9.3 Evaporators & Direct Expansion (DX) vs Liquid Chilling Coils

PE Mechanical: HVAC and Refrigeration Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Overview, Reference Handbook & Engineering Foundations

1.1 NCEES Exam Specification, CBT Delivery & Reference Handbook Strategy 1.2 Engineering Units, Dimensional Analysis & Physical Property Lookups 1.3 Engineering Economics, Life Cycle Cost Analysis & Equipment Financial Evaluation 1.4 Electrical Foundations, Motor Ratings & Variable Frequency Drives (VFDs)

2 Chapter 2: Thermodynamics & Energy Balances

2.1 First and Second Laws of Thermodynamics & Open/Closed System Energy Balances 2.2 Thermodynamic Cycles: Carnot, Rankine, Brayton & Reversed Carnot Limit 2.3 Gas & Vapor Property Evaluation: Steam Tables, Superheat & Subcooling 2.4 Mass, Energy & Combustion Balances for HVAC Equipment

3 Chapter 3: Psychrometrics, Moist Air Processes & Humidity Equipment

3.1 Psychrometric Properties: DBT, WBT, DPT, RH, Humidity Ratio & Enthalpy 3.2 Chart Reading & Psychrometric Equations at Sea Level vs. Altitude (5,000 ft) 3.3 Basic Psychrometric Processes: Sensible Heating/Cooling, Humidification & Dehumidification 3.4 Mixed Air Calculations & Complex Air Conditioning Cycles (Preheat, Reheat & Bypass) 3.5 Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP) & Coil Bypass Factor 3.6 Humidification & Dehumidification Equipment: Steam, Adiabatic, Desiccant & Low-Temperature Processes

4 Chapter 4: Heat Transfer Principles & Sizing

4.1 Steady-State Conduction & Multilayer Thermal Resistance (R-Value & U-Factor) 4.2 Convective Heat Transfer & Forced/Natural Convection Coefficients 4.3 Radiation Heat Transfer, Surface Emissivity & View Factors 4.4 Overall Heat Transfer Coefficients, Fouling Factors & Transient/Thermal Mass Effects 4.5 Heat Exchanger Analysis: Log Mean Temperature Difference (LMTD) & Effectiveness-NTU (ε-NTU)

5 Chapter 5: Fluid Mechanics & Hydraulic Fundamentals

5.1 Fluid Statics, Incompressible Continuity & Bernoulli Energy Equation 5.2 Pipe Friction, Moody Diagram & Darcy-Weisbach / Hazen-Williams Calculations 5.3 Minor Losses: Equivalent Length, Loss Coefficients (K-factors) & Total System Head 5.4 Pump Sizing, Net Positive Suction Head (NPSHa vs NPSHr) & Cavitation Prevention 5.5 Affinity Laws & Parallel/Series Pump/Fan System Curves

6 Chapter 6: Heating & Cooling Load Calculations

6.1 Outdoor & Indoor Design Conditions (ASHRAE Fundamentals, Climatic Data & Indoor Setpoints) 6.2 Envelope Heat Transmission & Infiltration/Exfiltration Load Methods 6.3 Solar Heat Gain (SHGC), Fenestration & Cooling Load Temperature Difference / Radiant Time Series (CLTD/RTS) 6.4 Internal Heat Gains: Lighting, People, Equipment & Diversity Factors 6.5 Ventilation Loads & Sensible / Latent / Total Cooling Load Synthesis

7 Chapter 7: Refrigeration Principles, Cycles & Cold Storage Applications

7.1 Standard Vapor-Compression Refrigeration Cycle on P-h & T-s Diagrams 7.2 Refrigeration Cycle Performance Metrics: COP, EER, SEER, kW/ton & Ton of Refrigeration 7.3 Cycle Enhancements: Subcooling, Superheating, Liquid-Suction Heat Exchangers & Economizers 7.4 Multi-Stage & Cascade Refrigeration Systems: Intercooling & Flash Gas Removal 7.5 Absorption Refrigeration Cycles: Water-Lithium Bromide & Ammonia-Water Systems 7.6 Food Processing & Cold Storage Refrigeration: Product Load, Pull-Down & Storage Design

8 Chapter 8: Refrigerants, Environmental Regulations & Safety

8.1 Refrigerant Classifications, Nomenclature & Thermodynamic Properties (ASHRAE Standard 34) 8.2 AIM Act, EPA Technology Transitions Sector GWP Limits & Low-GWP Refrigerants (R-32, R-454B) 8.3 Refrigerant Safety Requirements & Machinery Room Design (ASHRAE Standard 15) 8.4 Refrigerant Piping Sizing, Oil Return, Traps & Double Risers

