7.2 Refrigeration Cycle Performance Metrics: COP, EER, SEER, kW/ton & Ton of Refrigeration
PE Mechanical: HVAC and Refrigeration Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview, Reference Handbook & Engineering Foundations
1.1 NCEES Exam Specification, CBT Delivery & Reference Handbook Strategy 1.2 Engineering Units, Dimensional Analysis & Physical Property Lookups 1.3 Engineering Economics, Life Cycle Cost Analysis & Equipment Financial Evaluation 1.4 Electrical Foundations, Motor Ratings & Variable Frequency Drives (VFDs)
2 Chapter 2: Thermodynamics & Energy Balances
2.1 First and Second Laws of Thermodynamics & Open/Closed System Energy Balances 2.2 Thermodynamic Cycles: Carnot, Rankine, Brayton & Reversed Carnot Limit 2.3 Gas & Vapor Property Evaluation: Steam Tables, Superheat & Subcooling 2.4 Mass, Energy & Combustion Balances for HVAC Equipment
3 Chapter 3: Psychrometrics, Moist Air Processes & Humidity Equipment
3.1 Psychrometric Properties: DBT, WBT, DPT, RH, Humidity Ratio & Enthalpy 3.2 Chart Reading & Psychrometric Equations at Sea Level vs. Altitude (5,000 ft) 3.3 Basic Psychrometric Processes: Sensible Heating/Cooling, Humidification & Dehumidification 3.4 Mixed Air Calculations & Complex Air Conditioning Cycles (Preheat, Reheat & Bypass) 3.5 Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP) & Coil Bypass Factor 3.6 Humidification & Dehumidification Equipment: Steam, Adiabatic, Desiccant & Low-Temperature Processes
4 Chapter 4: Heat Transfer Principles & Sizing
4.1 Steady-State Conduction & Multilayer Thermal Resistance (R-Value & U-Factor) 4.2 Convective Heat Transfer & Forced/Natural Convection Coefficients 4.3 Radiation Heat Transfer, Surface Emissivity & View Factors 4.4 Overall Heat Transfer Coefficients, Fouling Factors & Transient/Thermal Mass Effects 4.5 Heat Exchanger Analysis: Log Mean Temperature Difference (LMTD) & Effectiveness-NTU (ε-NTU)
5 Chapter 5: Fluid Mechanics & Hydraulic Fundamentals
5.1 Fluid Statics, Incompressible Continuity & Bernoulli Energy Equation 5.2 Pipe Friction, Moody Diagram & Darcy-Weisbach / Hazen-Williams Calculations 5.3 Minor Losses: Equivalent Length, Loss Coefficients (K-factors) & Total System Head 5.4 Pump Sizing, Net Positive Suction Head (NPSHa vs NPSHr) & Cavitation Prevention 5.5 Affinity Laws & Parallel/Series Pump/Fan System Curves
6 Chapter 6: Heating & Cooling Load Calculations
6.1 Outdoor & Indoor Design Conditions (ASHRAE Fundamentals, Climatic Data & Indoor Setpoints) 6.2 Envelope Heat Transmission & Infiltration/Exfiltration Load Methods 6.3 Solar Heat Gain (SHGC), Fenestration & Cooling Load Temperature Difference / Radiant Time Series (CLTD/RTS) 6.4 Internal Heat Gains: Lighting, People, Equipment & Diversity Factors 6.5 Ventilation Loads & Sensible / Latent / Total Cooling Load Synthesis
7 Chapter 7: Refrigeration Principles, Cycles & Cold Storage Applications
7.1 Standard Vapor-Compression Refrigeration Cycle on P-h & T-s Diagrams 7.2 Refrigeration Cycle Performance Metrics: COP, EER, SEER, kW/ton & Ton of Refrigeration 7.3 Cycle Enhancements: Subcooling, Superheating, Liquid-Suction Heat Exchangers & Economizers 7.4 Multi-Stage & Cascade Refrigeration Systems: Intercooling & Flash Gas Removal 7.5 Absorption Refrigeration Cycles: Water-Lithium Bromide & Ammonia-Water Systems 7.6 Food Processing & Cold Storage Refrigeration: Product Load, Pull-Down & Storage Design
8 Chapter 8: Refrigerants, Environmental Regulations & Safety
