Study guide

7.5 Absorption Refrigeration Cycles: Water-Lithium Bromide & Ammonia-Water Systems

PE Mechanical: HVAC and Refrigeration Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Overview, Reference Handbook & Engineering Foundations

1.1 NCEES Exam Specification, CBT Delivery & Reference Handbook Strategy 1.2 Engineering Units, Dimensional Analysis & Physical Property Lookups 1.3 Engineering Economics, Life Cycle Cost Analysis & Equipment Financial Evaluation 1.4 Electrical Foundations, Motor Ratings & Variable Frequency Drives (VFDs)

2 Chapter 2: Thermodynamics & Energy Balances

2.1 First and Second Laws of Thermodynamics & Open/Closed System Energy Balances 2.2 Thermodynamic Cycles: Carnot, Rankine, Brayton & Reversed Carnot Limit 2.3 Gas & Vapor Property Evaluation: Steam Tables, Superheat & Subcooling 2.4 Mass, Energy & Combustion Balances for HVAC Equipment

3 Chapter 3: Psychrometrics, Moist Air Processes & Humidity Equipment

3.1 Psychrometric Properties: DBT, WBT, DPT, RH, Humidity Ratio & Enthalpy 3.2 Chart Reading & Psychrometric Equations at Sea Level vs. Altitude (5,000 ft) 3.3 Basic Psychrometric Processes: Sensible Heating/Cooling, Humidification & Dehumidification 3.4 Mixed Air Calculations & Complex Air Conditioning Cycles (Preheat, Reheat & Bypass) 3.5 Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP) & Coil Bypass Factor 3.6 Humidification & Dehumidification Equipment: Steam, Adiabatic, Desiccant & Low-Temperature Processes

4 Chapter 4: Heat Transfer Principles & Sizing

4.1 Steady-State Conduction & Multilayer Thermal Resistance (R-Value & U-Factor) 4.2 Convective Heat Transfer & Forced/Natural Convection Coefficients 4.3 Radiation Heat Transfer, Surface Emissivity & View Factors 4.4 Overall Heat Transfer Coefficients, Fouling Factors & Transient/Thermal Mass Effects 4.5 Heat Exchanger Analysis: Log Mean Temperature Difference (LMTD) & Effectiveness-NTU (ε-NTU)

5 Chapter 5: Fluid Mechanics & Hydraulic Fundamentals

5.1 Fluid Statics, Incompressible Continuity & Bernoulli Energy Equation 5.2 Pipe Friction, Moody Diagram & Darcy-Weisbach / Hazen-Williams Calculations 5.3 Minor Losses: Equivalent Length, Loss Coefficients (K-factors) & Total System Head 5.4 Pump Sizing, Net Positive Suction Head (NPSHa vs NPSHr) & Cavitation Prevention 5.5 Affinity Laws & Parallel/Series Pump/Fan System Curves

6 Chapter 6: Heating & Cooling Load Calculations

6.1 Outdoor & Indoor Design Conditions (ASHRAE Fundamentals, Climatic Data & Indoor Setpoints) 6.2 Envelope Heat Transmission & Infiltration/Exfiltration Load Methods 6.3 Solar Heat Gain (SHGC), Fenestration & Cooling Load Temperature Difference / Radiant Time Series (CLTD/RTS) 6.4 Internal Heat Gains: Lighting, People, Equipment & Diversity Factors 6.5 Ventilation Loads & Sensible / Latent / Total Cooling Load Synthesis

7 Chapter 7: Refrigeration Principles, Cycles & Cold Storage Applications

7.1 Standard Vapor-Compression Refrigeration Cycle on P-h & T-s Diagrams 7.2 Refrigeration Cycle Performance Metrics: COP, EER, SEER, kW/ton & Ton of Refrigeration 7.3 Cycle Enhancements: Subcooling, Superheating, Liquid-Suction Heat Exchangers & Economizers 7.4 Multi-Stage & Cascade Refrigeration Systems: Intercooling & Flash Gas Removal 7.5 Absorption Refrigeration Cycles: Water-Lithium Bromide & Ammonia-Water Systems 7.6 Food Processing & Cold Storage Refrigeration: Product Load, Pull-Down & Storage Design

8 Chapter 8: Refrigerants, Environmental Regulations & Safety

8.1 Refrigerant Classifications, Nomenclature & Thermodynamic Properties (ASHRAE Standard 34) 8.2 AIM Act, EPA Technology Transitions Sector GWP Limits & Low-GWP Refrigerants (R-32, R-454B) 8.3 Refrigerant Safety Requirements & Machinery Room Design (ASHRAE Standard 15) 8.4 Refrigerant Piping Sizing, Oil Return, Traps & Double Risers

9 Chapter 9: HVAC Equipment & Primary Machinery

9.1 Compressors: Reciprocating, Rotary, Scroll, Screw & Centrifugal 9.2 Condensers: Air-Cooled, Water-Cooled & Evaporative Condensers 9.3 Evaporators & Direct Expansion (DX) vs Liquid Chilling Coils 9.4 Water Chillers: Centrifugal, Screw & Scroll with ASHRAE 90.1 Path A/B IPLV Ratings 9.5 Cooling Towers: Range, Approach, Evaporation, Blowdown & Legionella Control 9.6 Heat Pumps & Variable Refrigerant Flow (VRF): Balance Point, Defrost & Heat Recovery 9.7 Thermal Energy Storage: Full vs. Partial Storage, Chilled Water & Ice Systems

