Study guide
3.4 Mixed Air Calculations & Complex Air Conditioning Cycles (Preheat, Reheat & Bypass)
PE Mechanical: HVAC and Refrigeration Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview, Reference Handbook & Engineering Foundations
1.1 NCEES Exam Specification, CBT Delivery & Reference Handbook Strategy 1.2 Engineering Units, Dimensional Analysis & Physical Property Lookups 1.3 Engineering Economics, Life Cycle Cost Analysis & Equipment Financial Evaluation 1.4 Electrical Foundations, Motor Ratings & Variable Frequency Drives (VFDs)
2 Chapter 2: Thermodynamics & Energy Balances
2.1 First and Second Laws of Thermodynamics & Open/Closed System Energy Balances 2.2 Thermodynamic Cycles: Carnot, Rankine, Brayton & Reversed Carnot Limit 2.3 Gas & Vapor Property Evaluation: Steam Tables, Superheat & Subcooling 2.4 Mass, Energy & Combustion Balances for HVAC Equipment
3 Chapter 3: Psychrometrics, Moist Air Processes & Humidity Equipment
3.1 Psychrometric Properties: DBT, WBT, DPT, RH, Humidity Ratio & Enthalpy 3.2 Chart Reading & Psychrometric Equations at Sea Level vs. Altitude (5,000 ft) 3.3 Basic Psychrometric Processes: Sensible Heating/Cooling, Humidification & Dehumidification 3.4 Mixed Air Calculations & Complex Air Conditioning Cycles (Preheat, Reheat & Bypass) 3.5 Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP) & Coil Bypass Factor 3.6 Humidification & Dehumidification Equipment: Steam, Adiabatic, Desiccant & Low-Temperature Processes
4 Chapter 4: Heat Transfer Principles & Sizing
4.1 Steady-State Conduction & Multilayer Thermal Resistance (R-Value & U-Factor) 4.2 Convective Heat Transfer & Forced/Natural Convection Coefficients 4.3 Radiation Heat Transfer, Surface Emissivity & View Factors 4.4 Overall Heat Transfer Coefficients, Fouling Factors & Transient/Thermal Mass Effects 4.5 Heat Exchanger Analysis: Log Mean Temperature Difference (LMTD) & Effectiveness-NTU (ε-NTU)
5 Chapter 5: Fluid Mechanics & Hydraulic Fundamentals
5.1 Fluid Statics, Incompressible Continuity & Bernoulli Energy Equation 5.2 Pipe Friction, Moody Diagram & Darcy-Weisbach / Hazen-Williams Calculations 5.3 Minor Losses: Equivalent Length, Loss Coefficients (K-factors) & Total System Head 5.4 Pump Sizing, Net Positive Suction Head (NPSHa vs NPSHr) & Cavitation Prevention 5.5 Affinity Laws & Parallel/Series Pump/Fan System Curves
6 Chapter 6: Heating & Cooling Load Calculations
6.1 Outdoor & Indoor Design Conditions (ASHRAE Fundamentals, Climatic Data & Indoor Setpoints) 6.2 Envelope Heat Transmission & Infiltration/Exfiltration Load Methods 6.3 Solar Heat Gain (SHGC), Fenestration & Cooling Load Temperature Difference / Radiant Time Series (CLTD/RTS) 6.4 Internal Heat Gains: Lighting, People, Equipment & Diversity Factors 6.5 Ventilation Loads & Sensible / Latent / Total Cooling Load Synthesis
7 Chapter 7: Refrigeration Principles, Cycles & Cold Storage Applications
7.1 Standard Vapor-Compression Refrigeration Cycle on P-h & T-s Diagrams 7.2 Refrigeration Cycle Performance Metrics: COP, EER, SEER, kW/ton & Ton of Refrigeration 7.3 Cycle Enhancements: Subcooling, Superheating, Liquid-Suction Heat Exchangers & Economizers 7.4 Multi-Stage & Cascade Refrigeration Systems: Intercooling & Flash Gas Removal 7.5 Absorption Refrigeration Cycles: Water-Lithium Bromide & Ammonia-Water Systems 7.6 Food Processing & Cold Storage Refrigeration: Product Load, Pull-Down & Storage Design
8 Chapter 8: Refrigerants, Environmental Regulations & Safety