8.1 Refrigerant Classifications, Nomenclature & Thermodynamic Properties (ASHRAE Standard 34) 8.2 AIM Act, EPA Technology Transitions Sector GWP Limits & Low-GWP Refrigerants (R-32, R-454B) 8.3 Refrigerant Safety Requirements & Machinery Room Design (ASHRAE Standard 15) 8.4 Refrigerant Piping Sizing, Oil Return, Traps & Double Risers
9 Chapter 9: HVAC Equipment & Primary Machinery
9.1 Compressors: Reciprocating, Rotary, Scroll, Screw & Centrifugal 9.2 Condensers: Air-Cooled, Water-Cooled & Evaporative Condensers 9.3 Evaporators & Direct Expansion (DX) vs Liquid Chilling Coils 9.4 Water Chillers: Centrifugal, Screw & Scroll with ASHRAE 90.1 Path A/B IPLV Ratings 9.5 Cooling Towers: Range, Approach, Evaporation, Blowdown & Legionella Control 9.6 Heat Pumps & Variable Refrigerant Flow (VRF): Balance Point, Defrost & Heat Recovery 9.7 Thermal Energy Storage: Full vs. Partial Storage, Chilled Water & Ice Systems
10 Chapter 10: Air-Side Systems & Distribution
10.1 Air Handling Units (AHUs), Dedicated Outdoor Air Systems (DOAS) & Fan-Coil Units 10.2 Duct Design Methodologies: Equal Friction, Static Regain & Velocity Reduction 10.3 Duct Fittings, Dynamic Pressure Losses & SMACNA Construction Standards 10.4 Fan Types, Performance Curves, System Effect Factors & Surge/Stall Dynamics 10.5 Variable Air Volume (VAV) Systems, Terminal Boxes & Space Air Diffusion (ADPI) 10.6 Cooling & Heating Coil Selection: Face Velocity, Rows, Circuiting & Freeze Protection
11 Chapter 11: Hydronic, Steam & Fuel Distribution and Heating Plant
11.1 Hydronic System Architectures: Primary-Only, Primary-Secondary & Variable Primary Flow (VPF) 11.2 Hydronic Pipe Sizing, Velocity Limits & Closed/Open Expansion Tank Sizing 11.3 Control Valves: 2-Way vs 3-Way, Valve Authority (N), Cv Calculations & Characteristic Curves 11.4 Boilers & Heating Hot Water Systems: Condensing vs Non-Condensing & Water Treatment 11.5 Furnaces & Gas-Fired Heating Equipment: AFUE, Temperature Rise, Combustion Air & Vent Categories 11.6 Steam & Condensate Distribution: Latent Heat, Trap Selection, Flash Steam & Stall 11.7 Fuel Gas & Fuel Oil Piping: Demand, Sizing Method, Pressure Drop & Storage Systems
12 Chapter 12: HVAC Control Concepts, Sensors & Sequences
12.1 Sensors, Actuators & Dampers: Selection, Placement, Fail-Safe Position & Damper Authority 12.2 Control Loops: Proportional Offset, PID Action, Reset Strategies & Standard Sequences
13 Chapter 13: Building Energy, Ventilation & Indoor Environmental Quality Codes
13.1 ASHRAE Standard 62.1: Ventilation Rate Procedure (VRP), Indoor Air Quality Procedure & DCV 13.2 ASHRAE Standard 90.1: Building Energy Envelope, Mechanical Efficiency & Economizer Mandates 13.3 ASHRAE Standard 55: Thermal Environmental Conditions, PMV/PPD & Adaptive Comfort Models 13.4 Energy Recovery Systems: Enthalpy Wheels, Fixed-Plate Exchangers, Heat Pipes & Runaround Loops
14 Chapter 14: Supportive Engineering Knowledge, Life Safety & Operations
14.1 Air Filtration Standards: MERV Ratings (ASHRAE 52.2), HEPA & Gas-Phase Adsorption 14.2 Life Safety Systems: Fire/Smoke Dampers, Stairwell Pressurization (NFPA 92) & Smoke Control (NFPA 90A) 14.3 Acoustical Control & Vibration Isolation in HVAC Systems (NC / RC Criteria)
7.2 Refrigeration Cycle Performance Metrics: COP, EER, SEER, kW/ton & Ton of Refrigeration
Key Takeaways Explain This Topic AI
One Ton of Refrigeration (TR) is defined as 12,000 Btu/hr = 200 Btu/min = 3.51685 kW = 211.0 kJ/min, representing the latent heat extraction rate required to freeze 2,000 lbm of water at 32°F in 24 hours.