10 Chapter 10: Air-Side Systems & Distribution

10.1 Air Handling Units (AHUs), Dedicated Outdoor Air Systems (DOAS) & Fan-Coil Units 10.2 Duct Design Methodologies: Equal Friction, Static Regain & Velocity Reduction 10.3 Duct Fittings, Dynamic Pressure Losses & SMACNA Construction Standards 10.4 Fan Types, Performance Curves, System Effect Factors & Surge/Stall Dynamics 10.5 Variable Air Volume (VAV) Systems, Terminal Boxes & Space Air Diffusion (ADPI) 10.6 Cooling & Heating Coil Selection: Face Velocity, Rows, Circuiting & Freeze Protection

11 Chapter 11: Hydronic, Steam & Fuel Distribution and Heating Plant

11.1 Hydronic System Architectures: Primary-Only, Primary-Secondary & Variable Primary Flow (VPF) 11.2 Hydronic Pipe Sizing, Velocity Limits & Closed/Open Expansion Tank Sizing 11.3 Control Valves: 2-Way vs 3-Way, Valve Authority (N), Cv Calculations & Characteristic Curves 11.4 Boilers & Heating Hot Water Systems: Condensing vs Non-Condensing & Water Treatment 11.5 Furnaces & Gas-Fired Heating Equipment: AFUE, Temperature Rise, Combustion Air & Vent Categories 11.6 Steam & Condensate Distribution: Latent Heat, Trap Selection, Flash Steam & Stall 11.7 Fuel Gas & Fuel Oil Piping: Demand, Sizing Method, Pressure Drop & Storage Systems

12 Chapter 12: HVAC Control Concepts, Sensors & Sequences

12.1 Sensors, Actuators & Dampers: Selection, Placement, Fail-Safe Position & Damper Authority 12.2 Control Loops: Proportional Offset, PID Action, Reset Strategies & Standard Sequences

13 Chapter 13: Building Energy, Ventilation & Indoor Environmental Quality Codes

13.1 ASHRAE Standard 62.1: Ventilation Rate Procedure (VRP), Indoor Air Quality Procedure & DCV 13.2 ASHRAE Standard 90.1: Building Energy Envelope, Mechanical Efficiency & Economizer Mandates 13.3 ASHRAE Standard 55: Thermal Environmental Conditions, PMV/PPD & Adaptive Comfort Models 13.4 Energy Recovery Systems: Enthalpy Wheels, Fixed-Plate Exchangers, Heat Pipes & Runaround Loops

14 Chapter 14: Supportive Engineering Knowledge, Life Safety & Operations

14.1 Air Filtration Standards: MERV Ratings (ASHRAE 52.2), HEPA & Gas-Phase Adsorption 14.2 Life Safety Systems: Fire/Smoke Dampers, Stairwell Pressurization (NFPA 92) & Smoke Control (NFPA 90A) 14.3 Acoustical Control & Vibration Isolation in HVAC Systems (NC / RC Criteria)

7.5 Absorption Refrigeration Cycles: Water-Lithium Bromide & Ammonia-Water Systems

Key Takeaways Explain This Topic AI

Absorption refrigeration replaces the mechanical compressor with a thermal compressor comprising an absorber, solution pump, generator (desorber), and solution heat exchanger (SHX), utilizing low-grade thermal energy (steam, hot water, waste heat, direct firing) as the primary driving source.

Mechanical pump work is thermodynamically negligible (< 1% to 2% of total energy input) because liquid solution specific volume is thousands of times smaller than vapor specific volume ( w pump = ∫ v d P ≪ w vapor comp w_{\text{pump}} = \int v\,dP \ll w_{\text{vapor comp}} w pump ​ = ∫ v d P ≪ w vapor comp ​ ).

Water-Lithium Bromide ( H 2 O − LiBr \text{H}_2\text{O}-\text{LiBr} H 2 ​ O − LiBr ) systems operate under deep vacuum for air conditioning and chilled water production above 32°F (0°C); salt crystallization occurs if solution concentration exceeds solubility limits (typically > 65% to 68% mass fraction).

Ammonia-Water ( NH 3 − H 2 O \text{NH}_3-\text{H}_2\text{O} NH 3 ​ − H 2 ​ O ) systems operate at elevated positive pressures for industrial low-temperature refrigeration below freezing, requiring a distillation/rectification column downstream of the generator to remove residual water vapor from the ammonia stream.

Single-effect absorption chillers achieve thermal COP thermal ≈ 0.65 to 0.75 \text{COP}_{\text{thermal}} \approx 0.65 \text{ to } 0.75 COP thermal ​ ≈ 0.65 to 0.75 , while double-effect chillers achieve COP thermal ≈ 1.1 to 1.3 \text{COP}_{\text{thermal}} \approx 1.1 \text{ to } 1.3 COP thermal ​ ≈ 1.1 to 1.3 ; both reject roughly 80% to 100% more heat per ton to cooling towers than electric vapor-compression machines.

