Study guide

9.2 Condensers: Air-Cooled, Water-Cooled & Evaporative Condensers

PE Mechanical: HVAC and Refrigeration Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Overview, Reference Handbook & Engineering Foundations

1.1 NCEES Exam Specification, CBT Delivery & Reference Handbook Strategy 1.2 Engineering Units, Dimensional Analysis & Physical Property Lookups 1.3 Engineering Economics, Life Cycle Cost Analysis & Equipment Financial Evaluation 1.4 Electrical Foundations, Motor Ratings & Variable Frequency Drives (VFDs)

2 Chapter 2: Thermodynamics & Energy Balances

2.1 First and Second Laws of Thermodynamics & Open/Closed System Energy Balances 2.2 Thermodynamic Cycles: Carnot, Rankine, Brayton & Reversed Carnot Limit 2.3 Gas & Vapor Property Evaluation: Steam Tables, Superheat & Subcooling 2.4 Mass, Energy & Combustion Balances for HVAC Equipment

3 Chapter 3: Psychrometrics, Moist Air Processes & Humidity Equipment

3.1 Psychrometric Properties: DBT, WBT, DPT, RH, Humidity Ratio & Enthalpy 3.2 Chart Reading & Psychrometric Equations at Sea Level vs. Altitude (5,000 ft) 3.3 Basic Psychrometric Processes: Sensible Heating/Cooling, Humidification & Dehumidification 3.4 Mixed Air Calculations & Complex Air Conditioning Cycles (Preheat, Reheat & Bypass) 3.5 Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP) & Coil Bypass Factor 3.6 Humidification & Dehumidification Equipment: Steam, Adiabatic, Desiccant & Low-Temperature Processes

4 Chapter 4: Heat Transfer Principles & Sizing

4.1 Steady-State Conduction & Multilayer Thermal Resistance (R-Value & U-Factor) 4.2 Convective Heat Transfer & Forced/Natural Convection Coefficients 4.3 Radiation Heat Transfer, Surface Emissivity & View Factors 4.4 Overall Heat Transfer Coefficients, Fouling Factors & Transient/Thermal Mass Effects 4.5 Heat Exchanger Analysis: Log Mean Temperature Difference (LMTD) & Effectiveness-NTU (ε-NTU)

5 Chapter 5: Fluid Mechanics & Hydraulic Fundamentals

5.1 Fluid Statics, Incompressible Continuity & Bernoulli Energy Equation 5.2 Pipe Friction, Moody Diagram & Darcy-Weisbach / Hazen-Williams Calculations 5.3 Minor Losses: Equivalent Length, Loss Coefficients (K-factors) & Total System Head 5.4 Pump Sizing, Net Positive Suction Head (NPSHa vs NPSHr) & Cavitation Prevention 5.5 Affinity Laws & Parallel/Series Pump/Fan System Curves

6 Chapter 6: Heating & Cooling Load Calculations

6.1 Outdoor & Indoor Design Conditions (ASHRAE Fundamentals, Climatic Data & Indoor Setpoints) 6.2 Envelope Heat Transmission & Infiltration/Exfiltration Load Methods 6.3 Solar Heat Gain (SHGC), Fenestration & Cooling Load Temperature Difference / Radiant Time Series (CLTD/RTS) 6.4 Internal Heat Gains: Lighting, People, Equipment & Diversity Factors 6.5 Ventilation Loads & Sensible / Latent / Total Cooling Load Synthesis

7 Chapter 7: Refrigeration Principles, Cycles & Cold Storage Applications

7.1 Standard Vapor-Compression Refrigeration Cycle on P-h & T-s Diagrams 7.2 Refrigeration Cycle Performance Metrics: COP, EER, SEER, kW/ton & Ton of Refrigeration 7.3 Cycle Enhancements: Subcooling, Superheating, Liquid-Suction Heat Exchangers & Economizers 7.4 Multi-Stage & Cascade Refrigeration Systems: Intercooling & Flash Gas Removal 7.5 Absorption Refrigeration Cycles: Water-Lithium Bromide & Ammonia-Water Systems 7.6 Food Processing & Cold Storage Refrigeration: Product Load, Pull-Down & Storage Design

8 Chapter 8: Refrigerants, Environmental Regulations & Safety

8.1 Refrigerant Classifications, Nomenclature & Thermodynamic Properties (ASHRAE Standard 34) 8.2 AIM Act, EPA Technology Transitions Sector GWP Limits & Low-GWP Refrigerants (R-32, R-454B) 8.3 Refrigerant Safety Requirements & Machinery Room Design (ASHRAE Standard 15) 8.4 Refrigerant Piping Sizing, Oil Return, Traps & Double Risers

