GSHR)
The slope of the state line across the cooling coil between mixed air ( M M M ) and leaving supply air ( S S S ) includes both room loads and ventilation outdoor air loads: GSHR = q total, sensible q total, sensible + q total, latent = q s s + q o a , s q s t + q o a , t \text{GSHR} = \frac{q_{\text{total, sensible}}}{q_{\text{total, sensible}} + q_{\text{total, latent}}} = \frac{q_{ss} + q_{oa,s}}{q_{st} + q_{oa,t}} GSHR = q total, sensible + q total, latent q total, sensible = q s t + q o a , t q ss + q o a , s
3. Supply Airflow ( CFM supply \text{CFM}_{\text{supply}} CFM supply ) Determination
Supply airflow is determined strictly by the room sensible heat load ( q s s q_{ss} q ss ) and design supply-to-room temperature difference (typically Δ T = 75 ∘ F − 55 ∘ F = 20 ∘ F \Delta T = 75^\circ\text{F} - 55^\circ\text{F} = 20^\circ\text{F} Δ T = 7 5 ∘ F − 5 5 ∘ F = 2 0 ∘ F ): CFM supply = q space, sensible 1.08 × ( T room − T supply ) \text{CFM}_{\text{supply}} = \frac{q_{\text{space, sensible}}}{1.08 \times (T_{\text{room}} - T_{\text{supply}})} CFM supply = 1.08 × ( T room − T supply ) q space, sensible
4. Mixed Air Psychrometric State Evaluation
When outdoor air and return air mix in the AHU plenum, the mixed air state ( M M M ) represents a mass-weighted average: +-----------------------------------------------------------------------------------------+
- | MIXED AIR PSYCHROMETRIC EQUATIONS |
- +-----------------------------------------------------------------------------------------+
- | Mixed Dry-Bulb: T_mix = (CFM_oa * T_oa + CFM_ra * T_ra) / CFM_supply |
- | Mixed Humidity: W_mix = (CFM_oa * W_oa + CFM_ra * W_ra) / CFM_supply |
- | Mixed Enthalpy: h_mix = (CFM_oa * h_oa + CFM_ra * h_ra) / CFM_supply |
- +-----------------------------------------------------------------------------------------+
Letting the outdoor air fraction be X o a = CFM o a CFM supply X_{oa} = \frac{\text{CFM}_{oa}}{\text{CFM}_{\text{supply}}} X o a = CFM supply CFM o a : T mix = X o a ⋅ T o a + ( 1 − X o a ) ⋅ T r a T_{\text{mix}} = X_{oa} \cdot T_{oa} + (1 - X_{oa}) \cdot T_{ra} T mix = X o a ⋅ T o a + ( 1 − X o a ) ⋅ T r a W mix = X o a ⋅ W o a + ( 1 − X o a ) ⋅ W r a W_{\text{mix}} = X_{oa} \cdot W_{oa} + (1 - X_{oa}) \cdot W_{ra} W mix = X o a ⋅ W o a + ( 1 − X o a ) ⋅ W r a h mix = X o a ⋅ h o a + ( 1 − X o a ) ⋅ h r a h_{\text{mix}} = X_{oa} \cdot h_{oa} + (1 - X_{oa}) \cdot h_{ra} h mix = X o a ⋅ h o a + ( 1 − X o a ) ⋅ h r a
5. Total Cooling Coil Capacity & Tonnage Calculations
Once mixed air and leaving coil states are established, central coil capacity is calculated using the three standard moist air equations:
1. Coil Sensible Capacity ( q coil, sensible q_{\text{coil, sensible}} q coil, sensible ) q coil, sensible = 1.08 × CFM supply × ( T mix − T leaving ) q_{\text{coil, sensible}} = 1.08 \times \text{CFM}_{\text{supply}} \times (T_{\text{mix}} - T_{\text{leaving}}) q coil, sensible = 1.08 × CFM supply × ( T mix − T leaving )
