Study guide

3.2 Chart Reading & Psychrometric Equations at Sea Level vs. Altitude (5,000 ft)

PE Mechanical: HVAC and Refrigeration Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Overview, Reference Handbook & Engineering Foundations

1.1 NCEES Exam Specification, CBT Delivery & Reference Handbook Strategy 1.2 Engineering Units, Dimensional Analysis & Physical Property Lookups 1.3 Engineering Economics, Life Cycle Cost Analysis & Equipment Financial Evaluation 1.4 Electrical Foundations, Motor Ratings & Variable Frequency Drives (VFDs)

2 Chapter 2: Thermodynamics & Energy Balances

2.1 First and Second Laws of Thermodynamics & Open/Closed System Energy Balances 2.2 Thermodynamic Cycles: Carnot, Rankine, Brayton & Reversed Carnot Limit 2.3 Gas & Vapor Property Evaluation: Steam Tables, Superheat & Subcooling 2.4 Mass, Energy & Combustion Balances for HVAC Equipment

3 Chapter 3: Psychrometrics, Moist Air Processes & Humidity Equipment

3.1 Psychrometric Properties: DBT, WBT, DPT, RH, Humidity Ratio & Enthalpy 3.2 Chart Reading & Psychrometric Equations at Sea Level vs. Altitude (5,000 ft) 3.3 Basic Psychrometric Processes: Sensible Heating/Cooling, Humidification & Dehumidification 3.4 Mixed Air Calculations & Complex Air Conditioning Cycles (Preheat, Reheat & Bypass) 3.5 Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP) & Coil Bypass Factor 3.6 Humidification & Dehumidification Equipment: Steam, Adiabatic, Desiccant & Low-Temperature Processes

4 Chapter 4: Heat Transfer Principles & Sizing

4.1 Steady-State Conduction & Multilayer Thermal Resistance (R-Value & U-Factor) 4.2 Convective Heat Transfer & Forced/Natural Convection Coefficients 4.3 Radiation Heat Transfer, Surface Emissivity & View Factors 4.4 Overall Heat Transfer Coefficients, Fouling Factors & Transient/Thermal Mass Effects 4.5 Heat Exchanger Analysis: Log Mean Temperature Difference (LMTD) & Effectiveness-NTU (ε-NTU)

5 Chapter 5: Fluid Mechanics & Hydraulic Fundamentals

5.1 Fluid Statics, Incompressible Continuity & Bernoulli Energy Equation 5.2 Pipe Friction, Moody Diagram & Darcy-Weisbach / Hazen-Williams Calculations 5.3 Minor Losses: Equivalent Length, Loss Coefficients (K-factors) & Total System Head 5.4 Pump Sizing, Net Positive Suction Head (NPSHa vs NPSHr) & Cavitation Prevention 5.5 Affinity Laws & Parallel/Series Pump/Fan System Curves

6 Chapter 6: Heating & Cooling Load Calculations

6.1 Outdoor & Indoor Design Conditions (ASHRAE Fundamentals, Climatic Data & Indoor Setpoints) 6.2 Envelope Heat Transmission & Infiltration/Exfiltration Load Methods 6.3 Solar Heat Gain (SHGC), Fenestration & Cooling Load Temperature Difference / Radiant Time Series (CLTD/RTS) 6.4 Internal Heat Gains: Lighting, People, Equipment & Diversity Factors 6.5 Ventilation Loads & Sensible / Latent / Total Cooling Load Synthesis

7 Chapter 7: Refrigeration Principles, Cycles & Cold Storage Applications

7.1 Standard Vapor-Compression Refrigeration Cycle on P-h & T-s Diagrams 7.2 Refrigeration Cycle Performance Metrics: COP, EER, SEER, kW/ton & Ton of Refrigeration 7.3 Cycle Enhancements: Subcooling, Superheating, Liquid-Suction Heat Exchangers & Economizers 7.4 Multi-Stage & Cascade Refrigeration Systems: Intercooling & Flash Gas Removal 7.5 Absorption Refrigeration Cycles: Water-Lithium Bromide & Ammonia-Water Systems 7.6 Food Processing & Cold Storage Refrigeration: Product Load, Pull-Down & Storage Design

8 Chapter 8: Refrigerants, Environmental Regulations & Safety

8.1 Refrigerant Classifications, Nomenclature & Thermodynamic Properties (ASHRAE Standard 34) 8.2 AIM Act, EPA Technology Transitions Sector GWP Limits & Low-GWP Refrigerants (R-32, R-454B) 8.3 Refrigerant Safety Requirements & Machinery Room Design (ASHRAE Standard 15) 8.4 Refrigerant Piping Sizing, Oil Return, Traps & Double Risers

