3.3 Basic Psychrometric Processes: Sensible Heating/Cooling, Humidification & Dehumidification
PE Mechanical: HVAC and Refrigeration Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview, Reference Handbook & Engineering Foundations
1.1 NCEES Exam Specification, CBT Delivery & Reference Handbook Strategy 1.2 Engineering Units, Dimensional Analysis & Physical Property Lookups 1.3 Engineering Economics, Life Cycle Cost Analysis & Equipment Financial Evaluation 1.4 Electrical Foundations, Motor Ratings & Variable Frequency Drives (VFDs)
2 Chapter 2: Thermodynamics & Energy Balances
2.1 First and Second Laws of Thermodynamics & Open/Closed System Energy Balances 2.2 Thermodynamic Cycles: Carnot, Rankine, Brayton & Reversed Carnot Limit 2.3 Gas & Vapor Property Evaluation: Steam Tables, Superheat & Subcooling 2.4 Mass, Energy & Combustion Balances for HVAC Equipment
3 Chapter 3: Psychrometrics, Moist Air Processes & Humidity Equipment
3.1 Psychrometric Properties: DBT, WBT, DPT, RH, Humidity Ratio & Enthalpy 3.2 Chart Reading & Psychrometric Equations at Sea Level vs. Altitude (5,000 ft) 3.3 Basic Psychrometric Processes: Sensible Heating/Cooling, Humidification & Dehumidification 3.4 Mixed Air Calculations & Complex Air Conditioning Cycles (Preheat, Reheat & Bypass) 3.5 Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP) & Coil Bypass Factor 3.6 Humidification & Dehumidification Equipment: Steam, Adiabatic, Desiccant & Low-Temperature Processes
4 Chapter 4: Heat Transfer Principles & Sizing
4.1 Steady-State Conduction & Multilayer Thermal Resistance (R-Value & U-Factor) 4.2 Convective Heat Transfer & Forced/Natural Convection Coefficients 4.3 Radiation Heat Transfer, Surface Emissivity & View Factors 4.4 Overall Heat Transfer Coefficients, Fouling Factors & Transient/Thermal Mass Effects 4.5 Heat Exchanger Analysis: Log Mean Temperature Difference (LMTD) & Effectiveness-NTU (ε-NTU)
5 Chapter 5: Fluid Mechanics & Hydraulic Fundamentals
5.1 Fluid Statics, Incompressible Continuity & Bernoulli Energy Equation 5.2 Pipe Friction, Moody Diagram & Darcy-Weisbach / Hazen-Williams Calculations 5.3 Minor Losses: Equivalent Length, Loss Coefficients (K-factors) & Total System Head 5.4 Pump Sizing, Net Positive Suction Head (NPSHa vs NPSHr) & Cavitation Prevention 5.5 Affinity Laws & Parallel/Series Pump/Fan System Curves
6 Chapter 6: Heating & Cooling Load Calculations
6.1 Outdoor & Indoor Design Conditions (ASHRAE Fundamentals, Climatic Data & Indoor Setpoints) 6.2 Envelope Heat Transmission & Infiltration/Exfiltration Load Methods 6.3 Solar Heat Gain (SHGC), Fenestration & Cooling Load Temperature Difference / Radiant Time Series (CLTD/RTS) 6.4 Internal Heat Gains: Lighting, People, Equipment & Diversity Factors 6.5 Ventilation Loads & Sensible / Latent / Total Cooling Load Synthesis
7 Chapter 7: Refrigeration Principles, Cycles & Cold Storage Applications
7.1 Standard Vapor-Compression Refrigeration Cycle on P-h & T-s Diagrams 7.2 Refrigeration Cycle Performance Metrics: COP, EER, SEER, kW/ton & Ton of Refrigeration 7.3 Cycle Enhancements: Subcooling, Superheating, Liquid-Suction Heat Exchangers & Economizers 7.4 Multi-Stage & Cascade Refrigeration Systems: Intercooling & Flash Gas Removal 7.5 Absorption Refrigeration Cycles: Water-Lithium Bromide & Ammonia-Water Systems 7.6 Food Processing & Cold Storage Refrigeration: Product Load, Pull-Down & Storage Design
8 Chapter 8: Refrigerants, Environmental Regulations & Safety
