3.1 Psychrometric Properties: DBT, WBT, DPT, RH, Humidity Ratio & Enthalpy
PE Mechanical: HVAC and Refrigeration Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview, Reference Handbook & Engineering Foundations
1.1 NCEES Exam Specification, CBT Delivery & Reference Handbook Strategy 1.2 Engineering Units, Dimensional Analysis & Physical Property Lookups 1.3 Engineering Economics, Life Cycle Cost Analysis & Equipment Financial Evaluation 1.4 Electrical Foundations, Motor Ratings & Variable Frequency Drives (VFDs)
2 Chapter 2: Thermodynamics & Energy Balances
2.1 First and Second Laws of Thermodynamics & Open/Closed System Energy Balances 2.2 Thermodynamic Cycles: Carnot, Rankine, Brayton & Reversed Carnot Limit 2.3 Gas & Vapor Property Evaluation: Steam Tables, Superheat & Subcooling 2.4 Mass, Energy & Combustion Balances for HVAC Equipment
3 Chapter 3: Psychrometrics, Moist Air Processes & Humidity Equipment
3.1 Psychrometric Properties: DBT, WBT, DPT, RH, Humidity Ratio & Enthalpy 3.2 Chart Reading & Psychrometric Equations at Sea Level vs. Altitude (5,000 ft) 3.3 Basic Psychrometric Processes: Sensible Heating/Cooling, Humidification & Dehumidification 3.4 Mixed Air Calculations & Complex Air Conditioning Cycles (Preheat, Reheat & Bypass) 3.5 Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP) & Coil Bypass Factor 3.6 Humidification & Dehumidification Equipment: Steam, Adiabatic, Desiccant & Low-Temperature Processes
4 Chapter 4: Heat Transfer Principles & Sizing
4.1 Steady-State Conduction & Multilayer Thermal Resistance (R-Value & U-Factor) 4.2 Convective Heat Transfer & Forced/Natural Convection Coefficients 4.3 Radiation Heat Transfer, Surface Emissivity & View Factors 4.4 Overall Heat Transfer Coefficients, Fouling Factors & Transient/Thermal Mass Effects 4.5 Heat Exchanger Analysis: Log Mean Temperature Difference (LMTD) & Effectiveness-NTU (ε-NTU)
5 Chapter 5: Fluid Mechanics & Hydraulic Fundamentals
5.1 Fluid Statics, Incompressible Continuity & Bernoulli Energy Equation 5.2 Pipe Friction, Moody Diagram & Darcy-Weisbach / Hazen-Williams Calculations 5.3 Minor Losses: Equivalent Length, Loss Coefficients (K-factors) & Total System Head 5.4 Pump Sizing, Net Positive Suction Head (NPSHa vs NPSHr) & Cavitation Prevention 5.5 Affinity Laws & Parallel/Series Pump/Fan System Curves
6 Chapter 6: Heating & Cooling Load Calculations
6.1 Outdoor & Indoor Design Conditions (ASHRAE Fundamentals, Climatic Data & Indoor Setpoints) 6.2 Envelope Heat Transmission & Infiltration/Exfiltration Load Methods 6.3 Solar Heat Gain (SHGC), Fenestration & Cooling Load Temperature Difference / Radiant Time Series (CLTD/RTS) 6.4 Internal Heat Gains: Lighting, People, Equipment & Diversity Factors 6.5 Ventilation Loads & Sensible / Latent / Total Cooling Load Synthesis
7 Chapter 7: Refrigeration Principles, Cycles & Cold Storage Applications
7.1 Standard Vapor-Compression Refrigeration Cycle on P-h & T-s Diagrams 7.2 Refrigeration Cycle Performance Metrics: COP, EER, SEER, kW/ton & Ton of Refrigeration 7.3 Cycle Enhancements: Subcooling, Superheating, Liquid-Suction Heat Exchangers & Economizers 7.4 Multi-Stage & Cascade Refrigeration Systems: Intercooling & Flash Gas Removal 7.5 Absorption Refrigeration Cycles: Water-Lithium Bromide & Ammonia-Water Systems 7.6 Food Processing & Cold Storage Refrigeration: Product Load, Pull-Down & Storage Design
8 Chapter 8: Refrigerants, Environmental Regulations & Safety
8.1 Refrigerant Classifications, Nomenclature & Thermodynamic Properties (ASHRAE Standard 34) 8.2 AIM Act, EPA Technology Transitions Sector GWP Limits & Low-GWP Refrigerants (R-32, R-454B) 8.3 Refrigerant Safety Requirements & Machinery Room Design (ASHRAE Standard 15) 8.4 Refrigerant Piping Sizing, Oil Return, Traps & Double Risers
