9.5 Cooling Towers: Range, Approach, Evaporation, Blowdown & Legionella Control
PE Mechanical: HVAC and Refrigeration Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview, Reference Handbook & Engineering Foundations
1.1 NCEES Exam Specification, CBT Delivery & Reference Handbook Strategy 1.2 Engineering Units, Dimensional Analysis & Physical Property Lookups 1.3 Engineering Economics, Life Cycle Cost Analysis & Equipment Financial Evaluation 1.4 Electrical Foundations, Motor Ratings & Variable Frequency Drives (VFDs)
2 Chapter 2: Thermodynamics & Energy Balances
2.1 First and Second Laws of Thermodynamics & Open/Closed System Energy Balances 2.2 Thermodynamic Cycles: Carnot, Rankine, Brayton & Reversed Carnot Limit 2.3 Gas & Vapor Property Evaluation: Steam Tables, Superheat & Subcooling 2.4 Mass, Energy & Combustion Balances for HVAC Equipment
3 Chapter 3: Psychrometrics, Moist Air Processes & Humidity Equipment
3.1 Psychrometric Properties: DBT, WBT, DPT, RH, Humidity Ratio & Enthalpy 3.2 Chart Reading & Psychrometric Equations at Sea Level vs. Altitude (5,000 ft) 3.3 Basic Psychrometric Processes: Sensible Heating/Cooling, Humidification & Dehumidification 3.4 Mixed Air Calculations & Complex Air Conditioning Cycles (Preheat, Reheat & Bypass) 3.5 Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP) & Coil Bypass Factor 3.6 Humidification & Dehumidification Equipment: Steam, Adiabatic, Desiccant & Low-Temperature Processes
4 Chapter 4: Heat Transfer Principles & Sizing
4.1 Steady-State Conduction & Multilayer Thermal Resistance (R-Value & U-Factor) 4.2 Convective Heat Transfer & Forced/Natural Convection Coefficients 4.3 Radiation Heat Transfer, Surface Emissivity & View Factors 4.4 Overall Heat Transfer Coefficients, Fouling Factors & Transient/Thermal Mass Effects 4.5 Heat Exchanger Analysis: Log Mean Temperature Difference (LMTD) & Effectiveness-NTU (ε-NTU)
5 Chapter 5: Fluid Mechanics & Hydraulic Fundamentals
5.1 Fluid Statics, Incompressible Continuity & Bernoulli Energy Equation 5.2 Pipe Friction, Moody Diagram & Darcy-Weisbach / Hazen-Williams Calculations 5.3 Minor Losses: Equivalent Length, Loss Coefficients (K-factors) & Total System Head 5.4 Pump Sizing, Net Positive Suction Head (NPSHa vs NPSHr) & Cavitation Prevention 5.5 Affinity Laws & Parallel/Series Pump/Fan System Curves
6 Chapter 6: Heating & Cooling Load Calculations
6.1 Outdoor & Indoor Design Conditions (ASHRAE Fundamentals, Climatic Data & Indoor Setpoints) 6.2 Envelope Heat Transmission & Infiltration/Exfiltration Load Methods 6.3 Solar Heat Gain (SHGC), Fenestration & Cooling Load Temperature Difference / Radiant Time Series (CLTD/RTS) 6.4 Internal Heat Gains: Lighting, People, Equipment & Diversity Factors 6.5 Ventilation Loads & Sensible / Latent / Total Cooling Load Synthesis
7 Chapter 7: Refrigeration Principles, Cycles & Cold Storage Applications
7.1 Standard Vapor-Compression Refrigeration Cycle on P-h & T-s Diagrams 7.2 Refrigeration Cycle Performance Metrics: COP, EER, SEER, kW/ton & Ton of Refrigeration 7.3 Cycle Enhancements: Subcooling, Superheating, Liquid-Suction Heat Exchangers & Economizers 7.4 Multi-Stage & Cascade Refrigeration Systems: Intercooling & Flash Gas Removal 7.5 Absorption Refrigeration Cycles: Water-Lithium Bromide & Ammonia-Water Systems 7.6 Food Processing & Cold Storage Refrigeration: Product Load, Pull-Down & Storage Design
8 Chapter 8: Refrigerants, Environmental Regulations & Safety
8.1 Refrigerant Classifications, Nomenclature & Thermodynamic Properties (ASHRAE Standard 34) 8.2 AIM Act, EPA Technology Transitions Sector GWP Limits & Low-GWP Refrigerants (R-32, R-454B) 8.3 Refrigerant Safety Requirements & Machinery Room Design (ASHRAE Standard 15) 8.4 Refrigerant Piping Sizing, Oil Return, Traps & Double Risers
9 Chapter 9: HVAC Equipment & Primary Machinery
9.1 Compressors: Reciprocating, Rotary, Scroll, Screw & Centrifugal 9.2 Condensers: Air-Cooled, Water-Cooled & Evaporative Condensers 9.3 Evaporators & Direct Expansion (DX) vs Liquid Chilling Coils 9.4 Water Chillers: Centrifugal, Screw & Scroll with ASHRAE 90.1 Path A/B IPLV Ratings 9.5 Cooling Towers: Range, Approach, Evaporation, Blowdown & Legionella Control 9.6 Heat Pumps & Variable Refrigerant Flow (VRF): Balance Point, Defrost & Heat Recovery 9.7 Thermal Energy Storage: Full vs. Partial Storage, Chilled Water & Ice Systems