8.1 Refrigerant Classifications, Nomenclature & Thermodynamic Properties (ASHRAE Standard 34) 8.2 AIM Act, EPA Technology Transitions Sector GWP Limits & Low-GWP Refrigerants (R-32, R-454B) 8.3 Refrigerant Safety Requirements & Machinery Room Design (ASHRAE Standard 15) 8.4 Refrigerant Piping Sizing, Oil Return, Traps & Double Risers
9 Chapter 9: HVAC Equipment & Primary Machinery
9.1 Compressors: Reciprocating, Rotary, Scroll, Screw & Centrifugal 9.2 Condensers: Air-Cooled, Water-Cooled & Evaporative Condensers 9.3 Evaporators & Direct Expansion (DX) vs Liquid Chilling Coils 9.4 Water Chillers: Centrifugal, Screw & Scroll with ASHRAE 90.1 Path A/B IPLV Ratings 9.5 Cooling Towers: Range, Approach, Evaporation, Blowdown & Legionella Control 9.6 Heat Pumps & Variable Refrigerant Flow (VRF): Balance Point, Defrost & Heat Recovery 9.7 Thermal Energy Storage: Full vs. Partial Storage, Chilled Water & Ice Systems
10 Chapter 10: Air-Side Systems & Distribution
10.1 Air Handling Units (AHUs), Dedicated Outdoor Air Systems (DOAS) & Fan-Coil Units 10.2 Duct Design Methodologies: Equal Friction, Static Regain & Velocity Reduction 10.3 Duct Fittings, Dynamic Pressure Losses & SMACNA Construction Standards 10.4 Fan Types, Performance Curves, System Effect Factors & Surge/Stall Dynamics 10.5 Variable Air Volume (VAV) Systems, Terminal Boxes & Space Air Diffusion (ADPI) 10.6 Cooling & Heating Coil Selection: Face Velocity, Rows, Circuiting & Freeze Protection
11 Chapter 11: Hydronic, Steam & Fuel Distribution and Heating Plant
11.1 Hydronic System Architectures: Primary-Only, Primary-Secondary & Variable Primary Flow (VPF) 11.2 Hydronic Pipe Sizing, Velocity Limits & Closed/Open Expansion Tank Sizing 11.3 Control Valves: 2-Way vs 3-Way, Valve Authority (N), Cv Calculations & Characteristic Curves 11.4 Boilers & Heating Hot Water Systems: Condensing vs Non-Condensing & Water Treatment 11.5 Furnaces & Gas-Fired Heating Equipment: AFUE, Temperature Rise, Combustion Air & Vent Categories 11.6 Steam & Condensate Distribution: Latent Heat, Trap Selection, Flash Steam & Stall 11.7 Fuel Gas & Fuel Oil Piping: Demand, Sizing Method, Pressure Drop & Storage Systems
12 Chapter 12: HVAC Control Concepts, Sensors & Sequences
12.1 Sensors, Actuators & Dampers: Selection, Placement, Fail-Safe Position & Damper Authority 12.2 Control Loops: Proportional Offset, PID Action, Reset Strategies & Standard Sequences
13 Chapter 13: Building Energy, Ventilation & Indoor Environmental Quality Codes
13.1 ASHRAE Standard 62.1: Ventilation Rate Procedure (VRP), Indoor Air Quality Procedure & DCV 13.2 ASHRAE Standard 90.1: Building Energy Envelope, Mechanical Efficiency & Economizer Mandates 13.3 ASHRAE Standard 55: Thermal Environmental Conditions, PMV/PPD & Adaptive Comfort Models 13.4 Energy Recovery Systems: Enthalpy Wheels, Fixed-Plate Exchangers, Heat Pipes & Runaround Loops
14 Chapter 14: Supportive Engineering Knowledge, Life Safety & Operations
14.1 Air Filtration Standards: MERV Ratings (ASHRAE 52.2), HEPA & Gas-Phase Adsorption 14.2 Life Safety Systems: Fire/Smoke Dampers, Stairwell Pressurization (NFPA 92) & Smoke Control (NFPA 90A) 14.3 Acoustical Control & Vibration Isolation in HVAC Systems (NC / RC Criteria)
3.4 Mixed Air Calculations & Complex Air Conditioning Cycles (Preheat, Reheat & Bypass)
Key Takeaways Explain This Topic AI
Adiabatic mixing of two moist airstreams follows conservation of mass and energy; the mixed air state point lies on the straight line connecting the entering states, divided inversely proportional to mass flow rates.