9 Chapter 9: HVAC Equipment & Primary Machinery
9.1 Compressors: Reciprocating, Rotary, Scroll, Screw & Centrifugal 9.2 Condensers: Air-Cooled, Water-Cooled & Evaporative Condensers 9.3 Evaporators & Direct Expansion (DX) vs Liquid Chilling Coils 9.4 Water Chillers: Centrifugal, Screw & Scroll with ASHRAE 90.1 Path A/B IPLV Ratings 9.5 Cooling Towers: Range, Approach, Evaporation, Blowdown & Legionella Control 9.6 Heat Pumps & Variable Refrigerant Flow (VRF): Balance Point, Defrost & Heat Recovery 9.7 Thermal Energy Storage: Full vs. Partial Storage, Chilled Water & Ice Systems
10 Chapter 10: Air-Side Systems & Distribution
10.1 Air Handling Units (AHUs), Dedicated Outdoor Air Systems (DOAS) & Fan-Coil Units 10.2 Duct Design Methodologies: Equal Friction, Static Regain & Velocity Reduction 10.3 Duct Fittings, Dynamic Pressure Losses & SMACNA Construction Standards 10.4 Fan Types, Performance Curves, System Effect Factors & Surge/Stall Dynamics 10.5 Variable Air Volume (VAV) Systems, Terminal Boxes & Space Air Diffusion (ADPI) 10.6 Cooling & Heating Coil Selection: Face Velocity, Rows, Circuiting & Freeze Protection
11 Chapter 11: Hydronic, Steam & Fuel Distribution and Heating Plant
11.1 Hydronic System Architectures: Primary-Only, Primary-Secondary & Variable Primary Flow (VPF) 11.2 Hydronic Pipe Sizing, Velocity Limits & Closed/Open Expansion Tank Sizing 11.3 Control Valves: 2-Way vs 3-Way, Valve Authority (N), Cv Calculations & Characteristic Curves 11.4 Boilers & Heating Hot Water Systems: Condensing vs Non-Condensing & Water Treatment 11.5 Furnaces & Gas-Fired Heating Equipment: AFUE, Temperature Rise, Combustion Air & Vent Categories 11.6 Steam & Condensate Distribution: Latent Heat, Trap Selection, Flash Steam & Stall 11.7 Fuel Gas & Fuel Oil Piping: Demand, Sizing Method, Pressure Drop & Storage Systems
12 Chapter 12: HVAC Control Concepts, Sensors & Sequences
12.1 Sensors, Actuators & Dampers: Selection, Placement, Fail-Safe Position & Damper Authority 12.2 Control Loops: Proportional Offset, PID Action, Reset Strategies & Standard Sequences
13 Chapter 13: Building Energy, Ventilation & Indoor Environmental Quality Codes
13.1 ASHRAE Standard 62.1: Ventilation Rate Procedure (VRP), Indoor Air Quality Procedure & DCV 13.2 ASHRAE Standard 90.1: Building Energy Envelope, Mechanical Efficiency & Economizer Mandates 13.3 ASHRAE Standard 55: Thermal Environmental Conditions, PMV/PPD & Adaptive Comfort Models 13.4 Energy Recovery Systems: Enthalpy Wheels, Fixed-Plate Exchangers, Heat Pipes & Runaround Loops
14 Chapter 14: Supportive Engineering Knowledge, Life Safety & Operations
14.1 Air Filtration Standards: MERV Ratings (ASHRAE 52.2), HEPA & Gas-Phase Adsorption 14.2 Life Safety Systems: Fire/Smoke Dampers, Stairwell Pressurization (NFPA 92) & Smoke Control (NFPA 90A) 14.3 Acoustical Control & Vibration Isolation in HVAC Systems (NC / RC Criteria)
3.1 Psychrometric Properties: DBT, WBT, DPT, RH, Humidity Ratio & Enthalpy
Key Takeaways Explain This Topic AI
Atmospheric moist air is modeled as a binary mixture of ideal dry air and water vapor governed by Dalton's Law of Partial Pressures: P = p a + p v P = p_a + p_v P = p a + p v .
Humidity ratio ( W W W ) is the mass of water vapor per unit mass of dry air: W = 0.62198 p v P − p v W = 0.62198 \frac{p_v}{P - p_v} W = 0.62198 P − p v p v , expressed in lb w / lb d a \text{lb}_w/\text{lb}_{da} lb w / lb d a or grains / lb d a \text{grains}/\text{lb}_{da} grains / lb d a ( 1 lb = 7 , 000 grains 1\text{ lb} = 7,000\text{ grains} 1 lb = 7 , 000 grains ).