2. Coil Latent Capacity ( q coil, latent q_{\text{coil, latent}} q coil, latent ) q coil, latent = 4840 × CFM supply × ( W mix − W leaving ) q_{\text{coil, latent}} = 4840 \times \text{CFM}_{\text{supply}} \times (W_{\text{mix}} - W_{\text{leaving}}) q coil, latent = 4840 × CFM supply × ( W mix − W leaving )
3. Total Coil Capacity ( q coil, total q_{\text{coil, total}} q coil, total ) q coil, total = 4.5 × CFM supply × ( h mix − h leaving ) q_{\text{coil, total}} = 4.5 \times \text{CFM}_{\text{supply}} \times (h_{\text{mix}} - h_{\text{leaving}}) q coil, total = 4.5 × CFM supply × ( h mix − h leaving ) Coil Tonnage (TR) = q coil, total (Btu/hr) 12 , 000 Btu/(hr ⋅ Ton) \text{Coil Tonnage (TR)} = \frac{q_{\text{coil, total}}\text{ (Btu/hr)}}{12,000\text{ Btu/(hr}\cdot\text{Ton)}} Coil Tonnage (TR) = 12 , 000 Btu/(hr ⋅ Ton) q coil, total (Btu/hr)
Fan Heat Gain & Duct Parasitic Corrections
Supply Fan Temperature Rise (Draw-Through Fan): The fan is located downstream of the cooling coil. Motor and impeller mechanical dissipation heat the supply air before it reaches the zone: Δ T fan = Δ P total (in. w.g.) 6356 × η fan × η motor × 2545 × 1 1.08 ≈ Δ P total 2.7 × η total \Delta T_{\text{fan}} = \frac{\Delta P_{\text{total}}\text{ (in. w.g.)}}{6356 \times \eta_{\text{fan}} \times \eta_{\text{motor}}} \times 2545 \times \frac{1}{1.08} \approx \frac{\Delta P_{\text{total}}}{2.7 \times \eta_{\text{total}}} Δ T fan = 6356 × η fan × η motor Δ P total (in. w.g.) × 2545 × 1.08 1 ≈ 2.7 × η total Δ P total Typically, Δ T fan = 1.0 ∘ F to 2.5 ∘ F \Delta T_{\text{fan}} = 1.0^\circ\text{F}\text{ to }2.5^\circ\text{F} Δ T fan = 1. 0 ∘ F to 2. 5 ∘ F . To deliver 55 ∘ F 55^\circ\text{F} 5 5 ∘ F air to the room, the coil must leave at T coil, leaving = 55 − Δ T fan = 53 ∘ F T_{\text{coil, leaving}} = 55 - \Delta T_{\text{fan}} = 53^\circ\text{F} T coil, leaving = 55 − Δ T fan = 5 3 ∘ F .
Duct Heat Gain: Conditioned supply air traveling through unconditioned ceiling plenums absorbs 1.0 ∘ F to 2.0 ∘ F 1.0^\circ\text{F}\text{ to }2.0^\circ\text{F} 1. 0 ∘ F to 2. 0 ∘ F of sensible heat.
6. NCEES Reference Handbook Navigation Tactics
ASHRAE 62.1 Equations: Search "Ventilation Rate Procedure" or "Breathing Zone" in Section 7 (HVAC & Refrigeration Applications) to find V b z = R p P z + R a A z V_{bz} = R_p P_z + R_a A_z V b z = R p P z + R a A z and E z E_z E z tables.
Psychrometric Equations: Search "Sensible Heat Ratio" or "RSHR" in Section 6 (Psychrometrics) to find formulas for RSHR, GSHR, mixed air equations, and shortcut constants ( 1.08 , 4840 , 4.5 1.08, 4840, 4.5 1.08 , 4840 , 4.5 ).
Fan Temperature Rise: Search "Fan Heat Gain" to find the exact mechanical energy temperature rise equation.
- 7. Master Worked Computational Example
- Comprehensive Building Cooling Load & Psychrometric Synthesis
A single-zone commercial office building ( 12 , 000 ft 2 12,000\text{ ft}^2 12 , 000 ft 2 , 14 ft 14\text{ ft} 14 ft floor-to-floor) in Charlotte, NC has the following design parameters:
Indoor Design Conditions: 75 ∘ F 75^\circ\text{F} 7 5 ∘ F DB, 50 % RH 50\%\text{ RH} 50% RH ( W r = 0.00925 lb w / lb d a W_r = 0.00925\text{ lb}_w/\text{lb}_{da} W r = 0.00925 lb w / lb d a , h r = 28.14 Btu/lb h_r = 28.14\text{ Btu/lb} h r = 28.14 Btu/lb ).