Last updated: August 2026

7.5 Absorption Refrigeration Cycles: Water-Lithium Bromide & Ammonia-Water Systems

Absorption refrigeration cycles produce cooling through thermal sorption rather than mechanical vapor compression. By substituting the electric motor and compressor with a thermal compressor —composed of an absorber, liquid solution pump, generator (desorber), and solution heat exchanger—absorption chillers utilize low-grade thermal energy such as district steam, engine jacket hot water, industrial waste heat, or direct natural gas firing. On the PE Mechanical exam, understanding the thermodynamic distinctions between Water-Lithium Bromide ( H 2 O − LiBr \text{H}_2\text{O}-\text{LiBr} H 2 ​ O − LiBr ) and Ammonia-Water ( NH 3 − H 2 O \text{NH}_3-\text{H}_2\text{O} NH 3 ​ − H 2 ​ O ) systems, solution concentration balances, crystallization limits, and heat rejection multipliers is critical.

1. Fundamental Principle of the Thermal Compressor

In a mechanical vapor-compression cycle, compressing low-pressure vapor to high pressure consumes substantial mechanical shaft work because the specific volume of gas is enormous ( w = ∫ v d P w = \int v\,dP w = ∫ v d P ). The absorption cycle bypasses this work penalty by absorbing low-pressure vapor into a liquid solvent and pumping the resulting liquid solution to high pressure. +-----------------------------------------------------------------------------------------+

  • | THERMAL COMPRESSOR VS. MECHANICAL COMPRESSOR COMPARISON |
  • +-----------------------------------------------------------------------------------------+
  • | Mechanical Compression: Low-P Vapor ---> [ ELECTRIC COMPRESSOR ] ---> High-P Vapor |
  • | (Consumes massive shaft work: w = int v_vapor * dP) |
  • | |
  • | Thermal Compression: Low-P Vapor ---> [ Absorber ] (Refrigerant absorbed in liquid) |
  • | | |
  • | v |
  • | [ Solution Pump ] (Negligible work: v_liquid) |
  • | | |
  • | v |
  • | High-P Vapor <--- [ Generator ] <-- Thermal Heat Input (Q_gen) |
  • +-----------------------------------------------------------------------------------------+

Because liquid specific volume is roughly 1 / 1 , 000 th 1/1,000\text{th} 1/1 , 000 th that of refrigerant vapor ( v liquid ≪ v vapor v_{\text{liquid}} \ll v_{\text{vapor}} v liquid ​ ≪ v vapor ​ ), the mechanical pump work accounts for less than 1% to 2% of total cycle energy input. The primary driving potential is thermal energy ( Q ˙ gen \dot{Q}_{\text{gen}} Q ˙ ​ gen ​ ) supplied to the generator.

2. The Two Dominant Working Fluid Pairs

Industrial and commercial absorption systems rely on two primary refrigerant-absorbent fluid pairs: +-----------------------------------------------------------------------------------------+

  • | ABSORPTION FLUID PAIRS CLASSIFICATION & CHARACTERISTICS |
  • +-----------------------------------------------------------------------------------------+
  • | 1. WATER - LITHIUM BROMIDE (H2O - LiBr): |
  • | - Refrigerant: Water (H2O) | Absorbent: Lithium Bromide Salt (LiBr) |
  • | - Application: Commercial HVAC Chilled Water (40°F to 45°F / 4.4°C to 7.2°C) |
  • | - Pressure: Deep Vacuum (Evaporator ~0.12 psia / Condenser ~1.0 psia) |
  • | - Minimum Evap Temp: > 32°F (0°C) -> Water freezes at 32°F! |
  • | - Critical Hazard: Salt Crystallization at high concentration / low temperature |
  • | |
  • | 2. AMMONIA - WATER (NH3 - H2O): |
  • | - Refrigerant: Ammonia (NH3) | Absorbent: Water (H2O) |
  • | - Application: Sub-freezing Industrial Cold Storage & Blast Freezing (-40°F to 20°F) |
  • | - Pressure: High Positive Pressure (Evaporator ~20-30 psig / Condenser ~150-250 psig)|
  • | - Critical Requirement: Distillation / Rectification Column to purify ammonia vapor |
  • +-----------------------------------------------------------------------------------------+
  • Detailed Analysis: Water-Lithium Bromide ( H 2 O − LiBr \text{H}_2\text{O}-\text{LiBr} H 2 ​ O − LiBr )

Deep Vacuum Operation: Because water is the refrigerant, the system operates at sub-atmospheric pressures. At an evaporating temperature of 40 ∘ F 40^\circ\text{F} 4 0 ∘ F , water saturation pressure is only P evap = 0.1217 psia = 6.3 mmHg = 0.84 kPa P_{\text{evap}} = 0.1217\text{ psia} = 6.3\text{ mmHg} = 0.84\text{ kPa} P evap ​ = 0.1217 psia = 6.3 mmHg = 0.84 kPa . At a condensing temperature of 104 ∘ F 104^\circ\text{F} 10 4 ∘ F , P cond = 1.07 psia = 55.3 mmHg = 7.38 kPa P_{\text{cond}} = 1.07\text{ psia} = 55.3\text{ mmHg} = 7.38\text{ kPa} P cond ​ = 1.07 psia = 55.3 mmHg = 7.38 kPa . The entire machine is a hermetically sealed vacuum vessel; non-condensable gas purge units are essential.

Crystallization Phenomenon: Lithium bromide is a solid salt dissolved in water. On a Dühring equilibrium diagram, if the solution mass fraction ( x = m salt / ( m salt + m water ) x = m_{\text{salt}} / (m_{\text{salt}} + m_{\text{water}}) x = m salt ​ / ( m salt ​ + m water ​ ) ) exceeds the solubility limit (typically 65 % to 68 % LiBr 65\%\text{ to }68\%\text{ LiBr} 65% to 68% LiBr by mass ) or if the solution is overcooled in the Solution Heat Exchanger (SHX), solid salt crystals precipitate out, completely plugging the piping and heat exchanger tubes. Systems incorporate automatic dilution cycles and J-tube overflow bypasses to dissolve crystals.