Relative humidity ( RH \text{RH} RH or ϕ \phi ϕ ) is the ratio of actual water vapor partial pressure to saturation pressure at dry-bulb temperature: RH = p v p w s ( T d b ) × 100 % \text{RH} = \frac{p_v}{p_{ws}(T_{db})} \times 100\% RH = p w s ( T d b ) p v × 100% .
Moist air specific enthalpy ( h h h ) combines dry air sensible heat and water vapor total heat: h = 0.240 T d b + W ( 1061 + 0.444 T d b ) h = 0.240 T_{db} + W (1061 + 0.444 T_{db}) h = 0.240 T d b + W ( 1061 + 0.444 T d b ) in Btu / lb d a \text{Btu}/\text{lb}_{da} Btu / lb d a (USCS) or h = 1.006 T d b + W ( 2501 + 1.86 T d b ) h = 1.006 T_{db} + W (2501 + 1.86 T_{db}) h = 1.006 T d b + W ( 2501 + 1.86 T d b ) in kJ / kg d a \text{kJ}/\text{kg}_{da} kJ / kg d a (SI).
At saturation ( RH = 100 % \text{RH} = 100\% RH = 100% ), dry-bulb temperature ( T d b T_{db} T d b ), wet-bulb temperature ( T w b T_{wb} T w b ), and dew-point temperature ( T d p T_{dp} T d p ) are identical; for unsaturated air ( RH < 100 % \text{RH} < 100\% RH < 100% ), the strict thermodynamic inequality T d b > T w b > T d p T_{db} > T_{wb} > T_{dp} T d b > T w b > T d p always holds.
Last updated: August 2026
3.1 Psychrometric Properties: DBT, WBT, DPT, RH, Humidity Ratio & Enthalpy
Psychrometrics is the branch of thermodynamics dedicated to the evaluation of the physical, thermodynamic, and hygrometric properties of moist air (a binary mixture of dry air and water vapor). Mastery of psychrometric properties is essential for the NCEES PE Mechanical: HVAC and Refrigeration examination, serving as the quantitative backbone for heating and cooling load analysis, air-handling unit (AHU) sizing, coil selection, and indoor environmental control.
1. Thermodynamic Model of Atmospheric Moist Air
Under standard HVAC operating conditions (temperatures between − 40 ∘ F -40^\circ\text{F} − 4 0 ∘ F and 140 ∘ F 140^\circ\text{F} 14 0 ∘ F and pressures near atmospheric), dry air and water vapor behave as ideal gases with negligible error ( < 0.5 % <0.5\% < 0.5% ). By Dalton's Law of Partial Pressures , the total barometric pressure P P P exerted by moist air is the sum of the partial pressure of dry air ( p a p_a p a ) and the partial pressure of water vapor ( p v p_v p v ): P = p a + p v P = p_a + p_v P = p a + p v
Where:
P = total atmospheric barometric pressure ( psia or in. Hg ) P = \text{total atmospheric barometric pressure } (\text{psia or in. Hg}) P = total atmospheric barometric pressure ( psia or in. Hg )
p a = partial pressure of dry air ( psia ) p_a = \text{partial pressure of dry air } (\text{psia}) p a = partial pressure of dry air ( psia )
p v = partial pressure of water vapor ( psia ) p_v = \text{partial pressure of water vapor } (\text{psia}) p v = partial pressure of water vapor ( psia )
Applying the ideal gas law ( p V = m R T p V = m R T p V = m RT ) to both constituents individually: p a v = R d a T and p v v = R v T p_a v = R_{da} T \quad \text{and} \quad p_v v = R_v T p a v = R d a T and p v v = R v T
Where:
R d a = R ˉ M d a = 1545.35 28.966 = 53.352 ft ⋅ lbf / ( lbm ⋅ ∘ R ) = 0.06855 Btu / ( lbm ⋅ ∘ R ) R_{da} = \frac{\bar{R}}{M_{da}} = \frac{1545.35}{28.966} = 53.352 \text{ ft}\cdot\text{lbf}/(\text{lbm}\cdot^\circ\text{R}) = 0.06855 \text{ Btu}/(\text{lbm}\cdot^\circ\text{R}) R d a = M d a R ˉ = 28.966 1545.35 = 53.352 ft ⋅ lbf / ( lbm ⋅ ∘ R ) = 0.06855 Btu / ( lbm ⋅ ∘ R )
R v = R ˉ M v = 1545.35 18.015 = 85.781 ft ⋅ lbf / ( lbm ⋅ ∘ R ) = 0.11024 Btu / ( lbm ⋅ ∘ R ) R_v = \frac{\bar{R}}{M_v} = \frac{1545.35}{18.015} = 85.781 \text{ ft}\cdot\text{lbf}/(\text{lbm}\cdot^\circ\text{R}) = 0.11024 \text{ Btu}/(\text{lbm}\cdot^\circ\text{R}) R v = M v R ˉ = 18.015 1545.35 = 85.781 ft ⋅ lbf / ( lbm ⋅ ∘ R ) = 0.11024 Btu / ( lbm ⋅ ∘ R )
The molecular weight ratio is M v M d a = 18.01528 28.966 ≈ 0.62198 \frac{M_v}{M_{da}} = \frac{18.01528}{28.966} \approx 0.62198 M d a M v = 28.966 18.01528 ≈ 0.62198
2. Core Psychrometric State Variables
An equilibrium thermodynamic state of moist air at a fixed barometric pressure is uniquely fixed by any two independent intensive psychrometric properties (e.g., T d b T_{db} T d b and T w b T_{wb} T w b , or T d b T_{db} T d b and RH \text{RH} RH , or T d b T_{db} T d b and W W W ).
Dry-Bulb Temperature ( T d b T_{db} T d b or t t t )
The temperature of moist air indicated by an ordinary thermometer unaffected by radiation or moisture condensation/evaporation, expressed in ∘ F ^\circ\text{F} ∘ F or ∘ C ^\circ\text{C} ∘ C .
Wet-Bulb Temperature ( T w b T_{wb} T w b or t ′ t' t ′ )
The dynamic equilibrium temperature reached by a wetted thermometer sensor exposed to a high-velocity airstream ( > 900 ft/min >900\text{ ft/min} > 900 ft/min ) under steady-state conditions where convective sensible heat transfer from the air to the wick equals the latent heat required to evaporate water from the wick into the airstream. In the NCEES handbook, thermodynamic wet-bulb temperature is rigorously treated as the adiabatic saturation temperature.
Dew-Point Temperature ( T d p T_{dp} T d p or t d p t_{dp} t d p )
The saturation temperature corresponding to the partial pressure of water vapor present in the mixture: T d p = T s a t ( p v ) T_{dp} = T_{sat}(p_v) T d p = T s a t ( p v ) . When moist air is cooled at constant pressure and constant humidity ratio, condensation begins exactly when T d b T_{db} T d b reaches T d p T_{dp} T d p .
Saturation Pressure ( p w s p_{ws} p w s )
The maximum equilibrium vapor pressure of water at a given dry-bulb temperature. In ASHRAE / NCEES reference tables, p w s p_{ws} p w s is tabulated as a function of temperature. For manual estimation between 32 ∘ F 32^\circ\text{F} 3 2 ∘ F and 140 ∘ F 140^\circ\text{F} 14 0 ∘ F , Antoine-type equations or table lookups are used:
At T = 32 ∘ F T = 32^\circ\text{F} T = 3 2 ∘ F : p w s = 0.08866 psia = 0.1805 in. Hg p_{ws} = 0.08866 \text{ psia} = 0.1805 \text{ in. Hg} p w s = 0.08866 psia = 0.1805 in. Hg
At T = 60 ∘ F T = 60^\circ\text{F} T = 6 0 ∘ F : p w s = 0.2563 psia = 0.5218 in. Hg p_{ws} = 0.2563 \text{ psia} = 0.5218 \text{ in. Hg} p w s = 0.2563 psia = 0.5218 in. Hg
