3.5 Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP) & Coil Bypass Factor
PE Mechanical: HVAC and Refrigeration Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview, Reference Handbook & Engineering Foundations
1.1 NCEES Exam Specification, CBT Delivery & Reference Handbook Strategy 1.2 Engineering Units, Dimensional Analysis & Physical Property Lookups 1.3 Engineering Economics, Life Cycle Cost Analysis & Equipment Financial Evaluation 1.4 Electrical Foundations, Motor Ratings & Variable Frequency Drives (VFDs)
2 Chapter 2: Thermodynamics & Energy Balances
2.1 First and Second Laws of Thermodynamics & Open/Closed System Energy Balances 2.2 Thermodynamic Cycles: Carnot, Rankine, Brayton & Reversed Carnot Limit 2.3 Gas & Vapor Property Evaluation: Steam Tables, Superheat & Subcooling 2.4 Mass, Energy & Combustion Balances for HVAC Equipment
3 Chapter 3: Psychrometrics, Moist Air Processes & Humidity Equipment
3.1 Psychrometric Properties: DBT, WBT, DPT, RH, Humidity Ratio & Enthalpy 3.2 Chart Reading & Psychrometric Equations at Sea Level vs. Altitude (5,000 ft) 3.3 Basic Psychrometric Processes: Sensible Heating/Cooling, Humidification & Dehumidification 3.4 Mixed Air Calculations & Complex Air Conditioning Cycles (Preheat, Reheat & Bypass) 3.5 Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP) & Coil Bypass Factor 3.6 Humidification & Dehumidification Equipment: Steam, Adiabatic, Desiccant & Low-Temperature Processes
4 Chapter 4: Heat Transfer Principles & Sizing
4.1 Steady-State Conduction & Multilayer Thermal Resistance (R-Value & U-Factor) 4.2 Convective Heat Transfer & Forced/Natural Convection Coefficients 4.3 Radiation Heat Transfer, Surface Emissivity & View Factors 4.4 Overall Heat Transfer Coefficients, Fouling Factors & Transient/Thermal Mass Effects 4.5 Heat Exchanger Analysis: Log Mean Temperature Difference (LMTD) & Effectiveness-NTU (ε-NTU)
5 Chapter 5: Fluid Mechanics & Hydraulic Fundamentals
5.1 Fluid Statics, Incompressible Continuity & Bernoulli Energy Equation 5.2 Pipe Friction, Moody Diagram & Darcy-Weisbach / Hazen-Williams Calculations 5.3 Minor Losses: Equivalent Length, Loss Coefficients (K-factors) & Total System Head 5.4 Pump Sizing, Net Positive Suction Head (NPSHa vs NPSHr) & Cavitation Prevention 5.5 Affinity Laws & Parallel/Series Pump/Fan System Curves
6 Chapter 6: Heating & Cooling Load Calculations
6.1 Outdoor & Indoor Design Conditions (ASHRAE Fundamentals, Climatic Data & Indoor Setpoints) 6.2 Envelope Heat Transmission & Infiltration/Exfiltration Load Methods 6.3 Solar Heat Gain (SHGC), Fenestration & Cooling Load Temperature Difference / Radiant Time Series (CLTD/RTS) 6.4 Internal Heat Gains: Lighting, People, Equipment & Diversity Factors 6.5 Ventilation Loads & Sensible / Latent / Total Cooling Load Synthesis
7 Chapter 7: Refrigeration Principles, Cycles & Cold Storage Applications
7.1 Standard Vapor-Compression Refrigeration Cycle on P-h & T-s Diagrams 7.2 Refrigeration Cycle Performance Metrics: COP, EER, SEER, kW/ton & Ton of Refrigeration 7.3 Cycle Enhancements: Subcooling, Superheating, Liquid-Suction Heat Exchangers & Economizers 7.4 Multi-Stage & Cascade Refrigeration Systems: Intercooling & Flash Gas Removal 7.5 Absorption Refrigeration Cycles: Water-Lithium Bromide & Ammonia-Water Systems 7.6 Food Processing & Cold Storage Refrigeration: Product Load, Pull-Down & Storage Design
8 Chapter 8: Refrigerants, Environmental Regulations & Safety