9 Chapter 9: HVAC Equipment & Primary Machinery

9.1 Compressors: Reciprocating, Rotary, Scroll, Screw & Centrifugal 9.2 Condensers: Air-Cooled, Water-Cooled & Evaporative Condensers 9.3 Evaporators & Direct Expansion (DX) vs Liquid Chilling Coils 9.4 Water Chillers: Centrifugal, Screw & Scroll with ASHRAE 90.1 Path A/B IPLV Ratings 9.5 Cooling Towers: Range, Approach, Evaporation, Blowdown & Legionella Control 9.6 Heat Pumps & Variable Refrigerant Flow (VRF): Balance Point, Defrost & Heat Recovery 9.7 Thermal Energy Storage: Full vs. Partial Storage, Chilled Water & Ice Systems

10 Chapter 10: Air-Side Systems & Distribution

10.1 Air Handling Units (AHUs), Dedicated Outdoor Air Systems (DOAS) & Fan-Coil Units 10.2 Duct Design Methodologies: Equal Friction, Static Regain & Velocity Reduction 10.3 Duct Fittings, Dynamic Pressure Losses & SMACNA Construction Standards 10.4 Fan Types, Performance Curves, System Effect Factors & Surge/Stall Dynamics 10.5 Variable Air Volume (VAV) Systems, Terminal Boxes & Space Air Diffusion (ADPI) 10.6 Cooling & Heating Coil Selection: Face Velocity, Rows, Circuiting & Freeze Protection

11 Chapter 11: Hydronic, Steam & Fuel Distribution and Heating Plant

11.1 Hydronic System Architectures: Primary-Only, Primary-Secondary & Variable Primary Flow (VPF) 11.2 Hydronic Pipe Sizing, Velocity Limits & Closed/Open Expansion Tank Sizing 11.3 Control Valves: 2-Way vs 3-Way, Valve Authority (N), Cv Calculations & Characteristic Curves 11.4 Boilers & Heating Hot Water Systems: Condensing vs Non-Condensing & Water Treatment 11.5 Furnaces & Gas-Fired Heating Equipment: AFUE, Temperature Rise, Combustion Air & Vent Categories 11.6 Steam & Condensate Distribution: Latent Heat, Trap Selection, Flash Steam & Stall 11.7 Fuel Gas & Fuel Oil Piping: Demand, Sizing Method, Pressure Drop & Storage Systems

12 Chapter 12: HVAC Control Concepts, Sensors & Sequences

12.1 Sensors, Actuators & Dampers: Selection, Placement, Fail-Safe Position & Damper Authority 12.2 Control Loops: Proportional Offset, PID Action, Reset Strategies & Standard Sequences

13 Chapter 13: Building Energy, Ventilation & Indoor Environmental Quality Codes

13.1 ASHRAE Standard 62.1: Ventilation Rate Procedure (VRP), Indoor Air Quality Procedure & DCV 13.2 ASHRAE Standard 90.1: Building Energy Envelope, Mechanical Efficiency & Economizer Mandates 13.3 ASHRAE Standard 55: Thermal Environmental Conditions, PMV/PPD & Adaptive Comfort Models 13.4 Energy Recovery Systems: Enthalpy Wheels, Fixed-Plate Exchangers, Heat Pipes & Runaround Loops

14 Chapter 14: Supportive Engineering Knowledge, Life Safety & Operations

14.1 Air Filtration Standards: MERV Ratings (ASHRAE 52.2), HEPA & Gas-Phase Adsorption 14.2 Life Safety Systems: Fire/Smoke Dampers, Stairwell Pressurization (NFPA 92) & Smoke Control (NFPA 90A) 14.3 Acoustical Control & Vibration Isolation in HVAC Systems (NC / RC Criteria)

9.2 Condensers: Air-Cooled, Water-Cooled & Evaporative Condensers

Key Takeaways Explain This Topic AI

The Total Heat of Rejection (THR) equals the evaporator cooling load plus the compressor work of compression: Q ˙ cond = Q ˙ evap + W ˙ comp = Q ˙ evap ( 1 + 1 COP R ) = Q ˙ evap ( 1 + kW/ton 3.517 ) \dot{Q}_{\text{cond}} = \dot{Q}_{\text{evap}} + \dot{W}_{\text{comp}} = \dot{Q}_{\text{evap}} \left(1 + \frac{1}{\text{COP}_R}\right) = \dot{Q}_{\text{evap}} \left(1 + \frac{\text{kW/ton}}{3.517}\right) Q ˙ ​ cond ​ = Q ˙ ​ evap ​ + W ˙ comp ​ = Q ˙ ​ evap ​ ( 1 + COP R ​ 1 ​ ) = Q ˙ ​ evap ​ ( 1 + 3.517 kW/ton ​ ) .

Air-cooled condensers reject heat against ambient dry-bulb temperature (DBT), operating at a condensing temperature over ambient (CTOA or TD) of 15 ∘ F 15^\circ\text{F} 1 5 ∘ F to 30 ∘ F 30^\circ\text{F} 3 0 ∘ F and requiring head pressure controls in cold ambient conditions.