Detailed Analysis: Ammonia-Water ( NH 3 − H 2 O \text{NH}_3-\text{H}_2\text{O} NH 3 ​ − H 2 ​ O )

Sub-Freezing Capability: Because ammonia freezes at − 108 ∘ F -108^\circ\text{F} − 10 8 ∘ F ( − 77.7 ∘ C -77.7^\circ\text{C} − 77. 7 ∘ C ), it can operate at low industrial evaporating temperatures ( − 40 ∘ F -40^\circ\text{F} − 4 0 ∘ F to 10 ∘ F 10^\circ\text{F} 1 0 ∘ F ).

The Distillation/Rectification Column: Both ammonia and water are volatile liquids (unlike non-volatile LiBr salt). When the generator boils the strong solution, the resulting vapor contains approximately 90 % to 95 % ammonia 90\%\text{ to }95\%\text{ ammonia} 90% to 95% ammonia and 5 % to 10 % water vapor 5\%\text{ to }10\%\text{ water vapor} 5% to 10% water vapor . If water vapor enters the condenser and evaporator, it raises the boiling temperature and causes water accumulation (water logging) in the evaporator. A vertical fractionating column (analyzer and rectifier) is installed above the generator to condense out residual water vapor, ensuring 99.5 % + pure ammonia vapor 99.5\%+\text{ pure ammonia vapor} 99.5% + pure ammonia vapor enters the condenser.

3. The Single-Effect Absorption Cycle Architecture

A complete single-effect absorption cycle consists of two interconnected circulation loops: the Refrigerant Loop and the Solution Loop . +-----------------------------------------------------------------------------------------+

  • | COMPLETE SINGLE-EFFECT ABSORPTION CHILLER CYCLE (H2O - LiBr) |
  • +-----------------------------------------------------------------------------------------+
  • | GENERATOR (DESORBER) |
  • | +-------------------------------------+ |
  • | Heat Input: Q_gen ---> | Strong solution boiled by steam/gas | ---> Refrigerant Vapor |
  • | +-------------------------------------+ (State 7: High-P) |
  • | | ^ | |
  • | Strong Sol'n | | Weak Sol'n v |
  • | (Conc. LiBr) | | (Dilute LiBr) [ CONDENSER ] |
  • | State 4 v | State 3 (Rejects Q_c) |
  • | +-------------------------------------+ | |
  • | | SOLUTION HEAT EXCHANGER (SHX) | | State 8 |
  • | | (Preheats weak sol / cools strong) | v |
  • | +-------------------------------------+ [ EXP VALVE ] |
  • | | ^ | |
  • | v | v State 9 |
  • | [ Sol'n Exp ] [ Sol'n Pump ] [ EVAPORATOR ] |
  • | | (Work: W_pump ~ 0)| (Chills Water: |
  • | v | | Q_evap) |
  • | +-------------------------------------+ | |
  • | | ABSORBER | <------------+ |
  • | | (Absorbs vapor, rejects Q_absorber) | Low-P Vapor (State 1)|
  • | +-------------------------------------+ |
  • +-----------------------------------------------------------------------------------------+
  • The Solution Heat Exchanger (SHX)

The counter-flow Solution Heat Exchanger preheats the cool, dilute (weak) solution traveling from the absorber to the generator while precooling the hot, concentrated (strong) solution returning from the generator to the absorber. This delivers a dual energy benefit:

Reduces required thermal heat input ( Q ˙ gen \dot{Q}_{\text{gen}} Q ˙ ​ gen ​ ) at the generator.

Reduces required heat rejection ( Q ˙ abs \dot{Q}_{\text{abs}} Q ˙ ​ abs ​ ) at the absorber, improving overall cycle COP by up to 50% .

4. Single-Effect vs. Double-Effect Absorption Chillers

Classification Heat Source Temperature Thermal COP Range ( COP thermal \text{COP}_{\text{thermal}} COP thermal ​ ) Heat Rejection to Cooling Tower

Single-Effect Low-pressure steam ( 10 − 15 psig 10-15\text{ psig} 10 − 15 psig ) or hot water ( 180 ∘ F − 210 ∘ F 180^\circ\text{F}-210^\circ\text{F} 18 0 ∘ F − 21 0 ∘ F ) 0.65 to 0.75 0.65\text{ to }0.75 0.65 to 0.75 ≈ 2.3 to 2.6 Tons HR / Ton Cooling \approx 2.3\text{ to }2.6\text{ Tons HR / Ton Cooling} ≈ 2.3 to 2.6 Tons HR / Ton Cooling

Double-Effect High-pressure steam ( 100 − 120 psig 100-120\text{ psig} 100 − 120 psig ) or direct natural gas burner ( 320 ∘ F − 360 ∘ F 320^\circ\text{F}-360^\circ\text{F} 32 0 ∘ F − 36 0 ∘ F ) 1.10 to 1.35 1.10\text{ to }1.35 1.10 to 1.35 ≈ 1.7 to 1.9 Tons HR / Ton Cooling \approx 1.7\text{ to }1.9\text{ Tons HR / Ton Cooling} ≈ 1.7 to 1.9 Tons HR / Ton Cooling