9 Chapter 9: HVAC Equipment & Primary Machinery

9.1 Compressors: Reciprocating, Rotary, Scroll, Screw & Centrifugal 9.2 Condensers: Air-Cooled, Water-Cooled & Evaporative Condensers 9.3 Evaporators & Direct Expansion (DX) vs Liquid Chilling Coils 9.4 Water Chillers: Centrifugal, Screw & Scroll with ASHRAE 90.1 Path A/B IPLV Ratings 9.5 Cooling Towers: Range, Approach, Evaporation, Blowdown & Legionella Control 9.6 Heat Pumps & Variable Refrigerant Flow (VRF): Balance Point, Defrost & Heat Recovery 9.7 Thermal Energy Storage: Full vs. Partial Storage, Chilled Water & Ice Systems

10 Chapter 10: Air-Side Systems & Distribution

10.1 Air Handling Units (AHUs), Dedicated Outdoor Air Systems (DOAS) & Fan-Coil Units 10.2 Duct Design Methodologies: Equal Friction, Static Regain & Velocity Reduction 10.3 Duct Fittings, Dynamic Pressure Losses & SMACNA Construction Standards 10.4 Fan Types, Performance Curves, System Effect Factors & Surge/Stall Dynamics 10.5 Variable Air Volume (VAV) Systems, Terminal Boxes & Space Air Diffusion (ADPI) 10.6 Cooling & Heating Coil Selection: Face Velocity, Rows, Circuiting & Freeze Protection

11 Chapter 11: Hydronic, Steam & Fuel Distribution and Heating Plant

11.1 Hydronic System Architectures: Primary-Only, Primary-Secondary & Variable Primary Flow (VPF) 11.2 Hydronic Pipe Sizing, Velocity Limits & Closed/Open Expansion Tank Sizing 11.3 Control Valves: 2-Way vs 3-Way, Valve Authority (N), Cv Calculations & Characteristic Curves 11.4 Boilers & Heating Hot Water Systems: Condensing vs Non-Condensing & Water Treatment 11.5 Furnaces & Gas-Fired Heating Equipment: AFUE, Temperature Rise, Combustion Air & Vent Categories 11.6 Steam & Condensate Distribution: Latent Heat, Trap Selection, Flash Steam & Stall 11.7 Fuel Gas & Fuel Oil Piping: Demand, Sizing Method, Pressure Drop & Storage Systems

12 Chapter 12: HVAC Control Concepts, Sensors & Sequences

12.1 Sensors, Actuators & Dampers: Selection, Placement, Fail-Safe Position & Damper Authority 12.2 Control Loops: Proportional Offset, PID Action, Reset Strategies & Standard Sequences

13 Chapter 13: Building Energy, Ventilation & Indoor Environmental Quality Codes

13.1 ASHRAE Standard 62.1: Ventilation Rate Procedure (VRP), Indoor Air Quality Procedure & DCV 13.2 ASHRAE Standard 90.1: Building Energy Envelope, Mechanical Efficiency & Economizer Mandates 13.3 ASHRAE Standard 55: Thermal Environmental Conditions, PMV/PPD & Adaptive Comfort Models 13.4 Energy Recovery Systems: Enthalpy Wheels, Fixed-Plate Exchangers, Heat Pipes & Runaround Loops

14 Chapter 14: Supportive Engineering Knowledge, Life Safety & Operations

14.1 Air Filtration Standards: MERV Ratings (ASHRAE 52.2), HEPA & Gas-Phase Adsorption 14.2 Life Safety Systems: Fire/Smoke Dampers, Stairwell Pressurization (NFPA 92) & Smoke Control (NFPA 90A) 14.3 Acoustical Control & Vibration Isolation in HVAC Systems (NC / RC Criteria)

3.2 Chart Reading & Psychrometric Equations at Sea Level vs. Altitude (5,000 ft)

Key Takeaways Explain This Topic AI

Standard sea level barometric pressure is 14.696 psia 14.696\text{ psia} 14.696 psia ( 29.921 in. Hg = 101.325 kPa 29.921\text{ in. Hg} = 101.325\text{ kPa} 29.921 in. Hg = 101.325 kPa ); at 5 , 000 ft 5,000\text{ ft} 5 , 000 ft altitude (e.g., Denver), barometric pressure drops to 12.23 psia 12.23\text{ psia} 12.23 psia ( 24.89 in. Hg = 84.3 kPa 24.89\text{ in. Hg} = 84.3\text{ kPa} 24.89 in. Hg = 84.3 kPa ).