Water-cooled condensers reject heat to an open or closed cooling tower loop, typically designed for 85 ∘ F 85^\circ\text{F} 8 5 ∘ F entering condenser water (ECWT), 95 ∘ F 95^\circ\text{F} 9 5 ∘ F leaving condenser water (LCWT) at 3.0 GPM/ton 3.0\text{ GPM/ton} 3.0 GPM/ton , with saturated condensing temperatures around 100 ∘ F 100^\circ\text{F} 10 0 ∘ F to 105 ∘ F 105^\circ\text{F} 10 5 ∘ F .

Evaporative condensers combine a coil and wet cooling tower into a single unit, rejecting heat directly to ambient wet-bulb temperature (WBT) and achieving saturated condensing temperatures 15 ∘ F 15^\circ\text{F} 1 5 ∘ F to 25 ∘ F 25^\circ\text{F} 2 5 ∘ F lower than air-cooled units.

Liquid subcooling ( T sat ( P cond ) − T liquid, out T_{\text{sat}}(P_{\text{cond}}) - T_{\text{liquid, out}} T sat ​ ( P cond ​ ) − T liquid, out ​ ) is essential to prevent vapor flashing before the thermal expansion valve and increases system net refrigeration effect by approximately 0.5 % 0.5\% 0.5% to 1.0 % 1.0\% 1.0% per ∘ F ^\circ\text{F} ∘ F .

Last updated: August 2026

9.2 Condensers: Air-Cooled, Water-Cooled & Evaporative Condensers

The condenser is the primary heat-rejection heat exchanger in a vapor-compression refrigeration system. Its thermodynamic function is to receive high-pressure, superheated discharge vapor from the compressor, desuperheat the vapor, condense it into saturated liquid, and subcool the liquid before delivering it to the liquid line and expansion device. Understanding condenser heat transfer mechanisms, water-flow rates, fouling resistances, and head-pressure regulation is a core competency tested on the PE Mechanical HVAC exam.

1. Total Heat of Rejection (THR) & Energy Balance

By the First Law of Thermodynamics, for an open steady-flow refrigeration system, the rate of heat rejected at the condenser ( Q ˙ cond \dot{Q}_{\text{cond}} Q ˙ ​ cond ​ ) must equal the thermal energy absorbed at the evaporator plus the work added to the refrigerant by the compressor: Q ˙ cond = Q ˙ evap + W ˙ comp \dot{Q}_{\text{cond}} = \dot{Q}_{\text{evap}} + \dot{W}_{\text{comp}} Q ˙ ​ cond ​ = Q ˙ ​ evap ​ + W ˙ comp ​ +-------------------------+ +--------------------------+

  • | Evaporator Cooling | | Compressor Electrical |
  • | Load (Q_evap) | | Power / Work (W_comp) |
  • | 1.0 Ton = 12,000 Btu/hr| | ~0.5 to 1.2 kW/ton |
  • +------------+------------+ +------------+-------------+
  • | |
  • +--------------------+----------------------+
  • |
  • V
  • +------------------------------+
  • | TOTAL HEAT OF REJECTION |
  • | (THR = Q_evap + W_comp) |
  • | ~14,000 to 16,000 Btu/hr/ton|
  • +------------------------------+

Total Heat Rejection Factor ( F THR F_{\text{THR}} F THR ​ ) THR = Q ˙ evap × F THR \text{THR} = \dot{Q}_{\text{evap}} \times F_{\text{THR}} THR = Q ˙ ​ evap ​ × F THR ​ F THR = 1 + W ˙ comp Q ˙ evap = 1 + 1 COP R = 1 + kW/ton × 3 , 412.14 12 , 000 = 1 + kW/ton 3.51685 F_{\text{THR}} = 1 + \frac{\dot{W}_{\text{comp}}}{\dot{Q}_{\text{evap}}} = 1 + \frac{1}{\text{COP}_R} = 1 + \frac{\text{kW/ton} \times 3,412.14}{12,000} = 1 + \frac{\text{kW/ton}}{3.51685} F THR ​ = 1 + Q ˙ ​ evap ​ W ˙ comp ​ ​ = 1 + COP R ​ 1 ​ = 1 + 12 , 000 kW/ton × 3 , 412.14 ​ = 1 + 3.51685 kW/ton ​

Open-Drive Chillers: Motor losses stay in the ambient mechanical room; fluid work is w a = m ˙ ( h 2 − h 1 ) w_a = \dot{m}(h_2 - h_1) w a ​ = m ˙ ( h 2 ​ − h 1 ​ ) .