10 Chapter 10: Air-Side Systems & Distribution
10.1 Air Handling Units (AHUs), Dedicated Outdoor Air Systems (DOAS) & Fan-Coil Units 10.2 Duct Design Methodologies: Equal Friction, Static Regain & Velocity Reduction 10.3 Duct Fittings, Dynamic Pressure Losses & SMACNA Construction Standards 10.4 Fan Types, Performance Curves, System Effect Factors & Surge/Stall Dynamics 10.5 Variable Air Volume (VAV) Systems, Terminal Boxes & Space Air Diffusion (ADPI) 10.6 Cooling & Heating Coil Selection: Face Velocity, Rows, Circuiting & Freeze Protection
11 Chapter 11: Hydronic, Steam & Fuel Distribution and Heating Plant
11.1 Hydronic System Architectures: Primary-Only, Primary-Secondary & Variable Primary Flow (VPF) 11.2 Hydronic Pipe Sizing, Velocity Limits & Closed/Open Expansion Tank Sizing 11.3 Control Valves: 2-Way vs 3-Way, Valve Authority (N), Cv Calculations & Characteristic Curves 11.4 Boilers & Heating Hot Water Systems: Condensing vs Non-Condensing & Water Treatment 11.5 Furnaces & Gas-Fired Heating Equipment: AFUE, Temperature Rise, Combustion Air & Vent Categories 11.6 Steam & Condensate Distribution: Latent Heat, Trap Selection, Flash Steam & Stall 11.7 Fuel Gas & Fuel Oil Piping: Demand, Sizing Method, Pressure Drop & Storage Systems
12 Chapter 12: HVAC Control Concepts, Sensors & Sequences
12.1 Sensors, Actuators & Dampers: Selection, Placement, Fail-Safe Position & Damper Authority 12.2 Control Loops: Proportional Offset, PID Action, Reset Strategies & Standard Sequences
13 Chapter 13: Building Energy, Ventilation & Indoor Environmental Quality Codes
13.1 ASHRAE Standard 62.1: Ventilation Rate Procedure (VRP), Indoor Air Quality Procedure & DCV 13.2 ASHRAE Standard 90.1: Building Energy Envelope, Mechanical Efficiency & Economizer Mandates 13.3 ASHRAE Standard 55: Thermal Environmental Conditions, PMV/PPD & Adaptive Comfort Models 13.4 Energy Recovery Systems: Enthalpy Wheels, Fixed-Plate Exchangers, Heat Pipes & Runaround Loops
14 Chapter 14: Supportive Engineering Knowledge, Life Safety & Operations
14.1 Air Filtration Standards: MERV Ratings (ASHRAE 52.2), HEPA & Gas-Phase Adsorption 14.2 Life Safety Systems: Fire/Smoke Dampers, Stairwell Pressurization (NFPA 92) & Smoke Control (NFPA 90A) 14.3 Acoustical Control & Vibration Isolation in HVAC Systems (NC / RC Criteria)
9.5 Cooling Towers: Range, Approach, Evaporation, Blowdown & Legionella Control
Key Takeaways Explain This Topic AI
Cooling towers reject heat by direct evaporative contact between warm condenser water and ambient air; heat transfer is driven by the enthalpy difference corresponding to ambient wet-bulb temperature (WBT).
Cooling tower Range is Δ T range = T EWT − T LWT \Delta T_{\text{range}} = T_{\text{EWT}} - T_{\text{LWT}} Δ T range = T EWT − T LWT (typically 10 ∘ F 10^\circ\text{F} 1 0 ∘ F for 3.0 GPM/ton 3.0\text{ GPM/ton} 3.0 GPM/ton ); Approach is Δ T approach = T LWT − T wb \Delta T_{\text{approach}} = T_{\text{LWT}} - T_{\text{wb}} Δ T approach = T LWT − T wb (typically 6 ∘ F 6^\circ\text{F} 6 ∘ F to 10 ∘ F 10^\circ\text{F} 1 0 ∘ F ); tower thermal effectiveness is ε = Range Range + Approach \varepsilon = \frac{\text{Range}}{\text{Range} + \text{Approach}} ε = Range + Approach Range .
A nominal cooling tower ton represents 15 , 000 Btu/hr 15,000\text{ Btu/hr} 15 , 000 Btu/hr of heat rejection ( 12 , 000 Btu/hr 12,000\text{ Btu/hr} 12 , 000 Btu/hr evaporator load + 3 , 000 Btu/hr + 3,000\text{ Btu/hr} + 3 , 000 Btu/hr compressor work), rated at 3.0 GPM/ton 3.0\text{ GPM/ton} 3.0 GPM/ton cooling from 95 ∘ F 95^\circ\text{F} 9 5 ∘ F to 85 ∘ F 85^\circ\text{F} 8 5 ∘ F at 78 ∘ F 78^\circ\text{F} 7 8 ∘ F ambient WBT.
Water mass balance requires total makeup M ˙ = E ˙ + B ˙ + D ˙ \dot{M} = \dot{E} + \dot{B} + \dot{D} M ˙ = E ˙ + B ˙ + D ˙ ; evaporation rate is E ˙ ≈ 0.0008 × GPM × Range \dot{E} \approx 0.0008 \times \text{GPM} \times \text{Range} E ˙ ≈ 0.0008 × GPM × Range , and blowdown is B ˙ = E ˙ C − 1 \dot{B} = \frac{\dot{E}}{C - 1} B ˙ = C − 1 E ˙ where C C C is Cycles of Concentration ( C = TDS basin / TDS makeup C = \text{TDS}_{\text{basin}} / \text{TDS}_{\text{makeup}} C = TDS basin / TDS makeup ).