At T = 70 ∘ F T = 70^\circ\text{F} T = 7 0 ∘ F : p w s = 0.3632 psia = 0.7392 in. Hg p_{ws} = 0.3632 \text{ psia} = 0.7392 \text{ in. Hg} p w s = 0.3632 psia = 0.7392 in. Hg
At T = 80 ∘ F T = 80^\circ\text{F} T = 8 0 ∘ F : p w s = 0.5073 psia = 1.0326 in. Hg p_{ws} = 0.5073 \text{ psia} = 1.0326 \text{ in. Hg} p w s = 0.5073 psia = 1.0326 in. Hg
Relative Humidity ( ϕ \phi ϕ or RH \text{RH} RH )
The ratio of the actual water vapor partial pressure p v p_v p v to the saturation vapor pressure p w s p_{ws} p w s at the same dry-bulb temperature: RH = ϕ = p v p w s ( T d b ) × 100 % \text{RH} = \phi = \frac{p_v}{p_{ws}(T_{db})} \times 100\% RH = ϕ = p w s ( T d b ) p v × 100%
Humidity Ratio ( W W W or ω \omega ω )
The ratio of the mass of water vapor to the mass of dry air in the mixture. Also referred to as moisture content or specific humidity: W = m v m d a = M v p v M d a p a = 0.62198 p v P − p v [ lb w lb d a ] W = \frac{m_v}{m_{da}} = \frac{M_v p_v}{M_{da} p_a} = 0.62198 \frac{p_v}{P - p_v} \quad \left[\frac{\text{lb}_{w}}{\text{lb}_{da}}\right] W = m d a m v = M d a p a M v p v = 0.62198 P − p v p v [ lb d a lb w ]
To express W W W in grains of moisture per pound of dry air ( 1 lb = 7 , 000 grains 1\text{ lb} = 7,000\text{ grains} 1 lb = 7 , 000 grains ): W grains = 7000 × W = 7000 × 0.62198 p v P − p v = 4353.9 p v P − p v [ grains lb d a ] W_{\text{grains}} = 7000 \times W = 7000 \times 0.62198 \frac{p_v}{P - p_v} = 4353.9 \frac{p_v}{P - p_v} \quad \left[\frac{\text{grains}}{\text{lb}_{da}}\right] W grains = 7000 × W = 7000 × 0.62198 P − p v p v = 4353.9 P − p v p v [ lb d a grains ]
Degree of Saturation ( μ \mu μ )
The ratio of the actual humidity ratio W W W to the saturation humidity ratio W s W_s W s at the same dry-bulb temperature and total pressure: μ = W W s ∣ T , P = 0.62198 p v P − p v 0.62198 p w s P − p w s = ϕ [ P − p w s P − p v ] = ϕ 1 + ( 1 − ϕ ) p w s P − p w s \mu = \left. \frac{W}{W_s} \right|_{T, P} = \frac{0.62198 \frac{p_v}{P - p_v}}{0.62198 \frac{p_{ws}}{P - p_{ws}}} = \phi \left[ \frac{P - p_{ws}}{P - p_v} \right] = \frac{\phi}{1 + (1 - \phi)\frac{p_{ws}}{P - p_{ws}}} μ = W s W T , P = 0.62198 P − p w s p w s 0.62198 P − p v p v = ϕ [ P − p v P − p w s ] = 1 + ( 1 − ϕ ) P − p w s p w s ϕ
Notice that μ < ϕ \mu < \phi μ < ϕ whenever ϕ < 100 % \phi < 100\% ϕ < 100% , though for typical HVAC temperatures ( p w s ≪ P p_{ws} \ll P p w s ≪ P ), μ ≈ ϕ \mu \approx \phi μ ≈ ϕ .
Specific Volume of Moist Air ( v v v )
The volume of mixture per unit mass of dry air, expressed in ft 3 / lb d a \text{ft}^3/\text{lb}_{da} ft 3 / lb d a (or m 3 / kg d a \text{m}^3/\text{kg}_{da} m 3 / kg d a ): v = R d a T p a = R d a T P − p v = R d a T ( 1 + 1.6078 W ) P v = \frac{R_{da} T}{p_a} = \frac{R_{da} T}{P - p_v} = \frac{R_{da} T (1 + 1.6078 W)}{P} v = p a R d a T = P − p v R d a T = P R d a T ( 1 + 1.6078 W )
Where T T T is in absolute temperature ( ∘ R = ∘ F + 459.67 ^\circ\text{R} = ^\circ\text{F} + 459.67 ∘ R = ∘ F + 459.67 ).