Hermetic & Semi-Hermetic Compressors: The motor is cooled directly by suction gas. Therefore, 100% of motor electrical losses are added to the refrigerant, increasing THR \text{THR} THR to: Q ˙ cond, hermetic = Q ˙ evap + W ˙ electrical, in \dot{Q}_{\text{cond, hermetic}} = \dot{Q}_{\text{evap}} + \dot{W}_{\text{electrical, in}} Q ˙ ​ cond, hermetic ​ = Q ˙ ​ evap ​ + W ˙ electrical, in ​

For typical air-conditioning applications ( COP ≈ 3.0 \text{COP} \approx 3.0 COP ≈ 3.0 to 4.0 4.0 4.0 ), THR \text{THR} THR ranges from 14 , 400 14,400 14 , 400 to 15 , 600 Btu/(hr ⋅ ton) 15,600\text{ Btu/(hr}\cdot\text{ton)} 15 , 600 Btu/(hr ⋅ ton) ( 1.20 1.20 1.20 to 1.30 tons of heat rejection per ton of cooling 1.30\text{ tons of heat rejection per ton of cooling} 1.30 tons of heat rejection per ton of cooling ). In low-temperature refrigeration ( COP ≈ 1.5 \text{COP} \approx 1.5 COP ≈ 1.5 ), THR \text{THR} THR can reach 20 , 000 Btu/(hr ⋅ ton) 20,000\text{ Btu/(hr}\cdot\text{ton)} 20 , 000 Btu/(hr ⋅ ton) ( F THR ≈ 1.67 F_{\text{THR}} \approx 1.67 F THR ​ ≈ 1.67 ).

2. Three Internal Condenser Thermal Zones

Refrigerant flows through three distinct thermodynamic regimes inside the condenser: Enthalpy / Phase Progression:

  • [ Superheated Vapor ] ===> [ Two-Phase Vapor/Liquid Mixture ] ===> [ Subcooled Liquid ]
  • (1. Desuperheating Zone) (2. Condensing Zone / Latent) (3. Subcooling Zone)
  • ~10% to 15% Area ~80% to 85% Area ~5% Area
  • Single-phase vapor gas Constant Temp & Pressure Single-phase liquid
  • h_discharge -> h_g h_g -> h_f (h_fg rejected) h_f -> h_out

Desuperheating Zone (10% to 15% of total heat duty): Single-phase gas cooling from discharge temperature ( 140 ∘ F 140^\circ\text{F} 14 0 ∘ F to 220 ∘ F 220^\circ\text{F} 22 0 ∘ F ) down to the Saturated Condensing Temperature ( T sat T_{\text{sat}} T sat ​ ). Convective heat transfer coefficient is relatively low ( h ≈ 30 − 80 Btu/(hr ⋅ ft 2 ⋅ ∘ F) h \approx 30-80\text{ Btu/(hr}\cdot\text{ft}^2\cdot^\circ\text{F)} h ≈ 30 − 80 Btu/(hr ⋅ ft 2 ⋅ ∘ F) ).

Condensing Zone (80% to 85% of total heat duty): Two-phase condensation at constant saturation temperature ( T sat T_{\text{sat}} T sat ​ ) and constant saturation pressure ( P cond P_{\text{cond}} P cond ​ ). Latent heat of condensation ( h f g h_{fg} h f g ​ ) is released. Two-phase film boiling/condensation produces extremely high heat transfer coefficients ( h ≈ 300 − 1 , 200 Btu/(hr ⋅ ft 2 ⋅ ∘ F) h \approx 300-1,200\text{ Btu/(hr}\cdot\text{ft}^2\cdot^\circ\text{F)} h ≈ 300 − 1 , 200 Btu/(hr ⋅ ft 2 ⋅ ∘ F) ).

Subcooling Zone (5% of total heat duty): Single-phase liquid cooling from T sat T_{\text{sat}} T sat ​ down to leaving liquid temperature ( T liquid T_{\text{liquid}} T liquid ​ ). Essential for bubble-free liquid feed to the expansion valve.

3. Comparison of Condenser Types +---------------------------------------------------------------------------------------------------------+

  • | CONDENSER ARCHITECTURE COMPARISON |
  • +-----------------------+---------------------------------+-----------------------------------------------+
  • | Condenser Type | Heat Sink Fluid | Typical Saturated Condensing Temp (SCT) |
  • +-----------------------+---------------------------------+-----------------------------------------------+
  • | **Air-Cooled** | Ambient Air (Dry-BulB Temp) | SCT = Ambient DBT + 20°F to 30°F (115°F to 125°F)|
  • | **Water-Cooled** | Condenser Water (Cooling Tower) | SCT = Tower Water LWT + 5°F to 10°F (95°F-105°F)|
  • | **Evaporative** | Air + Evaporating Water Spray | SCT = Ambient WBT + 12°F to 18°F (90°F-96°F) |
  • +-----------------------+---------------------------------+-----------------------------------------------+
  • Detailed Engineering Analysis of Each Type
  • A. Air-Cooled Condensers

Mechanics: Hot refrigerant vapor flows inside finned copper or aluminum tubes while propeller fans draw ambient air across external fins. Microchannel coils utilize multi-port extruded aluminum tubes with folded louvered fins, reducing refrigerant charge by 40% to 70%.