9 Chapter 9: HVAC Equipment & Primary Machinery

9.1 Compressors: Reciprocating, Rotary, Scroll, Screw & Centrifugal 9.2 Condensers: Air-Cooled, Water-Cooled & Evaporative Condensers 9.3 Evaporators & Direct Expansion (DX) vs Liquid Chilling Coils 9.4 Water Chillers: Centrifugal, Screw & Scroll with ASHRAE 90.1 Path A/B IPLV Ratings 9.5 Cooling Towers: Range, Approach, Evaporation, Blowdown & Legionella Control 9.6 Heat Pumps & Variable Refrigerant Flow (VRF): Balance Point, Defrost & Heat Recovery 9.7 Thermal Energy Storage: Full vs. Partial Storage, Chilled Water & Ice Systems

10 Chapter 10: Air-Side Systems & Distribution

10.1 Air Handling Units (AHUs), Dedicated Outdoor Air Systems (DOAS) & Fan-Coil Units 10.2 Duct Design Methodologies: Equal Friction, Static Regain & Velocity Reduction 10.3 Duct Fittings, Dynamic Pressure Losses & SMACNA Construction Standards 10.4 Fan Types, Performance Curves, System Effect Factors & Surge/Stall Dynamics 10.5 Variable Air Volume (VAV) Systems, Terminal Boxes & Space Air Diffusion (ADPI) 10.6 Cooling & Heating Coil Selection: Face Velocity, Rows, Circuiting & Freeze Protection

11 Chapter 11: Hydronic, Steam & Fuel Distribution and Heating Plant

11.1 Hydronic System Architectures: Primary-Only, Primary-Secondary & Variable Primary Flow (VPF) 11.2 Hydronic Pipe Sizing, Velocity Limits & Closed/Open Expansion Tank Sizing 11.3 Control Valves: 2-Way vs 3-Way, Valve Authority (N), Cv Calculations & Characteristic Curves 11.4 Boilers & Heating Hot Water Systems: Condensing vs Non-Condensing & Water Treatment 11.5 Furnaces & Gas-Fired Heating Equipment: AFUE, Temperature Rise, Combustion Air & Vent Categories 11.6 Steam & Condensate Distribution: Latent Heat, Trap Selection, Flash Steam & Stall 11.7 Fuel Gas & Fuel Oil Piping: Demand, Sizing Method, Pressure Drop & Storage Systems

12 Chapter 12: HVAC Control Concepts, Sensors & Sequences

12.1 Sensors, Actuators & Dampers: Selection, Placement, Fail-Safe Position & Damper Authority 12.2 Control Loops: Proportional Offset, PID Action, Reset Strategies & Standard Sequences

13 Chapter 13: Building Energy, Ventilation & Indoor Environmental Quality Codes

13.1 ASHRAE Standard 62.1: Ventilation Rate Procedure (VRP), Indoor Air Quality Procedure & DCV 13.2 ASHRAE Standard 90.1: Building Energy Envelope, Mechanical Efficiency & Economizer Mandates 13.3 ASHRAE Standard 55: Thermal Environmental Conditions, PMV/PPD & Adaptive Comfort Models 13.4 Energy Recovery Systems: Enthalpy Wheels, Fixed-Plate Exchangers, Heat Pipes & Runaround Loops

14 Chapter 14: Supportive Engineering Knowledge, Life Safety & Operations

14.1 Air Filtration Standards: MERV Ratings (ASHRAE 52.2), HEPA & Gas-Phase Adsorption 14.2 Life Safety Systems: Fire/Smoke Dampers, Stairwell Pressurization (NFPA 92) & Smoke Control (NFPA 90A) 14.3 Acoustical Control & Vibration Isolation in HVAC Systems (NC / RC Criteria)

9.3 Evaporators & Direct Expansion (DX) vs Liquid Chilling Coils

Key Takeaways Explain This Topic AI

Evaporators operate via two-phase boiling heat transfer at constant saturation temperature and pressure; the entering mixture is typically 15 % 15\% 15% to 25 % 25\% 25% flash gas vapor and 75 % 75\% 75% to 85 % 85\% 85% liquid by mass.

Direct Expansion (DX) coils boil refrigerant inside finned tubes directly cooling an airstream; operating superheat ( T suction − T sat T_{\text{suction}} - T_{\text{sat}} T suction ​ − T sat ​ ) of 8 ∘ F 8^\circ\text{F} 8 ∘ F to 12 ∘ F 12^\circ\text{F} 1 2 ∘ F is maintained by a thermostatic or electronic expansion valve to prevent compressor liquid floodback.