8.1 Refrigerant Classifications, Nomenclature & Thermodynamic Properties (ASHRAE Standard 34) 8.2 AIM Act, EPA Technology Transitions Sector GWP Limits & Low-GWP Refrigerants (R-32, R-454B) 8.3 Refrigerant Safety Requirements & Machinery Room Design (ASHRAE Standard 15) 8.4 Refrigerant Piping Sizing, Oil Return, Traps & Double Risers
9 Chapter 9: HVAC Equipment & Primary Machinery
9.1 Compressors: Reciprocating, Rotary, Scroll, Screw & Centrifugal 9.2 Condensers: Air-Cooled, Water-Cooled & Evaporative Condensers 9.3 Evaporators & Direct Expansion (DX) vs Liquid Chilling Coils 9.4 Water Chillers: Centrifugal, Screw & Scroll with ASHRAE 90.1 Path A/B IPLV Ratings 9.5 Cooling Towers: Range, Approach, Evaporation, Blowdown & Legionella Control 9.6 Heat Pumps & Variable Refrigerant Flow (VRF): Balance Point, Defrost & Heat Recovery 9.7 Thermal Energy Storage: Full vs. Partial Storage, Chilled Water & Ice Systems
10 Chapter 10: Air-Side Systems & Distribution
10.1 Air Handling Units (AHUs), Dedicated Outdoor Air Systems (DOAS) & Fan-Coil Units 10.2 Duct Design Methodologies: Equal Friction, Static Regain & Velocity Reduction 10.3 Duct Fittings, Dynamic Pressure Losses & SMACNA Construction Standards 10.4 Fan Types, Performance Curves, System Effect Factors & Surge/Stall Dynamics 10.5 Variable Air Volume (VAV) Systems, Terminal Boxes & Space Air Diffusion (ADPI) 10.6 Cooling & Heating Coil Selection: Face Velocity, Rows, Circuiting & Freeze Protection
11 Chapter 11: Hydronic, Steam & Fuel Distribution and Heating Plant
11.1 Hydronic System Architectures: Primary-Only, Primary-Secondary & Variable Primary Flow (VPF) 11.2 Hydronic Pipe Sizing, Velocity Limits & Closed/Open Expansion Tank Sizing 11.3 Control Valves: 2-Way vs 3-Way, Valve Authority (N), Cv Calculations & Characteristic Curves 11.4 Boilers & Heating Hot Water Systems: Condensing vs Non-Condensing & Water Treatment 11.5 Furnaces & Gas-Fired Heating Equipment: AFUE, Temperature Rise, Combustion Air & Vent Categories 11.6 Steam & Condensate Distribution: Latent Heat, Trap Selection, Flash Steam & Stall 11.7 Fuel Gas & Fuel Oil Piping: Demand, Sizing Method, Pressure Drop & Storage Systems
12 Chapter 12: HVAC Control Concepts, Sensors & Sequences
12.1 Sensors, Actuators & Dampers: Selection, Placement, Fail-Safe Position & Damper Authority 12.2 Control Loops: Proportional Offset, PID Action, Reset Strategies & Standard Sequences
13 Chapter 13: Building Energy, Ventilation & Indoor Environmental Quality Codes
13.1 ASHRAE Standard 62.1: Ventilation Rate Procedure (VRP), Indoor Air Quality Procedure & DCV 13.2 ASHRAE Standard 90.1: Building Energy Envelope, Mechanical Efficiency & Economizer Mandates 13.3 ASHRAE Standard 55: Thermal Environmental Conditions, PMV/PPD & Adaptive Comfort Models 13.4 Energy Recovery Systems: Enthalpy Wheels, Fixed-Plate Exchangers, Heat Pipes & Runaround Loops
14 Chapter 14: Supportive Engineering Knowledge, Life Safety & Operations
14.1 Air Filtration Standards: MERV Ratings (ASHRAE 52.2), HEPA & Gas-Phase Adsorption 14.2 Life Safety Systems: Fire/Smoke Dampers, Stairwell Pressurization (NFPA 92) & Smoke Control (NFPA 90A) 14.3 Acoustical Control & Vibration Isolation in HVAC Systems (NC / RC Criteria)
3.3 Basic Psychrometric Processes: Sensible Heating/Cooling, Humidification & Dehumidification
Key Takeaways Explain This Topic AI
Sensible heating and cooling follow perfectly horizontal paths on the psychrometric chart at constant humidity ratio ( W W W ) and constant dew-point temperature ( T d p T_{dp} T d p ).