Specific Enthalpy ( h h h )
The total energy per unit mass of dry air, defined as the sum of dry air sensible enthalpy and water vapor enthalpy referenced to 0 ∘ F 0^\circ\text{F} 0 ∘ F dry air and 32 ∘ F 32^\circ\text{F} 3 2 ∘ F saturated liquid water: h = h d a + W h v = c p , d a T d b + W ( h g 0 + c p , v T d b ) h = h_{da} + W h_v = c_{p,da} T_{db} + W (h_{g0} + c_{p,v} T_{db}) h = h d a + W h v = c p , d a T d b + W ( h g 0 + c p , v T d b )
Using standard USCS coefficients ( c p , d a = 0.240 Btu / lb ⋅ ∘ F c_{p,da} = 0.240\text{ Btu}/\text{lb}\cdot^\circ\text{F} c p , d a = 0.240 Btu / lb ⋅ ∘ F , h g 0 = 1061.2 Btu / lb h_{g0} = 1061.2\text{ Btu}/\text{lb} h g 0 = 1061.2 Btu / lb , c p , v = 0.444 Btu / lb ⋅ ∘ F c_{p,v} = 0.444\text{ Btu}/\text{lb}\cdot^\circ\text{F} c p , v = 0.444 Btu / lb ⋅ ∘ F ): h = 0.240 T d b + W ( 1061 + 0.444 T d b ) [ Btu lb d a ] h = 0.240 T_{db} + W (1061 + 0.444 T_{db}) \quad \left[\frac{\text{Btu}}{\text{lb}_{da}}\right] h = 0.240 T d b + W ( 1061 + 0.444 T d b ) [ lb d a Btu ]
In SI units ( c p , d a = 1.006 kJ / kg ⋅ ∘ C c_{p,da} = 1.006\text{ kJ}/\text{kg}\cdot^\circ\text{C} c p , d a = 1.006 kJ / kg ⋅ ∘ C , h g 0 = 2501 kJ / kg h_{g0} = 2501\text{ kJ}/\text{kg} h g 0 = 2501 kJ / kg , c p , v = 1.86 kJ / kg ⋅ ∘ C c_{p,v} = 1.86\text{ kJ}/\text{kg}\cdot^\circ\text{C} c p , v = 1.86 kJ / kg ⋅ ∘ C ): h = 1.006 T d b + W ( 2501 + 1.86 T d b ) [ kJ kg d a ] h = 1.006 T_{db} + W (2501 + 1.86 T_{db}) \quad \left[\frac{\text{kJ}}{\text{kg}_{da}}\right] h = 1.006 T d b + W ( 2501 + 1.86 T d b ) [ kg d a kJ ]
3. Property Relationships & Thermodynamic Inequalities
Understanding the mathematical and physical relationship among the three key temperatures ( T d b , T w b , T d p T_{db}, T_{wb}, T_{dp} T d b , T w b , T d p ) is a high-yield concept on the PE exam:
Air Condition Temperature Relationship Relative Humidity Vapor Pressure
Saturated Air T d b = T w b = T d p T_{db} = T_{wb} = T_{dp} T d b = T w b = T d p RH = 100 % \text{RH} = 100\% RH = 100% p v = p w s ( T d b ) p_v = p_{ws}(T_{db}) p v = p w s ( T d b )
Unsaturated Air T d b > T w b > T d p T_{db} > T_{wb} > T_{dp} T d b > T w b > T d p RH < 100 % \text{RH} < 100\% RH < 100% p v < p w s ( T d b ) p_v < p_{ws}(T_{db}) p v < p w s ( T d b )
Supersaturated / Fog Condensation occurs RH → 100 % \text{RH} \to 100\% RH → 100% Suspended droplets
NCEES CBT Handbook Tip — Wet-Bulb Equation: The relation connecting wet-bulb temperature T w b T_{wb} T w b to partial vapor pressure p v p_v p v at standard pressure is Carrier's equation: p v = p w s ′ − ( P − p w s ′ ) ( T d b − T w b ) 2800 − 1.3 T w b p_v = p_{ws}' - \frac{(P - p_{ws}')(T_{db} - T_{wb})}{2800 - 1.3 T_{wb}} p v = p w s ′ − 2800 − 1.3 T w b ( P − p w s ′ ) ( T d b − T w b ) Where p w s ′ p_{ws}' p w s ′ is the saturation pressure evaluated at the wet-bulb temperature T w b T_{wb} T w b (in ∘ F ^\circ\text{F} ∘ F ). On the exam, when reading psychrometric charts, you can locate state points directly via chart grid lines without solving Carrier's equation manually.