Outdoor Design Conditions (0.4%): 95 ∘ F 95^\circ\text{F} 9 5 ∘ F DB, 75 ∘ F 75^\circ\text{F} 7 5 ∘ F MCWB ( W o = 0.01410 lb w / lb d a W_o = 0.01410\text{ lb}_w/\text{lb}_{da} W o = 0.01410 lb w / lb d a , h o = 38.60 Btu/lb h_o = 38.60\text{ Btu/lb} h o = 38.60 Btu/lb ).
Occupancy: 100 people ( q s = 250 Btu/hr q_s = 250\text{ Btu/hr} q s = 250 Btu/hr , q l = 200 Btu/hr q_l = 200\text{ Btu/hr} q l = 200 Btu/hr per person).
ASHRAE 62.1 Ventilation Rates: R p = 5 CFM/person R_p = 5\text{ CFM/person} R p = 5 CFM/person , R a = 0.06 CFM/ft 2 R_a = 0.06\text{ CFM/ft}^2 R a = 0.06 CFM/ft 2 , E z = 1.0 E_z = 1.0 E z = 1.0 .
Lighting & Plug Loads: Lighting = 1.0 W/ft 2 1.0\text{ W/ft}^2 1.0 W/ft 2 (all entering room space); Plug Loads = 0.75 W/ft 2 0.75\text{ W/ft}^2 0.75 W/ft 2 .
Building Envelope & Glazing Transmission: Net space envelope conduction + solar heat gain = 78 , 000 Btu/hr 78,000\text{ Btu/hr} 78 , 000 Btu/hr (100% sensible).
Infiltration: 0.15 ACH 0.15\text{ ACH} 0.15 ACH (unconditioned direct space infiltration).
Supply Air Conditions: Air leaves cooling coil at 53.0 ∘ F 53.0^\circ\text{F} 53. 0 ∘ F DB saturated ( W coil = 0.00850 lb w / lb d a W_{\text{coil}} = 0.00850\text{ lb}_w/\text{lb}_{da} W coil = 0.00850 lb w / lb d a , h coil = 22.00 Btu/lb h_{\text{coil}} = 22.00\text{ Btu/lb} h coil = 22.00 Btu/lb ). Supply fan adds 2.0 ∘ F 2.0^\circ\text{F} 2. 0 ∘ F of draw-through heat, delivering air to the space at T supply = 55.0 ∘ F T_{\text{supply}} = 55.0^\circ\text{F} T supply = 55. 0 ∘ F DB.
Calculate: (1) Required ventilation airflow, (2) Space sensible and latent loads, (3) Required supply airflow, (4) Mixed air psychrometric properties, (5) Total cooling coil capacity and chiller tonnage.
Solution Step-by-Step:
Step 1: Calculate Outdoor Ventilation Airflow (ASHRAE 62.1) V b z = ( 5 CFM/person × 100 ) + ( 0.06 CFM/ft 2 × 12 , 000 ft 2 ) = 500 + 720 = 1 , 220 CFM V_{bz} = (5\text{ CFM/person} \times 100) + (0.06\text{ CFM/ft}^2 \times 12,000\text{ ft}^2) = 500 + 720 = 1,220\text{ CFM} V b z = ( 5 CFM/person × 100 ) + ( 0.06 CFM/ft 2 × 12 , 000 ft 2 ) = 500 + 720 = 1 , 220 CFM V o a = 1 , 220 1.0 = 1 , 220 CFM V_{oa} = \frac{1,220}{1.0} = 1,220\text{ CFM} V o a = 1.0 1 , 220 = 1 , 220 CFM
Step 2: Calculate Infiltration Load Entering Space Volume = 12 , 000 ft 2 × 14 ft = 168 , 000 ft 3 \text{Volume } = 12,000\text{ ft}^2 \times 14\text{ ft} = 168,000\text{ ft}^3 Volume = 12 , 000 ft 2 × 14 ft = 168 , 000 ft 3 CFM inf = 0.15 × 168 , 000 60 = 420 CFM \text{CFM}_{\text{inf}} = \frac{0.15 \times 168,000}{60} = 420\text{ CFM} CFM inf = 60 0.15 × 168 , 000 = 420 CFM q s , inf = 1.08 × 420 × ( 95 − 75 ) = 1.08 × 420 × 20 = 9 , 072 Btu/hr q_{s,\text{inf}} = 1.08 \times 420 \times (95 - 75) = 1.08 \times 420 \times 20 = 9,072\text{ Btu/hr} q s , inf = 1.08 × 420 × ( 95 − 75 ) = 1.08 × 420 × 20 = 9 , 072 Btu/hr q l , inf = 4840 × 420 × ( 0.01410 − 0.00925 ) = 4840 × 420 × 0.00485 = 9 , 859 Btu/hr q_{l,\text{inf}} = 4840 \times 420 \times (0.01410 - 0.00925) = 4840 \times 420 \times 0.00485 = 9,859\text{ Btu/hr} q l , inf = 4840 × 420 × ( 0.01410 − 0.00925 ) = 4840 × 420 × 0.00485 = 9 , 859 Btu/hr