Design Temperature Difference (TD or CTOA): Defined as Saturated Condensing Temperature minus Entering Air Dry-Bulb Temperature: TD = T cond, sat − T ambient, DB \text{TD} = T_{\text{cond, sat}} - T_{\text{ambient, DB}} TD = T cond, sat ​ − T ambient, DB ​ Typical commercial design: TD = 20 ∘ F \text{TD} = 20^\circ\text{F} TD = 2 0 ∘ F to 30 ∘ F 30^\circ\text{F} 3 0 ∘ F . On a 95 ∘ F 95^\circ\text{F} 9 5 ∘ F summer day, T cond = 115 ∘ F T_{\text{cond}} = 115^\circ\text{F} T cond ​ = 11 5 ∘ F to 125 ∘ F 125^\circ\text{F} 12 5 ∘ F .

Advantages: Zero water consumption, zero water treatment chemicals, zero risk of Legionella, simple maintenance.

Disadvantages: High condensing pressure reduces compressor COP ( 1.0 1.0 1.0 to 1.3 kW/ton 1.3\text{ kW/ton} 1.3 kW/ton vs 0.5 0.5 0.5 to 0.6 kW/ton 0.6\text{ kW/ton} 0.6 kW/ton for water-cooled), high fan acoustic noise, large rooftop footprint.

B. Water-Cooled Condensers

Mechanics: Shell-and-tube or brazed plate heat exchangers. In a shell-and-tube condenser, high-pressure refrigerant condenses on the shell side over enhanced copper tubes while cooling tower water circulates through multiple tube passes.

Standard Rating Conditions (AHRI 550/590):

Entering Condenser Water Temp (ECWT): 85.0 ∘ F 85.0^\circ\text{F} 85. 0 ∘ F

Leaving Condenser Water Temp (LCWT): 95.0 ∘ F 95.0^\circ\text{F} 95. 0 ∘ F (Standard Δ T = 10.0 ∘ F \Delta T = 10.0^\circ\text{F} Δ T = 10. 0 ∘ F at 3.0 GPM/ton 3.0\text{ GPM/ton} 3.0 GPM/ton )

Low-flow Design: 85.0 ∘ F 85.0^\circ\text{F} 85. 0 ∘ F in, 94.0 ∘ F 94.0^\circ\text{F} 94. 0 ∘ F out ( Δ T = 9.0 ∘ F \Delta T = 9.0^\circ\text{F} Δ T = 9. 0 ∘ F at 3.33 GPM/ton 3.33\text{ GPM/ton} 3.33 GPM/ton ) or 85.0 ∘ F → 97.5 ∘ F 85.0^\circ\text{F} \to 97.5^\circ\text{F} 85. 0 ∘ F → 97. 5 ∘ F ( Δ T = 12.5 ∘ F \Delta T = 12.5^\circ\text{F} Δ T = 12. 5 ∘ F at 2.4 GPM/ton 2.4\text{ GPM/ton} 2.4 GPM/ton ).

Condenser Water Flow Formula: Q ˙ cond (Btu/hr) = 500 × GPM CW × ( T LCWT − T ECWT ) \dot{Q}_{\text{cond}}\text{ (Btu/hr)} = 500 \times \text{GPM}_{\text{CW}} \times (T_{\text{LCWT}} - T_{\text{ECWT}}) Q ˙ ​ cond ​ (Btu/hr) = 500 × GPM CW ​ × ( T LCWT ​ − T ECWT ​ ) GPM CW = THR (Btu/hr) 500 × Δ T CW = Tons × 15 , 000 500 × 10 ∘ F = 3.0 GPM/ton \text{GPM}_{\text{CW}} = \frac{\text{THR (Btu/hr)}}{500 \times \Delta T_{\text{CW}}} = \frac{\text{Tons} \times 15,000}{500 \times 10^\circ\text{F}} = 3.0\text{ GPM/ton} GPM CW ​ = 500 × Δ T CW ​ THR (Btu/hr) ​ = 500 × 1 0 ∘ F Tons × 15 , 000 ​ = 3.0 GPM/ton

Waterside Fouling Factor ( R f R_f R f ​ ): Mineral scale, biological slime, and silt increase thermal resistance. AHRI 550/590 standard rating fouling allowance is R f = 0.00025 hr ⋅ ft 2 ⋅ ∘ F/Btu R_f = 0.00025\text{ hr}\cdot\text{ft}^2\cdot^\circ\text{F/Btu} R f ​ = 0.00025 hr ⋅ ft 2 ⋅ ∘ F/Btu . Waterside tube cleaning is performed mechanically with nylon brushes or chemically via acid circulation.

C. Evaporative Condensers

Mechanics: Combines a condensing coil bundle and an open cooling tower inside a single enclosure. Water is pumped from a lower basin to spray nozzles that cascade water over bare serpentine refrigerant coils. Axial fans draw air upward counterflow to falling water.

Thermodynamic Advantage: Latent evaporation of water directly from the coil surface transfers heat against the ambient wet-bulb temperature (WBT) rather than the dry-bulb temperature.