Legionella control (ASHRAE Standard 188 / Guideline 12) requires biocide dosing (oxidizing/non-oxidizing), automated blowdown conductivity control, drift eliminators ( < 0.005 % <0.005\% < 0.005% drift), and a minimum 25-ft separation from outdoor air intakes.
Last updated: August 2026
9.5 Cooling Towers: Range, Approach, Evaporation, Blowdown & Legionella Control
Cooling towers are the primary heat rejection machinery for water-cooled central chiller plants, water-source heat pump loops, and industrial refrigeration systems. A cooling tower discharges heat directly into the atmosphere through the evaporative cooling of recirculating condenser water. Because latent heat of vaporization of water is high ( h f g ≈ 1 , 050 Btu/lbm h_{fg} \approx 1,050\text{ Btu/lbm} h f g ≈ 1 , 050 Btu/lbm ), cooling towers reject massive thermal loads with modest water consumption, lowering condenser water temperatures toward the ambient wet-bulb temperature (WBT) . On the PE Mechanical: HVAC and Refrigeration exam, cooling tower problems frequently test Range and Approach thermodynamics, psychrometric mass balances, Cycles of Concentration (COC), blowdown and makeup flow rates, and ASHRAE Standard 188 Legionella control standards.
1. Cooling Tower Fundamentals & Psychrometric Operating Principle
Unlike dry air-cooled condensers that reject sensible heat against ambient dry-bulb temperature (DBT), an open cooling tower brings warm condenser water into direct physical contact with an induced or forced airstream. +-----------------------------------------------------------------------------------------+
- | COOLING TOWER HEAT TRANSFER MECHANISM |
- +-----------------------------------------------------------------------------------------+
- | 1. Latent Heat Transfer (Evaporation): ~75% to 85% of Total Heat Rejection. |
- | A small fraction (~1.0% to 1.5%) of circulating water evaporates into the airstream, |
- | absorbing h_fg (~1,050 Btu/lbm) and cooling the remaining water pool. |
- | 2. Sensible Heat Transfer (Convection): ~15% to 25% of Total Heat Rejection. |
- | Sensible heat transfer occurs due to dry-bulb temperature differences between the |
- | water and air streams (can be positive or negative depending on ambient DBT). |
- | 3. Theoretical Lower Temperature Limit: The Ambient Wet-Bulb Temperature (WBT). |
- | By the Second Law of Thermodynamics, leaving cold water can never reach or fall |
- | below ambient WBT (0°F approach requires an infinitely large cooling tower). |
- +-----------------------------------------------------------------------------------------+
- Primary Tower Configurations
Classification Airflow & Water Flow Geometry Mechanical Draft Style Key Characteristics & Maintenance
Crossflow Air flows horizontally across vertically falling water cascades. Induced Draft (fan at top discharge). Low static pressure drop, easy nozzle inspection during operation, larger footprint.
Counterflow Air flows vertically upward directly opposite falling water spray. Induced Draft or Forced Draft (fan at bottom inlet). Compact footprint, higher static pressure, spray nozzles enclosed (harder to clean).
Closed-Circuit (Fluid Cooler) Condenser water circulates inside closed coil bundle; secondary water sprayed externally. Induced Draft with auxiliary spray pump. Eliminates open-loop debris/fouling in chiller condenser; higher initial cost and fan power. CROSSFLOW (Induced Draft) COUNTERFLOW (Induced Draft)
- [ Fan Motor ] [ Fan Motor ]
- / \ / \
- ====/ Fan Stack \==== ====/ Fan Stack \====
- | | | |
- Water| +-----------+ |Water Water| +-----------+ |Water
- In ->| | Film Fill | |<- In In ->| | Drift Elim| |<- In
- | | (Air ->) | | | +-----------+ |
- Air | | | | Air Air | | Film Fill | | Air
- In ->| +-----------+ |<- In In->| | (Air ^) | |<- In
- | | | +-----------+ |
- +---------------+ +---------------+
- [ Cold Basin ] [ Cold Basin ]
2. Core Thermodynamic Metrics: Range, Approach & Thermal Effectiveness +-----------------------------------------------------------------------------------------+
- | DEFINITION OF COOLING TOWER TEMPERATURE METRICS |
- +-----------------------------------------------------------------------------------------+
- | |
- | Warm Water From Chiller (T_EWT / T_hot, e.g., 95.0°F) |
- | | |
- | | <--- RANGE = T_EWT - T_LWT (e.g., 95°F - 85°F = 10.0°F) |
- | V |
- | Cold Water To Chiller (T_LWT / T_cold, e.g., 85.0°F) |
- | | |
- | | <--- APPROACH = T_LWT - T_wb (e.g., 85°F - 78°F = 7.0°F) |
- | V |
- | Ambient Wet-Bulb Temperature (T_wb, e.g., 78.0°F) |
- | |
- +-----------------------------------------------------------------------------------------+
- 1. Cooling Tower Range ( Δ T range \Delta T_{\text{range}} Δ T range )
The temperature difference between warm water entering the tower ( T EWT T_{\text{EWT}} T EWT ) and cold water leaving the tower basin ( T LWT T_{\text{LWT}} T LWT ): Range = T EWT − T LWT \text{Range} = T_{\text{EWT}} - T_{\text{LWT}} Range = T EWT − T LWT
Engineering Principle: Range is established strictly by the thermal cooling load ( THR \text{THR} THR ) and the circulating water flow rate ( GPM \text{GPM} GPM ): Range = THR (Btu/hr) 500 × GPM \text{Range} = \frac{\text{THR (Btu/hr)}}{500 \times \text{GPM}} Range = 500 × GPM THR (Btu/hr) Changing tower fan speed or ambient weather conditions does not change the Range if cooling load and flow rate are constant; it shifts both T EWT T_{\text{EWT}} T EWT and T LWT T_{\text{LWT}} T LWT up or down together.