Step 3: Calculate Internal Heat Gains Entering Space
Occupants: q s , occ = 100 × 250 = 25 , 000 Btu/hr q_{s,\text{occ}} = 100 \times 250 = 25,000\text{ Btu/hr} q s , occ = 100 × 250 = 25 , 000 Btu/hr ; q l , occ = 100 × 200 = 20 , 000 Btu/hr q_{l,\text{occ}} = 100 \times 200 = 20,000\text{ Btu/hr} q l , occ = 100 × 200 = 20 , 000 Btu/hr
Lighting: q light = 12 , 000 ft 2 × 1.0 W/ft 2 × 3.412 = 40 , 944 Btu/hr q_{\text{light}} = 12,000\text{ ft}^2 \times 1.0\text{ W/ft}^2 \times 3.412 = 40,944\text{ Btu/hr} q light = 12 , 000 ft 2 × 1.0 W/ft 2 × 3.412 = 40 , 944 Btu/hr
Plug Loads: q plug = 12 , 000 ft 2 × 0.75 W/ft 2 × 3.412 = 30 , 708 Btu/hr q_{\text{plug}} = 12,000\text{ ft}^2 \times 0.75\text{ W/ft}^2 \times 3.412 = 30,708\text{ Btu/hr} q plug = 12 , 000 ft 2 × 0.75 W/ft 2 × 3.412 = 30 , 708 Btu/hr
Step 4: Sum Total Space Loads & Determine Supply Airflow ( CFM supply \text{CFM}_{\text{supply}} CFM supply ) q space, sensible = 78 , 000 (envelope) + 9 , 072 (inf) + 25 , 000 (occ) + 40 , 944 (light) + 30 , 708 (plug) = 183 , 724 Btu/hr q_{\text{space, sensible}} = 78,000\text{ (envelope)} + 9,072\text{ (inf)} + 25,000\text{ (occ)} + 40,944\text{ (light)} + 30,708\text{ (plug)} = 183,724\text{ Btu/hr} q space, sensible = 78 , 000 (envelope) + 9 , 072 (inf) + 25 , 000 (occ) + 40 , 944 (light) + 30 , 708 (plug) = 183 , 724 Btu/hr q space, latent = 9 , 859 (inf) + 20 , 000 (occ) = 29 , 859 Btu/hr q_{\text{space, latent}} = 9,859\text{ (inf)} + 20,000\text{ (occ)} = 29,859\text{ Btu/hr} q space, latent = 9 , 859 (inf) + 20 , 000 (occ) = 29 , 859 Btu/hr q space, total = 183 , 724 + 29 , 859 = 213 , 583 Btu/hr q_{\text{space, total}} = 183,724 + 29,859 = 213,583\text{ Btu/hr} q space, total = 183 , 724 + 29 , 859 = 213 , 583 Btu/hr RSHR = 183 , 724 213 , 583 = 0.860 \text{RSHR} = \frac{183,724}{213,583} = 0.860 RSHR = 213 , 583 183 , 724 = 0.860 CFM supply = q space, sensible 1.08 × ( T room − T supply ) = 183 , 724 1.08 × ( 75 − 55 ) = 183 , 724 21.6 = 8 , 506 CFM \text{CFM}_{\text{supply}} = \frac{q_{\text{space, sensible}}}{1.08 \times (T_{\text{room}} - T_{\text{supply}})} = \frac{183,724}{1.08 \times (75 - 55)} = \frac{183,724}{21.6} = 8,506\text{ CFM} CFM supply = 1.08 × ( T room − T supply ) q space, sensible = 1.08 × ( 75 − 55 ) 183 , 724 = 21.6 183 , 724 = 8 , 506 CFM