Cooling with dehumidification occurs when the cooling coil surface temperature is below the entering air dew point ( T s u r f a c e < T d p T_{surface} < T_{dp} T s u r f a ce < T d p ), causing the state path to slope downward and to the left.
Condensate drainage rate from a cooling coil is calculated as m ˙ c o n d = 60 ρ × CFM × ( W 1 − W 2 ) \dot{m}_{cond} = 60 \rho \times \text{CFM} \times (W_1 - W_2) m ˙ co n d = 60 ρ × CFM × ( W 1 − W 2 ) [lb/hr] \text{[lb/hr]} [lb/hr] , or GPH = m ˙ c o n d / 8.33 \text{GPH} = \dot{m}_{cond} / 8.33 GPH = m ˙ co n d /8.33 .
Direct evaporative cooling is an adiabatic process following lines of constant wet-bulb temperature ( T w b ≈ const T_{wb} \approx \text{const} T w b ≈ const ) and constant enthalpy ( h ≈ const h \approx \text{const} h ≈ const ) upward and to the left with saturation effectiveness ϵ = T d b , i n − T d b , o u t T d b , i n − T w b , i n \epsilon = \frac{T_{db,in} - T_{db,out}}{T_{db,in} - T_{wb,in}} ϵ = T d b , in − T w b , in T d b , in − T d b , o u t .
Isothermal steam humidification introduces moisture along a nearly vertical upward path ( T d b ≈ const T_{db} \approx \text{const} T d b ≈ const ), whereas adiabatic water spray humidification cools the airstream while adding moisture.
Last updated: August 2026
3.3 Basic Psychrometric Processes: Sensible Heating/Cooling, Humidification & Dehumidification
Every HVAC air-conditioning cycle consists of a sequence of fundamental thermodynamic state changes. Understanding the exact path of each process on the psychrometric chart, along with its governing mass and energy balances, is vital for predicting equipment performance and passing the PE exam.
1. Directional Vector Map of Psychrometric Processes
From any initial state point ( T d b 1 , W 1 ) (T_{db1}, W_1) ( T d b 1 , W 1 ) on the psychrometric chart, air conditioning processes move in eight characteristic directions:
Sensible Heating (Due East → \to → ): Dry-bulb temperature increases at constant humidity ratio ( W = const W = \text{const} W = const , T d p = const T_{dp} = \text{const} T d p = const , p v = const p_v = \text{const} p v = const ). Relative humidity decreases.
Sensible Cooling (Due West ← \leftarrow ← ): Dry-bulb temperature decreases at constant humidity ratio ( W = const W = \text{const} W = const , T d p = const T_{dp} = \text{const} T d p = const ). Relative humidity increases until saturation ( 100 % RH 100\%\text{ RH} 100% RH ) is reached.
Humidification with Heating (North-East ↗ \nearrow ↗ ): Both temperature and moisture content increase (e.g., heated steam or hot water spray).
Cooling and Dehumidification (South-West ↙ \swarrow ↙ ): Temperature and moisture content both decrease. Occurs when air passes over a cooling coil whose effective surface temperature is below the entering air dew point ( T c o i l < T d p 1 T_{coil} < T_{dp1} T co i l < T d p 1 ).