Performance: On a 95 ∘ F DB / 75 ∘ F WB 95^\circ\text{F}\text{ DB} / 75^\circ\text{F}\text{ WB} 9 5 ∘ F DB /7 5 ∘ F WB design day, an evaporative condenser achieves T cond ≈ 90 ∘ F T_{\text{cond}} \approx 90^\circ\text{F} T cond ​ ≈ 9 0 ∘ F to 95 ∘ F 95^\circ\text{F} 9 5 ∘ F (compared to 120 ∘ F 120^\circ\text{F} 12 0 ∘ F for air-cooled), slashing compressor power by 25% to 35%.

Application: Industrial ammonia (R-717) cold storage, food processing plants, and large supermarket central rack systems.

4. Condenser Log Mean Temperature Difference (LMTD)

Heat transfer across the condenser is calculated using the overall heat transfer equation: Q ˙ cond = U ⋅ A ⋅ LMTD \dot{Q}_{\text{cond}} = U \cdot A \cdot \text{LMTD} Q ˙ ​ cond ​ = U ⋅ A ⋅ LMTD LMTD = Δ T 1 − Δ T 2 ln ⁡ ( Δ T 1 Δ T 2 ) \text{LMTD} = \frac{\Delta T_1 - \Delta T_2}{\ln\left(\frac{\Delta T_1}{\Delta T_2}\right)} LMTD = ln ( Δ T 2 ​ Δ T 1 ​ ​ ) Δ T 1 ​ − Δ T 2 ​ ​

For a water-cooled condenser with constant refrigerant condensing temperature ( T cond T_{\text{cond}} T cond ​ ):

Δ T 1 = T cond − T LCWT \Delta T_1 = T_{\text{cond}} - T_{\text{LCWT}} Δ T 1 ​ = T cond ​ − T LCWT ​ (at refrigerant inlet / water exit)

Δ T 2 = T cond − T ECWT \Delta T_2 = T_{\text{cond}} - T_{\text{ECWT}} Δ T 2 ​ = T cond ​ − T ECWT ​ (at refrigerant liquid exit / water inlet) Temperature Profile (Water-Cooled Shell & Tube):

  • Refrigerant: T_cond ========================================> Saturated Condensing Temp (T_cond)
  • |
  • ^ | Approach = T_cond - T_LCWT
  • | V
  • Water Stream: |-------------------------------------> T_LCWT (95°F)
  • | Water Temperature Rise (10°F) ^

+-------------------------------------+ T_ECWT (85°F) Condenser Approach Temperature = T cond, sat − T LCWT \text{Condenser Approach Temperature} = T_{\text{cond, sat}} - T_{\text{LCWT}} Condenser Approach Temperature = T cond, sat ​ − T LCWT ​

Typical approach temperatures for clean water-cooled condensers range from 3 ∘ F 3^\circ\text{F} 3 ∘ F to 8 ∘ F 8^\circ\text{F} 8 ∘ F .

5. Low-Ambient Head Pressure Control

In air-cooled systems operating during winter or cold shoulder months, cold ambient air dramatically increases condenser heat rejection capacity, causing condensing pressure to plummet. Insufficient head pressure results in:

Inadequate pressure differential across the thermal expansion valve (TXV), causing starving of the evaporator.

Inadequate oil return from DX coils due to low refrigerant velocity.

Nuisance low-pressure cut-out tripping.

Low-Ambient Control Strategies

Control Mechanism Method of Operation Advantages & Limitations

Fan Cycling Pressure switches cycle individual condenser fans on/off based on discharge pressure. Inexpensive; causes wide pressure swings and noisy stepping.

VFD Fan Speed Control Variable frequency drive modulates fan speed to maintain constant discharge pressure setpoint. Smooth, stable head pressure control; quiet operation; excellent energy efficiency.

Flooded Condenser Control A head pressure control valve (e.g., Sporlan Head Master ORD/ORI) backs up liquid refrigerant into condenser tubes. Flooding reduces effective heat transfer area, keeping SCT high even at − 20 ∘ F -20^\circ\text{F} − 2 0 ∘ F ambient; requires oversized receiver and large refrigerant charge.

Air Dampers / Louvers Modulating motorized face louvers restrict cooling airflow across condenser coil face. Protects against windmilling in subzero winds; mechanical linkages prone to icing.

6. Worked Example: Water-Cooled vs. Air-Cooled Condenser Sizing

Problem: A water-cooled water chiller produces 350 tons 350\text{ tons} 350 tons of cooling capacity with an operating efficiency of 0.58 kW/ton 0.58\text{ kW/ton} 0.58 kW/ton . The condenser operates with entering condenser water at 85.0 ∘ F 85.0^\circ\text{F} 85. 0 ∘ F and leaving condenser water at 95.0 ∘ F 95.0^\circ\text{F} 95. 0 ∘ F . Saturated condensing temperature is 101.0 ∘ F 101.0^\circ\text{F} 101. 0 ∘ F .

Find:

The Total Heat of Rejection ( THR \text{THR} THR ) in Btu/hr \text{Btu/hr} Btu/hr and the heat rejection factor ( F THR F_{\text{THR}} F THR ​ ).

The required condenser water flow rate ( GPM CW \text{GPM}_{\text{CW}} GPM CW ​ ).