Electric Centrifugal Electric motor 5.50 to 7.00 5.50\text{ to }7.00 5.50 to 7.00 (Electric COP \text{COP} COP ) ≈ 1.15 to 1.25 Tons HR / Ton Cooling \approx 1.15\text{ to }1.25\text{ Tons HR / Ton Cooling} ≈ 1.15 to 1.25 Tons HR / Ton Cooling

The Double-Effect Cycle Principle

A double-effect absorption chiller features two generators in series: a High-Temperature Generator (HTG) and a Low-Temperature Generator (LTG) . High-temperature heat drives the HTG, boiling off high-pressure refrigerant vapor. Instead of routing this vapor directly to the condenser, it is routed through condensing tubes inside the LTG, where its latent heat of condensation boils off a second batch of refrigerant vapor from intermediate solution. This reuses the thermal energy twice , nearly doubling thermal COP from 0.70 0.70 0.70 to 1.25 1.25 1.25 .

5. Thermodynamic Equations & Mass/Concentration Balances

1. Thermal Coefficient of Performance ( COP thermal \text{COP}_{\text{thermal}} COP thermal ​ ) COP thermal = Q ˙ evap Q ˙ gen + W ˙ pump ≈ Q ˙ evap Q ˙ gen \text{COP}_{\text{thermal}} = \frac{\dot{Q}_{\text{evap}}}{\dot{Q}_{\text{gen}} + \dot{W}_{\text{pump}}} \approx \frac{\dot{Q}_{\text{evap}}}{\dot{Q}_{\text{gen}}} COP thermal ​ = Q ˙ ​ gen ​ + W ˙ pump ​ Q ˙ ​ evap ​ ​ ≈ Q ˙ ​ gen ​ Q ˙ ​ evap ​ ​

2. Maximum Theoretical Carnot Absorption COP

An absorption cycle can be conceptualized as a reversible Carnot heat engine driving a reversible Carnot refrigerator between three temperature levels: generator heat source ( T gen T_{\text{gen}} T gen ​ ), ambient heat rejection sink ( T 0 = T absorber = T condenser T_0 = T_{\text{absorber}} = T_{\text{condenser}} T 0 ​ = T absorber ​ = T condenser ​ ), and refrigerated load ( T evap T_{\text{evap}} T evap ​ ). All temperatures in Rankine ( ∘ R {}^\circ\text{R} ∘ R ) or Kelvin ( K \text{K} K ): COP Carnot, abs = η Carnot, engine × COP Carnot, refrig = ( T gen − T 0 T gen ) × ( T evap T 0 − T evap ) \mathbf{\text{COP}_{\text{Carnot, abs}} = \eta_{\text{Carnot, engine}} \times \text{COP}_{\text{Carnot, refrig}} = \left( \frac{T_{\text{gen}} - T_0}{T_{\text{gen}}} \right) \times \left( \frac{T_{\text{evap}}}{T_0 - T_{\text{evap}}} \right)} COP Carnot, abs ​ = η Carnot, engine ​ × COP Carnot, refrig ​ = ( T gen ​ T gen ​ − T 0 ​ ​ ) × ( T 0 ​ − T evap ​ T evap ​ ​ )

3. Mass & Solute (LiBr) Conservation Equations

Let m ˙ w \dot{m}_w m ˙ w ​ be weak solution mass flow rate, m ˙ s \dot{m}_s m ˙ s ​ be strong solution mass flow rate, and m ˙ r \dot{m}_r m ˙ r ​ be pure refrigerant mass flow rate:

Total Mass Balance: m ˙ w = m ˙ s + m ˙ r \dot{m}_w = \dot{m}_s + \dot{m}_r m ˙ w ​ = m ˙ s ​ + m ˙ r ​

Solute (LiBr Salt) Conservation Balance: m ˙ w ⋅ x w = m ˙ s ⋅ x s \dot{m}_w \cdot x_w = \dot{m}_s \cdot x_s m ˙ w ​ ⋅ x w ​ = m ˙ s ​ ⋅ x s ​

Where x w x_w x w ​ is weak solution mass fraction and x s x_s x s ​ is strong solution mass fraction. m ˙ s = m ˙ w − m ˙ r ⟹ m ˙ w x w = ( m ˙ w − m ˙ r ) x s \dot{m}_s = \dot{m}_w - \dot{m}_r \quad \Longrightarrow \quad \dot{m}_w x_w = (\dot{m}_w - \dot{m}_r) x_s m ˙ s ​ = m ˙ w ​ − m ˙ r ​ ⟹ m ˙ w ​ x w ​ = ( m ˙ w ​ − m ˙ r ​ ) x s ​ m ˙ w = m ˙ r ( x s x s − x w ) m ˙ s = m ˙ r ( x w x s − x w ) \mathbf{\dot{m}_w = \dot{m}_r \left( \frac{x_s}{x_s - x_w} \right)} \qquad \mathbf{\dot{m}_s = \dot{m}_r \left( \frac{x_w}{x_s - x_w} \right)} m ˙ w ​ = m ˙ r ​ ( x s ​ − x w ​ x s ​ ​ ) m ˙ s ​ = m ˙ r ​ ( x s ​ − x w ​ x w ​ ​ )