Humidification with Cooling / Evaporative Cooling (North-West ↖ \nwarrow ↖ ): Adiabatic saturation along lines of constant wet-bulb / constant enthalpy. Moisture evaporates into the air, extracting sensible heat and lowering T d b T_{db} T d b while increasing W W W and RH \text{RH} RH .
Chemical / Desiccant Dehumidification (South-East ↘ \searrow ↘ ): Moisture is adsorbed by a solid or liquid desiccant. The latent heat of sorption is released into the airstream, causing T d b T_{db} T d b to increase as W W W decreases along a nearly constant enthalpy line.
Isothermal Humidification (Due North ↑ \uparrow ↑ ): Pure dry steam injection at 212 ∘ F 212^\circ\text{F} 21 2 ∘ F adds moisture with minimal change in dry-bulb temperature.
Pure Dehumidification (Due South ↓ \downarrow ↓ ): Moisture extraction at constant dry bulb (rarely achieved in practice without reheat).
Loading diagram... Directional Process Map on Psychrometric Coordinates
- 2. Governing Equations for Basic Processes
- 1. Sensible Heating & Cooling Coils
When air flows across a hot water, steam, or electric heating coil (or a dry cooling coil operating above the entering air dew point T c o i l > T d p T_{coil} > T_{dp} T co i l > T d p ), no moisture is added or removed: W 1 = W 2 and T d p 1 = T d p 2 W_1 = W_2 \quad \text{and} \quad T_{dp1} = T_{dp2} W 1 = W 2 and T d p 1 = T d p 2 q ˙ s = m ˙ d a c p , m a ( T 2 − T 1 ) = 1.08 × CFM × ( T 2 − T 1 ) [ Btu/hr ] \dot{q}_s = \dot{m}_{da} c_{p,ma} (T_2 - T_1) = 1.08 \times \text{CFM} \times (T_2 - T_1) \quad [\text{Btu/hr}] q ˙ s = m ˙ d a c p , ma ( T 2 − T 1 ) = 1.08 × CFM × ( T 2 − T 1 ) [ Btu/hr ]
For electric resistance heating coils, thermal capacity is directly related to electrical power P k W P_{kW} P kW : P k W = q ˙ s 3412.14 = 1.08 × CFM × Δ T 3412.14 P_{kW} = \frac{\dot{q}_s}{3412.14} = \frac{1.08 \times \text{CFM} \times \Delta T}{3412.14} P kW = 3412.14 q ˙ s = 3412.14 1.08 × CFM × Δ T
2. Cooling and Dehumidification (Wet Cooling Coils)
When the effective surface temperature of a cooling coil ( T s T_s T s ) is below the dew point of the entering air ( T s < T d p 1 T_s < T_{dp1} T s < T d p 1 ), water vapor condenses on the coil fins: Total Coil Load: q ˙ t o t a l = m ˙ d a ( h 1 − h 2 ) = 4.5 × CFM × ( h 1 − h 2 ) [ Btu/hr ] \text{Total Coil Load: } \dot{q}_{total} = \dot{m}_{da} (h_1 - h_2) = 4.5 \times \text{CFM} \times (h_1 - h_2) \quad [\text{Btu/hr}] Total Coil Load: q ˙ t o t a l = m ˙ d a ( h 1 − h 2 ) = 4.5 × CFM × ( h 1 − h 2 ) [ Btu/hr ] Sensible Load: q ˙ s e n s i b l e = 1.08 × CFM × ( T 1 − T 2 ) [ Btu/hr ] \text{Sensible Load: } \dot{q}_{sensible} = 1.08 \times \text{CFM} \times (T_1 - T_2) \quad [\text{Btu/hr}] Sensible Load: q ˙ se n s ib l e = 1.08 × CFM × ( T 1 − T 2 ) [ Btu/hr ] Latent Load: q ˙ l a t e n t = q ˙ t o t a l − q ˙ s e n s i b l e = 4840 × CFM × ( W 1 − W 2 ) [ Btu/hr ] \text{Latent Load: } \dot{q}_{latent} = \dot{q}_{total} - \dot{q}_{sensible} = 4840 \times \text{CFM} \times (W_1 - W_2) \quad [\text{Btu/hr}] Latent Load: q ˙ l a t e n t = q ˙ t o t a l − q ˙ se n