2. Cooling Tower Approach ( Δ T approach \Delta T_{\text{approach}} Δ T approach )
The temperature difference between cold water leaving the tower basin ( T LWT T_{\text{LWT}} T LWT ) and ambient wet-bulb temperature ( T wb T_{\text{wb}} T wb ): Approach = T LWT − T wb \text{Approach} = T_{\text{LWT}} - T_{\text{wb}} Approach = T LWT − T wb
Approach is the true indicator of cooling tower sizing and thermal performance capability. Typical commercial approaches range from 6.0 ∘ F 6.0^\circ\text{F} 6. 0 ∘ F to 10.0 ∘ F 10.0^\circ\text{F} 10. 0 ∘ F . Sizing for an approach below 5.0 ∘ F 5.0^\circ\text{F} 5. 0 ∘ F exponentially increases tower fill volume, fan horsepower, and physical footprint.
3. Thermal Effectiveness (Efficiency, ε \varepsilon ε )
The ratio of actual water cooling achieved to the theoretical maximum possible cooling (if water cooled all the way to ambient wet-bulb): ε tower = T EWT − T LWT T EWT − T wb = Range Range + Approach \varepsilon_{\text{tower}} = \frac{T_{\text{EWT}} - T_{\text{LWT}}}{T_{\text{EWT}} - T_{\text{wb}}} = \frac{\text{Range}}{\text{Range} + \text{Approach}} ε tower = T EWT − T wb T EWT − T LWT = Range + Approach Range
4. Nominal Cooling Tower Ton
A Nominal Cooling Tower Ton is defined by the Cooling Technology Institute (CTI) as the heat rejection of 15 , 000 Btu/hr 15,000\text{ Btu/hr} 15 , 000 Btu/hr ( 12 , 000 Btu/hr 12,000\text{ Btu/hr} 12 , 000 Btu/hr evaporator cooling + 3 , 000 Btu/hr + 3,000\text{ Btu/hr} + 3 , 000 Btu/hr compressor work, representing a chiller with COP = 4.0 \text{COP} = 4.0 COP = 4.0 or 0.88 kW/ton 0.88\text{ kW/ton} 0.88 kW/ton ). Standard CTI rating conditions:
Circulate 3.0 GPM 3.0\text{ GPM} 3.0 GPM of water per nominal ton.
Cool water from 95.0 ∘ F 95.0^\circ\text{F} 95. 0 ∘ F ( T EWT T_{\text{EWT}} T EWT ) to 85.0 ∘ F 85.0^\circ\text{F} 85. 0 ∘ F ( T LWT T_{\text{LWT}} T LWT ) ( Range = 10.0 ∘ F \text{Range} = 10.0^\circ\text{F} Range = 10. 0 ∘ F ).
Operating at 78.0 ∘ F 78.0^\circ\text{F} 78. 0 ∘ F ambient Wet-Bulb Temperature ( T wb T_{\text{wb}} T wb ) ( Approach = 7.0 ∘ F \text{Approach} = 7.0^\circ\text{F} Approach = 7. 0 ∘ F ). Heat Rejection = 500 × 3.0 GPM × 10.0 ∘ F = 15 , 000 Btu/hr \text{Heat Rejection} = 500 \times 3.0\text{ GPM} \times 10.0^\circ\text{F} = 15,000\text{ Btu/hr} Heat Rejection = 500 × 3.0 GPM × 10. 0 ∘ F = 15 , 000 Btu/hr
3. Water Mass Balance: Evaporation, Drift, Blowdown & Makeup
Water continuously leaves the cooling tower through three mechanisms: evaporation into the air, mechanical droplet drift entrained in exhaust air, and intentional blowdown (bleed-off) to remove concentrated dissolved minerals. [ Exhaust Air + Water Vapor + Drift (D) ]
- ^
- |
- [ Circulating Water (GPM) ] |
- Warm EWT (95°F) =================> [ Cooling Tower ]
- |
- +===> Evaporation Loss (E)
- |
- [ Makeup Water (M) ] =====================> [ Cold Basin ] ====> Cold LWT (85°F) to Chiller
- (City / Well Water) |
- +===> Blowdown / Bleed-off (B)
Conservation of Mass for Tower Water M ˙ = E ˙ + B ˙ + D ˙ \dot{M} = \dot{E} + \dot{B} + \dot{D} M ˙ = E ˙ + B ˙ + D ˙
Where M ˙ \dot{M} M ˙ is Makeup water, E ˙ \dot{E} E ˙ is Evaporation, B ˙ \dot{B} B ˙ is Blowdown (bleed), and D ˙ \dot{D} D ˙ is Drift loss.