Step 5: Evaluate Mixed Air State at AHU Intake Outdoor Air Fraction X o a = 1 , 220 CFM 8 , 506 CFM = 0.1434 (14.34%) \text{Outdoor Air Fraction } X_{oa} = \frac{1,220\text{ CFM}}{8,506\text{ CFM}} = 0.1434\text{ (14.34\%)} Outdoor Air Fraction X o a = 8 , 506 CFM 1 , 220 CFM = 0.1434 (14.34%) Return Airflow CFM r a = 8 , 506 − 1 , 220 = 7 , 286 CFM \text{Return Airflow } \text{CFM}_{ra} = 8,506 - 1,220 = 7,286\text{ CFM} Return Airflow CFM r a = 8 , 506 − 1 , 220 = 7 , 286 CFM T mix = ( 0.1434 × 95 ) + ( 1 − 0.1434 ) × 75 = 13.62 + 64.25 = 77.87 ∘ F T_{\text{mix}} = (0.1434 \times 95) + (1 - 0.1434) \times 75 = 13.62 + 64.25 = 77.87^\circ\text{F} T mix = ( 0.1434 × 95 ) + ( 1 − 0.1434 ) × 75 = 13.62 + 64.25 = 77.8 7 ∘ F W mix = ( 0.1434 × 0.01410 ) + ( 1 − 0.1434 ) × 0.00925 = 0.002022 + 0.007924 = 0.009946 lb w / lb d a W_{\text{mix}} = (0.1434 \times 0.01410) + (1 - 0.1434) \times 0.00925 = 0.002022 + 0.007924 = 0.009946\text{ lb}_w/\text{lb}_{da} W mix = ( 0.1434 × 0.01410 ) + ( 1 − 0.1434 ) × 0.00925 = 0.002022 + 0.007924 = 0.009946 lb w / lb d a h mix = ( 0.1434 × 38.60 ) + ( 1 − 0.1434 ) × 28.14 = 5.535 + 24.105 = 29.64 Btu/lb h_{\text{mix}} = (0.1434 \times 38.60) + (1 - 0.1434) \times 28.14 = 5.535 + 24.105 = 29.64\text{ Btu/lb} h mix = ( 0.1434 × 38.60 ) + ( 1 − 0.1434 ) × 28.14 = 5.535 + 24.105 = 29.64 Btu/lb
Step 6: Sizing Central Cooling Coil Capacity & Tonnage q coil, sensible = 1.08 × 8 , 506 × ( 77.87 − 53.0 ) = 1.08 × 8 , 506 × 24.87 = 228 , 468 Btu/hr q_{\text{coil, sensible}} = 1.08 \times 8,506 \times (77.87 - 53.0) = 1.08 \times 8,506 \times 24.87 = 228,468\text{ Btu/hr} q coil, sensible = 1.08 × 8 , 506 × ( 77.87 − 53.0 ) = 1.08 × 8 , 506 × 24.87 = 228 , 468 Btu/hr q coil, latent = 4840 × 8 , 506 × ( 0.009946 − 0.00850 ) = 4840 × 8 , 506 × 0.001446 = 59 , 531 Btu/hr q_{\text{coil, latent}} = 4840 \times 8,506 \times (0.009946 - 0.00850) = 4840 \times 8,506 \times 0.001446 = 59,531\text{ Btu/hr} q coil, latent = 4840 × 8 , 506 × ( 0.009946 − 0.00850 ) = 4840 × 8 , 506 × 0.001446 = 59 , 531 Btu/hr q coil, total = 4.5 × 8 , 506 × ( 29.64 − 22.00 ) = 4.5 × 8 , 506 × 7.64 = 292 , 442 Btu/hr q_{\text{coil, total}} = 4.5 \times 8,506 \times (29.64 - 22.00) = 4.5 \times 8,506 \times 7.64 = 292,442\text{ Btu/hr} q coil, total = 4.5 × 8 , 506 × ( 29.64 − 22.00 ) = 4.5 × 8 , 506 × 7.64 = 292 , 442 Btu/hr Total Coil Tonnage = 292 , 442 Btu/hr 12 , 000 Btu/(hr ⋅ Ton) = 24.37 Tons \text{Total Coil Tonnage} = \frac{292,442\text{ Btu/hr}}{12,000\text{ Btu/(hr}\cdot\text{Ton)}} = 24.37\text{ Tons} Total Coil Tonnage = 12 , 000 Btu/(hr ⋅ Ton) 292 , 442 Btu/hr = 24.37 Tons
(Notice that the central coil capacity of 24.37 Tons exceeds the net space load of 17.80 Tons by 6.57 Tons due to the ventilation outdoor air load and fan heat gain!)