Mixed air dry-bulb temperature, humidity ratio, and enthalpy are calculated as: T m a = % O A ⋅ T o a + ( 1 − % O A ) ⋅ T r a T_{ma} = \%OA \cdot T_{oa} + (1 - \%OA) \cdot T_{ra} T ma = % O A ⋅ T o a + ( 1 − % O A ) ⋅ T r a , W m a = % O A ⋅ W o a + ( 1 − % O A ) ⋅ W r a W_{ma} = \%OA \cdot W_{oa} + (1 - \%OA) \cdot W_{ra} W ma = % O A ⋅ W o a + ( 1 − % O A ) ⋅ W r a , and h m a = % O A ⋅ h o a + ( 1 − % O A ) ⋅ h r a h_{ma} = \%OA \cdot h_{oa} + (1 - \%OA) \cdot h_{ra} h ma = % O A ⋅ h o a + ( 1 − % O A ) ⋅ h r a .
In freezing climates ( T o a < 32 ∘ F T_{oa} < 32^\circ\text{F} T o a < 3 2 ∘ F ), preheat coils or air blenders are mandatory to prevent air stratification and freeze-stat nuisance tripping or coil freeze-ups.
Supply fan heat gain increases the airstream dry-bulb temperature: Δ T f a n = Δ P t o t a l [in. wg] 6356 × η f a n × ρ × c p ≈ Δ P t o t a l [in. wg] 2.54 × η f a n \Delta T_{fan} = \frac{\Delta P_{total} \text{ [in. wg]}}{6356 \times \eta_{fan} \times \rho \times c_p} \approx \frac{\Delta P_{total} \text{ [in. wg]}}{2.54 \times \eta_{fan}} Δ T f an = 6356 × η f an × ρ × c p Δ P t o t a l [in. wg] ≈ 2.54 × η f an Δ P t o t a l [in. wg] , typically adding 1.0 ∘ F 1.0^\circ\text{F} 1. 0 ∘ F to 2.5 ∘ F 2.5^\circ\text{F} 2. 5 ∘ F before delivery.
Subcooling with reheat cycles are essential for tight relative humidity control in spaces with high latent loads (e.g., surgical operating rooms, cleanrooms, and museums).
Last updated: August 2026
3.4 Mixed Air Calculations & Complex Air Conditioning Cycles (Preheat, Reheat & Bypass)
Practical HVAC systems rarely operate with a single heating or cooling coil treating 100% recirculated air. Modern air-handling units (AHUs) blend outdoor ventilation air with recirculated return air, navigate freeze-protection constraints, compensate for supply fan thermal energy dissipation, and incorporate reheat or face-and-bypass dampers for precise zone humidity and temperature regulation.
1. Adiabatic Mixing of Two Airstreams
When outdoor air ( O A OA O A ) and return air ( R A RA R A ) mix adiabatically in an AHU mixing box, the resulting mixed air ( M A MA M A ) state point is governed by the conservation of dry air mass, water vapor mass, and thermal energy:
Dry Air Mass Balance: m ˙ m a = m ˙ o a + m ˙ r a \dot{m}_{ma} = \dot{m}_{oa} + \dot{m}_{ra} m ˙ ma = m ˙ o a + m ˙ r a
Water Vapor Mass Balance: m ˙ m a W m a = m ˙ o a W o a + m ˙ r a W r a ⟹ W m a = ( m ˙ o a m ˙ m a ) W o a + ( m ˙ r a m ˙ m a ) W r a \dot{m}_{ma} W_{ma} = \dot{m}_{oa} W_{oa} + \dot{m}_{ra} W_{ra} \implies W_{ma} = \left( \frac{\dot{m}_{oa}}{\dot{m}_{ma}} \right) W_{oa} + \left( \frac{\dot{m}_{ra}}{\dot{m}_{ma}} \right) W_{ra} m ˙ ma W ma = m ˙ o a W o a + m ˙ r a W r a ⟹ W ma = ( m ˙ ma m ˙ o a ) W o a + ( m ˙ ma m ˙ r a ) W r a