Loading diagram... Psychrometric Property Coordinate System & State Lines
4. Comprehensive Property Lookup & Conversion Reference
- Property Symbol USCS Unit SI Unit Primary Governing Equation
- Dry-Bulb Temp T d b T_{db} T d b or t t t ∘ F ^\circ\text{F} ∘ F ∘ C ^\circ\text{C} ∘ C Measured directly
Wet-Bulb Temp T w b T_{wb} T w b or t ′ t' t ′ ∘ F ^\circ\text{F} ∘ F ∘ C ^\circ\text{C} ∘ C Adiabatic saturation balance
Dew-Point Temp T d p T_{dp} T d p or t d p t_{dp} t d p ∘ F ^\circ\text{F} ∘ F ∘ C ^\circ\text{C} ∘ C T s a t ( p v ) T_{sat}(p_v) T s a t ( p v )
Relative Humidity ϕ \phi ϕ or RH \text{RH} RH % \% % % \% % p v p w s ( T d b ) × 100 % \frac{p_v}{p_{ws}(T_{db})} \times 100\% p w s ( T d b ) p v × 100%
Humidity Ratio W W W or ω \omega ω lb w lb d a \frac{\text{lb}_w}{\text{lb}_{da}} lb d a lb w or gr lb d a \frac{\text{gr}}{\text{lb}_{da}} lb d a gr kg w kg d a \frac{\text{kg}_w}{\text{kg}_{da}} kg d a kg w or g kg d a \frac{\text{g}}{\text{kg}_{da}} kg d a g 0.62198 p v P − p v 0.62198 \frac{p_v}{P - p_v} 0.62198 P − p v p v
Specific Volume v v v ft 3 lb d a \frac{\text{ft}^3}{\text{lb}_{da}} lb d a ft 3 m 3 kg d a \frac{\text{m}^3}{\text{kg}_{da}} kg d a m 3 R d a T P − p v \frac{R_{da} T}{P - p_v} P − p v R d a T
Specific Enthalpy h h h Btu lb d a \frac{\text{Btu}}{\text{lb}_{da}} lb d a Btu kJ kg d a \frac{\text{kJ}}{\text{kg}_{da}} kg d a kJ 0.240 T d b + W ( 1061 + 0.444 T d b ) 0.240 T_{db} + W (1061 + 0.444 T_{db}) 0.240 T d b + W ( 1061 + 0.444 T d b )
Moist Air Density ρ \rho ρ lb m ft 3 \frac{\text{lb}_m}{\text{ft}^3} ft 3 lb m kg m 3 \frac{\text{kg}}{\text{m}^3} m 3 kg ρ = 1 + W v \rho = \frac{1 + W}{v} ρ = v 1 + W
- 5. Step-by-Step Worked Example: Exact Psychrometric State Determination
- Problem Statement
Moist air at standard sea level atmospheric pressure ( P = 14.696 psia P = 14.696\text{ psia} P = 14.696 psia ) has a dry-bulb temperature of T d b = 80.0 ∘ F T_{db} = 80.0^\circ\text{F} T d b = 80. 0 ∘ F and a wet-bulb temperature of T w b = 67.0 ∘ F T_{wb} = 67.0^\circ\text{F} T w b = 67. 0 ∘ F . From steam saturation tables:
Saturation pressure at 80 ∘ F 80^\circ\text{F} 8 0 ∘ F : p w s ( 80 ∘ F ) = 0.5073 psia p_{ws}(80^\circ\text{F}) = 0.5073\text{ psia} p w s ( 8 0 ∘ F ) = 0.5073 psia
Saturation pressure at 67 ∘ F 67^\circ\text{F} 6 7 ∘ F : p w s ′ ( 67 ∘ F ) = 0.3288 psia p_{ws}'(67^\circ\text{F}) = 0.3288\text{ psia} p w s ′ ( 6 7 ∘ F ) = 0.3288 psia
Calculate:
Partial vapor pressure p v p_v p v (psia)
Humidity ratio W W W (in lb w / lb d a \text{lb}_w/\text{lb}_{da} lb w / lb d a and grains / lb d a \text{grains}/\text{lb}_{da} grains / lb d a )
- Relative humidity RH \text{RH} RH (%)
- Specific enthalpy h h h ( Btu / lb d a \text{Btu}/\text{lb}_{da} Btu / lb d a )
- Specific volume v v v ( ft 3 / lb d a \text{ft}^3/\text{lb}_{da} ft 3 / lb d a )
- Solution Steps
