Study guide

9.7 Thermal Energy Storage: Full vs. Partial Storage, Chilled Water & Ice Systems

PE Mechanical: HVAC and Refrigeration Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Overview, Reference Handbook & Engineering Foundations

1.1 NCEES Exam Specification, CBT Delivery & Reference Handbook Strategy 1.2 Engineering Units, Dimensional Analysis & Physical Property Lookups 1.3 Engineering Economics, Life Cycle Cost Analysis & Equipment Financial Evaluation 1.4 Electrical Foundations, Motor Ratings & Variable Frequency Drives (VFDs)

2 Chapter 2: Thermodynamics & Energy Balances

2.1 First and Second Laws of Thermodynamics & Open/Closed System Energy Balances 2.2 Thermodynamic Cycles: Carnot, Rankine, Brayton & Reversed Carnot Limit 2.3 Gas & Vapor Property Evaluation: Steam Tables, Superheat & Subcooling 2.4 Mass, Energy & Combustion Balances for HVAC Equipment

3 Chapter 3: Psychrometrics, Moist Air Processes & Humidity Equipment

3.1 Psychrometric Properties: DBT, WBT, DPT, RH, Humidity Ratio & Enthalpy 3.2 Chart Reading & Psychrometric Equations at Sea Level vs. Altitude (5,000 ft) 3.3 Basic Psychrometric Processes: Sensible Heating/Cooling, Humidification & Dehumidification 3.4 Mixed Air Calculations & Complex Air Conditioning Cycles (Preheat, Reheat & Bypass) 3.5 Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP) & Coil Bypass Factor 3.6 Humidification & Dehumidification Equipment: Steam, Adiabatic, Desiccant & Low-Temperature Processes

4 Chapter 4: Heat Transfer Principles & Sizing

4.1 Steady-State Conduction & Multilayer Thermal Resistance (R-Value & U-Factor) 4.2 Convective Heat Transfer & Forced/Natural Convection Coefficients 4.3 Radiation Heat Transfer, Surface Emissivity & View Factors 4.4 Overall Heat Transfer Coefficients, Fouling Factors & Transient/Thermal Mass Effects 4.5 Heat Exchanger Analysis: Log Mean Temperature Difference (LMTD) & Effectiveness-NTU (ε-NTU)

5 Chapter 5: Fluid Mechanics & Hydraulic Fundamentals

5.1 Fluid Statics, Incompressible Continuity & Bernoulli Energy Equation 5.2 Pipe Friction, Moody Diagram & Darcy-Weisbach / Hazen-Williams Calculations 5.3 Minor Losses: Equivalent Length, Loss Coefficients (K-factors) & Total System Head 5.4 Pump Sizing, Net Positive Suction Head (NPSHa vs NPSHr) & Cavitation Prevention 5.5 Affinity Laws & Parallel/Series Pump/Fan System Curves

6 Chapter 6: Heating & Cooling Load Calculations

6.1 Outdoor & Indoor Design Conditions (ASHRAE Fundamentals, Climatic Data & Indoor Setpoints) 6.2 Envelope Heat Transmission & Infiltration/Exfiltration Load Methods 6.3 Solar Heat Gain (SHGC), Fenestration & Cooling Load Temperature Difference / Radiant Time Series (CLTD/RTS) 6.4 Internal Heat Gains: Lighting, People, Equipment & Diversity Factors 6.5 Ventilation Loads & Sensible / Latent / Total Cooling Load Synthesis

7 Chapter 7: Refrigeration Principles, Cycles & Cold Storage Applications

7.1 Standard Vapor-Compression Refrigeration Cycle on P-h & T-s Diagrams 7.2 Refrigeration Cycle Performance Metrics: COP, EER, SEER, kW/ton & Ton of Refrigeration 7.3 Cycle Enhancements: Subcooling, Superheating, Liquid-Suction Heat Exchangers & Economizers 7.4 Multi-Stage & Cascade Refrigeration Systems: Intercooling & Flash Gas Removal 7.5 Absorption Refrigeration Cycles: Water-Lithium Bromide & Ammonia-Water Systems 7.6 Food Processing & Cold Storage Refrigeration: Product Load, Pull-Down & Storage Design