Enthalpy (Energy) Balance: m ˙ m a h m a = m ˙ o a h o a + m ˙ r a h r a ⟹ h m a = ( m ˙ o a m ˙ m a ) h o a + ( m ˙ r a m ˙ m a ) h r a \dot{m}_{ma} h_{ma} = \dot{m}_{oa} h_{oa} + \dot{m}_{ra} h_{ra} \implies h_{ma} = \left( \frac{\dot{m}_{oa}}{\dot{m}_{ma}} \right) h_{oa} + \left( \frac{\dot{m}_{ra}}{\dot{m}_{ma}} \right) h_{ra} m ˙ ma h ma = m ˙ o a h o a + m ˙ r a h r a ⟹ h ma = ( m ˙ ma m ˙ o a ) h o a + ( m ˙ ma m ˙ r a ) h r a
Dry-Bulb Temperature (Sensible Approximation): T m a = ( m ˙ o a m ˙ m a ) T o a + ( m ˙ r a m ˙ m a ) T r a = % O A ⋅ T o a + ( 1 − % O A ) ⋅ T r a T_{ma} = \left( \frac{\dot{m}_{oa}}{\dot{m}_{ma}} \right) T_{oa} + \left( \frac{\dot{m}_{ra}}{\dot{m}_{ma}} \right) T_{ra} = \%OA \cdot T_{oa} + (1 - \%OA) \cdot T_{ra} T ma = ( m ˙ ma m ˙ o a ) T o a + ( m ˙ ma m ˙ r a ) T r a = % O A ⋅ T o a + ( 1 − % O A ) ⋅ T r a
Where: % O A = m ˙ o a m ˙ m a ≈ CFM o a CFM m a \%OA = \frac{\dot{m}_{oa}}{\dot{m}_{ma}} \approx \frac{\text{CFM}_{oa}}{\text{CFM}_{ma}} % O A = m ˙ ma m ˙ o a ≈ CFM ma CFM o a
Geometric Lever Rule on Psychrometric Chart: The mixed air state point M A MA M A lies directly on the straight line connecting state O A OA O A and state R A RA R A . The distance from R A RA R A to M A MA M A is proportional to the fraction of outdoor air: R A − M A ‾ R A − O A ‾ = m ˙ o a m ˙ m a \frac{\overline{RA-MA}}{\overline{RA-OA}} = \frac{\dot{m}_{oa}}{\dot{m}_{ma}} R A − O A R A − M A = m ˙ ma m ˙ o a .
Loading diagram... Complex Air Conditioning Cycle Flow Architecture
- 2. Advanced Cycle Components and Phenomena
- 1. Preheat Coil & Freeze Protection
In cold climates when outdoor air design temperatures fall below 35 ∘ F 35^\circ\text{F} 3 5 ∘ F , cold outdoor air entering an AHU mixing box risks freezing chilled water or domestic water coils downstream due to air stratification. A preheat coil is located in the 100% outdoor air stream to elevate T o a T_{oa} T o a to a safe mixing temperature (typically 40 ∘ F 40^\circ\text{F} 4 0 ∘ F to 45 ∘ F 45^\circ\text{F} 4 5 ∘ F ): q ˙ p r e h e a t = 1.08 × CFM o a × ( T o a , l e a v i n g − T o a , e n t e r i n g ) [ Btu/hr ] \dot{q}_{preheat} = 1.08 \times \text{CFM}_{oa} \times (T_{oa,leaving} - T_{oa,entering}) \quad [\text{Btu/hr}] q ˙ p re h e a t = 1.08 × CFM o a × ( T o a , l e a v in g − T o a , e n t er in g ) [ Btu/hr ]
2. Supply and Return Fan Heat Gain
Fans convert electrical and mechanical shaft power into kinetic and thermal energy. All aerodynamic losses and internal flow friction dissipate directly into the airstream as heat, raising the dry-bulb temperature: Δ T f a n = Δ P t o t a l [in. wg] 6356 × η t o t a l × ρ × c p ≈ Δ P t o t a l [in. wg] 2.69 × η t o t a l [ ∘ F ] \Delta T_{fan} = \frac{\Delta P_{total} \text{ [in. wg]}}{6356 \times \eta_{total} \times \rho \times c_p} \approx \frac{\Delta P_{total} \text{ [in. wg]}}{2.69 \times \eta_{total}} \quad [^\circ\text{F}] Δ T f an = 6356 × η t o t a l × ρ × c p Δ P t o t a l [in. wg] ≈ 2.69 × η t o t a l Δ P t o t a l [in. wg] [ ∘ F ]