Because total pressure P P P is reduced at altitude, the humidity ratio W = 0.622 p v P − p v W = 0.622 \frac{p_v}{P - p_v} W = 0.622 P − p v ​ p v ​ ​ and specific volume v = R T P − p v v = \frac{R T}{P - p_v} v = P − p v ​ RT ​ are significantly higher for identical dry-bulb and dew-point temperatures.

Standard air equations ( q s = 1.08 × CFM × Δ T q_s = 1.08 \times \text{CFM} \times \Delta T q s ​ = 1.08 × CFM × Δ T , q l = 4840 × CFM × Δ W q_l = 4840 \times \text{CFM} \times \Delta W q l ​ = 4840 × CFM × Δ W , q t = 4.5 × CFM × Δ h q_t = 4.5 \times \text{CFM} \times \Delta h q t ​ = 4.5 × CFM × Δ h ) apply ONLY to standard sea-level air density ( ρ = 0.075 lb/ft 3 \rho = 0.075\text{ lb/ft}^3 ρ = 0.075 lb/ft 3 , c p = 0.24 Btu/lb ⋅ ∘ F c_p = 0.24\text{ Btu/lb}\cdot^\circ\text{F} c p ​ = 0.24 Btu/lb ⋅ ∘ F ).

At altitude, equations must be adjusted using actual density: q s = 60 ρ c p × ACFM × Δ T q_s = 60 \rho c_p \times \text{ACFM} \times \Delta T q s ​ = 60 ρ c p ​ × ACFM × Δ T , q l = 60 ρ h f g × ACFM × Δ W q_l = 60 \rho h_{fg} \times \text{ACFM} \times \Delta W q l ​ = 60 ρ h f g ​ × ACFM × Δ W , and q t = 60 ρ × ACFM × Δ h q_t = 60 \rho \times \text{ACFM} \times \Delta h q t ​ = 60 ρ × ACFM × Δ h . At 5 , 000 ft 5,000\text{ ft} 5 , 000 ft , the sensible constant drops from 1.08 1.08 1.08 to ≈ 0.90 \approx 0.90 ≈ 0.90 .

To deliver the identical mass flow rate ( m ˙ d a \dot{m}_{da} m ˙ d a ​ ) and cooling capacity at high elevation, fans must move a proportionally greater volumetric flow rate ( ACFM = SCFM × ρ s t d ρ a l t \text{ACFM} = \text{SCFM} \times \frac{\rho_{std}}{\rho_{alt}} ACFM = SCFM × ρ a lt ​ ρ s t d ​ ​ ).

Last updated: August 2026

3.2 Chart Reading & Psychrometric Equations at Sea Level vs. Altitude (5,000 ft)

In standard HVAC design, engineers frequently rely on standard sea-level psychrometric charts and rule-of-thumb thermal equations. However, on the PE Mechanical exam, questions involving high altitude (such as 5,000 ft in Denver, CO) are classic test items designed to verify that candidates understand the underlying physics rather than blindly plugging numbers into standard formulas.

1. Atmospheric Pressure Variation with Altitude

The U.S. Standard Atmosphere model defines atmospheric barometric pressure P P P as a function of altitude Z Z Z (in feet) above sea level up to 36 , 000 ft 36,000\text{ ft} 36 , 000 ft : P = 14.696 ( 1 − 6.8754 × 10 − 6 Z ) 5.2559 [ psia ] P = 14.696 \left( 1 - 6.8754 \times 10^{-6} Z \right)^{5.2559} \quad [\text{psia}] P = 14.696 ( 1 − 6.8754 × 1 0 − 6 Z ) 5.2559 [ psia ] or P = 29.921 ( 1 − 6.8754 × 10 − 6 Z ) 5.2559 [ in. Hg ] \text{or} \quad P = 29.921 \left( 1 - 6.8754 \times 10^{-6} Z \right)^{5.2559} \quad [\text{in. Hg}] or P = 29.921 ( 1 − 6.8754 × 1 0 − 6 Z ) 5.2559 [ in. Hg ]