The cooling Coefficient of Performance (COP_R) is the dimensionless ratio of net cooling capacity to net work input (COP_R = Q_cool / W_in), whereas a heat pump's heating COP satisfies COP_HP = COP_R + 1.
Carnot performance defines the theoretical thermodynamic upper limit based on absolute temperatures: C O P R , Carnot = T L / ( T H − T L ) COP_{R,\text{Carnot}} = T_L / (T_H - T_L) CO P R , Carnot = T L / ( T H − T L ) ; the Second Law efficiency η II = COP actual / COP Carnot \eta_{\text{II}} = \text{COP}_{\text{actual}} / \text{COP}_{\text{Carnot}} η II = COP actual / COP Carnot quantifies how closely a real machine approaches thermodynamic perfection.
Industry rating parameters convert seamlessly through exact mathematical equivalencies: EER = 3.41214 × COP R \text{EER} = 3.41214 \times \text{COP}_R EER = 3.41214 × COP R , kW/ton = 12 / EER = 3.51685 / COP R \text{kW/ton} = 12 / \text{EER} = 3.51685 / \text{COP}_R kW/ton = 12/ EER = 3.51685/ COP R , and HSPF = 3.41214 × COP H P , seasonal \text{HSPF} = 3.41214 \times \text{COP}_{HP,\text{seasonal}} HSPF = 3.41214 × COP H P , seasonal .
Chiller part-load performance is rated via AHRI Standard 550/590 Integrated Part-Load Value (IPLV), which applies empirical operating weights: 1% at 100% load, 42% at 75% load, 45% at 50% load, and 12% at 25% load.
Last updated: August 2026
7.2 Refrigeration Cycle Performance Metrics: COP, EER, SEER, kW/ton & Ton of Refrigeration
Evaluating the energy performance of refrigeration, chilled water, and heat pump equipment requires converting between thermodynamic dimensionless ratios, North American engineering units, electrical consumption indices, and seasonal part-load ratings. On the PE Mechanical exam, candidates must fluidly translate between Coefficient of Performance ( COP \text{COP} COP ), Energy Efficiency Ratio ( EER \text{EER} EER ), power per unit capacity ( kW/ton \text{kW/ton} kW/ton ), and seasonal metrics ( SEER \text{SEER} SEER , HSPF \text{HSPF} HSPF ), while benchmarking real machines against the theoretical Carnot limit.
1. The Ton of Refrigeration: Historical Origin & Dimensional Equivalencies
The standard unit of cooling capacity in North American practice is the Ton of Refrigeration (TR) . It originated during the 19th-century ice trade, defined as the steady rate of heat absorption required to freeze (or melt) one short ton ( 2 , 000 lbm 2,000\text{ lbm} 2 , 000 lbm ) of pure water at 32 ∘ F 32^\circ\text{F} 3 2 ∘ F into ice at 32 ∘ F 32^\circ\text{F} 3 2 ∘ F over a 24-hour period.