Where:
Δ P t o t a l = fan total pressure rise ( in. w.g. ) \Delta P_{total} = \text{fan total pressure rise } (\text{in. w.g.}) Δ P t o t a l = fan total pressure rise ( in. w.g. )
η t o t a l = combined fan and drive efficiency (decimal, typically 0.60 − 0.75 ) \eta_{total} = \text{combined fan and drive efficiency (decimal, typically } 0.60 - 0.75) η t o t a l = combined fan and drive efficiency (decimal, typically 0.60 − 0.75 )
ρ = 0.075 lb/ft 3 \rho = 0.075\text{ lb/ft}^3 ρ = 0.075 lb/ft 3 , c p = 0.24 Btu/lb ⋅ ∘ F c_p = 0.24\text{ Btu/lb}\cdot^\circ\text{F} c p = 0.24 Btu/lb ⋅ ∘ F
For a typical draw-through system with Δ P t = 3.5 in. wg \Delta P_t = 3.5\text{ in. wg} Δ P t = 3.5 in. wg and η = 0.65 \eta = 0.65 η = 0.65 : Δ T f a n = 3.5 2.69 × 0.65 = 2.00 ∘ F \Delta T_{fan} = \frac{3.5}{2.69 \times 0.65} = 2.00^\circ\text{F} Δ T f an = 2.69 × 0.65 3.5 = 2.0 0 ∘ F
If the fan motor is located inside the airstream (common in packaged units), motor inefficiency heat is also added: η t o t a l = η f a n × η m o t o r \eta_{total} = \eta_{fan} \times \eta_{motor} η t o t a l = η f an × η m o t or .
3. Dehumidification with Subcooling and Reheat
When an occupied space has high internal latent loads (e.g., hospital operating rooms, natatoriums, cleanrooms) or during humid part-load conditions, simply cooling air to the required room sensible supply temperature will not remove enough water vapor.
The Subcool/Reheat Process:
Cool air down to a low apparatus dew point (e.g., 48 ∘ F − 52 ∘ F 48^\circ\text{F}-52^\circ\text{F} 4 8 ∘ F − 5 2 ∘ F ) across the cooling coil to wring out excess moisture.
Reheat the dry air sensibly (via hot water, electric, or condenser heat recovery) to the design supply temperature ( 60 ∘ F − 65 ∘ F 60^\circ\text{F}-65^\circ\text{F} 6 0 ∘ F − 6 5 ∘ F ) to prevent overcooling the space. q ˙ r e h e a t = 1.08 × CFM s a × ( T s u p p l y − T l e a v i n g _ c o i l ) [ Btu/hr ] \dot{q}_{reheat} = 1.08 \times \text{CFM}_{sa} \times (T_{supply} - T_{leaving\_coil}) \quad [\text{Btu/hr}] q ˙ re h e a t = 1.08 × CFM s a × ( T s u ppl y − T l e a v in g _ co i l ) [ Btu/hr ]
4. Face and Bypass Damper Systems
In face-and-bypass systems, a portion of the mixed air is directed through the cooling coil (face damper) while the remainder bypasses around the coil (bypass damper). The two streams remix downstream. This provides precise space temperature control without varying the total airflow or modulating coil water temperature.