8.1 Refrigerant Classifications, Nomenclature & Thermodynamic Properties (ASHRAE Standard 34) 8.2 AIM Act, EPA Technology Transitions Sector GWP Limits & Low-GWP Refrigerants (R-32, R-454B) 8.3 Refrigerant Safety Requirements & Machinery Room Design (ASHRAE Standard 15) 8.4 Refrigerant Piping Sizing, Oil Return, Traps & Double Risers
9 Chapter 9: HVAC Equipment & Primary Machinery
9.1 Compressors: Reciprocating, Rotary, Scroll, Screw & Centrifugal 9.2 Condensers: Air-Cooled, Water-Cooled & Evaporative Condensers 9.3 Evaporators & Direct Expansion (DX) vs Liquid Chilling Coils 9.4 Water Chillers: Centrifugal, Screw & Scroll with ASHRAE 90.1 Path A/B IPLV Ratings 9.5 Cooling Towers: Range, Approach, Evaporation, Blowdown & Legionella Control 9.6 Heat Pumps & Variable Refrigerant Flow (VRF): Balance Point, Defrost & Heat Recovery 9.7 Thermal Energy Storage: Full vs. Partial Storage, Chilled Water & Ice Systems
10 Chapter 10: Air-Side Systems & Distribution
10.1 Air Handling Units (AHUs), Dedicated Outdoor Air Systems (DOAS) & Fan-Coil Units 10.2 Duct Design Methodologies: Equal Friction, Static Regain & Velocity Reduction 10.3 Duct Fittings, Dynamic Pressure Losses & SMACNA Construction Standards 10.4 Fan Types, Performance Curves, System Effect Factors & Surge/Stall Dynamics 10.5 Variable Air Volume (VAV) Systems, Terminal Boxes & Space Air Diffusion (ADPI) 10.6 Cooling & Heating Coil Selection: Face Velocity, Rows, Circuiting & Freeze Protection
11 Chapter 11: Hydronic, Steam & Fuel Distribution and Heating Plant
11.1 Hydronic System Architectures: Primary-Only, Primary-Secondary & Variable Primary Flow (VPF) 11.2 Hydronic Pipe Sizing, Velocity Limits & Closed/Open Expansion Tank Sizing 11.3 Control Valves: 2-Way vs 3-Way, Valve Authority (N), Cv Calculations & Characteristic Curves 11.4 Boilers & Heating Hot Water Systems: Condensing vs Non-Condensing & Water Treatment 11.5 Furnaces & Gas-Fired Heating Equipment: AFUE, Temperature Rise, Combustion Air & Vent Categories 11.6 Steam & Condensate Distribution: Latent Heat, Trap Selection, Flash Steam & Stall 11.7 Fuel Gas & Fuel Oil Piping: Demand, Sizing Method, Pressure Drop & Storage Systems
12 Chapter 12: HVAC Control Concepts, Sensors & Sequences
12.1 Sensors, Actuators & Dampers: Selection, Placement, Fail-Safe Position & Damper Authority 12.2 Control Loops: Proportional Offset, PID Action, Reset Strategies & Standard Sequences
13 Chapter 13: Building Energy, Ventilation & Indoor Environmental Quality Codes
13.1 ASHRAE Standard 62.1: Ventilation Rate Procedure (VRP), Indoor Air Quality Procedure & DCV 13.2 ASHRAE Standard 90.1: Building Energy Envelope, Mechanical Efficiency & Economizer Mandates 13.3 ASHRAE Standard 55: Thermal Environmental Conditions, PMV/PPD & Adaptive Comfort Models 13.4 Energy Recovery Systems: Enthalpy Wheels, Fixed-Plate Exchangers, Heat Pipes & Runaround Loops
14 Chapter 14: Supportive Engineering Knowledge, Life Safety & Operations
14.1 Air Filtration Standards: MERV Ratings (ASHRAE 52.2), HEPA & Gas-Phase Adsorption 14.2 Life Safety Systems: Fire/Smoke Dampers, Stairwell Pressurization (NFPA 92) & Smoke Control (NFPA 90A) 14.3 Acoustical Control & Vibration Isolation in HVAC Systems (NC / RC Criteria)
3.5 Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP) & Coil Bypass Factor
Key Takeaways Explain This Topic AI
Room Sensible Heat Ratio ( RSHR = q s , r o o m q s , r o o m + q l , r o o m \text{RSHR} = \frac{q_{s,room}}{q_{s,room} + q_{l,room}} RSHR = q s , roo m + q l , roo m q s , roo m ) determines the slope of the Room Condition Line connecting the room state to the required supply air state.