s ib l e = 4840 × CFM × ( W 1 − W 2 ) [ Btu/hr ] Sensible Heat Ratio (SHR): SHR = q ˙ s e n s i b l e q ˙ t o t a l = q ˙ s q ˙ s + q ˙ l \text{Sensible Heat Ratio (SHR): } \text{SHR} = \frac{\dot{q}_{sensible}}{\dot{q}_{total}} = \frac{\dot{q}_s}{\dot{q}_s + \dot{q}_l} Sensible Heat Ratio (SHR): SHR = q ˙ t o t a l q ˙ se n s ib l e = q ˙ s + q ˙ l q ˙ s Condensate Water Drainage Rate: m ˙ c o n d = m ˙ d a ( W 1 − W 2 ) = 60 × 0.075 × CFM × ( W 1 − W 2 ) [ lb m / hr ] \text{Condensate Water Drainage Rate: } \dot{m}_{cond} = \dot{m}_{da} (W_1 - W_2) = 60 \times 0.075 \times \text{CFM} \times (W_1 - W_2) \quad [\text{lb}_m/\text{hr}] Condensate Water Drainage Rate: m ˙ co n d = m ˙ d a ( W 1 − W 2 ) = 60 × 0.075 × CFM × ( W 1 − W 2 ) [ lb m / hr ] Condensate Volumetric Rate: GPH = m ˙ c o n d 8.33 lb/gal [ gallons per hour ] \text{Condensate Volumetric Rate: } \text{GPH} = \frac{\dot{m}_{cond}}{8.33\text{ lb/gal}} \quad [\text{gallons per hour}] Condensate Volumetric Rate: GPH = 8.33 lb/gal m ˙ co n d [ gallons per hour ]
3. Direct Evaporative Cooling (Swamp Coolers)
In a direct evaporative cooler, unsaturated air passes through a wetted media where water evaporates without external heat addition (adiabatic process). The heat of vaporization is supplied entirely by the air's sensible heat: h 1 ≈ h 2 and T w b 1 = T w b 2 h_1 \approx h_2 \quad \text{and} \quad T_{wb1} = T_{wb2} h 1 ≈ h 2 and T w b 1 = T w b 2 Saturation Effectiveness ( ϵ ): ϵ = T d b , i n − T d b , o u t T d b , i n − T w b , i n \text{Saturation Effectiveness (}\epsilon\text{): } \epsilon = \frac{T_{db,in} - T_{db,out}}{T_{db,in} - T_{wb,in}} Saturation Effectiveness ( ϵ ): ϵ = T d b , in − T w b , in T d b , in − T d b , o u t T d b , o u t = T d b , i n − ϵ ( T d b , i n − T w b , i n ) T_{db,out} = T_{db,in} - \epsilon \left( T_{db,in} - T_{wb,in} \right) T d b , o u t = T d b , in − ϵ ( T d b , in − T w b , in ) Water Consumption Rate: m ˙ w a t e r = m ˙ d a ( W 2 − W 1 ) = 4.5 × CFM × ( W 2 − W 1 ) [ lb/hr ] \text{Water Consumption Rate: } \dot{m}_{water} = \dot{m}_{da} (W_2 - W_1) = 4.5 \times \text{CFM} \times (W_2 - W_1) \quad [\text{lb/hr}] Water Consumption Rate: m ˙ w a t er = m ˙ d a ( W 2 − W 1 ) = 4.5 × CFM × ( W 2 − W 1 ) [ lb/hr ]
4. Steam Humidification vs. Water Spray Humidification
Steam Humidification (Isothermal): Steam at 212 ∘ F 212^\circ\text{F} 21 2 ∘ F ( h g = 1150.5 Btu/lb h_g = 1150.5\text{ Btu/lb} h g = 1150.5 Btu/lb ) injected into an airstream causes negligible change in dry-bulb temperature ( Δ T ≈ + 1 ∘ F \Delta T \approx +1^\circ\text{F} Δ T ≈ + 1 ∘ F for typical additions): m ˙ s t e a m = m ˙ d a ( W 2 − W 1 ) = 4.5 × CFM × ( W 2 − W 1 ) [ lb/hr ] \dot{m}_{steam} = \dot{m}_{da} (W_2 - W_1) = 4.5 \times \text{CFM} \times (W_2 - W_1) \quad [\text{lb/hr}] m ˙ s t e am = m ˙ d a ( W 2 − W 1 ) = 4.5 × CFM × ( W 2 − W 1 ) [ lb/hr ]
Water Spray Humidification (Adiabatic): Atomized unheated liquid water spray absorbs latent heat from the airstream, reducing dry-bulb temperature while raising humidity ratio along the wet-bulb line.