- 3. Step-by-Step Worked Example: Comprehensive Complex AHU Cycle Analysis
- Problem Statement
A commercial AHU serves an office suite with the following design specifications at standard sea-level pressure ( 14.696 psia 14.696\text{ psia} 14.696 psia ):
Total Supply Airflow: CFM s a = 12 , 000 CFM \text{CFM}_{sa} = 12,000\text{ CFM} CFM s a = 12 , 000 CFM
Outdoor Ventilation Air: CFM o a = 3 , 000 CFM \text{CFM}_{oa} = 3,000\text{ CFM} CFM o a = 3 , 000 CFM ( 25 % OA 25\%\text{ OA} 25% OA ) at 92.0 ∘ F 92.0^\circ\text{F} 92. 0 ∘ F DB, 76.0 ∘ F 76.0^\circ\text{F} 76. 0 ∘ F WB ( h o a = 39.6 Btu/lb h_{oa} = 39.6\text{ Btu/lb} h o a = 39.6 Btu/lb , W o a = 0.0158 lb/lb W_{oa} = 0.0158\text{ lb/lb} W o a = 0.0158 lb/lb )
Recirculated Return Air: CFM r a = 9 , 000 CFM \text{CFM}_{ra} = 9,000\text{ CFM} CFM r a = 9 , 000 CFM ( 75 % RA 75\%\text{ RA} 75% RA ) at 76.0 ∘ F 76.0^\circ\text{F} 76. 0 ∘ F DB, 50 % RH 50\%\text{ RH} 50% RH ( h r a = 28.3 Btu/lb h_{ra} = 28.3\text{ Btu/lb} h r a = 28.3 Btu/lb , W r a = 0.0094 lb/lb W_{ra} = 0.0094\text{ lb/lb} W r a = 0.0094 lb/lb )
Cooling Coil: Cools and dehumidifies mixed air to a leaving condition of 52.0 ∘ F 52.0^\circ\text{F} 52. 0 ∘ F DB, 51.0 ∘ F 51.0^\circ\text{F} 51. 0 ∘ F WB ( h c c = 20.8 Btu/lb h_{cc} = 20.8\text{ Btu/lb} h cc = 20.8 Btu/lb , W c c = 0.0078 lb/lb W_{cc} = 0.0078\text{ lb/lb} W cc = 0.0078 lb/lb )
Supply Fan: Draw-through configuration with a measured temperature rise of Δ T f a n = 1.5 ∘ F \Delta T_{fan} = 1.5^\circ\text{F} Δ T f an = 1. 5 ∘ F
Reheat Coil: Heats the air from the fan discharge state to a final supply air temperature of 58.0 ∘ F 58.0^\circ\text{F} 58. 0 ∘ F DB
Calculate:
- Mixed air properties ( T m a , W m a , h m a T_{ma}, W_{ma}, h_{ma} T ma , W ma , h ma )
- Total cooling coil load in tons of refrigeration
- Supply fan heat gain in Btu/hr
- Reheat coil thermal duty in Btu/hr
- Net sensible cooling delivered to the conditioned space (room)
- Solution Steps
Step 1: Calculate Mixed Air State Points % O A = 3 , 000 12 , 000 = 0.25 and % R A = 9 , 000 12 , 000 = 0.75 \%OA = \frac{3,000}{12,000} = 0.25 \quad \text{and} \quad \%RA = \frac{9,000}{12,000} = 0.75 % O A = 12 , 000 3 , 000 = 0.25 and % R A = 12 , 000 9 , 000 = 0.75 T m a = 0.25 ( 92.0 ∘ F ) + 0.75 ( 76.0 ∘ F ) = 23.0 + 57.0 = 80.0 ∘ F T_{ma} = 0.25(92.0^\circ\text{F}) + 0.75(76.0^\circ\text{F}) = 23.0 + 57.0 = 80.0^\circ\text{F} T ma = 0.25 ( 92. 0 ∘ F ) + 0.75 ( 76. 0 ∘ F ) = 23.0 + 57.0 = 80. 0 ∘ F W m a = 0.25 ( 0.0158 ) + 0.75 ( 0.0094 ) = 0.00395 + 0.00705 = 0.0110 lb w / lb d a W_{ma} = 0.25(0.0158) + 0.75(0.0094) = 0.00395 + 0.00705 = 0.0110\text{ lb}_w/\text{lb}_{da} W ma = 0.25 ( 0.0158 ) + 0.75 ( 0.0094 ) = 0.00395 + 0.00705 = 0.0110 lb w / lb d a h m a = 0.25 ( 39.6 ) + 0.75 ( 28.3 ) = 9.90 + 21.225 = 31.13 Btu / lb d a h_{ma} = 0.25(39.6) + 0.75(28.3) = 9.90 + 21.225 = 31.13\text{ Btu}/\text{lb}_{da} h ma = 0.25 ( 39.6 ) + 0.75 ( 28.3 ) = 9.90 + 21.225 = 31.13 Btu / lb d a