Grand Sensible Heat Ratio ( GSHR = q s , t o t a l q t , t o t a l \text{GSHR} = \frac{q_{s,total}}{q_{t,total}} GSHR = q t , t o t a l q s , t o t a l ) includes ventilation loads and determines the slope of the process line connecting the mixed air state to the Apparatus Dew Point ( A D P ADP A D P ).
The Apparatus Dew Point ( A D P ADP A D P ) is the effective surface temperature of the cooling coil where the condition line intersects the 100 % RH 100\%\text{ RH} 100% RH saturation curve.
Coil Bypass Factor ( B F BF BF ) represents the fraction of air passing through the coil unaffected: B F = T l e a v i n g − T a d p T e n t e r i n g − T a d p = W l e a v i n g − W a d p W e n t e r i n g − W a d p BF = \frac{T_{leaving} - T_{adp}}{T_{entering} - T_{adp}} = \frac{W_{leaving} - W_{adp}}{W_{entering} - W_{adp}} BF = T e n t er in g − T a d p T l e a v in g − T a d p = W e n t er in g − W a d p W l e a v in g − W a d p ; Contact Factor is C F = 1 − B F CF = 1 - BF CF = 1 − BF .
Required supply airflow accounting for coil bypass is: CFM s a = q s , r o o m 1.08 × ( T r o o m − T a d p ) × ( 1 − B F ) \text{CFM}_{sa} = \frac{q_{s,room}}{1.08 \times (T_{room} - T_{adp}) \times (1 - BF)} CFM s a = 1.08 × ( T roo m − T a d p ) × ( 1 − BF ) q s , roo m .
Last updated: August 2026
3.5 Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP) & Coil Bypass Factor
Designing a cooling coil requires satisfying both the sensible cooling load (temperature reduction) and the latent cooling load (moisture removal) simultaneously. The Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP), and Coil Bypass Factor (BF) are the engineering parameters that link space cooling loads to physical coil construction and required airflow.
1. Sensible Heat Ratio (SHR) Definitions
Sensible Heat Ratio (also called Sensible Heat Factor, SHF) is the ratio of sensible heat to total heat: SHR = q ˙ s e n s i b l e q ˙ t o t a l = q ˙ s q ˙ s + q ˙ l \text{SHR} = \frac{\dot{q}_{sensible}}{\dot{q}_{total}} = \frac{\dot{q}_s}{\dot{q}_s + \dot{q}_l} SHR = q ˙ t o t a l q ˙ se n s ib l e = q ˙ s + q ˙ l q ˙ s
1. Room Sensible Heat Ratio (RSHR)
Governs the slope of the Room Condition Line (RCL) on the psychrometric chart connecting the room design state ( R R R ) and the supply air state ( S S S ): RSHR = q s , r o o m q s , r o o m + q l , r o o m \text{RSHR} = \frac{q_{s,room}}{q_{s,room} + q_{l,room}} RSHR = q s , roo m + q l , roo m q s , roo m
Where q s , r o o m q_{s,room} q s , roo m and q l , r o o m q_{l,room} q l , roo m include internal loads (people, lighting, equipment, envelope conduction, solar gain) but exclude outdoor ventilation air loads .