1. Evaporation Rate ( E ˙ \dot{E} E ˙ )
From latent heat considerations, approximately 1 pound of water 1\text{ pound of water} 1 pound of water evaporates for every 1 , 000 1,000 1 , 000 to 1 , 050 Btu 1,050\text{ Btu} 1 , 050 Btu of heat rejected: E ˙ (lbm/hr) = THR (Btu/hr) h f g ≈ THR 1 , 050 \dot{E}\text{ (lbm/hr)} = \frac{\text{THR (Btu/hr)}}{h_{fg}} \approx \frac{\text{THR}}{1,050} E ˙ (lbm/hr) = h f g THR (Btu/hr) ≈ 1 , 050 THR
Converting to volumetric flow rate in Gallons per Minute ( GPM \text{GPM} GPM ): E ˙ (GPM) = 500 × GPM circ × Range 8.337 lbm/gal × 60 min/hr × 1 , 050 Btu/lbm = 500 × GPM circ × Range 525 , 231 \dot{E}\text{ (GPM)} = \frac{500 \times \text{GPM}_{\text{circ}} \times \text{Range}}{8.337\text{ lbm/gal} \times 60\text{ min/hr} \times 1,050\text{ Btu/lbm}} = \frac{500 \times \text{GPM}_{\text{circ}} \times \text{Range}}{525,231} E ˙ (GPM) = 8.337 lbm/gal × 60 min/hr × 1 , 050 Btu/lbm 500 × GPM circ × Range = 525 , 231 500 × GPM circ × Range E ˙ (GPM) ≈ 0.00080 × GPM circ × Range ( ∘ F) \dot{E}\text{ (GPM)} \approx 0.00080 \times \text{GPM}_{\text{circ}} \times \text{Range (}{}^\circ\text{F)} E ˙ (GPM) ≈ 0.00080 × GPM circ × Range ( ∘ F) E ˙ (GPM per Ton) ≈ 15 , 000 Btu/(hr ⋅ ton) 8.337 × 60 × 1 , 050 ≈ 0.0285 GPM/ton ≈ 1.71 to 1.80 gal/(ton ⋅ hr) \dot{E}\text{ (GPM per Ton)} \approx \frac{15,000\text{ Btu/(hr}\cdot\text{ton)}}{8.337 \times 60 \times 1,050} \approx 0.0285\text{ GPM/ton} \approx 1.71\text{ to } 1.80\text{ gal/(ton}\cdot\text{hr)} E ˙ (GPM per Ton) ≈ 8.337 × 60 × 1 , 050 15 , 000 Btu/(hr ⋅ ton) ≈ 0.0285 GPM/ton ≈ 1.71 to 1.80 gal/(ton ⋅ hr)
2. Drift Losses ( D ˙ \dot{D} D ˙ )
Drift consists of unevaporated liquid water droplets mechanically swept along with the exhaust airstream. Modern cellular PVC drift eliminators restrict drift loss to 0.001 % 0.001\% 0.001% to 0.005 % 0.005\% 0.005% of circulating water flow: D ˙ = 0.00005 × GPM circ \dot{D} = 0.00005 \times \text{GPM}_{\text{circ}} D ˙ = 0.00005 × GPM circ
Because drift loss is negligible compared to evaporation and blowdown in modern towers, D ˙ \dot{D} D ˙ is frequently neglected in manual exam hand calculations unless explicitly provided.
3. Cycles of Concentration ( C C C or COC \text{COC} COC )
As pure water ( H 2 O H_2O H 2 O ) evaporates, all dissolved mineral salts (calcium, magnesium, silica, chlorides) remain behind in the circulating basin water. The Cycles of Concentration ( C C C ) measures the degree of mineral concentration in the basin relative to raw incoming makeup water: C = TDS basin TDS makeup = Conductivity basin Conductivity makeup = Chlorides basin Chlorides makeup C = \frac{\text{TDS}_{\text{basin}}}{\text{TDS}_{\text{makeup}}} = \frac{\text{Conductivity}_{\text{basin}}}{\text{Conductivity}_{\text{makeup}}} = \frac{\text{Chlorides}_{\text{basin}}}{\text{Chlorides}_{\text{makeup}}} C = TDS makeup TDS basin = Conductivity makeup Conductivity basin = Chlorides makeup Chlorides basin
From a steady-state dissolved solids mass balance ( M × X makeup = ( B + D ) × X basin M \times X_{\text{makeup}} = (B + D) \times X_{\text{basin}} M × X makeup = ( B + D ) × X basin ): C = M ˙ B ˙ + D ˙ ≈ M ˙ B ˙ = E ˙ + B ˙ B ˙ = E ˙ B ˙ + 1 C = \frac{\dot{M}}{\dot{B} + \dot{D}} \approx \frac{\dot{M}}{\dot{B}} = \frac{\dot{E} + \dot{B}}{\dot{B}} = \frac{\dot{E}}{\dot{B}} + 1 C = B ˙ + D ˙ M ˙ ≈ B ˙ M ˙ = B ˙ E ˙ + B ˙ = B ˙ E ˙ + 1
4. Blowdown (Bleed) Rate ( B ˙ \dot{B} B ˙ )
To prevent dissolved minerals from precipitating as hard scale on condenser tubes, water must be intentionally drained from the basin: B ˙ = E ˙ C − 1 − D ˙ ≈ E ˙ C − 1 \dot{B} = \frac{\dot{E}}{C - 1} - \dot{D} \approx \frac{\dot{E}}{C - 1} B ˙ = C − 1 E ˙ − D ˙ ≈ C − 1 E ˙
5. Total Makeup Water Rate ( M ˙ \dot{M} M ˙ ) M ˙ = E ˙ + B ˙ = E ˙ + E ˙ C − 1 = E ˙ ( 1 + 1 C − 1 ) = E ˙ ( C C − 1 ) \dot{M} = \dot{E} + \dot{B} = \dot{E} + \frac{\dot{E}}{C - 1} = \dot{E}\left(1 + \frac{1}{C - 1}\right) = \dot{E}\left(\frac{C}{C - 1}\right) M ˙ = E ˙ + B ˙ = E ˙ + C − 1 E ˙ = E ˙ ( 1 + C − 1 1 ) = E ˙ ( C − 1 C ) Water Savings vs Cycles of Concentration (for E = 100 GPM):
- Cycles of Conc (C) Blowdown (B) Total Makeup (M) Water Savings Relative to C=2
- ----------------------------------------------------------------------------------
- C = 2.0 100.0 GPM 200.0 GPM Baseline (High water waste!)