Step 2: Calculate Total Cooling Coil Load q ˙ c o i l = 4.5 × CFM s a × ( h m a − h c c ) \dot{q}_{coil} = 4.5 \times \text{CFM}_{sa} \times (h_{ma} - h_{cc}) q ˙ co i l = 4.5 × CFM s a × ( h ma − h cc ) q ˙ c o i l = 4.5 × 12 , 000 × ( 31.13 − 20.80 ) = 54 , 000 × 10.33 = 557 , 820 Btu/hr \dot{q}_{coil} = 4.5 \times 12,000 \times (31.13 - 20.80) = 54,000 \times 10.33 = 557,820\text{ Btu/hr} q ˙ co i l = 4.5 × 12 , 000 × ( 31.13 − 20.80 ) = 54 , 000 × 10.33 = 557 , 820 Btu/hr Coil Capacity (Tons) = 557 , 820 12 , 000 = 46.49 tons \text{Coil Capacity (Tons)} = \frac{557,820}{12,000} = 46.49\text{ tons} Coil Capacity (Tons) = 12 , 000 557 , 820 = 46.49 tons
Step 3: Calculate Supply Fan Heat Addition q ˙ f a n = 1.08 × CFM s a × Δ T f a n = 1.08 × 12 , 000 × 1.5 ∘ F = 19 , 440 Btu/hr \dot{q}_{fan} = 1.08 \times \text{CFM}_{sa} \times \Delta T_{fan} = 1.08 \times 12,000 \times 1.5^\circ\text{F} = 19,440\text{ Btu/hr} q ˙ f an = 1.08 × CFM s a × Δ T f an = 1.08 × 12 , 000 × 1. 5 ∘ F = 19 , 440 Btu/hr T f a n , o u t = T c c , o u t + Δ T f a n = 52.0 ∘ F + 1.5 ∘ F = 53.5 ∘ F T_{fan,out} = T_{cc,out} + \Delta T_{fan} = 52.0^\circ\text{F} + 1.5^\circ\text{F} = 53.5^\circ\text{F} T f an , o u t = T cc , o u t + Δ T f an = 52. 0 ∘ F + 1. 5 ∘ F = 53. 5 ∘ F
Step 4: Calculate Reheat Coil Thermal Duty Δ T r e h e a t = T s u p p l y − T f a n , o u t = 58.0 ∘ F − 53.5 ∘ F = 4.5 ∘ F \Delta T_{reheat} = T_{supply} - T_{fan,out} = 58.0^\circ\text{F} - 53.5^\circ\text{F} = 4.5^\circ\text{F} Δ T re h e a t = T s u ppl y − T f an , o u t = 58. 0 ∘ F − 53. 5 ∘ F = 4. 5 ∘ F q ˙ r e h e a t = 1.08 × CFM s a × Δ T r e h e a t = 1.08 × 12 , 000 × 4.5 ∘ F = 58 , 320 Btu/hr \dot{q}_{reheat} = 1.08 \times \text{CFM}_{sa} \times \Delta T_{reheat} = 1.08 \times 12,000 \times 4.5^\circ\text{F} = 58,320\text{ Btu/hr} q ˙ re h e a t = 1.08 × CFM s a × Δ T re h e a t = 1.08 × 12 , 000 × 4. 5 ∘ F = 58 , 320 Btu/hr
Step 5: Calculate Net Space Sensible Cooling Capacity q ˙ s , s p a c e = 1.08 × CFM s a × ( T r o o m − T s u p p l y ) \dot{q}_{s,space} = 1.08 \times \text{CFM}_{sa} \times (T_{room} - T_{supply}) q ˙ s , s p a ce = 1.08 × CFM s a × ( T roo m − T s u ppl y ) q ˙ s , s p a c e = 1.08 × 12 , 000 × ( 76.0 ∘ F − 58.0 ∘ F ) = 12 , 960 × 18.0 = 233 , 280 Btu/hr = 19.44 tons \dot{q}_{s,space} = 1.08 \times 12,000 \times (76.0^\circ\text{F} - 58.0^\circ\text{F}) = 12,960 \times 18.0 = 233,280\text{ Btu/hr} = 19.44\text{ tons} q ˙ s , s p a ce = 1.08 × 12 , 000 × ( 76. 0 ∘ F − 58. 0 ∘ F ) = 12 , 960 × 18.0 = 233 , 280 Btu/hr = 19.44 tons
(Notice how the total refrigeration capacity of 46.5 tons satisfies outdoor ventilation load + coil latent load + fan heat + reheat load to deliver 19.4 tons of net space cooling).