Flooded shell-and-tube evaporators submerge water tubes in a pool of boiling refrigerant, achieving high overall heat transfer coefficients ( U ≈ 300 − 800 Btu/(hr ⋅ ft 2 ⋅ ∘ F) U \approx 300-800\text{ Btu/(hr}\cdot\text{ft}^2\cdot^\circ\text{F)} U ≈ 300 − 800 Btu/(hr ⋅ ft 2 ⋅ ∘ F) ) and close approach temperatures ( 1 ∘ F 1^\circ\text{F} 1 ∘ F to 3 ∘ F 3^\circ\text{F} 3 ∘ F ), but require specialized oil recovery systems.

DX liquid chillers circulate refrigerant inside tubes with water in the shell; they ensure positive oil return through high refrigerant velocity but exhibit higher approach temperatures ( 4 ∘ F 4^\circ\text{F} 4 ∘ F to 8 ∘ F 8^\circ\text{F} 8 ∘ F ).

Evaporator approach temperature is defined as leaving fluid temperature minus saturated evaporating temperature ( T CHWS, leaving − T evap, sat T_{\text{CHWS, leaving}} - T_{\text{evap, sat}} T CHWS, leaving ​ − T evap, sat ​ ); each 1 ∘ F 1^\circ\text{F} 1 ∘ F reduction in evaporating temperature increases chiller power consumption by approximately 1.5 % 1.5\% 1.5% to 2.5 % 2.5\% 2.5% .

Last updated: August 2026

9.3 Evaporators & Direct Expansion (DX) vs Liquid Chilling Coils

The evaporator is the heat-absorbing component of the vapor-compression refrigeration cycle. Within the evaporator, low-pressure liquid refrigerant absorbs thermal energy from the process fluid (air, water, or brine) and vaporizes at a constant saturation temperature. Evaporator design directly dictates system cooling capacity, sensible heat ratio (SHR), dehumidification performance, compressor operating pressure, and overall thermodynamic efficiency. On the PE Mechanical exam, candidates must analyze DX coil circuiting, superheat regulation, approach temperatures, and liquid chilling heat exchanger dynamics.

1. Evaporator Boiling Heat Transfer & Thermodynamic Zones

Refrigerant enters the evaporator following isenthalpic expansion through a throttling valve at state 4 as a low-temperature, low-pressure two-phase mixture (typically 15 % 15\% 15% to 25 % 25\% 25% vapor quality by mass, known as flash gas ). As it flows through the evaporator, it absorbs heat ( q ˙ e = h 1 − h 4 \dot{q}_e = h_1 - h_4 q ˙ ​ e ​ = h 1 ​ − h 4 ​ ) and undergoes two distinct heat transfer regimes: Enthalpy & Heat Transfer Regime Progression:

  • [ Two-Phase Boiling Zone (Latent) ] ================> [ Superheat Zone (Sensible) ]
  • Quality x: ~0.20 -> 1.0 (Saturated Vapor) Saturated Vapor -> Superheated Gas
  • Constant Saturation Temp (T_sat) & Pressure T_sat -> T_suction
  • High nucleate/forced convective boiling (h ~ 500+) Single-phase vapor (h ~ 20-50)
  • Accounts for ~90% to 95% of Evaporator Surface Area Accounts for ~5% to 10% of Surface Area

Two-Phase Boiling Zone (90% to 95% of surface area): Highly efficient nucleate and forced convective annular boiling. Heat transfer occurs at constant saturation temperature ( T evap, sat T_{\text{evap, sat}} T evap, sat ​ ) determined strictly by evaporating pressure ( P evap P_{\text{evap}} P evap ​ ).

Superheating Zone (5% to 10% of surface area): Once the liquid completely evaporates ( x = 1.0 x = 1.0 x = 1.0 ), single-phase vapor absorbs sensible heat, raising its dry-bulb temperature above saturation.

Operating Superheat Definition Operating Superheat = T suction, actual − T sat ( P evap ) \text{Operating Superheat} = T_{\text{suction, actual}} - T_{\text{sat}}(P_{\text{evap}}) Operating Superheat = T suction, actual ​ − T sat ​ ( P evap ​ )

Purpose of Superheat: Guarantees that zero unevaporated liquid droplets reach the compressor suction inlet, protecting compressor valves and cylinders from mechanical liquid slugging and crankcase oil wash-out.

Typical Superheat Settings: 8.0 ∘ F 8.0^\circ\text{F} 8. 0 ∘ F to 12.0 ∘ F 12.0^\circ\text{F} 12. 0 ∘ F for comfort air-conditioning; 4.0 ∘ F 4.0^\circ\text{F} 4. 0 ∘ F to 6.0 ∘ F 6.0^\circ\text{F} 6. 0 ∘ F for precision electronic expansion valve (EEV) liquid chillers.