8 Chapter 8: Refrigerants, Environmental Regulations & Safety

8.1 Refrigerant Classifications, Nomenclature & Thermodynamic Properties (ASHRAE Standard 34) 8.2 AIM Act, EPA Technology Transitions Sector GWP Limits & Low-GWP Refrigerants (R-32, R-454B) 8.3 Refrigerant Safety Requirements & Machinery Room Design (ASHRAE Standard 15) 8.4 Refrigerant Piping Sizing, Oil Return, Traps & Double Risers

9 Chapter 9: HVAC Equipment & Primary Machinery

9.1 Compressors: Reciprocating, Rotary, Scroll, Screw & Centrifugal 9.2 Condensers: Air-Cooled, Water-Cooled & Evaporative Condensers 9.3 Evaporators & Direct Expansion (DX) vs Liquid Chilling Coils 9.4 Water Chillers: Centrifugal, Screw & Scroll with ASHRAE 90.1 Path A/B IPLV Ratings 9.5 Cooling Towers: Range, Approach, Evaporation, Blowdown & Legionella Control 9.6 Heat Pumps & Variable Refrigerant Flow (VRF): Balance Point, Defrost & Heat Recovery 9.7 Thermal Energy Storage: Full vs. Partial Storage, Chilled Water & Ice Systems

10 Chapter 10: Air-Side Systems & Distribution

10.1 Air Handling Units (AHUs), Dedicated Outdoor Air Systems (DOAS) & Fan-Coil Units 10.2 Duct Design Methodologies: Equal Friction, Static Regain & Velocity Reduction 10.3 Duct Fittings, Dynamic Pressure Losses & SMACNA Construction Standards 10.4 Fan Types, Performance Curves, System Effect Factors & Surge/Stall Dynamics 10.5 Variable Air Volume (VAV) Systems, Terminal Boxes & Space Air Diffusion (ADPI) 10.6 Cooling & Heating Coil Selection: Face Velocity, Rows, Circuiting & Freeze Protection

11 Chapter 11: Hydronic, Steam & Fuel Distribution and Heating Plant

11.1 Hydronic System Architectures: Primary-Only, Primary-Secondary & Variable Primary Flow (VPF) 11.2 Hydronic Pipe Sizing, Velocity Limits & Closed/Open Expansion Tank Sizing 11.3 Control Valves: 2-Way vs 3-Way, Valve Authority (N), Cv Calculations & Characteristic Curves 11.4 Boilers & Heating Hot Water Systems: Condensing vs Non-Condensing & Water Treatment 11.5 Furnaces & Gas-Fired Heating Equipment: AFUE, Temperature Rise, Combustion Air & Vent Categories 11.6 Steam & Condensate Distribution: Latent Heat, Trap Selection, Flash Steam & Stall 11.7 Fuel Gas & Fuel Oil Piping: Demand, Sizing Method, Pressure Drop & Storage Systems

12 Chapter 12: HVAC Control Concepts, Sensors & Sequences

12.1 Sensors, Actuators & Dampers: Selection, Placement, Fail-Safe Position & Damper Authority 12.2 Control Loops: Proportional Offset, PID Action, Reset Strategies & Standard Sequences

13 Chapter 13: Building Energy, Ventilation & Indoor Environmental Quality Codes

13.1 ASHRAE Standard 62.1: Ventilation Rate Procedure (VRP), Indoor Air Quality Procedure & DCV 13.2 ASHRAE Standard 90.1: Building Energy Envelope, Mechanical Efficiency & Economizer Mandates 13.3 ASHRAE Standard 55: Thermal Environmental Conditions, PMV/PPD & Adaptive Comfort Models 13.4 Energy Recovery Systems: Enthalpy Wheels, Fixed-Plate Exchangers, Heat Pipes & Runaround Loops