4. Circulation Ratio ( λ \lambda λ )

The ratio of weak solution pumped per unit mass of refrigerant generated: λ = m ˙ w m ˙ r = x s x s − x w \lambda = \frac{\dot{m}_w}{\dot{m}_r} = \frac{x_s}{x_s - x_w} λ = m ˙ r ​ m ˙ w ​ ​ = x s ​ − x w ​ x s ​ ​

5. Cooling Tower Heat Rejection Multiplier

Unlike vapor-compression chillers where heat is rejected only at the condenser, absorption chillers reject heat from both the condenser and the absorber : Q ˙ tower = Q ˙ cond + Q ˙ abs = Q ˙ gen + Q ˙ evap + W ˙ pump ≈ Q ˙ gen + Q ˙ evap \dot{Q}_{\text{tower}} = \dot{Q}_{\text{cond}} + \dot{Q}_{\text{abs}} = \dot{Q}_{\text{gen}} + \dot{Q}_{\text{evap}} + \dot{W}_{\text{pump}} \approx \dot{Q}_{\text{gen}} + \dot{Q}_{\text{evap}} Q ˙ ​ tower ​ = Q ˙ ​ cond ​ + Q ˙ ​ abs ​ = Q ˙ ​ gen ​ + Q ˙ ​ evap ​ + W ˙ pump ​ ≈ Q ˙ ​ gen ​ + Q ˙ ​ evap ​

Exam Sizing Impact: For a single-effect chiller with COP thermal = 0.70 \text{COP}_{\text{thermal}} = 0.70 COP thermal ​ = 0.70 , Q ˙ gen = Q ˙ evap / 0.70 = 1.43 Q ˙ evap \dot{Q}_{\text{gen}} = \dot{Q}_{\text{evap}} / 0.70 = 1.43 \dot{Q}_{\text{evap}} Q ˙ ​ gen ​ = Q ˙ ​ evap ​ /0.70 = 1.43 Q ˙ ​ evap ​ . Total heat rejection to the cooling tower is Q ˙ tower = 1.43 Q ˙ evap + 1.0 Q ˙ evap = 2.43 × Q ˙ evap \dot{Q}_{\text{tower}} = 1.43 \dot{Q}_{\text{evap}} + 1.0 \dot{Q}_{\text{evap}} = \mathbf{2.43 \times \dot{Q}_{\text{evap}}} Q ˙ ​ tower ​ = 1.43 Q ˙ ​ evap ​ + 1.0 Q ˙ ​ evap ​ = 2.43 × Q ˙ ​ evap ​ ( 2.43 Tons of Heat Rejection per Ton of Cooling 2.43\text{ Tons of Heat Rejection per Ton of Cooling} 2.43 Tons of Heat Rejection per Ton of Cooling ). Cooling towers for absorption chillers must be sized roughly twice as large as cooling towers for electric chillers!

6. NCEES Reference Handbook Navigation Tactics

Carnot Absorption COP Formula: Search "Absorption Refrigeration" or "Carnot Absorption" in Section 7 to locate the product equation [ ( T g − T 0 ) / T g ] × [ T e / ( T 0 − T e ) ] [(T_g - T_0)/T_g] \times [T_e / (T_0 - T_e)] [( T g ​ − T 0 ​ ) / T g ​ ] × [ T e ​ / ( T 0 ​ − T e ​ )] .

Mass Balance Formulas: Locate solution mass balance equations m ˙ w x w = m ˙ s x s \dot{m}_w x_w = \dot{m}_s x_s m ˙ w ​ x w ​ = m ˙ s ​ x s ​ and circulation ratio definition λ = x s / ( x s − x w ) \lambda = x_s / (x_s - x_w) λ = x s ​ / ( x s ​ − x w ​ ) .

Dühring Plot Navigation: Read solution equilibrium temperatures and concentration lines from the LiBr − H 2 O \text{LiBr}-\text{H}_2\text{O} LiBr − H 2 ​ O chart.

7. Worked Computational Examples

Example 1: 100-Ton Single-Effect H 2 O − LiBr \text{H}_2\text{O}-\text{LiBr} H 2 ​ O − LiBr Mass & Energy Balance

A single-effect H 2 O − LiBr \text{H}_2\text{O}-\text{LiBr} H 2 ​ O − LiBr absorption chiller provides 100 Tons 100\text{ Tons} 100 Tons of chilled water cooling ( 1 , 200 , 000 Btu/hr 1,200,000\text{ Btu/hr} 1 , 200 , 000 Btu/hr ). The evaporator produces 40 ∘ F 40^\circ\text{F} 4 0 ∘ F saturated vapor ( h v = 1 , 079.3 Btu/lbm h_v = 1,079.3\text{ Btu/lbm} h v ​ = 1 , 079.3 Btu/lbm ) and the condenser produces 100 ∘ F 100^\circ\text{F} 10 0 ∘ F saturated liquid ( h l = 68.0 Btu/lbm h_l = 68.0\text{ Btu/lbm} h l ​ = 68.0 Btu/lbm ).