Minimum Stable Superheat (MSS): The lowest superheat setting at which the expansion valve control loop remains stable without "hunting" (periodic cycling between overfeeding and starvation).

2. Direct Expansion (DX) Air Cooling Coils

In a Direct Expansion (DX) system, refrigerant expands directly inside finned tubes located in the air handling unit or ductwork, cooling and dehumidifying the supply airstream directly. +-----------------------------------------------------------------------------------------+

  • | DIRECT EXPANSION (DX) REFRIGERANT CIRCUIT ARCHITECTURE |
  • +-----------------------------------------------------------------------------------------+
  • | High-Pressure Liquid Line |
  • | | |
  • | V |
  • | [ Thermal Expansion Valve (TXV / EEV) ] |
  • | | (Throttles liquid to low-pressure 2-phase mixture) |
  • | V |
  • | [ Refrigerant Distributor & Nozzle ] |
  • | +=======> Circuit 1 (Capillary Feeder Tube) ----+ |
  • | +=======> Circuit 2 (Capillary Feeder Tube) ----|===> [ Finned Tube DX Coil ] |
  • | +=======> Circuit 3 (Capillary Feeder Tube) ----| (Cross-Counterflow Air) |
  • | +=======> Circuit 4 (Capillary Feeder Tube) ----+ |
  • | | |
  • | V |
  • | [ Suction Header Manifold ] |
  • | | (Equalized Superheated Vapor) |
  • | V |
  • | To Compressor Suction Inlet |
  • +-----------------------------------------------------------------------------------------+
  • Refrigerant Distribution & Circuiting

Because two-phase refrigerant tends to separate into liquid and vapor streams, multi-circuit DX coils require a precision distributor :

A calibrated orifice nozzle creates a high-velocity jet that mixes liquid and flash gas into a homogeneous aerosol mist.

Symmetrical capillary feeder tubes of identical length and internal diameter deliver equal mass flow and quality to each parallel coil circuit.

Unequal refrigerant distribution causes individual circuits to overfeed (liquid carryover) or starve (excessive superheat), drastically reducing total coil sensible and latent capacity.

Air-Side Coil Design Parameters

Face Velocity ( V face V_{\text{face}} V face ​ ): Standard design is 400 400 400 to 500 FPM 500\text{ FPM} 500 FPM . Exceeding 550 FPM 550\text{ FPM} 550 FPM causes condensed water droplets on fins to become entrained in the supply airstream (moisture carryover), causing downstream duct mold and water damage.

Fin Spacing: Typically 8 8 8 to 14 fins per inch (FPI) 14\text{ fins per inch (FPI)} 14 fins per inch (FPI) for comfort cooling. Lower fin density ( 3 3 3 to 6 FPI 6\text{ FPI} 6 FPI ) is used in refrigeration coils to accommodate frost accumulation between defrost cycles.

Coil Depth: 3 3 3 to 8 8 8 rows deep. Deeper coils provide higher contact factor ( 1 − BF 1 - \text{BF} 1 − BF ), lower leaving air temperature, and greater latent dehumidification.

3. Liquid Chilling Evaporator Configurations

Liquid chillers cool water, glycol, or brine for hydronic distribution throughout buildings or industrial facilities. +---------------------------------------------------------------------------------------------------------+

  • | LIQUID CHILLER EVAPORATOR TYPES |
  • +-------------------+---------------------------------+---------------------------------------------------+
  • | Evaporator Design | Fluid Locations | Key Engineering Characteristics |
  • +-------------------+---------------------------------+---------------------------------------------------+
  • | **Flooded** | Water inside tubes; | • High heat transfer coefficient (pool boiling) |
  • | **Shell-and-Tube**| Boiling refrigerant in shell | • Close approach temperature (1°F to 3°F) |
  • | | | • High refrigerant charge; requires oil recovery |
  • +-------------------+---------------------------------+---------------------------------------------------+
  • | **Direct Expansion| Refrigerant inside tubes; | • Positive oil return via high suction velocity |
  • | (DX) Shell-Tube** | Water in baffled shell | • Lower refrigerant charge; higher approach (4-8°F)|
  • +-------------------+---------------------------------+---------------------------------------------------+
  • | **Brazed Plate** | Alternate stacked corrugated | • Extremely compact; ultra-high U-value |
  • | **(BPHE)** | stainless steel plates | • Very low charge; sensitive to freezing/fouling |
  • +-------------------+---------------------------------+---------------------------------------------------+
  • | **Falling Film** | Water inside tubes; thin film of| • Superior heat transfer with 30-50% lower charge |
  • | | refrigerant sprayed over tubes | • Eliminates hydrostatic head boiling penalty |
  • +-------------------+---------------------------------+---------------------------------------------------+
  • Detailed Engineering Comparison
  • A. Flooded Shell-and-Tube Evaporators

Mechanics: Chilled water circulates through multiple passes inside enhanced copper tubes submerged in a liquid refrigerant pool inside the shell. Liquid level is controlled by a low-side float valve or electronic level transmitter.