2. Grand Sensible Heat Ratio (GSHR)
Governs the slope of the Grand Condition Line (GCL) connecting the mixed air state ( M M M ) to the apparatus dew point ( A D P ADP A D P ): GSHR = q s , t o t a l q t , t o t a l = q s , r o o m + q s , v e n t q t , r o o m + q t , v e n t \text{GSHR} = \frac{q_{s,total}}{q_{t,total}} = \frac{q_{s,room} + q_{s,vent}}{q_{t,room} + q_{t,vent}} GSHR = q t , t o t a l q s , t o t a l = q t , roo m + q t , v e n t q s , roo m + q s , v e n t
Where:
q s , v e n t = 1.08 × CFM o a × ( T o a − T r o o m ) q_{s,vent} = 1.08 \times \text{CFM}_{oa} \times (T_{oa} - T_{room}) q s , v e n t = 1.08 × CFM o a × ( T o a − T roo m )
q l , v e n t = 4840 × CFM o a × ( W o a − W r o o m ) q_{l,vent} = 4840 \times \text{CFM}_{oa} \times (W_{oa} - W_{room}) q l , v e n t = 4840 × CFM o a × ( W o a − W roo m )
3. Effective Sensible Heat Ratio (ESHR)
Used when coil bypass factor B F > 0 BF > 0 BF > 0 . It accounts for the fraction of outdoor ventilation air that bypasses the coil fins and enters the conditioned space directly: ESHR = q s , r o o m + ( 1 − B F ) q s , v e n t q t , r o o m + ( 1 − B F ) q t , v e n t \text{ESHR} = \frac{q_{s,room} + (1 - BF) q_{s,vent}}{q_{t,room} + (1 - BF) q_{t,vent}} ESHR = q t , roo m + ( 1 − BF ) q t , v e n t q s , roo m + ( 1 − BF ) q s , v e n t
Loading diagram... Psychrometric Construction of RSHR, GSHR, ADP, and Coil Bypass
- 2. Apparatus Dew Point (ADP) & Coil Bypass Factor (BF)
- Apparatus Dew Point (ADP)
The Apparatus Dew Point is the effective average surface temperature of the cooling coil fins and tubes. Geometrically on the psychrometric chart, the A D P ADP A D P is the point where the condition line intersects the 100 % RH 100\%\text{ RH} 100% RH saturation curve ( T d b = T w b = T d p = T a d p T_{db} = T_{wb} = T_{dp} = T_{adp} T d b = T w b = T d p = T a d p ).
Coil Bypass Factor ( B F BF BF )
In a physical cooling coil, not all air molecules make direct thermal contact with the cold fin surfaces. A fraction of the air ( B F BF BF ) passes through between fins unaffected, while the remaining fraction ( 1 − B F 1 - BF 1 − BF ) comes into complete thermal equilibrium at the A D P ADP A D P . Bypass Factor: B F = T l e a v i n g − T a d p T e n t e r i n g − T a d p = W l e a v i n g − W a d p W e n t e r i n g − W a d p = h l e a v i n g − h a d p h e n t e r i n g − h a d p \text{Bypass Factor: } BF = \frac{T_{leaving} - T_{adp}}{T_{entering} - T_{adp}} = \frac{W_{leaving} - W_{adp}}{W_{entering} - W_{adp}} = \frac{h_{leaving} - h_{adp}}{h_{entering} - h_{adp}} Bypass Factor: BF = T e n t er in g − T a d p T l e a v in g − T a d p = W e n t er in g − W a d p W l e a v in g − W a d p = h e n t er in g − h a d p h l e a v in g − h a d p Contact Factor: C F = 1 − B F = T e n t e r i n g − T l e a v i n g T e n t e r i n g − T a d p \text{Contact Factor: } CF = 1 - BF = \frac{T_{entering} - T_{leaving}}{T_{entering} - T_{adp}} Contact Factor: CF = 1 − BF = T e n t er in g − T a d p T e n t er in g − T l e a v in g