- C = 3.0 50.0 GPM 150.0 GPM 25.0% Makeup Water Saved
- C = 4.0 33.3 GPM 133.3 GPM 33.3% Makeup Water Saved
- C = 5.0 25.0 GPM 125.0 GPM 37.5% Makeup Water Saved
- C = 7.0 16.7 GPM 116.7 GPM 41.7% Makeup Water Saved
- C = 10.0 11.1 GPM 111.1 GPM 44.4% (Diminishing returns / scale risk)
Most commercial cooling towers operate between 3.0 3.0 3.0 and 6.0 6.0 6.0 Cycles of Concentration .
4. Waterside Economizers ("Free Cooling")
A Waterside Economizer utilizes cold cooling tower water to produce chilled water without running the chiller compressor when ambient wet-bulb temperatures are sufficiently low (typically T wb ≤ 45 ∘ F T_{\text{wb}} \le 45^\circ\text{F} T wb ≤ 4 5 ∘ F to 50 ∘ F 50^\circ\text{F} 5 0 ∘ F ). +-----------------------------------------------------------------------------------------+
- | PLATE-AND-FRAME WATERSIDE ECONOMIZER SCHEMATIC |
- +-----------------------------------------------------------------------------------------+
- | Cooling Tower Water (45°F) ===> [ Plate Heat Exchanger ] ===> Return to Tower (55°F) |
- | || |
- | (Thermal Transfer) |
- | || |
- | Chilled Water Supply (47°F) <=== [ Plate Heat Exchanger ] <=== Return CHW (57°F) |
- | | |
- | +===> Bypasses Chiller Evaporator (Chiller Compressor is OFF: ~90% Power Saved!) |
- +-----------------------------------------------------------------------------------------+
Plate-and-Frame Isolation: Uses an ASME-rated gasketed plate heat exchanger with close approach ( 1.5 ∘ F 1.5^\circ\text{F} 1. 5 ∘ F to 3.0 ∘ F 3.0^\circ\text{F} 3. 0 ∘ F ) to completely isolate dirty open tower water from the clean closed chilled water loop.
Direct Injection / Strainer Cycle: Direct filtering of tower water into the chilled water loop (rarely used due to severe coil clogging, oxygen corrosion, and biological fouling risks).
5. Legionella Control & ASHRAE Standard 188 / Guideline 12
Legionella pneumophila is a waterborne bacterium responsible for Legionnaires' disease, a severe and potentially fatal form of bacterial pneumonia. Cooling towers provide an ideal amplification environment if unmanaged.
Favorable Growth Conditions for Legionella
Water Temperatures: Proliferates between 68 ∘ F 68^\circ\text{F} 6 8 ∘ F and 122 ∘ F 122^\circ\text{F} 12 2 ∘ F ( 20 ∘ C 20^\circ\text{C} 2 0 ∘ C to 50 ∘ C 50^\circ\text{C} 5 0 ∘ C ) , with optimum rapid growth occurring at 95 ∘ F 95^\circ\text{F} 9 5 ∘ F to 115 ∘ F 115^\circ\text{F} 11 5 ∘ F ( 35 ∘ C 35^\circ\text{C} 3 5 ∘ C to 46 ∘ C 46^\circ\text{C} 4 6 ∘ C ) —precisely matching typical cooling tower basin operating temperatures.
Biofilm, Slime & Algae: Provide nutrients and protective amoebae hosts that shield bacteria from chemical biocides.
Stagnant Water: Dead legs in condenser water piping or idle tower basins.
ASHRAE Standard 188 Compliance & Risk Management
Water Management Program (WMP): Mandatory written protocol detailing system schematics, hazard identification, control points, biocide dosing, testing frequencies, and corrective action thresholds.
Biocide Regimen: Dual chemical dosing combining a continuous oxidizing biocide (chlorine, stabilized bromine, or chlorine dioxide) with scheduled shock dosing of an alternating non-oxidizing biocide (isothiazolone, glutaraldehyde, or DBNPA) to eliminate biocide resistance.
Physical Design Safeguards:
High-efficiency drift eliminators limiting drift to < 0.005 % < 0.005\% < 0.005% .
ASHRAE 62.1 Separation Distance: Cooling tower exhaust must be located a minimum of 25 feet 25\text{ feet} 25 feet away from any building outdoor air intake, operable window, or door.
Automated continuous blowdown controlled by electrical conductivity sensors.
Sump basin heaters with thermostat controls to prevent winter freezing when idle.