The Condenser Log Mean Temperature Difference ( LMTD \text{LMTD} LMTD ) and Condenser Approach Temperature.

If the chiller were replaced with an air-cooled unit operating at 1.15 kW/ton 1.15\text{ kW/ton} 1.15 kW/ton on a 95 ∘ F 95^\circ\text{F} 9 5 ∘ F ambient day, compute the new THR \text{THR} THR in Btu/hr \text{Btu/hr} Btu/hr .

Step-by-Step Solution:

Step 1: Compute THR and Rejection Factor for the water-cooled chiller. Q ˙ evap = 350 tons × 12 , 000 Btu/(hr ⋅ ton) = 4 , 200 , 000 Btu/hr \dot{Q}_{\text{evap}} = 350\text{ tons} \times 12,000\text{ Btu/(hr}\cdot\text{ton)} = 4,200,000\text{ Btu/hr} Q ˙ ​ evap ​ = 350 tons × 12 , 000 Btu/(hr ⋅ ton) = 4 , 200 , 000 Btu/hr Compressor Electrical Power: W ˙ comp = 350 tons × 0.58 kW/ton = 203.0 kW \text{Compressor Electrical Power: } \dot{W}_{\text{comp}} = 350\text{ tons} \times 0.58\text{ kW/ton} = 203.0\text{ kW} Compressor Electrical Power: W ˙ comp ​ = 350 tons × 0.58 kW/ton = 203.0 kW W ˙ comp = 203.0 kW × 3 , 412.14 Btu/(hr ⋅ kW) = 692 , 664 Btu/hr \dot{W}_{\text{comp}} = 203.0\text{ kW} \times 3,412.14\text{ Btu/(hr}\cdot\text{kW)} = 692,664\text{ Btu/hr} W ˙ comp ​ = 203.0 kW × 3 , 412.14 Btu/(hr ⋅ kW) = 692 , 664 Btu/hr THR water = Q ˙ evap + W ˙ comp = 4 , 200 , 000 + 692 , 664 = 4 , 892 , 664 Btu/hr \text{THR}_{\text{water}} = \dot{Q}_{\text{evap}} + \dot{W}_{\text{comp}} = 4,200,000 + 692,664 = 4,892,664\text{ Btu/hr} THR water ​ = Q ˙ ​ evap ​ + W ˙ comp ​ = 4 , 200 , 000 + 692 , 664 = 4 , 892 , 664 Btu/hr F THR = 4 , 892 , 664 4 , 200 , 000 = 1.1649 F_{\text{THR}} = \frac{4,892,664}{4,200,000} = 1.1649 F THR ​ = 4 , 200 , 000 4 , 892 , 664 ​ = 1.1649

Step 2: Compute Condenser Water Flow Rate ( GPM \text{GPM} GPM ). Δ T CW = 95.0 ∘ F − 85.0 ∘ F = 10.0 ∘ F \Delta T_{\text{CW}} = 95.0^\circ\text{F} - 85.0^\circ\text{F} = 10.0^\circ\text{F} Δ T CW ​ = 95. 0 ∘ F − 85. 0 ∘ F = 10. 0 ∘ F GPM CW = THR 500 × Δ T CW = 4 , 892 , 664 Btu/hr 500 × 10.0 ∘ F = 978.53 GPM \text{GPM}_{\text{CW}} = \frac{\text{THR}}{500 \times \Delta T_{\text{CW}}} = \frac{4,892,664\text{ Btu/hr}}{500 \times 10.0^\circ\text{F}} = 978.53\text{ GPM} GPM CW ​ = 500 × Δ T CW ​ THR ​ = 500 × 10. 0 ∘ F 4 , 892 , 664 Btu/hr ​ = 978.53 GPM Flow per ton: 978.53 GPM 350 tons = 2.80 GPM/ton \text{Flow per ton: } \frac{978.53\text{ GPM}}{350\text{ tons}} = 2.80\text{ GPM/ton} Flow per ton: 350 tons 978.53 GPM ​ = 2.80 GPM/ton