Weak solution leaving absorber: x w = 58 % LiBr x_w = 58\%\text{ LiBr} x w ​ = 58% LiBr ( 0.58 0.58 0.58 ), enters generator at enthalpy h weak, in = 42.0 Btu/lbm h_{\text{weak, in}} = 42.0\text{ Btu/lbm} h weak, in ​ = 42.0 Btu/lbm

Strong solution leaving generator: x s = 64 % LiBr x_s = 64\%\text{ LiBr} x s ​ = 64% LiBr ( 0.64 0.64 0.64 ), exits at enthalpy h strong, out = 98.0 Btu/lbm h_{\text{strong, out}} = 98.0\text{ Btu/lbm} h strong, out ​ = 98.0 Btu/lbm

Superheated water vapor leaves generator at 180 ∘ F 180^\circ\text{F} 18 0 ∘ F with enthalpy h vapor = 1 , 140.0 Btu/lbm h_{\text{vapor}} = 1,140.0\text{ Btu/lbm} h vapor ​ = 1 , 140.0 Btu/lbm

Calculate: (a) Refrigerant water mass flow rate ( m ˙ r \dot{m}_r m ˙ r ​ ), (b) Circulation ratio ( λ \lambda λ ) and solution flow rates ( m ˙ w , m ˙ s \dot{m}_w, \dot{m}_s m ˙ w ​ , m ˙ s ​ ), (c) Generator thermal heat input ( Q ˙ gen \dot{Q}_{\text{gen}} Q ˙ ​ gen ​ ), (d) Thermal COP thermal \text{COP}_{\text{thermal}} COP thermal ​ , and (e) Total heat rejection rate to the cooling tower.

Solution:

Refrigerant Mass Flow Rate ( m ˙ r \dot{m}_r m ˙ r ​ ): q evap = h v − h l = 1 , 079.3 − 68.0 = 1 , 011.3 Btu/lbm q_{\text{evap}} = h_v - h_l = 1,079.3 - 68.0 = 1,011.3\text{ Btu/lbm} q evap ​ = h v ​ − h l ​ = 1 , 079.3 − 68.0 = 1 , 011.3 Btu/lbm m ˙ r = Q ˙ evap q evap = 1 , 200 , 000 Btu/hr 1 , 011.3 Btu/lbm = 1 , 186.60 lbm/hr \dot{m}_r = \frac{\dot{Q}_{\text{evap}}}{q_{\text{evap}}} = \frac{1,200,000\text{ Btu/hr}}{1,011.3\text{ Btu/lbm}} = \mathbf{1,186.60\text{ lbm/hr}} m ˙ r ​ = q evap ​ Q ˙ ​ evap ​ ​ = 1 , 011.3 Btu/lbm 1 , 200 , 000 Btu/hr ​ = 1 , 186.60 lbm/hr

Circulation Ratio & Solution Flow Rates: λ = x s x s − x w = 0.64 0.64 − 0.58 = 0.64 0.06 = 10.667 \lambda = \frac{x_s}{x_s - x_w} = \frac{0.64}{0.64 - 0.58} = \frac{0.64}{0.06} = \mathbf{10.667} λ = x s ​ − x w ​ x s ​ ​ = 0.64 − 0.58 0.64 ​ = 0.06 0.64 ​ = 10.667 m ˙ w = λ ⋅ m ˙ r = 10.667 × 1 , 186.60 lbm/hr = 12 , 657.1 lbm/hr \dot{m}_w = \lambda \cdot \dot{m}_r = 10.667 \times 1,186.60\text{ lbm/hr} = \mathbf{12,657.1\text{ lbm/hr}} m ˙ w ​ = λ ⋅ m ˙ r ​ = 10.667 × 1 , 186.60 lbm/hr = 12 , 657.1 lbm/hr m ˙ s = m ˙ w − m ˙ r = 12 , 657.1 − 1 , 186.60 = 11 , 470.5 lbm/hr \dot{m}_s = \dot{m}_w - \dot{m}_r = 12,657.1 - 1,186.60 = \mathbf{11,470.5\text{ lbm/hr}} m ˙ s ​ = m ˙ w ​ − m ˙ r ​ = 12 , 657.1 − 1 , 186.60 = 11 , 470.5 lbm/hr

Generator Heat Input Rate ( Q ˙ gen \dot{Q}_{\text{gen}} Q ˙ ​ gen ​ ): Energy balance around generator: Q ˙ gen = m ˙ r h vapor + m ˙ s h strong, out − m ˙ w h weak, in \dot{Q}_{\text{gen}} = \dot{m}_r h_{\text{vapor}} + \dot{m}_s h_{\text{strong, out}} - \dot{m}_w h_{\text{weak, in}} Q ˙ ​ gen ​ = m ˙ r ​ h vapor ​ + m ˙ s ​ h strong, out ​ − m ˙ w ​ h weak, in ​ Q ˙ gen = ( 1 , 186.60 × 1 , 140.0 ) + ( 11 , 470.5 × 98.0 ) − ( 12 , 657.1 × 42.0 ) \dot{Q}_{\text{gen}} = (1,186.60 \times 1,140.0) + (11,470.5 \times 98.0) - (12,657.1 \times 42.0) Q ˙ ​ gen ​ = ( 1 , 186.60 × 1 , 140.0 ) + ( 11 , 470.5 × 98.0 ) − ( 12 , 657.1 × 42.0 ) Q ˙ gen = 1 , 352 , 724 + 1 , 124 , 109 − 531 , 598 = 1 , 945 , 235 Btu/hr \dot{Q}_{\text{gen}} = 1,352,724 + 1,124,109 - 531,598 = \mathbf{1,945,235\text{ Btu/hr}} Q ˙ ​ gen ​ = 1 , 352 , 724 + 1 , 124 , 109 − 531 , 598 = 1 , 945 , 235 Btu/hr