Step 1: Calculate actual partial vapor pressure p v p_v p v via Carrier's equation p v = p w s ′ − ( P − p w s ′ ) ( T d b − T w b ) 2800 − 1.3 T w b p_v = p_{ws}' - \frac{(P - p_{ws}')(T_{db} - T_{wb})}{2800 - 1.3 T_{wb}} p v = p w s ′ − 2800 − 1.3 T w b ( P − p w s ′ ) ( T d b − T w b ) p v = 0.3288 − ( 14.696 − 0.3288 ) ( 80.0 − 67.0 ) 2800 − 1.3 ( 67.0 ) p_v = 0.3288 - \frac{(14.696 - 0.3288)(80.0 - 67.0)}{2800 - 1.3(67.0)} p v = 0.3288 − 2800 − 1.3 ( 67.0 ) ( 14.696 − 0.3288 ) ( 80.0 − 67.0 ) p v = 0.3288 − ( 14.3672 ) ( 13.0 ) 2800 − 87.1 = 0.3288 − 186.774 2712.9 = 0.3288 − 0.06885 = 0.25995 psia ≈ 0.2600 psia p_v = 0.3288 - \frac{(14.3672)(13.0)}{2800 - 87.1} = 0.3288 - \frac{186.774}{2712.9} = 0.3288 - 0.06885 = 0.25995\text{ psia} \approx 0.2600\text{ psia} p v = 0.3288 − 2800 − 87.1 ( 14.3672 ) ( 13.0 ) = 0.3288 − 2712.9 186.774 = 0.3288 − 0.06885 = 0.25995 psia ≈ 0.2600 psia
Step 2: Calculate humidity ratio W W W W = 0.62198 p v P − p v = 0.62198 × 0.2600 14.696 − 0.2600 = 0.62198 × 0.2600 14.4360 = 0.011195 lb w / lb d a W = 0.62198 \frac{p_v}{P - p_v} = 0.62198 \times \frac{0.2600}{14.696 - 0.2600} = 0.62198 \times \frac{0.2600}{14.4360} = 0.011195\text{ lb}_w/\text{lb}_{da} W = 0.62198 P − p v p v = 0.62198 × 14.696 − 0.2600 0.2600 = 0.62198 × 14.4360 0.2600 = 0.011195 lb w / lb d a W grains = 0.011195 × 7000 = 78.37 grains / lb d a W_{\text{grains}} = 0.011195 \times 7000 = 78.37\text{ grains}/\text{lb}_{da} W grains = 0.011195 × 7000 = 78.37 grains / lb d a
Step 3: Calculate relative humidity RH \text{RH} RH RH = p v p w s ( 80 ∘ F ) × 100 % = 0.2600 0.5073 × 100 % = 51.25 % \text{RH} = \frac{p_v}{p_{ws}(80^\circ\text{F})} \times 100\% = \frac{0.2600}{0.5073} \times 100\% = 51.25\% RH = p w s ( 8 0 ∘ F ) p v × 100% = 0.5073 0.2600 × 100% = 51.25%
Step 4: Calculate mixture specific enthalpy h h h h = 0.240 T d b + W ( 1061 + 0.444 T d b ) h = 0.240 T_{db} + W (1061 + 0.444 T_{db}) h = 0.240 T d b + W ( 1061 + 0.444 T d b ) h = 0.240 ( 80.0 ) + 0.011195 ( 1061 + 0.444 × 80.0 ) h = 0.240(80.0) + 0.011195(1061 + 0.444 \times 80.0) h = 0.240 ( 80.0 ) + 0.011195 ( 1061 + 0.444 × 80.0 ) h = 19.20 + 0.011195 ( 1061 + 35.52 ) = 19.20 + 12.28 = 31.48 Btu / lb d a h = 19.20 + 0.011195(1061 + 35.52) = 19.20 + 12.28 = 31.48\text{ Btu}/\text{lb}_{da} h = 19.20 + 0.011195 ( 1061 + 35.52 ) = 19.20 + 12.28 = 31.48 Btu / lb d a
Step 5: Calculate specific volume v v v v = R d a T P − p v = 53.352 × ( 80.0 + 459.67 ) 144 × ( 14.696 − 0.2600 ) = 53.352 × 539.67 144 × 14.4360 = 28792.1 2078.78 = 13.85 ft 3 / lb d a v = \frac{R_{da} T}{P - p_v} = \frac{53.352 \times (80.0 + 459.67)}{144 \times (14.696 - 0.2600)} = \frac{53.352 \times 539.67}{144 \times 14.4360} = \frac{28792.1}{2078.78} = 13.85\text{ ft}^3/\text{lb}_{da} v = P − p v R d a T = 144 × ( 14.696 − 0.2600 ) 53.352 × ( 80.0 + 459.67 ) = 144 × 14.4360 53.352 × 539.67 = 2078.78 28792.1 = 13.85 ft 3 / lb d a
Total moist air density ρ = 1 + W v = 1 + 0.011195 13.85 = 0.0730 lb m / ft 3 \rho = \frac{1 + W}{v} = \frac{1 + 0.011195}{13.85} = 0.0730\text{ lb}_m/\text{ft}^3 ρ = v 1 + W = 13.85 1 + 0.011195 = 0.0730 lb m / ft 3 .