Step 3: Compute LMTD and Approach Temperature. Δ T 1 = T cond − T LCWT = 101.0 ∘ F − 95.0 ∘ F = 6.0 ∘ F \Delta T_1 = T_{\text{cond}} - T_{\text{LCWT}} = 101.0^\circ\text{F} - 95.0^\circ\text{F} = 6.0^\circ\text{F} Δ T 1 ​ = T cond ​ − T LCWT ​ = 101. 0 ∘ F − 95. 0 ∘ F = 6. 0 ∘ F Δ T 2 = T cond − T ECWT = 101.0 ∘ F − 85.0 ∘ F = 16.0 ∘ F \Delta T_2 = T_{\text{cond}} - T_{\text{ECWT}} = 101.0^\circ\text{F} - 85.0^\circ\text{F} = 16.0^\circ\text{F} Δ T 2 ​ = T cond ​ − T ECWT ​ = 101. 0 ∘ F − 85. 0 ∘ F = 16. 0 ∘ F LMTD = Δ T 2 − Δ T 1 ln ⁡ ( Δ T 2 / Δ T 1 ) = 16.0 − 6.0 ln ⁡ ( 16.0 / 6.0 ) = 10.0 ln ⁡ ( 2.6667 ) = 10.0 0.98083 = 10.20 ∘ F \text{LMTD} = \frac{\Delta T_2 - \Delta T_1}{\ln(\Delta T_2 / \Delta T_1)} = \frac{16.0 - 6.0}{\ln(16.0 / 6.0)} = \frac{10.0}{\ln(2.6667)} = \frac{10.0}{0.98083} = 10.20^\circ\text{F} LMTD = ln ( Δ T 2 ​ /Δ T 1 ​ ) Δ T 2 ​ − Δ T 1 ​ ​ = ln ( 16.0/6.0 ) 16.0 − 6.0 ​ = ln ( 2.6667 ) 10.0 ​ = 0.98083 10.0 ​ = 10.2 0 ∘ F Approach = T cond − T LCWT = 101.0 ∘ F − 95.0 ∘ F = 6.0 ∘ F \text{Approach} = T_{\text{cond}} - T_{\text{LCWT}} = 101.0^\circ\text{F} - 95.0^\circ\text{F} = 6.0^\circ\text{F} Approach = T cond ​ − T LCWT ​ = 101. 0 ∘ F − 95. 0 ∘ F = 6. 0 ∘ F

Step 4: Compute Air-Cooled Chiller THR. W ˙ comp, air = 350 tons × 1.15 kW/ton = 402.5 kW \dot{W}_{\text{comp, air}} = 350\text{ tons} \times 1.15\text{ kW/ton} = 402.5\text{ kW} W ˙ comp, air ​ = 350 tons × 1.15 kW/ton = 402.5 kW W ˙ comp, air = 402.5 kW × 3 , 412.14 Btu/hr/kW = 1 , 373 , 386 Btu/hr \dot{W}_{\text{comp, air}} = 402.5\text{ kW} \times 3,412.14\text{ Btu/hr/kW} = 1,373,386\text{ Btu/hr} W ˙ comp, air ​ = 402.5 kW × 3 , 412.14 Btu/hr/kW = 1 , 373 , 386 Btu/hr THR air = 4 , 200 , 000 + 1 , 373 , 386 = 5 , 573 , 386 Btu/hr \text{THR}_{\text{air}} = 4,200,000 + 1,373,386 = 5,573,386\text{ Btu/hr} THR air ​ = 4 , 200 , 000 + 1 , 373 , 386 = 5 , 573 , 386 Btu/hr F THR, air = 5 , 573 , 386 4 , 200 , 000 = 1.3270 F_{\text{THR, air}} = \frac{5,573,386}{4,200,000} = 1.3270 F THR, air ​ = 4 , 200 , 000 5 , 573 , 386 ​ = 1.3270

(Notice that the air-cooled condenser must reject 13.9 % 13.9\% 13.9% more heat than the water-cooled condenser due to higher compressor electrical power!)

7. NCEES Reference Handbook Navigation & Exam Traps

Heat Transfer Section: LMTD formula Δ T l m = Δ T 1 − Δ T 2 ln ⁡ ( Δ T 1 / Δ T 2 ) \Delta T_{lm} = \frac{\Delta T_1 - \Delta T_2}{\ln(\Delta T_1 / \Delta T_2)} Δ T l m ​ = l n ( Δ T 1 ​ /Δ T 2 ​ ) Δ T 1 ​ − Δ T 2 ​ ​ and overall heat exchanger relation q = U A Δ T l m q = U A \Delta T_{lm} q = U A Δ T l m ​ .

Hydronics Equation: q = 500 × GPM × Δ T q = 500 \times \text{GPM} \times \Delta T q = 500 × GPM × Δ T . The 500 constant is valid only for pure water at standard density ( ρ = 8.33 lbm/gal \rho = 8.33\text{ lbm/gal} ρ = 8.33 lbm/gal , c p = 1.0 Btu/lbm ⋅ ∘ F c_p = 1.0\text{ Btu/lbm}\cdot^\circ\text{F} c p ​ = 1.0 Btu/lbm ⋅ ∘ F ). If glycol is used, C = 500 × SG × c p C = 500 \times \text{SG} \times c_p C = 500 × SG × c p ​ .

THR Trap: Never assume THR = Q ˙ evap \text{THR} = \dot{Q}_{\text{evap}} THR = Q ˙ ​ evap ​ ( 12 , 000 Btu/ton 12,000\text{ Btu/ton} 12 , 000 Btu/ton ). Condensers must ALWAYS reject both evaporator heat and compressor work ( 14 , 000 14,000 14 , 000 to 16 , 000 + Btu/ton 16,000+\text{ Btu/ton} 16 , 000 + Btu/ton ).

Loading diagram... Condenser Types & Heat Transfer Driving Potentials