14 Chapter 14: Supportive Engineering Knowledge, Life Safety & Operations

14.1 Air Filtration Standards: MERV Ratings (ASHRAE 52.2), HEPA & Gas-Phase Adsorption 14.2 Life Safety Systems: Fire/Smoke Dampers, Stairwell Pressurization (NFPA 92) & Smoke Control (NFPA 90A) 14.3 Acoustical Control & Vibration Isolation in HVAC Systems (NC / RC Criteria)

9.7 Thermal Energy Storage: Full vs. Partial Storage, Chilled Water & Ice Systems

Key Takeaways Explain This Topic AI

Chilled water storage is sensible and requires roughly 90 gallons per ton-hour at a 16 F temperature difference, while ice storage is latent at 144 Btu/lb and requires only about 10 gallons of water per ton-hour, roughly one-sixth the tank volume.

Full storage shifts the entire on-peak cooling load to off-peak hours, while partial storage sizes the chiller for the level 24-hour average load and lets storage cover the difference during the peak.

A chiller making ice must produce roughly 22 F to 26 F glycol instead of 44 F chilled water, which derates its capacity by about 30% to 35% and raises its kW per ton.

Thermal storage rarely saves energy; it saves cost by moving consumption to lower-priced hours and by cutting the billed peak demand, so its economics depend entirely on the rate structure.

Storage capacity is expressed in ton-hours: one ton-hour is 12,000 Btu, so a stratified tank storing 1,580 ton-hours holds 18.96 million Btu of usable cooling.

Last updated: August 2026

9.7 Thermal Energy Storage: Full vs. Partial Storage, Chilled Water & Ice Systems

Thermal energy storage (TES) decouples when cooling is produced from when cooling is used . It is listed under NCEES sub-topic 3D alongside chillers and heat pumps because the storage decision changes the chiller selection - sometimes dramatically.

State the economics up front, because exam distractors depend on it: TES almost never reduces annual energy consumption. Making ice at a 22 F suction temperature is less efficient than making 44 F chilled water. What TES buys is a cost shift - cheaper off-peak energy and, usually more valuable, a lower billed peak demand.

  • 1. Storage Media and the Volume Math
  • Sensible Storage - Chilled Water

Capacity comes from the temperature swing of the stored water: Q = ρ V c p Δ T Q = \rho \, V \, c_p \, \Delta T Q = ρ V c p ​ Δ T

Converting to the units engineers actually use, with 8.33 lb/gal and a specific heat of 1 Btu/lb-F, the gallons required per ton-hour are: gal ton-hr = 12,000 8.33 × Δ T \frac{\text{gal}}{\text{ton-hr}} = \frac{12{,}000}{8.33 \times \Delta T} ton-hr gal ​ = 8.33 × Δ T 12 , 000 ​

  • At a 16 F swing: 12,000 / 133.3 = 90 gallons per ton-hour
  • At a 20 F swing: 12,000 / 166.6 = 72 gallons per ton-hour

The temperature swing is limited by what the coils can use. Stratified tanks rely on the density difference between roughly 40 F and 60 F water, and a thermocline of 1 to 3 ft separates the two layers. Excessive inlet velocity destroys stratification, so diffusers are sized to keep the inlet Froude number low.

Latent Storage - Ice

Ice stores the heat of fusion of water, 144 Btu/lb , which is far more than any practical sensible swing:

  • Ice required per ton-hour: 12,000 / 144 = 83.3 lb
  • As water volume: 83.3 / 8.33 = 10.0 gallons per ton-hour

Ice therefore needs roughly one-sixth the water inventory of a 16 F chilled water system. In practice the installed tank volume is larger than 10 gal/ton-hr - typically 2.4 to 3.3 ft3 (about 18 to 25 gallons) per ton-hour once you account for the heat exchanger coils, the unfrozen water that must remain to carry flow, and the fact that not all water is converted to ice. Even so, ice remains three to five times more compact than chilled water storage.