- 3. Step-by-Step Worked Example: Cooling & Dehumidifying Coil Sizing
- Problem Statement
An air-handling unit conditioning a lecture auditorium handles 8 , 000 CFM 8,000\text{ CFM} 8 , 000 CFM of air at standard sea-level pressure ( 14.696 psia 14.696\text{ psia} 14.696 psia ). The air enters the chilled-water cooling coil at State 1 and leaves at State 2:
Entering Air (State 1): T d b 1 = 82.0 ∘ F T_{db1} = 82.0^\circ\text{F} T d b 1 = 82. 0 ∘ F , T w b 1 = 68.0 ∘ F T_{wb1} = 68.0^\circ\text{F} T w b 1 = 68. 0 ∘ F ( h 1 = 32.40 Btu/lb d a h_1 = 32.40\text{ Btu/lb}_{da} h 1 = 32.40 Btu/lb d a , W 1 = 0.0116 lb w / lb d a W_1 = 0.0116\text{ lb}_w/\text{lb}_{da} W 1 = 0.0116 lb w / lb d a )
Leaving Air (State 2): T d b 2 = 54.0 ∘ F T_{db2} = 54.0^\circ\text{F} T d b 2 = 54. 0 ∘ F , T w b 2 = 52.5 ∘ F T_{wb2} = 52.5^\circ\text{F} T w b 2 = 52. 5 ∘ F ( h 2 = 21.75 Btu/lb d a h_2 = 21.75\text{ Btu/lb}_{da} h 2 = 21.75 Btu/lb d a , W 2 = 0.0081 lb w / lb d a W_2 = 0.0081\text{ lb}_w/\text{lb}_{da} W 2 = 0.0081 lb w / lb d a )
Calculate:
- Total cooling capacity in Btu/hr and tons of refrigeration
- Sensible cooling capacity in Btu/hr
- Latent cooling capacity in Btu/hr
- Coil Sensible Heat Ratio (SHR)
- Water condensation removal rate in pounds per hour (lb/hr) and gallons per hour (GPH)
- Solution Steps
Step 1: Calculate Total Cooling Capacity q ˙ t o t a l = 4.5 × CFM × ( h 1 − h 2 ) \dot{q}_{total} = 4.5 \times \text{CFM} \times (h_1 - h_2) q ˙ t o t a l = 4.5 × CFM × ( h 1 − h 2 ) q ˙ t o t a l = 4.5 × 8 , 000 × ( 32.40 − 21.75 ) = 36 , 000 × 10.65 = 383 , 400 Btu/hr \dot{q}_{total} = 4.5 \times 8,000 \times (32.40 - 21.75) = 36,000 \times 10.65 = 383,400\text{ Btu/hr} q ˙ t o t a l = 4.5 × 8 , 000 × ( 32.40 − 21.75 ) = 36 , 000 × 10.65 = 383 , 400 Btu/hr Tons of Refrigeration = 383 , 400 Btu/hr 12 , 000 Btu/hr ⋅ ton = 31.95 tons \text{Tons of Refrigeration} = \frac{383,400\text{ Btu/hr}}{12,000\text{ Btu/hr}\cdot\text{ton}} = 31.95\text{ tons} Tons of Refrigeration = 12 , 000 Btu/hr ⋅ ton 383 , 400 Btu/hr = 31.95 tons