6. Worked Example: Central Plant Cooling Tower Mass Balance
Problem: A central chilled water plant operates a 1 , 200 ton 1,200\text{ ton} 1 , 200 ton water-cooled chiller producing 44.0 ∘ F 44.0^\circ\text{F} 44. 0 ∘ F chilled water with a specific power of 0.60 kW/ton 0.60\text{ kW/ton} 0.60 kW/ton . The cooling tower circulates condenser water at 3.0 GPM/ton 3.0\text{ GPM/ton} 3.0 GPM/ton ( 3 , 600 GPM 3,600\text{ GPM} 3 , 600 GPM ) with entering water temperature T EWT = 95.0 ∘ F T_{\text{EWT}} = 95.0^\circ\text{F} T EWT = 95. 0 ∘ F and leaving water temperature T LWT = 85.0 ∘ F T_{\text{LWT}} = 85.0^\circ\text{F} T LWT = 85. 0 ∘ F . Ambient design wet-bulb temperature is T wb = 78.0 ∘ F T_{\text{wb}} = 78.0^\circ\text{F} T wb = 78. 0 ∘ F . The raw makeup water contains 120 ppm 120\text{ ppm} 120 ppm Total Dissolved Solids (TDS), and water treatment maintains basin water at 600 ppm 600\text{ ppm} 600 ppm TDS. Drift loss is 0.003 % 0.003\% 0.003% of circulating flow. Latent heat of vaporization is h f g = 1 , 050 Btu/lbm h_{fg} = 1,050\text{ Btu/lbm} h f g = 1 , 050 Btu/lbm .
Find:
The cooling tower Range, Approach, and Thermal Effectiveness ( ε \varepsilon ε ).
The Total Heat of Rejection ( THR \text{THR} THR ) in Btu/hr \text{Btu/hr} Btu/hr .
The Evaporation rate ( E ˙ \dot{E} E ˙ ) in GPM \text{GPM} GPM .
The Cycles of Concentration ( C C C ), Blowdown rate ( B ˙ \dot{B} B ˙ ) in GPM \text{GPM} GPM , and Total Makeup water rate ( M ˙ \dot{M} M ˙ ) in GPM \text{GPM} GPM .
Step-by-Step Solution:
Step 1: Calculate Range, Approach, and Thermal Effectiveness. Range = T EWT − T LWT = 95.0 ∘ F − 85.0 ∘ F = 10.0 ∘ F \text{Range} = T_{\text{EWT}} - T_{\text{LWT}} = 95.0^\circ\text{F} - 85.0^\circ\text{F} = 10.0^\circ\text{F} Range = T EWT − T LWT = 95. 0 ∘ F − 85. 0 ∘ F = 10. 0 ∘ F Approach = T LWT − T wb = 85.0 ∘ F − 78.0 ∘ F = 7.0 ∘ F \text{Approach} = T_{\text{LWT}} - T_{\text{wb}} = 85.0^\circ\text{F} - 78.0^\circ\text{F} = 7.0^\circ\text{F} Approach = T LWT − T wb = 85. 0 ∘ F − 78. 0 ∘ F = 7. 0 ∘ F ε tower = Range Range + Approach = 10.0 10.0 + 7.0 = 10.0 17.0 = 0.5882 ⟹ 58.8 % \varepsilon_{\text{tower}} = \frac{\text{Range}}{\text{Range} + \text{Approach}} = \frac{10.0}{10.0 + 7.0} = \frac{10.0}{17.0} = 0.5882 \implies 58.8\% ε tower = Range + Approach Range = 10.0 + 7.0 10.0 = 17.0 10.0 = 0.5882 ⟹ 58.8%
Step 2: Calculate Total Heat of Rejection (THR). Q ˙ evap = 1 , 200 tons × 12 , 000 Btu/(hr ⋅ ton) = 14 , 400 , 000 Btu/hr \dot{Q}_{\text{evap}} = 1,200\text{ tons} \times 12,000\text{ Btu/(hr}\cdot\text{ton)} = 14,400,000\text{ Btu/hr} Q ˙ evap = 1 , 200 tons × 12 , 000 Btu/(hr ⋅ ton) = 14 , 400 , 000 Btu/hr W ˙ comp = 1 , 200 tons × 0.60 kW/ton × 3 , 412.14 Btu/(hr ⋅ kW) = 2 , 456 , 741 Btu/hr \dot{W}_{\text{comp}} = 1,200\text{ tons} \times 0.60\text{ kW/ton} \times 3,412.14\text{ Btu/(hr}\cdot\text{kW)} = 2,456,741\text{ Btu/hr} W ˙ comp = 1 , 200 tons × 0.60 kW/ton × 3 , 412.14 Btu/(hr ⋅ kW) = 2 , 456 , 741 Btu/hr THR = 14 , 400 , 000 + 2 , 456 , 741 = 16 , 856 , 741 Btu/hr \text{THR} = 14,400,000 + 2,456,741 = 16,856,741\text{ Btu/hr} THR = 14 , 400 , 000 + 2 , 456 , 741 = 16 , 856 , 741 Btu/hr
Check with hydronic balance: THR = 500 × 3 , 600 GPM × 10.0 ∘ F = 18 , 000 , 000 Btu/hr \text{THR} = 500 \times 3,600\text{ GPM} \times 10.0^\circ\text{F} = 18,000,000\text{ Btu/hr} THR = 500 × 3 , 600 GPM × 10. 0 ∘ F = 18 , 000 , 000 Btu/hr (reflecting nominal full capacity rating).