Pool Boiling Advantages: Nucleate pool boiling over enhanced surfaces produces overall heat transfer coefficients U = 400 U = 400 U = 400 to 800 Btu/(hr ⋅ ft 2 ⋅ ∘ F) 800\text{ Btu/(hr}\cdot\text{ft}^2\cdot^\circ\text{F)} 800 Btu/(hr ⋅ ft 2 ⋅ ∘ F) .

The Oil Recovery Challenge: Because refrigerant boils quietly from the pool, lubricating oil concentrates in the liquid refrigerant rather than returning naturally with the vapor. Flooded chillers require dedicated continuous oil recovery systems (thermal distillation concentrators or venturi eductors) that bleed an oil-rich liquid stream from the pool, vaporize the refrigerant, and return pure oil to the compressor crankcase.

B. Falling Film Evaporators

Mechanics: A dedicated refrigerant pump or liquid header sprays liquid refrigerant over horizontal water tubes in a thin falling film. Vapor boils instantly from the thin liquid film without the liquid submersion height penalty.

Thermodynamic Superiority: In large flooded evaporators, liquid submersion increases hydrostatic pressure at the bottom of the shell, elevating local boiling temperature by 1 ∘ F 1^\circ\text{F} 1 ∘ F to 3 ∘ F 3^\circ\text{F} 3 ∘ F . Falling film evaporators eliminate this hydrostatic penalty, allowing uniform boiling throughout the bundle with 30 % 30\% 30% to 50 % 50\% 50% less total refrigerant charge .

C. Brazed Plate Heat Exchangers (BPHE)

Mechanics: Multiple corrugated herringbone 316 stainless steel plates vacuum-brazed with copper. Refrigerant and water flow in true counter-current thin channels.

Characteristics: Channels induce high turbulence at low Reynolds numbers, yielding U = 600 U = 600 U = 600 to 1 , 200 Btu/(hr ⋅ ft 2 ⋅ ∘ F) 1,200\text{ Btu/(hr}\cdot\text{ft}^2\cdot^\circ\text{F)} 1 , 200 Btu/(hr ⋅ ft 2 ⋅ ∘ F) .

Vulnerability: Small internal channels make BPHEs susceptible to particulate clogging (requiring 20-40 mesh upstream strainers) and catastrophic freeze rupture if water flow stops while evaporating below 32 ∘ F 32^\circ\text{F} 3 2 ∘ F .

4. Evaporator Approach Temperature & Plant Efficiency

The Evaporator Approach Temperature is the thermal driving difference between the leaving chilled fluid temperature and the saturated evaporating temperature of the refrigerant: Evaporator Approach = T CHWS, leaving − T evap, sat \text{Evaporator Approach} = T_{\text{CHWS, leaving}} - T_{\text{evap, sat}} Evaporator Approach = T CHWS, leaving ​ − T evap, sat ​ Temperature Profile (Chilled Water Evaporator):

  • Water Stream: T_CHWR (Entering 54°F) -----------------------------------> T_CHWS (Leaving 44°F)
  • |
  • | Approach = T_CHWS - T_evap
  • V
  • Refrigerant: T_evap ===================================================> Saturated Evap Temp (41°F)
  • Impact on Thermodynamic Efficiency

Evaporator Condition Saturated Evaporating Temp ( T evap T_{\text{evap}} T evap ​ ) Evaporator Approach Chiller Power Consumption (kW/ton)

Clean Enhanced Flooded Tubes 42.0 ∘ F 42.0^\circ\text{F} 42. 0 ∘ F (at 44 ∘ F 44^\circ\text{F} 4 4 ∘ F CHWS) 2.0 ∘ F 2.0^\circ\text{F} 2. 0 ∘ F 0.550 kW/ton 0.550\text{ kW/ton} 0.550 kW/ton (Baseline)

Slight Waterside Fouling 39.0 ∘ F 39.0^\circ\text{F} 39. 0 ∘ F (at 44 ∘ F 44^\circ\text{F} 4 4 ∘ F CHWS) 5.0 ∘ F 5.0^\circ\text{F} 5. 0 ∘ F 0.591 kW/ton 0.591\text{ kW/ton} 0.591 kW/ton ( + 7.5 % +7.5\% + 7.5% Power)