Mathematical Derivation from Latent Heat of Fusion
The latent heat of fusion of water at atmospheric pressure is h i f = 143.33 Btu/lbm ≈ 144 Btu/lbm h_{if} = 143.33\text{ Btu/lbm} \approx 144\text{ Btu/lbm} h i f = 143.33 Btu/lbm ≈ 144 Btu/lbm : Q total = 2 , 000 lbm × 144 Btu/lbm = 288 , 000 Btu Q_{\text{total}} = 2,000\text{ lbm} \times 144\text{ Btu/lbm} = 288,000\text{ Btu} Q total = 2 , 000 lbm × 144 Btu/lbm = 288 , 000 Btu Rate of Heat Absorption (1 TR) = 288 , 000 Btu 24 hours = 12 , 000 Btu/hr \text{Rate of Heat Absorption (1 TR)} = \frac{288,000\text{ Btu}}{24\text{ hours}} = 12,000\text{ Btu/hr} Rate of Heat Absorption (1 TR) = 24 hours 288 , 000 Btu = 12 , 000 Btu/hr
Primary Dimensional Equivalencies 1 Ton of Refrigeration (TR) = 12 , 000 Btu/hr = 200 Btu/min = 3.51685 kW = 211.0 kJ/min = 3.51685 kJ/s \mathbf{1\text{ Ton of Refrigeration (TR)}} = 12,000\text{ Btu/hr} = 200\text{ Btu/min} = 3.51685\text{ kW} = 211.0\text{ kJ/min} = 3.51685\text{ kJ/s} 1 Ton of Refrigeration (TR) = 12 , 000 Btu/hr = 200 Btu/min = 3.51685 kW = 211.0 kJ/min = 3.51685 kJ/s
2. Coefficient of Performance (COP) & The Theoretical Carnot Limit
The Coefficient of Performance (COP) is the fundamental thermodynamic dimensionless metric representing cycle thermal efficiency.
1. Cooling Mode ( COP R \text{COP}_R COP R )
The ratio of desired cooling effect extracted at the evaporator to the net work input supplied to the compressor: COP R = Cooling Capacity Work Input = Q ˙ L W ˙ in = q evap w comp = h 1 − h 4 h 2 − h 1 \text{COP}_R = \frac{\text{Cooling Capacity}}{\text{Work Input}} = \frac{\dot{Q}_L}{\dot{W}_{\text{in}}} = \frac{q_{\text{evap}}}{w_{\text{comp}}} = \frac{h_1 - h_4}{h_2 - h_1} COP R = Work Input Cooling Capacity = W ˙ in Q ˙ L = w comp q evap = h 2 − h 1 h 1 − h 4
2. Heating Mode / Heat Pump ( COP H P \text{COP}_{HP} COP H P )
In heat pump operation, the desired output is the heat rejected at the condenser to heat the building envelope: COP H P = Heating Output Work Input = Q ˙ H W ˙ in = q cond w comp = h 2 − h 3 h 2 − h 1 \text{COP}_{HP} = \frac{\text{Heating Output}}{\text{Work Input}} = \frac{\dot{Q}_H}{\dot{W}_{\text{in}}} = \frac{q_{\text{cond}}}{w_{\text{comp}}} = \frac{h_2 - h_3}{h_2 - h_1} COP H P = Work Input Heating Output = W ˙ in Q ˙ H = w comp q cond = h 2 − h 1 h 2 − h 3
Since First Law energy conservation dictates Q ˙ H = Q ˙ L + W ˙ in \dot{Q}_H = \dot{Q}_L + \dot{W}_{\text{in}} Q ˙ H = Q ˙ L + W ˙ in : COP H P = Q ˙ L + W ˙ in W ˙ in = Q ˙ L W ˙ in + 1 = COP R + 1 \text{COP}_{HP} = \frac{\dot{Q}_L + \dot{W}_{\text{in}}}{\dot{W}_{\text{in}}} = \frac{\dot{Q}_L}{\dot{W}_{\text{in}}} + 1 = \mathbf{\text{COP}_R + 1} COP H P = W ˙ in Q ˙ L + W ˙ in = W ˙ in Q ˙ L + 1 = COP R + 1
Fundamental Identity: For identical operating temperature limits and component enthalpies, a heat pump's heating COP is always exactly 1.0 greater than its cooling COP ( COP H P = COP R + 1 \text{COP}_{HP} = \text{COP}_R + 1 COP H P = COP R + 1 ). +-----------------------------------------------------------------------------------------+
- | FIRST LAW ENERGY BALANCE & COP DUALITY |