Ice Storage Configurations

Type How It Works Notes

Ice-on-coil, internal melt Glycol circulates in submerged coils; ice builds on them and melts from the inside out Most common; discharge temperature rises as ice recedes from the coil

Ice-on-coil, external melt Warm return water flows over the ice; melts from the outside in Holds a colder, flatter discharge temperature; used for low-temperature air systems

Encapsulated ice Water sealed in plastic spheres or bricks in a glycol-filled tank Modular, simple tank

Ice harvester Ice is periodically released from an evaporator plate into a water tank High discharge rate; more moving parts

Eutectic salt phase-change materials freeze near 47 F rather than 32 F, which lets a conventional chiller charge them without derating, at the cost of a much lower storage density (about 6 Btu/lb).

  • 2. Operating Strategies Cooling load (tons)
  • | FULL STORAGE PARTIAL STORAGE
  • | +---------------+ +---------------+
  • | | storage | | storage |
  • | | discharge | | discharge |
  • | ---+---------------+--- ---+===============+--- <- level chiller output
  • | chiller off on-peak chiller runs 24 hours
  • +------------------------------ ------------------------
  • on-peak window on-peak window

Strategy Chiller Sizing Storage Sizing When It Wins

Full storage (load shifting) Sized to make the entire daily requirement during off-peak hours Largest; holds the whole on-peak load Steep on-peak/off-peak rate differential; short on-peak window; high demand charges

Partial storage (load leveling) Sized for the level 24-hour average load - the smallest chiller of the three Moderate Most common; lowest combined first cost

Partial storage (demand limiting) Between the two; chiller runs on-peak but throttled to a demand cap Moderate to large Ratchet-based demand charges

Worked Example - Partial Storage, Load Leveling

A building has a peak cooling load of 400 tons , a total daily cooling requirement of 3,400 ton-hours , and a 10-hour on-peak window during which 3,000 ton-hours of cooling is required.

Step 1 - Level chiller size. Running continuously, the chiller only has to produce the daily average:

3,400 ton-hr / 24 hr = 142 tons

Step 2 - Storage required. During the on-peak window the chiller supplies 142 x 10 = 1,420 ton-hours directly, and storage must cover the rest:

3,000 - 1,420 = 1,580 ton-hours of usable storage

Step 3 - Compare tank volumes.

  • Chilled water at 16 F swing: 1,580 x 90 = 142,000 gallons
  • Ice, installed basis at roughly 21 gal/ton-hr: 1,580 x 21 = 33,000 gallons

Step 4 - Correct the chiller selection for ice-making. The 142-ton figure is a load requirement. A chiller producing 24 F glycol instead of 44 F water loses roughly 30% to 35% of its nameplate capacity, so the machine must be selected at approximately 142 / 0.68 = 209 nominal tons . Skipping this derate is the single most common error in TES problems.

Even after the derate, the plant is 209 nominal tons instead of 400 tons - and the entire on-peak electrical demand associated with 1,580 ton-hours has been removed from the utility bill.

3. What Storage Does and Does Not Change

  • Metric Effect of Adding TES
  • Annual kWh Typically flat to slightly worse; ice-making penalty offsets gains from cooler nighttime condensing
  • Peak kW demand Substantially reduced - usually the dominant economic driver
  • Energy cost Reduced when off-peak rates are materially lower
  • Chiller size Reduced for partial storage; possibly not reduced for full storage

Distribution Ice enables 38 F to 42 F supply water, allowing larger delta-T, smaller pipe, and low-temperature air distribution with smaller ducts and fans

Reliability Storage provides a short-duration cooling reserve during a chiller outage

That low-temperature air distribution point is the underrated one. Ice systems can supply 44 F air rather than 55 F air, which nearly doubles the temperature difference the air carries. Supply airflow, duct size, and fan power all drop accordingly - and those fan savings can offset the chiller's ice-making penalty entirely.