Step 2: Calculate Sensible Cooling Capacity q ˙ s e n s i b l e = 1.08 × CFM × ( T d b 1 − T d b 2 ) \dot{q}_{sensible} = 1.08 \times \text{CFM} \times (T_{db1} - T_{db2}) q ˙ se n s ib l e = 1.08 × CFM × ( T d b 1 − T d b 2 ) q ˙ s e n s i b l e = 1.08 × 8 , 000 × ( 82.0 − 54.0 ) = 8 , 640 × 28.0 = 241 , 920 Btu/hr = 20.16 tons \dot{q}_{sensible} = 1.08 \times 8,000 \times (82.0 - 54.0) = 8,640 \times 28.0 = 241,920\text{ Btu/hr} = 20.16\text{ tons} q ˙ se n s ib l e = 1.08 × 8 , 000 × ( 82.0 − 54.0 ) = 8 , 640 × 28.0 = 241 , 920 Btu/hr = 20.16 tons
Step 3: Calculate Latent Cooling Capacity q ˙ l a t e n t = q ˙ t o t a l − q ˙ s e n s i b l e = 383 , 400 − 241 , 920 = 141 , 480 Btu/hr = 11.79 tons \dot{q}_{latent} = \dot{q}_{total} - \dot{q}_{sensible} = 383,400 - 241,920 = 141,480\text{ Btu/hr} = 11.79\text{ tons} q ˙ l a t e n t = q ˙ t o t a l − q ˙ se n s ib l e = 383 , 400 − 241 , 920 = 141 , 480 Btu/hr = 11.79 tons
(Verification via humidity ratio: q ˙ l = 4840 × 8000 × ( 0.0116 − 0.0081 ) = 38 , 720 , 000 × 0.0035 = 135 , 520 Btu/hr \dot{q}_l = 4840 \times 8000 \times (0.0116 - 0.0081) = 38,720,000 \times 0.0035 = 135,520\text{ Btu/hr} q ˙ l = 4840 × 8000 × ( 0.0116 − 0.0081 ) = 38 , 720 , 000 × 0.0035 = 135 , 520 Btu/hr , well within rounding of psychrometric chart lookups).
Step 4: Calculate Sensible Heat Ratio (SHR) SHR = q ˙ s e n s i b l e q ˙ t o t a l = 241 , 920 383 , 400 = 0.631 \text{SHR} = \frac{\dot{q}_{sensible}}{\dot{q}_{total}} = \frac{241,920}{383,400} = 0.631 SHR = q ˙ t o t a l q ˙ se n s ib l e = 383 , 400 241 , 920 = 0.631
Step 5: Calculate Condensate Drainage Rate m ˙ c o n d = 60 × ρ × CFM × ( W 1 − W 2 ) = 4.5 × 8 , 000 × ( 0.0116 − 0.0081 ) \dot{m}_{cond} = 60 \times \rho \times \text{CFM} \times (W_1 - W_2) = 4.5 \times 8,000 \times (0.0116 - 0.0081) m ˙ co n d = 60 × ρ × CFM × ( W 1 − W 2 ) = 4.5 × 8 , 000 × ( 0.0116 − 0.0081 ) m ˙ c o n d = 36 , 000 × 0.0035 = 126.0 lb m / hr \dot{m}_{cond} = 36,000 \times 0.0035 = 126.0\text{ lb}_m/\text{hr} m ˙ co n d = 36 , 000 × 0.0035 = 126.0 lb m / hr Condensate Flow Rate (GPH) = 126.0 lb/hr 8.33 lb/gal = 15.13 GPH \text{Condensate Flow Rate (GPH)} = \frac{126.0\text{ lb/hr}}{8.33\text{ lb/gal}} = 15.13\text{ GPH} Condensate Flow Rate (GPH) = 8.33 lb/gal 126.0 lb/hr = 15.13 GPH
(A continuous 15.1 gallons per hour must be drained away from the coil pan).