Thermal COP: COP thermal = Q ˙ evap Q ˙ gen = 1 , 200 , 000 1 , 945 , 235 = 0.6169 ( ≈ 0.62 ) \text{COP}_{\text{thermal}} = \frac{\dot{Q}_{\text{evap}}}{\dot{Q}_{\text{gen}}} = \frac{1,200,000}{1,945,235} = \mathbf{0.6169} \quad (\approx 0.62) COP thermal ​ = Q ˙ ​ gen ​ Q ˙ ​ evap ​ ​ = 1 , 945 , 235 1 , 200 , 000 ​ = 0.6169 ( ≈ 0.62 )

Cooling Tower Heat Rejection: Q ˙ tower = Q ˙ gen + Q ˙ evap = 1 , 945 , 235 + 1 , 200 , 000 = 3 , 145 , 235 Btu/hr \dot{Q}_{\text{tower}} = \dot{Q}_{\text{gen}} + \dot{Q}_{\text{evap}} = 1,945,235 + 1,200,000 = \mathbf{3,145,235\text{ Btu/hr}} Q ˙ ​ tower ​ = Q ˙ ​ gen ​ + Q ˙ ​ evap ​ = 1 , 945 , 235 + 1 , 200 , 000 = 3 , 145 , 235 Btu/hr Tons of Heat Rejection = 3 , 145 , 235 12 , 000 = 262.10 THR ( 2.62 THR / Ton of Cooling ) \text{Tons of Heat Rejection} = \frac{3,145,235}{12,000} = \mathbf{262.10\text{ THR}} \quad (2.62\text{ THR / Ton of Cooling}) Tons of Heat Rejection = 12 , 000 3 , 145 , 235 ​ = 262.10 THR ( 2.62 THR / Ton of Cooling )

Example 2: Carnot Upper Limit for Direct-Fired Double-Effect Chiller

A direct-fired natural gas double-effect absorption chiller operates with a high-temperature generator driving temperature T gen = 340 ∘ F T_{\text{gen}} = 340^\circ\text{F} T gen ​ = 34 0 ∘ F , an evaporating temperature T evap = 40 ∘ F T_{\text{evap}} = 40^\circ\text{F} T evap ​ = 4 0 ∘ F , and an ambient heat rejection temperature (absorber/condenser) T 0 = 95 ∘ F T_0 = 95^\circ\text{F} T 0 ​ = 9 5 ∘ F . The actual machine achieves a thermal COP thermal = 1.22 \text{COP}_{\text{thermal}} = 1.22 COP thermal ​ = 1.22 .

Calculate: (a) The theoretical maximum Carnot absorption COP, and (b) The Second Law efficiency ( η II \eta_{\text{II}} η II ​ ).

Solution:

Convert all temperatures to absolute Rankine: T gen = 340 ∘ F + 459.67 = 799.67 ∘ R T_{\text{gen}} = 340^\circ\text{F} + 459.67 = 799.67^\circ\text{R} T gen ​ = 34 0 ∘ F + 459.67 = 799.6 7 ∘ R T evap = 40 ∘ F + 459.67 = 499.67 ∘ R T_{\text{evap}} = 40^\circ\text{F} + 459.67 = 499.67^\circ\text{R} T evap ​ = 4 0 ∘ F + 459.67 = 499.6 7 ∘ R T 0 = 95 ∘ F + 459.67 = 554.67 ∘ R T_0 = 95^\circ\text{F} + 459.67 = 554.67^\circ\text{R} T 0 ​ = 9 5 ∘ F + 459.67 = 554.6 7 ∘ R

Evaluate Carnot Heat Engine & Refrigeration Terms: η Carnot, engine = T gen − T 0 T gen = 799.67 − 554.67 799.67 = 245.0 799.67 = 0.30638 ( 30.64 % \eta_{\text{Carnot, engine}} = \frac{T_{\text{gen}} - T_0}{T_{\text{gen}}} = \frac{799.67 - 554.67}{799.67} = \frac{245.0}{799.67} = 0.30638 \quad (30.64\% η Carnot, engine ​ = T gen ​ T gen ​ − T 0 ​ ​ = 799.67 799.67 − 554.67 ​ = 799.67 245.0 ​ = 0.30638 ( 30.64% COP Carnot, refrig = T evap T 0 − T evap = 499.67 554.67 − 499.67 = 499.67 55.0 = 9.0849 \text{COP}_{\text{Carnot, refrig}} = \frac{T_{\text{evap}}}{T_0 - T_{\text{evap}}} = \frac{499.67}{554.67 - 499.67} = \frac{499.67}{55.0} = 9.0849 COP Carnot, refrig ​ = T 0 ​ − T evap ​ T evap ​ ​ = 554.67 − 499.67 499.67 ​ = 55.0 499.67 ​ = 9.0849

Carnot Absorption COP: COP Carnot, abs = 0.30638 × 9.0849 = 2.783 \text{COP}_{\text{Carnot, abs}} = 0.30638 \times 9.0849 = \mathbf{2.783} COP Carnot, abs ​ = 0.30638 × 9.0849 = 2.783

Second Law Efficiency: η II = COP actual COP Carnot, abs = 1.22 2.783 = 0.4384 = 43.84 % \eta_{\text{II}} = \frac{\text{COP}_{\text{actual}}}{\text{COP}_{\text{Carnot, abs}}} = \frac{1.22}{2.783} = 0.4384 = \mathbf{43.84\%} η II ​ = COP Carnot, abs ​ COP actual ​ ​ = 2.783 1.22 ​ = 0.4384 = 43.84%