Severe Scale / Oil Fouling 35.0 ∘ F 35.0^\circ\text{F} 35. 0 ∘ F (at 44 ∘ F 44^\circ\text{F} 4 4 ∘ F CHWS) 9.0 ∘ F 9.0^\circ\text{F} 9. 0 ∘ F 0.655 kW/ton 0.655\text{ kW/ton} 0.655 kW/ton ( + 19.1 % +19.1\% + 19.1% Power)

Golden Rule of Chiller Efficiency: Every 1.0 ∘ F 1.0^\circ\text{F} 1. 0 ∘ F drop in saturated evaporating temperature reduces chiller COP by ≈ 1.5 % \approx 1.5\% ≈ 1.5% to 2.5 % 2.5\% 2.5% (increases kW/ton \text{kW/ton} kW/ton by ≈ 1.5 % \approx 1.5\% ≈ 1.5% to 2.5 % 2.5\% 2.5% ) because the compressor must work across a higher pressure lift ( P cond / P evap P_{\text{cond}} / P_{\text{evap}} P cond ​ / P evap ​ ) to deliver the same cooling output.

5. Defrost Methods in Refrigeration Evaporators

When evaporators operate at saturated temperatures below 32 ∘ F 32^\circ\text{F} 3 2 ∘ F ( 0 ∘ C 0^\circ\text{C} 0 ∘ C ), moisture from air condenses and freezes as frost on the finned surfaces, insulating the coil and restricting airflow. +---------------------------------------------------------------------------------------------------------+

  • | EVAPORATOR DEFROST METHODOLOGIES |
  • +-------------------+---------------------------------+---------------------------------------------------+
  • | Defrost Method | Heat Source | Typical Applications & Cycle Times |
  • +-------------------+---------------------------------+---------------------------------------------------+

| **Air (Off-Cycle)**| Warm room air ($>36^\circ\text{F}$) circulated by coil fans while compressor is off. | Medium-temp walk-in coolers ($35^\circ\text{F}$ to $45^\circ\text{F}$). Simple and free. |

| **Electric** | Electric resistance heating elements interleaved inside coil fins. | Low-temp commercial freezers ($-20^\circ\text{F}$ to $0^\circ\text{F}$). Simple, high electric cost. |

| **Hot Gas** | High-pressure hot discharge vapor routed directly into the evaporator. | Large industrial refrigerated warehouses; fastest defrost (5-15 min), highest efficiency. |

| **Reverse Cycle** | 4-way reversing valve switches DX coil from evaporator to condenser mode. | Air-source heat pumps in heating mode. Rapid defrost (2-5 min). |

  • +-------------------+---------------------------------+---------------------------------------------------+
  • 6. Worked Example: DX Coil Capacity & Approach Analysis

Problem: A constant-volume air handler contains an R-410A direct expansion cooling coil. The fan delivers 10 , 000 CFM 10,000\text{ CFM} 10 , 000 CFM of standard air ( ρ = 0.075 lbm/ft 3 \rho = 0.075\text{ lbm/ft}^3 ρ = 0.075 lbm/ft 3 ). Mixed air enters the coil at 80.0 ∘ F 80.0^\circ\text{F} 80. 0 ∘ F dry-bulb ( T db,in T_{\text{db,in}} T db,in ​ ) and 67.0 ∘ F 67.0^\circ\text{F} 67. 0 ∘ F wet-bulb ( h in = 31.60 Btu/lbm h_{\text{in}} = 31.60\text{ Btu/lbm} h in ​ = 31.60 Btu/lbm ). Air leaves the coil at 55.0 ∘ F 55.0^\circ\text{F} 55. 0 ∘ F dry-bulb ( T db,out T_{\text{db,out}} T db,out ​ ) and 54.0 ∘ F 54.0^\circ\text{F} 54. 0 ∘ F wet-bulb ( h out = 22.60 Btu/lbm h_{\text{out}} = 22.60\text{ Btu/lbm} h out ​ = 22.60 Btu/lbm ). The refrigerant evaporates at P evap = 120.0 psia P_{\text{evap}} = 120.0\text{ psia} P evap ​ = 120.0 psia ( T sat = 41.0 ∘ F T_{\text{sat}} = 41.0^\circ\text{F} T sat ​ = 41. 0 ∘ F , h g = 180.20 Btu/lbm h_g = 180.20\text{ Btu/lbm} h g ​ = 180.20 Btu/lbm ) and leaves the coil at 51.0 ∘ F 51.0^\circ\text{F} 51. 0 ∘ F . Liquid refrigerant enters the expansion valve at h 4 = 65.20 Btu/lbm h_4 = 65.20\text{ Btu/lbm} h 4 ​ = 65.20 Btu/lbm .