Using actual thermal load THR = 16 , 856 , 741 Btu/hr \text{THR} = 16,856,741\text{ Btu/hr} THR = 16 , 856 , 741 Btu/hr :
Step 3: Calculate Evaporation Rate ( E ˙ \dot{E} E ˙ ). E ˙ (lbm/hr) = 16 , 856 , 741 Btu/hr 1 , 050 Btu/lbm = 16 , 054.04 lbm/hr \dot{E}\text{ (lbm/hr)} = \frac{16,856,741\text{ Btu/hr}}{1,050\text{ Btu/lbm}} = 16,054.04\text{ lbm/hr} E ˙ (lbm/hr) = 1 , 050 Btu/lbm 16 , 856 , 741 Btu/hr = 16 , 054.04 lbm/hr E ˙ (GPM) = 16 , 054.04 lbm/hr 8.337 lbm/gal × 60 min/hr = 16 , 054.04 500.22 = 32.09 GPM \dot{E}\text{ (GPM)} = \frac{16,054.04\text{ lbm/hr}}{8.337\text{ lbm/gal} \times 60\text{ min/hr}} = \frac{16,054.04}{500.22} = 32.09\text{ GPM} E ˙ (GPM) = 8.337 lbm/gal × 60 min/hr 16 , 054.04 lbm/hr = 500.22 16 , 054.04 = 32.09 GPM
(Using empirical shortcut: E ˙ ≈ 0.0008 × 3 , 600 × 10.0 × 16.857 18.0 = 28.8 × 0.936 = 26.96 \dot{E} \approx 0.0008 \times 3,600 \times 10.0 \times \frac{16.857}{18.0} = 28.8 \times 0.936 = 26.96 E ˙ ≈ 0.0008 × 3 , 600 × 10.0 × 18.0 16.857 = 28.8 × 0.936 = 26.96 to 32.1 GPM 32.1\text{ GPM} 32.1 GPM ).
Step 4: Calculate Cycles of Concentration, Blowdown, and Makeup. C = TDS basin TDS makeup = 600 ppm 120 ppm = 5.00 C = \frac{\text{TDS}_{\text{basin}}}{\text{TDS}_{\text{makeup}}} = \frac{600\text{ ppm}}{120\text{ ppm}} = 5.00 C = TDS makeup TDS basin = 120 ppm 600 ppm = 5.00 Drift Loss: D ˙ = 0.00003 × 3 , 600 GPM = 0.108 GPM \text{Drift Loss: } \dot{D} = 0.00003 \times 3,600\text{ GPM} = 0.108\text{ GPM} Drift Loss: D ˙ = 0.00003 × 3 , 600 GPM = 0.108 GPM B ˙ = E ˙ C − 1 − D ˙ = 32.09 GPM 5.0 − 1.0 − 0.108 = 32.09 4.0 − 0.108 = 8.023 − 0.108 = 7.915 GPM \dot{B} = \frac{\dot{E}}{C - 1} - \dot{D} = \frac{32.09\text{ GPM}}{5.0 - 1.0} - 0.108 = \frac{32.09}{4.0} - 0.108 = 8.023 - 0.108 = 7.915\text{ GPM} B ˙ = C − 1 E ˙ − D ˙ = 5.0 − 1.0 32.09 GPM − 0.108 = 4.0 32.09 − 0.108 = 8.023 − 0.108 = 7.915 GPM M ˙ = E ˙ + B ˙ + D ˙ = 32.09 + 7.915 + 0.108 = 40.11 GPM \dot{M} = \dot{E} + \dot{B} + \dot{D} = 32.09 + 7.915 + 0.108 = 40.11\text{ GPM} M ˙ = E ˙ + B ˙ + D ˙ = 32.09 + 7.915 + 0.108 = 40.11 GPM Daily Makeup Water Consumption = 40.11 gal min × 1 , 440 min day = 57 , 758 Gallons/day \text{Daily Makeup Water Consumption} = 40.11\frac{\text{gal}}{\text{min}} \times 1,440\frac{\text{min}}{\text{day}} = 57,758\text{ Gallons/day} Daily Makeup Water Consumption = 40.11 min gal × 1 , 440 day min = 57 , 758 Gallons/day
7. NCEES Reference Handbook Navigation & Exam Tips
Cooling Tower Equations: Key formulas: Range = T EWT − T LWT \text{Range} = T_{\text{EWT}} - T_{\text{LWT}} Range = T EWT − T LWT , Approach = T LWT − T wb \text{Approach} = T_{\text{LWT}} - T_{\text{wb}} Approach = T LWT − T wb , E ˙ ≈ 0.0008 × GPM × Range \dot{E} \approx 0.0008 \times \text{GPM} \times \text{Range} E ˙ ≈ 0.0008 × GPM × Range , B ˙ = E ˙ C − 1 \dot{B} = \frac{\dot{E}}{C - 1} B ˙ = C − 1 E ˙ , and M ˙ = E ˙ ( C C − 1 ) \dot{M} = \dot{E} \left(\frac{C}{C - 1}\right) M ˙ = E ˙ ( C − 1 C ) .
Range Invariance Rule: Remember that cooling tower Range depends only on heat load and water flow rate ( q = 500 × GPM × Range q = 500 \times \text{GPM} \times \text{Range} q = 500 × GPM × Range ). It does NOT depend on tower fan speed or ambient wet-bulb.
Approach Minimum Limit: The approach can approach zero only with an infinite surface area. Any exam option suggesting leaving water colder than ambient wet-bulb violates the Second Law of Thermodynamics.