Barometric Pressures and Densities Across Key Elevations

Altitude ( Z Z Z ) Pressure (psia) Pressure (in. Hg) Pressure (kPa) Approx. Air Density ρ \rho ρ ( 70 ∘ F 70^\circ\text{F} 7 0 ∘ F ) Density Ratio ( ρ / ρ 0 \rho/\rho_0 ρ / ρ 0 ​ )

0 ft (Sea Level) 14.696 14.696 14.696 29.921 29.921 29.921 101.325 101.325 101.325 0.0750 lb/ft 3 0.0750\text{ lb/ft}^3 0.0750 lb/ft 3 1.000 1.000 1.000

2,500 ft 13.411 13.411 13.411 27.303 27.303 27.303 92.464 92.464 92.464 0.0684 lb/ft 3 0.0684\text{ lb/ft}^3 0.0684 lb/ft 3 0.912 0.912 0.912

5,000 ft (Denver) 12.228 12.228 12.228 24.894 24.894 24.894 84.307 84.307 84.307 0.0624 lb/ft 3 0.0624\text{ lb/ft}^3 0.0624 lb/ft 3 0.832 0.832 0.832

7,500 ft 11.129 11.129 11.129 22.657 22.657 22.657 76.732 76.732 76.732 0.0568 lb/ft 3 0.0568\text{ lb/ft}^3 0.0568 lb/ft 3 0.757 0.757 0.757

10,000 ft 10.108 10.108 10.108 20.577 20.577 20.577 69.691 69.691 69.691 0.0516 lb/ft 3 0.0516\text{ lb/ft}^3 0.0516 lb/ft 3 0.688 0.688 0.688

2. Impact of Altitude on Psychrometric Properties

When altitude increases and total barometric pressure P P P decreases:

Humidity Ratio ( W W W ): W = 0.62198 p v P − p v W = 0.62198 \frac{p_v}{P - p_v} W = 0.62198 P − p v ​ p v ​ ​

For a given dew-point temperature (fixed partial vapor pressure p v p_v p v ​ ), as P P P decreases, the denominator ( P − p v ) (P - p_v) ( P − p v ​ ) becomes smaller. Therefore, the humidity ratio W W W is significantly higher at altitude for the same dry-bulb and dew-point temperatures.

Specific Volume ( v v v ): v = R d a T P − p v v = \frac{R_{da} T}{P - p_v} v = P − p v ​ R d a ​ T ​

As P P P decreases, specific volume v v v expands (air becomes less dense). At 5 , 000 ft 5,000\text{ ft} 5 , 000 ft , v v v is approximately 20 % 20\% 20% greater than at sea level for the same temperature.

Specific Enthalpy ( h h h ): h = 0.240 T d b + W ( 1061 + 0.444 T d b ) h = 0.240 T_{db} + W (1061 + 0.444 T_{db}) h = 0.240 T d b ​ + W ( 1061 + 0.444 T d b ​ )

Because W W W is higher at altitude for the same relative humidity and dry bulb, the specific enthalpy of moist air is higher at altitude .

Saturation Curve Shift: On an altitude psychrometric chart (such as ASHRAE Chart #2 for 5 , 000 ft 5,000\text{ ft} 5 , 000 ft ), the saturation curve shifts upward and to the left compared to the sea-level chart (Chart #1).

Loading diagram... Shift of Saturation Curve & Humidity Ratio at 5,000 ft vs. Sea Level

3. Derivation of Heat Transfer Rate Equations: Sea Level vs. Altitude

All continuous-flow thermal energy equations originate from First Law mass and energy rate balances: q ˙ = m ˙ d a Δ h = ( ρ × 60 × CFM ) × Δ h \dot{q} = \dot{m}_{da} \Delta h = (\rho \times 60 \times \text{CFM}) \times \Delta h q ˙ ​ = m ˙ d a ​ Δ h = ( ρ × 60 × CFM ) × Δ h

Sensible Heat Transfer Rate ( q ˙ s \dot{q}_s q ˙ ​ s ​ ) q ˙ s = m ˙ d a c p , m a Δ T = ( 60 × ρ × CFM ) × c p , m a × Δ T \dot{q}_s = \dot{m}_{da} c_{p,ma} \Delta T = (60 \times \rho \times \text{CFM}) \times c_{p,ma} \times \Delta T q ˙ ​ s ​ = m ˙ d a ​ c p , ma ​ Δ T = ( 60 × ρ × CFM ) × c p , ma ​ × Δ T

At Sea Level Standard Conditions:

ρ s t d = 0.0750 lb m / ft 3 \rho_{std} = 0.0750\text{ lb}_m/\text{ft}^3 ρ s t d ​ = 0.0750 lb m ​ / ft 3

c p , m a = c p , d a + W c p , v ≈ 0.240 + ( 0.010 ) ( 0.444 ) = 0.244 Btu / ( lb m ⋅ ∘ F ) c_{p,ma} = c_{p,da} + W c_{p,v} \approx 0.240 + (0.010)(0.444) = 0.244\text{ Btu}/(\text{lb}_m\cdot^\circ\text{F}) c p , ma ​ = c p , d a ​ + W c p , v ​ ≈ 0.240 + ( 0.010 ) ( 0.444 ) = 0.244 Btu / ( lb m ​ ⋅ ∘ F )

Constant C s = 60 × 0.0750 × 0.240 = 1.08 Btu / ( hr ⋅ CFM ⋅ ∘ F ) C_s = 60 \times 0.0750 \times 0.240 = 1.08\text{ Btu}/(\text{hr}\cdot\text{CFM}\cdot^\circ\text{F}) C s ​ = 60 × 0.0750 × 0.240 = 1.08 Btu / ( hr ⋅ CFM ⋅ ∘ F ) (or 1.10 1.10 1.10 using 0.244 0.244 0.244 ) q ˙ s = 1.08 × CFM × ( T 2 − T 1 ) [ Btu/hr ] \dot{q}_s = 1.08 \times \text{CFM} \times (T_2 - T_1) \quad [\text{Btu/hr}] q ˙ ​ s ​ = 1.08 × CFM × ( T 2 ​ − T 1 ​ ) [ Btu/hr ]

At 5,000 ft Altitude (Denver):

ρ a l t = 0.0624 lb m / ft 3 \rho_{alt} = 0.0624\text{ lb}_m/\text{ft}^3 ρ a lt ​ = 0.0624 lb m ​ / ft 3

Constant C s , a l t = 60 × 0.0624 × 0.240 = 0.8986 ≈ 0.90 Btu / ( hr ⋅ ACFM ⋅ ∘ F ) C_{s,alt} = 60 \times 0.0624 \times 0.240 = 0.8986 \approx 0.90\text{ Btu}/(\text{hr}\cdot\text{ACFM}\cdot^\circ\text{F}) C s , a lt ​ = 60 × 0.0624 × 0.240 = 0.8986 ≈ 0.90 Btu / ( hr ⋅ ACFM ⋅ ∘ F ) q ˙ s = 0.90 × ACFM × ( T 2 − T 1 ) [ Btu/hr ] \dot{q}_s = 0.90 \times \text{ACFM} \times (T_2 - T_1) \quad [\text{Btu/hr}] q ˙ ​ s ​ = 0.90 × ACFM × ( T 2 ​ − T 1 ​ ) [ Btu/hr ]

Latent Heat Transfer Rate ( q ˙ l \dot{q}_l q ˙ ​ l ​ ) q ˙ l = m ˙ d a h f g Δ W = ( 60 × ρ × CFM ) × h f g × Δ W \dot{q}_l = \dot{m}_{da} h_{fg} \Delta W = (60 \times \rho \times \text{CFM}) \times h_{fg} \times \Delta W q ˙ ​ l ​ = m ˙ d a ​ h f g ​ Δ W = ( 60 × ρ × CFM ) × h f g ​ × Δ W

At Sea Level Standard Conditions ( h f g ≈ 1060 Btu/lb w h_{fg} \approx 1060\text{ Btu/lb}_w h f g ​ ≈ 1060 Btu/lb w ​ ):

Constant C l = 60 × 0.0750 × 1060 = 4770 ≈ 4840 Btu ⋅ lb d a / ( hr ⋅ CFM ⋅ lb w ) C_l = 60 \times 0.0750 \times 1060 = 4770 \approx 4840\text{ Btu}\cdot\text{lb}_{da}/(\text{hr}\cdot\text{CFM}\cdot\text{lb}_w) C l ​ = 60 × 0.0750 × 1060 = 4770 ≈ 4840 Btu ⋅ lb d a ​ / ( hr ⋅ CFM ⋅ lb w ​ ) q ˙ l = 4840 × CFM × ( W 2 − W 1 ) [ Btu/hr , W in lb/lb ] \dot{q}_l = 4840 \times \text{CFM} \times (W_2 - W_1) \quad [\text{Btu/hr}, W \text{ in lb/lb}] q ˙ ​ l ​ = 4840 × CFM × ( W 2 ​ − W 1 ​ ) [ Btu/hr , W in lb/lb ]