Find:

The total cooling load ( Q ˙ total \dot{Q}_{\text{total}} Q ˙ ​ total ​ ), sensible cooling load ( Q ˙ sensible \dot{Q}_{\text{sensible}} Q ˙ ​ sensible ​ ), and Sensible Heat Ratio ( SHR \text{SHR} SHR ). Total cooling capacity in tons.

The operating superheat of the coil at the expansion valve bulb.

The required refrigerant mass flow rate ( m ˙ ref \dot{m}_{\text{ref}} m ˙ ref ​ ) in lbm/min \text{lbm/min} lbm/min .

The coil bypass factor ( BF \text{BF} BF ) assuming an Apparatus Dew Point (ADP) of 50.0 ∘ F 50.0^\circ\text{F} 50. 0 ∘ F .

Step-by-Step Solution:

Step 1: Compute air-side sensible, total cooling loads, and SHR. Q ˙ total = 4.5 × CFM × ( h in − h out ) = 4.5 × 10 , 000 × ( 31.60 − 22.60 ) = 4.5 × 10 , 000 × 9.00 = 405 , 000 Btu/hr \dot{Q}_{\text{total}} = 4.5 \times \text{CFM} \times (h_{\text{in}} - h_{\text{out}}) = 4.5 \times 10,000 \times (31.60 - 22.60) = 4.5 \times 10,000 \times 9.00 = 405,000\text{ Btu/hr} Q ˙ ​ total ​ = 4.5 × CFM × ( h in ​ − h out ​ ) = 4.5 × 10 , 000 × ( 31.60 − 22.60 ) = 4.5 × 10 , 000 × 9.00 = 405 , 000 Btu/hr Cooling Capacity (Tons) = 405 , 000 Btu/hr 12 , 000 Btu/(hr ⋅ ton) = 33.75 Tons \text{Cooling Capacity (Tons)} = \frac{405,000\text{ Btu/hr}}{12,000\text{ Btu/(hr}\cdot\text{ton)}} = 33.75\text{ Tons} Cooling Capacity (Tons) = 12 , 000 Btu/(hr ⋅ ton) 405 , 000 Btu/hr ​ = 33.75 Tons Q ˙ sensible = 1.08 × CFM × ( T db,in − T db,out ) = 1.08 × 10 , 000 × ( 80.0 − 55.0 ) = 10 , 800 × 25.0 = 270 , 000 Btu/hr \dot{Q}_{\text{sensible}} = 1.08 \times \text{CFM} \times (T_{\text{db,in}} - T_{\text{db,out}}) = 1.08 \times 10,000 \times (80.0 - 55.0) = 10,800 \times 25.0 = 270,000\text{ Btu/hr} Q ˙ ​ sensible ​ = 1.08 × CFM × ( T db,in ​ − T db,out ​ ) = 1.08 × 10 , 000 × ( 80.0 − 55.0 ) = 10 , 800 × 25.0 = 270 , 000 Btu/hr SHR = Q ˙ sensible Q ˙ total = 270 , 000 405 , 000 = 0.6667 ⟹ 66.7 % \text{SHR} = \frac{\dot{Q}_{\text{sensible}}}{\dot{Q}_{\text{total}}} = \frac{270,000}{405,000} = 0.6667 \implies 66.7\% SHR = Q ˙ ​ total ​ Q ˙ ​ sensible ​ ​ = 405 , 000 270 , 000 ​ = 0.6667 ⟹ 66.7%

Step 2: Calculate operating superheat. Superheat = T suction, leaving − T sat = 51.0 ∘ F − 41.0 ∘ F = 10.0 ∘ F \text{Superheat} = T_{\text{suction, leaving}} - T_{\text{sat}} = 51.0^\circ\text{F} - 41.0^\circ\text{F} = 10.0^\circ\text{F} Superheat = T suction, leaving ​ − T sat ​ = 51. 0 ∘ F − 41. 0 ∘ F = 10. 0 ∘ F

(A 10 ∘ F 10^\circ\text{F} 1 0 ∘ F superheat is ideal for standard TXV operation, ensuring complete vaporization without excess superheating surface area).