- +-----------------------------------------------------------------------------------------+
- | Heat In (Evaporator): Q_L ------> [ REFRIGERATION ] ------> Heat Out (Condenser): Q_H |
- | Work In (Compressor): W_in ------> [ CYCLE ] Q_H = Q_L + W_in |
- | |
- | Cooling COP: COP_R = Q_L / W_in |
- | Heating COP: COP_HP = Q_H / W_in = (Q_L + W_in) / W_in = COP_R + 1 |
- +-----------------------------------------------------------------------------------------+
- 3. Carnot Maximum Theoretical COP
Sadi Carnot established that the maximum possible efficiency between a low-temperature thermal reservoir ( T L T_L T L ) and a high-temperature reservoir ( T H T_H T H ) is achieved by a reversible Carnot cycle. All temperatures MUST be in absolute units ( ∘ R = ∘ F + 459.67 {}^\circ\text{R} = {}^\circ\text{F} + 459.67 ∘ R = ∘ F + 459.67 or K = ∘ C + 273.15 \text{K} = {}^\circ\text{C} + 273.15 K = ∘ C + 273.15 ). COP R , Carnot = T L T H − T L = T evap T cond − T evap \text{COP}_{R,\text{Carnot}} = \frac{T_L}{T_H - T_L} = \frac{T_{\text{evap}}}{T_{\text{cond}} - T_{\text{evap}}} COP R , Carnot = T H − T L T L = T cond − T evap T evap COP H P , Carnot = T H T H − T L = T cond T cond − T evap = COP R , Carnot + 1 \text{COP}_{HP,\text{Carnot}} = \frac{T_H}{T_H - T_L} = \frac{T_{\text{cond}}}{T_{\text{cond}} - T_{\text{evap}}} = \text{COP}_{R,\text{Carnot}} + 1 COP H P , Carnot = T H − T L T H = T cond − T evap T cond = COP R , Carnot + 1
4. Second Law Thermodynamic Efficiency ( η II \eta_{\text{II}} η II )
The Second Law efficiency quantifies the fraction of the theoretical Carnot potential realized by a real machine: η II = COP actual COP Carnot \eta_{\text{II}} = \frac{\text{COP}_{\text{actual}}}{\text{COP}_{\text{Carnot}}} η II = COP Carnot COP actual
3. Commercial & Residential Efficiency Indices (EER, SEER, kW/ton, HSPF)
In HVAC engineering specifications and energy codes (ASHRAE Standard 90.1 / IECC), equipment efficiency is reported in specialized empirical units.
1. Energy Efficiency Ratio (EER)
Defined as the ratio of steady-state cooling capacity in Btu/hr \text{Btu/hr} Btu/hr to total electrical power input in Watts ( W W W ) under standard full-load test conditions (e.g., 95 ∘ F 95^\circ\text{F} 9 5 ∘ F outdoor DB, 80 ∘ F 80^\circ\text{F} 8 0 ∘ F DB / 67 ∘ F 67^\circ\text{F} 6 7 ∘ F WB indoor): EER = Cooling Capacity [Btu/hr] Electrical Power [Watts] = Q ˙ cooling W ˙ Watts \text{EER} = \frac{\text{Cooling Capacity [Btu/hr]}}{\text{Electrical Power [Watts]}} = \frac{\dot{Q}_{\text{cooling}}}{\dot{W}_{\text{Watts}}} EER = Electrical Power [Watts] Cooling Capacity [Btu/hr] = W ˙ Watts Q ˙ cooling
Since 1 Watt = 3.41214 Btu/hr 1\text{ Watt} = 3.41214\text{ Btu/hr} 1 Watt = 3.41214 Btu/hr : EER = 3.41214 × COP R ⟺ COP R = EER 3.41214 = 0.29307 × EER \mathbf{\text{EER} = 3.41214 \times \text{COP}_R} \quad \Longleftrightarrow \quad \text{COP}_R = \frac{\text{EER}}{3.41214} = 0.29307 \times \text{EER} EER = 3.41214 × COP R ⟺ COP R = 3.41214 EER = 0.29307 × EER
2. Specific Power Consumption (kW/ton)