In grains of moisture ( 1 lb = 7000 grains 1\text{ lb} = 7000\text{ grains} 1 lb = 7000 grains ): q ˙ l = 4840 7000 × CFM × Δ W grains = 0.69 × CFM × Δ W grains [ Btu/hr ] \dot{q}_l = \frac{4840}{7000} \times \text{CFM} \times \Delta W_{\text{grains}} = 0.69 \times \text{CFM} \times \Delta W_{\text{grains}} \quad [\text{Btu/hr}] q ˙ ​ l ​ = 7000 4840 ​ × CFM × Δ W grains ​ = 0.69 × CFM × Δ W grains ​ [ Btu/hr ]

At 5,000 ft Altitude:

Constant C l , a l t = 60 × 0.0624 × 1060 = 3968 ≈ 4000 Btu ⋅ lb d a / ( hr ⋅ ACFM ⋅ lb w ) C_{l,alt} = 60 \times 0.0624 \times 1060 = 3968 \approx 4000\text{ Btu}\cdot\text{lb}_{da}/(\text{hr}\cdot\text{ACFM}\cdot\text{lb}_w) C l , a lt ​ = 60 × 0.0624 × 1060 = 3968 ≈ 4000 Btu ⋅ lb d a ​ / ( hr ⋅ ACFM ⋅ lb w ​ ) q ˙ l = 4000 × ACFM × ( W 2 − W 1 ) [ Btu/hr , W in lb/lb ] \dot{q}_l = 4000 \times \text{ACFM} \times (W_2 - W_1) \quad [\text{Btu/hr}, W \text{ in lb/lb}] q ˙ ​ l ​ = 4000 × ACFM × ( W 2 ​ − W 1 ​ ) [ Btu/hr , W in lb/lb ] q ˙ l = 0.57 × ACFM × Δ W grains [ Btu/hr ] \dot{q}_l = 0.57 \times \text{ACFM} \times \Delta W_{\text{grains}} \quad [\text{Btu/hr}] q ˙ ​ l ​ = 0.57 × ACFM × Δ W grains ​ [ Btu/hr ]

Total Heat Transfer Rate ( q ˙ t \dot{q}_t q ˙ ​ t ​ ) q ˙ t = m ˙ d a Δ h = ( 60 × ρ × CFM ) × Δ h \dot{q}_t = \dot{m}_{da} \Delta h = (60 \times \rho \times \text{CFM}) \times \Delta h q ˙ ​ t ​ = m ˙ d a ​ Δ h = ( 60 × ρ × CFM ) × Δ h

At Sea Level: C t = 60 × 0.0750 = 4.5 lb m / ( hr ⋅ CFM ) C_t = 60 \times 0.0750 = 4.5\text{ lb}_m/(\text{hr}\cdot\text{CFM}) C t ​ = 60 × 0.0750 = 4.5 lb m ​ / ( hr ⋅ CFM ) q ˙ t = 4.5 × CFM × ( h 2 − h 1 ) [ Btu/hr ] \dot{q}_t = 4.5 \times \text{CFM} \times (h_2 - h_1) \quad [\text{Btu/hr}] q ˙ ​ t ​ = 4.5 × CFM × ( h 2 ​ − h 1 ​ ) [ Btu/hr ]

At 5,000 ft Altitude: C t , a l t = 60 × 0.0624 = 3.74 lb m / ( hr ⋅ ACFM ) C_{t,alt} = 60 \times 0.0624 = 3.74\text{ lb}_m/(\text{hr}\cdot\text{ACFM}) C t , a lt ​ = 60 × 0.0624 = 3.74 lb m ​ / ( hr ⋅ ACFM ) q ˙ t = 3.74 × ACFM × ( h 2 − h 1 ) [ Btu/hr ] \dot{q}_t = 3.74 \times \text{ACFM} \times (h_2 - h_1) \quad [\text{Btu/hr}] q ˙ ​ t ​ = 3.74 × ACFM × ( h 2 ​ − h 1 ​ ) [ Btu/hr ]

4. Airflow Conversion: Standard CFM (SCFM) vs. Actual CFM (ACFM)

In HVAC equipment specifications, airflow can be expressed in two ways:

Standard CFM (SCFM): Volumetric flow referenced to standard sea-level air density ( ρ s t d = 0.075 lb/ft 3 \rho_{std} = 0.075\text{ lb/ft}^3 ρ s t d ​ = 0.075 lb/ft 3 ). SCFM is directly proportional to mass flow rate: m ˙ d a = 60 × 0.075 × SCFM = 4.5 × SCFM [lb/hr] \dot{m}_{da} = 60 \times 0.075 \times \text{SCFM} = 4.5 \times \text{SCFM} \text{ [lb/hr]} m ˙ d a ​ = 60 × 0.075 × SCFM = 4.5 × SCFM [lb/hr] .