Step 3: Compute required refrigerant mass flow rate. Assuming superheated vapor specific heat c p , vapor ≈ 0.38 Btu/(lbm ⋅ ∘ F) c_{p,\text{vapor}} \approx 0.38\text{ Btu/(lbm}\cdot^\circ\text{F)} c p , vapor ​ ≈ 0.38 Btu/(lbm ⋅ ∘ F) : h 1 = h g + c p × Superheat = 180.20 + 0.38 × 10.0 = 180.20 + 3.80 = 184.00 Btu/lbm h_1 = h_g + c_p \times \text{Superheat} = 180.20 + 0.38 \times 10.0 = 180.20 + 3.80 = 184.00\text{ Btu/lbm} h 1 ​ = h g ​ + c p ​ × Superheat = 180.20 + 0.38 × 10.0 = 180.20 + 3.80 = 184.00 Btu/lbm Net Refrigeration Effect: q e = h 1 − h 4 = 184.00 − 65.20 = 118.80 Btu/lbm \text{Net Refrigeration Effect: } q_e = h_1 - h_4 = 184.00 - 65.20 = 118.80\text{ Btu/lbm} Net Refrigeration Effect: q e ​ = h 1 ​ − h 4 ​ = 184.00 − 65.20 = 118.80 Btu/lbm m ˙ ref = Q ˙ total q e = 405 , 000 Btu/hr 118.80 Btu/lbm = 3 , 409.09 lbm/hr = 56.82 lbm/min \dot{m}_{\text{ref}} = \frac{\dot{Q}_{\text{total}}}{q_e} = \frac{405,000\text{ Btu/hr}}{118.80\text{ Btu/lbm}} = 3,409.09\text{ lbm/hr} = 56.82\text{ lbm/min} m ˙ ref ​ = q e ​ Q ˙ ​ total ​ ​ = 118.80 Btu/lbm 405 , 000 Btu/hr ​ = 3 , 409.09 lbm/hr = 56.82 lbm/min

Step 4: Compute Coil Bypass Factor ( BF \text{BF} BF ). BF = T db,out − ADP T db,in − ADP = 55.0 ∘ F − 50.0 ∘ F 80.0 ∘ F − 50.0 ∘ F = 5.0 30.0 = 0.1667 ⟹ 16.7 % \text{BF} = \frac{T_{\text{db,out}} - \text{ADP}}{T_{\text{db,in}} - \text{ADP}} = \frac{55.0^\circ\text{F} - 50.0^\circ\text{F}}{80.0^\circ\text{F} - 50.0^\circ\text{F}} = \frac{5.0}{30.0} = 0.1667 \implies 16.7\% BF = T db,in ​ − ADP T db,out ​ − ADP ​ = 80. 0 ∘ F − 50. 0 ∘ F 55. 0 ∘ F − 50. 0 ∘ F ​ = 30.0 5.0 ​ = 0.1667 ⟹ 16.7% Contact Factor (CF) = 1 − BF = 1 − 0.1667 = 0.8333 ⟹ 83.3 % \text{Contact Factor (CF)} = 1 - \text{BF} = 1 - 0.1667 = 0.8333 \implies 83.3\% Contact Factor (CF) = 1 − BF = 1 − 0.1667 = 0.8333 ⟹ 83.3%

7. NCEES Reference Handbook Navigation & Exam Traps

Psychrometrics Section: Standard air shortcut equations: q ˙ s = 1.08 × CFM × Δ T \dot{q}_s = 1.08 \times \text{CFM} \times \Delta T q ˙ ​ s ​ = 1.08 × CFM × Δ T , q ˙ t = 4.5 × CFM × Δ h \dot{q}_t = 4.5 \times \text{CFM} \times \Delta h q ˙ ​ t ​ = 4.5 × CFM × Δ h , SHR = q ˙ s / q ˙ t \text{SHR} = \dot{q}_s / \dot{q}_t SHR = q ˙ ​ s ​ / q ˙ ​ t ​ , and BF = T d b , o u t − A D P T d b , i n − A D P \text{BF} = \frac{T_{db,out} - ADP}{T_{db,in} - ADP} BF = T d b , in ​ − A D P T d b , o u t ​ − A D P ​ .

Superheat vs. Subcooling Trap: Superheat is measured at the evaporator outlet / compressor suction ( T actual − T sat T_{\text{actual}} - T_{\text{sat}} T actual ​ − T sat ​ ) on vapor. Subcooling is measured at the condenser outlet / expansion valve inlet ( T sat − T actual T_{\text{sat}} - T_{\text{actual}} T sat ​ − T actual ​ ) on liquid. Never mix them up.

Approach Temperature Definition: Evaporator Approach = T leaving water − T sat, evaporating = T_{\text{leaving water}} - T_{\text{sat, evaporating}} = T leaving water ​ − T sat, evaporating ​ . Condenser Approach = T sat, condensing − T leaving water = T_{\text{sat, condensing}} - T_{\text{leaving water}} = T sat, condensing ​ − T leaving water ​ .

Loading diagram... Evaporator Architecture & Temperature Profiles