Rearranging to find leaving coil air temperature ( T l e a v i n g T_{leaving} T l e a v in g ): T l e a v i n g = T a d p + B F ( T e n t e r i n g − T a d p ) = ( 1 − B F ) T a d p + B F ⋅ T e n t e r i n g T_{leaving} = T_{adp} + BF \left( T_{entering} - T_{adp} \right) = (1 - BF) T_{adp} + BF \cdot T_{entering} T l e a v in g = T a d p + BF ( T e n t er in g − T a d p ) = ( 1 − BF ) T a d p + BF ⋅ T e n t er in g
Parameters Governing Coil Bypass Factor ( B F BF BF )
Parameter Change Effect on Bypass Factor ( B F BF BF ) Physical Reason
Number of Tube Rows Increase (e.g., 4 to 8 rows) Decreases B F BF BF (improves contact) Longer air residence time and more fin surface contact
Fin Density (FPI) Increase (e.g., 8 to 14 fins/in) Decreases B F BF BF Narrower air passages between fins maximize boundary layer contact
Coil Face Velocity Increase (e.g., 400 to 600 FPM) Increases B F BF BF Higher air velocity reduces residence time across coil
Typical DX Coils Commercial Rooftop Units B F ≈ 0.10 − 0.20 BF \approx 0.10 - 0.20 BF ≈ 0.10 − 0.20 3 to 4 rows, lower fin density
Typical CW Coils Built-up Central AHUs B F ≈ 0.03 − 0.08 BF \approx 0.03 - 0.08 BF ≈ 0.03 − 0.08 6 to 8 rows, higher fin density
3. Supply Airflow (CFM) Calculation with Coil Bypass
To satisfy the room sensible cooling load ( q s , r o o m q_{s,room} q s , roo m ), the supply airflow must be sized based on the temperature difference between the room design temperature ( T r o o m T_{room} T roo m ) and the actual supply air temperature ( T s u p p l y T_{supply} T s u ppl y ): CFM s a = q s , r o o m 1.08 × ( T r o o m − T s u p p l y ) \text{CFM}_{sa} = \frac{q_{s,room}}{1.08 \times (T_{room} - T_{supply})} CFM s a = 1.08 × ( T roo m − T s u ppl y ) q s , roo m
Expressing T s u p p l y T_{supply} T s u ppl y (leaving coil) in terms of A D P ADP A D P and B F BF BF : T r o o m − T s u p p l y = T r o o m − [ T a d p + B F ( T r o o m − T a d p ) ] = ( 1 − B F ) ( T r o o m − T a d p ) T_{room} - T_{supply} = T_{room} - \left[ T_{adp} + BF(T_{room} - T_{adp}) \right] = (1 - BF)(T_{room} - T_{adp}) T roo m − T s u ppl y = T roo m − [ T a d p + BF ( T roo m − T a d p ) ] = ( 1 − BF ) ( T roo m − T a d p ) CFM s a = q s , r o o m 1.08 × ( 1 − B F ) × ( T r o o m − T a d p ) \text{CFM}_{sa} = \frac{q_{s,room}}{1.08 \times (1 - BF) \times (T_{room} - T_{adp})} CFM s a = 1.08 × ( 1 − BF ) × ( T roo m − T a d p ) q s , roo m
- 4. Step-by-Step Worked Example: Full SHR, ADP, and Airflow Sizing
- Problem Statement
A conditioned space has a design sensible cooling load of q s , r o o m = 194 , 400 Btu/hr q_{s,room} = 194,400\text{ Btu/hr} q s , roo m = 194 , 400 Btu/hr and a latent cooling load of q l , r o o m = 64 , 800 Btu/hr q_{l,room} = 64,800\text{ Btu/hr} q l , roo m = 64 , 800 Btu/hr .