Actual CFM (ACFM): The physical volume of air moving through the duct or fan per minute at actual operating pressure and temperature: m ˙ d a = 60 × ρ a c t u a l × ACFM \dot{m}_{da} = 60 \times \rho_{actual} \times \text{ACFM} m ˙ d a ​ = 60 × ρ a c t u a l ​ × ACFM .

Equating dry air mass flow rates: ACFM = SCFM × ( ρ s t d ρ a c t u a l ) = SCFM × ( P 0 P ) × ( T T 0 ) \text{ACFM} = \text{SCFM} \times \left( \frac{\rho_{std}}{\rho_{actual}} \right) = \text{SCFM} \times \left( \frac{P_0}{P} \right) \times \left( \frac{T}{T_0} \right) ACFM = SCFM × ( ρ a c t u a l ​ ρ s t d ​ ​ ) = SCFM × ( P P 0 ​ ​ ) × ( T 0 ​ T ​ )

Key Exam Rule of Thumb: For a given sensible cooling load ( q s q_s q s ​ ) and supply air temperature differential ( Δ T \Delta T Δ T ), a fan at 5,000 ft must deliver 20% MORE actual CFM (ACFM) than at sea level to achieve the same cooling capacity: ACFM 5000 CFM s l = 1.08 0.90 = 1.20 \frac{\text{ACFM}_{5000}}{\text{CFM}_{sl}} = \frac{1.08}{0.90} = 1.20 CFM s l ​ ACFM 5000 ​ ​ = 0.90 1.08 ​ = 1.20

  • 5. Step-by-Step Worked Example: High-Altitude Cooling Coil Sizing
  • Problem Statement

A commercial building located in Denver, Colorado (elevation 5 , 000 ft 5,000\text{ ft} 5 , 000 ft , barometric pressure P = 12.23 psia P = 12.23\text{ psia} P = 12.23 psia , air density ρ = 0.0624 lb/ft 3 \rho = 0.0624\text{ lb/ft}^3 ρ = 0.0624 lb/ft 3 ) has a calculated space sensible cooling load of q s = 180 , 000 Btu/hr q_s = 180,000\text{ Btu/hr} q s ​ = 180 , 000 Btu/hr and a space latent cooling load of q l = 40 , 000 Btu/hr q_l = 40,000\text{ Btu/hr} q l ​ = 40 , 000 Btu/hr .

The indoor design condition is 75.0 ∘ F 75.0^\circ\text{F} 75. 0 ∘ F DB and 50 % RH 50\%\text{ RH} 50% RH . The supply air temperature leaving the AHU is 55.0 ∘ F 55.0^\circ\text{F} 55. 0 ∘ F DB.

Calculate:

  • Required supply airflow in Actual CFM (ACFM) at 5 , 000 ft 5,000\text{ ft} 5 , 000 ft
  • What airflow would have been required if the identical building were located at sea level

The total cooling coil load in tons of refrigeration at 5 , 000 ft 5,000\text{ ft} 5 , 000 ft , assuming entering coil air enthalpy h 1 = 33.2 Btu/lb d a h_1 = 33.2\text{ Btu/lb}_{da} h 1 ​ = 33.2 Btu/lb d a ​ and leaving coil air enthalpy h 2 = 23.1 Btu/lb d a h_2 = 23.1\text{ Btu/lb}_{da} h 2 ​ = 23.1 Btu/lb d a ​

Solution Steps

Step 1: Calculate sensible heat constant at 5,000 ft C s , a l t = 60 × ρ a l t × c p = 60 × 0.0624 × 0.240 = 0.8986 ≈ 0.90 Btu / ( hr ⋅ ACFM ⋅ ∘ F ) C_{s,alt} = 60 \times \rho_{alt} \times c_p = 60 \times 0.0624 \times 0.240 = 0.8986 \approx 0.90\text{ Btu}/(\text{hr}\cdot\text{ACFM}\cdot^\circ\text{F}) C s , a lt ​ = 60 × ρ a lt ​ × c p ​ = 60 × 0.0624 × 0.240 = 0.8986 ≈ 0.90 Btu / ( hr ⋅ ACFM ⋅ ∘ F )

Step 2: Calculate required supply airflow at 5,000 ft Δ T = T r o o m − T s u p p l y = 75.0 ∘ F − 55.0 ∘ F = 20.0 ∘ F \Delta T = T_{room} - T_{supply} = 75.0^\circ\text{F} - 55.0^\circ\text{F} = 20.0^\circ\text{F} Δ T = T roo m ​ − T s u ppl y ​ = 75. 0 ∘ F − 55. 0 ∘ F = 20. 0 ∘ F ACFM = q s C s , a l t × Δ T = 180 , 000 0.8986 × 20.0 = 180 , 000 17.971 = 10 , 016 ACFM ≈ 10 , 000 ACFM \text{ACFM} = \frac{q_s}{C_{s,alt} \times \Delta T} = \frac{180,000}{0.8986 \times 20.0} = \frac{180,000}{17.971} = 10,016\text{ ACFM} \approx 10,000\text{ ACFM} ACFM = C s , a lt ​ × Δ T q s ​ ​ = 0.8986 × 20.0 180 , 000 ​ = 17.971 180 , 000 ​ = 10 , 016 ACFM ≈ 10 , 000 ACFM

Step 3: Calculate required airflow at sea level CFM s l = q s 1.08 × Δ T = 180 , 000 1.08 × 20.0 = 180 , 000 21.60 = 8 , 333 CFM \text{CFM}_{sl} = \frac{q_s}{1.08 \times \Delta T} = \frac{180,000}{1.08 \times 20.0} = \frac{180,000}{21.60} = 8,333\text{ CFM} CFM s l ​ = 1.08 × Δ T q s ​ ​ = 1.08 × 20.0 180 , 000 ​ = 21.60 180 , 000 ​ = 8 , 333 CFM Airflow Ratio = 10 , 016 8 , 333 = 1.202 ( + 20.2 % increase ) \text{Airflow Ratio} = \frac{10,016}{8,333} = 1.202 \quad (+20.2\%\text{ increase}) Airflow Ratio = 8 , 333 10 , 016 ​ = 1.202 ( + 20.2% increase )

Step 4: Calculate total cooling coil capacity at 5,000 ft C t , a l t = 60 × ρ a l t = 60 × 0.0624 = 3.744 lb m / ( hr ⋅ ACFM ) C_{t,alt} = 60 \times \rho_{alt} = 60 \times 0.0624 = 3.744\text{ lb}_m/(\text{hr}\cdot\text{ACFM}) C t , a lt ​ = 60 × ρ a lt ​ = 60 × 0.0624 = 3.744 lb m ​ / ( hr ⋅ ACFM ) q ˙ t o t a l = C t , a l t × ACFM × ( h 1 − h 2 ) \dot{q}_{total} = C_{t,alt} \times \text{ACFM} \times (h_1 - h_2) q ˙ ​ t o t a l ​ = C t , a lt ​ × ACFM × ( h 1 ​ − h 2 ​ ) q ˙ t o t a l = 3.744 × 10 , 016 × ( 33.2 − 23.1 ) = 3.744 × 10 , 016 × 10.1 = 378 , 749 Btu/hr \dot{q}_{total} = 3.744 \times 10,016 \times (33.2 - 23.1) = 3.744 \times 10,016 \times 10.1 = 378,749\text{ Btu/hr} q ˙ ​ t o t a l ​ = 3.744 × 10 , 016 × ( 33.2 − 23.1 ) = 3.744 × 10 , 016 × 10.1 = 378 , 749 Btu/hr Tons of Refrigeration = 378 , 749 Btu/hr 12 , 000 Btu/hr ⋅ ton = 31.56 tons \text{Tons of Refrigeration} = \frac{378,749\text{ Btu/hr}}{12,000\text{ Btu/hr}\cdot\text{ton}} = 31.56\text{ tons} Tons of Refrigeration = 12 , 000 Btu/hr ⋅ ton 378 , 749 Btu/hr ​ = 31.56 tons

(Note: If calculated using standard sea level 4.5 factor incorrectly: 4.5 × 10 , 016 × 10.1 = 455 , 227 Btu/hr = 37.9 tons 4.5 \times 10,016 \times 10.1 = 455,227\text{ Btu/hr} = 37.9\text{ tons} 4.5 × 10 , 016 × 10.1 = 455 , 227 Btu/hr = 37.9 tons , resulting in a 20 % 20\% 20% equipment oversizing error!)