Indoor Room Design Condition: T r o o m = 75.0 ∘ F T_{room} = 75.0^\circ\text{F} T roo m = 75. 0 ∘ F DB, 50 % RH 50\%\text{ RH} 50% RH ( W r o o m = 0.00925 lb/lb W_{room} = 0.00925\text{ lb/lb} W roo m = 0.00925 lb/lb )
Outdoor Ventilation Air: 2 , 000 CFM 2,000\text{ CFM} 2 , 000 CFM at 95.0 ∘ F 95.0^\circ\text{F} 95. 0 ∘ F DB, 78.0 ∘ F 78.0^\circ\text{F} 78. 0 ∘ F WB ( W o a = 0.0168 lb/lb W_{oa} = 0.0168\text{ lb/lb} W o a = 0.0168 lb/lb )
Selected Chilled Water Coil: Bypass Factor B F = 0.10 BF = 0.10 BF = 0.10
Calculate:
- Room Sensible Heat Ratio (RSHR)
- Grand Sensible Heat Ratio (GSHR)
Apparatus Dew Point ( A D P ADP A D P ) temperature from psychrometric alignment (RCL intersection with saturation curve yields T a d p = 51.0 ∘ F T_{adp} = 51.0^\circ\text{F} T a d p = 51. 0 ∘ F )
- Leaving coil air temperature ( T l e a v i n g T_{leaving} T l e a v in g )
- Required supply airflow rate ( CFM s a \text{CFM}_{sa} CFM s a )
- Solution Steps
Step 1: Calculate Room Sensible Heat Ratio (RSHR) RSHR = q s , r o o m q s , r o o m + q l , r o o m = 194 , 400 194 , 400 + 64 , 800 = 194 , 400 259 , 200 = 0.750 \text{RSHR} = \frac{q_{s,room}}{q_{s,room} + q_{l,room}} = \frac{194,400}{194,400 + 64,800} = \frac{194,400}{259,200} = 0.750 RSHR = q s , roo m + q l , roo m q s , roo m = 194 , 400 + 64 , 800 194 , 400 = 259 , 200 194 , 400 = 0.750
Step 2: Calculate Ventilation Loads and GSHR q s , v e n t = 1.08 × CFM o a × ( T o a − T r o o m ) = 1.08 × 2 , 000 × ( 95.0 − 75.0 ) = 2 , 160 × 20.0 = 43 , 200 Btu/hr q_{s,vent} = 1.08 \times \text{CFM}_{oa} \times (T_{oa} - T_{room}) = 1.08 \times 2,000 \times (95.0 - 75.0) = 2,160 \times 20.0 = 43,200\text{ Btu/hr} q s , v e n t = 1.08 × CFM o a × ( T o a − T roo m ) = 1.08 × 2 , 000 × ( 95.0 − 75.0 ) = 2 , 160 × 20.0 = 43 , 200 Btu/hr q l , v e n t = 4840 × CFM o a × ( W o a − W r o o m ) = 4840 × 2 , 000 × ( 0.0168 − 0.00925 ) = 9 , 680 , 000 × 0.00755 = 73 , 084 Btu/hr q_{l,vent} = 4840 \times \text{CFM}_{oa} \times (W_{oa} - W_{room}) = 4840 \times 2,000 \times (0.0168 - 0.00925) = 9,680,000 \times 0.00755 = 73,084\text{ Btu/hr} q l , v e n t = 4840 × CFM o a × ( W o a − W roo m ) = 4840 × 2 , 000 × ( 0.0168 − 0.00925 ) = 9 , 680 , 000 × 0.00755 = 73 , 084 Btu/hr q s , t o t a l = q s , r o o m + q s , v e n t = 194 , 400 + 43 , 200 = 237 , 600 Btu/hr q_{s,total} = q_{s,room} + q_{s,vent} = 194,400 + 43,200 = 237,600\text{ Btu/hr} q s , t o t a l = q s , roo m + q s , v e n t = 194 , 400 + 43 , 200 = 237 , 600 Btu/hr q t , t o t a l = ( q s , r o o m + q l , r o o m ) + ( q s , v e n t + q l , v e n t ) = 259 , 200 + 116 , 284 = 375 , 484 Btu/hr q_{t,total} = (q_{s,room} + q_{l,room}) + (q_{s,vent} + q_{l,vent}) = 259,200 + 116,284 = 375,484\text{ Btu/hr} q t , t o t a l = ( q s , roo m + q l , roo m ) + ( q s , v e n t + q l , v e n t ) = 259 , 200 + 116 , 284 = 375 , 484 Btu/hr GSHR = q s , t o t a l q t , t o t a l = 237 , 600 375 , 484 = 0.633 \text{GSHR} = \frac{q_{s,total}}{q_{t,total}} = \frac{237,600}{375,484} = 0.633 GSHR = q t , t o t a l q s , t o t a l = 375 , 484 237 , 600 = 0.633
Step 3: Determine Apparatus Dew Point ( A D P ADP A D P ) Plotting the RSHR line ( 0.75 0.75 0.75 ) through the room state ( 75.0 ∘ F 75.0^\circ\text{F} 75. 0 ∘ F DB, 50 % RH 50\%\text{ RH} 50% RH ) to the saturation curve yields: T a d p = 51.0 ∘ F T_{adp} = 51.0^\circ\text{F} T a d p = 51. 0 ∘ F
Step 4: Calculate Leaving Coil Air Temperature ( T l e a v i n g T_{leaving} T l e a v in g ) T l e a v i n g = T a d p + B F × ( T r o o m − T a d p ) = 51.0 ∘ F + 0.10 × ( 75.0 ∘ F − 51.0 ∘ F ) T_{leaving} = T_{adp} + BF \times (T_{room} - T_{adp}) = 51.0^\circ\text{F} + 0.10 \times (75.0^\circ\text{F} - 51.0^\circ\text{F}) T l e a v in g = T a d p + BF × ( T roo m − T a d p ) = 51. 0 ∘ F + 0.10 × ( 75. 0 ∘ F − 51. 0 ∘ F ) T l e a v i n g = 51.0 + 0.10 ( 24.0 ) = 51.0 + 2.4 = 53.4 ∘ F T_{leaving} = 51.0 + 0.10(24.0) = 51.0 + 2.4 = 53.4^\circ\text{F} T l e a v in g = 51.0 + 0.10 ( 24.0 ) = 51.0 + 2.4 = 53. 4 ∘ F
Step 5: Calculate Required Supply Airflow ( CFM s a \text{CFM}_{sa} CFM s a ) Δ T = T r o o m − T l e a v i n g = 75.0 ∘ F − 53.4 ∘ F = 21.6 ∘ F \Delta T = T_{room} - T_{leaving} = 75.0^\circ\text{F} - 53.4^\circ\text{F} = 21.6^\circ\text{F} Δ T = T roo m − T l e a v in g = 75. 0 ∘ F − 53. 4 ∘ F = 21. 6 ∘ F CFM s a = q s , r o o m 1.08 × Δ T = 194 , 400 1.08 × 21.6 = 194 , 400 23.328 = 8 , 333 CFM \text{CFM}_{sa} = \frac{q_{s,room}}{1.08 \times \Delta T} = \frac{194,400}{1.08 \times 21.6} = \frac{194,400}{23.328} = 8,333\text{ CFM} CFM s a = 1.08 × Δ T q s , roo m = 1.08 × 21.6 194 , 400 = 23.328 194 , 400 = 8 , 333 CFM
(Verification via direct formula: CFM = 194 , 400 1.08 × ( 1 − 0.10 ) × ( 75 − 51 ) = 194 , 400 1.08 × 0.90 × 24 = 194 , 400 23.328 = 8 , 333 CFM \text{CFM} = \frac{194,400}{1.08 \times (1 - 0.10) \times (75 - 51)} = \frac{194,400}{1.08 \times 0.90 \times 24} = \frac{194,400}{23.328} = 8,333\text{ CFM} CFM = 1.08 × ( 1 − 0.10 ) × ( 75 − 51 ) 194 , 400 = 1.08 × 0.90 × 24 194 , 400 = 23.328 194 , 400 = 8 , 333 CFM ).