Predominantly used for commercial water-cooled and air-cooled chillers, kW/ton \text{kW/ton} kW/ton expresses the electrical power in kW \text{kW} kW required to produce one Ton of refrigeration: kW/ton = Electrical Input [kW] Cooling Capacity [Tons] = W ˙ kW Tons \text{kW/ton} = \frac{\text{Electrical Input [kW]}}{\text{Cooling Capacity [Tons]}} = \frac{\dot{W}_{\text{kW}}}{\text{Tons}} kW/ton = Cooling Capacity [Tons] Electrical Input [kW] = Tons W ˙ kW
Connecting kW/ton \text{kW/ton} kW/ton to EER \text{EER} EER and COP R \text{COP}_R COP R : kW/ton = 12 EER = 12 3.41214 × COP R = 3.51685 COP R \mathbf{\text{kW/ton} = \frac{12}{\text{EER}} = \frac{12}{3.41214 \times \text{COP}_R} = \frac{3.51685}{\text{COP}_R}} kW/ton = EER 12 = 3.41214 × COP R 12 = COP R 3.51685 COP R = 3.51685 kW/ton ⟺ EER = 12 kW/ton \mathbf{\text{COP}_R = \frac{3.51685}{\text{kW/ton}}} \quad \Longleftrightarrow \quad \mathbf{\text{EER} = \frac{12}{\text{kW/ton}}} COP R = kW/ton 3.51685 ⟺ EER = kW/ton 12
Benchmark Chiller Efficiencies: High-efficiency water-cooled centrifugal chillers typically achieve 0.48 to 0.56 kW/ton 0.48\text{ to }0.56\text{ kW/ton} 0.48 to 0.56 kW/ton ( COP = 6.3 to 7.3 \text{COP} = 6.3\text{ to }7.3 COP = 6.3 to 7.3 ; EER = 21.4 to 25.0 \text{EER} = 21.4\text{ to }25.0 EER = 21.4 to 25.0 ). Air-cooled chillers operate around 0.90 to 1.20 kW/ton 0.90\text{ to }1.20\text{ kW/ton} 0.90 to 1.20 kW/ton ( COP = 2.9 to 3.9 \text{COP} = 2.9\text{ to }3.9 COP = 2.9 to 3.9 ; EER = 10.0 to 13.3 \text{EER} = 10.0\text{ to }13.3 EER = 10.0 to 13.3 ).
3. Seasonal Energy Efficiency Ratio (SEER & SEER2)
Represents the total seasonal cooling output in Btu \text{Btu} Btu divided by total seasonal electrical energy consumed in Watt-hours \text{Watt-hours} Watt-hours ( Wh \text{Wh} Wh ) across a standardized weather bin profile (AHRI 210/240 / DOE 2023): SEER = Total Seasonal Cooling Output [Btu] Total Seasonal Electrical Energy [Wh] \text{SEER} = \frac{\text{Total Seasonal Cooling Output [Btu]}}{\text{Total Seasonal Electrical Energy [Wh]}} SEER = Total Seasonal Electrical Energy [Wh] Total Seasonal Cooling Output [Btu]
4. Heating Seasonal Performance Factor (HSPF & HSPF2)
Measures the total seasonal heating output in Btu \text{Btu} Btu divided by total electrical energy in Wh \text{Wh} Wh consumed by a heat pump throughout the heating season: HSPF = Total Seasonal Heating Output [Btu] Total Seasonal Electrical Energy [Wh] = 3.41214 × COP H P , seasonal \text{HSPF} = \frac{\text{Total Seasonal Heating Output [Btu]}}{\text{Total Seasonal Electrical Energy [Wh]}} = 3.41214 \times \text{COP}_{HP,\text{seasonal}} HSPF = Total Seasonal Electrical Energy [Wh] Total Seasonal Heating Output [Btu] = 3.41214 × COP H P , seasonal
4. Master Metric Cross-Conversion Reference Table
From Metric ↓ \downarrow ↓ / To Metric → \rightarrow → COP R \text{COP}_R COP R EER [Btu/(W ⋅ hr)] \text{EER}\text{ [Btu/(W}\cdot\text{hr)]} EER [Btu/(W ⋅ hr)] kW/ton \text{kW/ton} kW/ton COP H P \text{COP}_{HP} COP H P
COP R \text{COP}_R COP R 1.0 1.0 1.0 3.41214 × COP R 3.41214 \times \text{COP}_R 3.41214 × COP R 3.51685 COP R \frac{3.51685}{\text{COP}_R} COP R 3.51685 COP R + 1 \text{COP}_R + 1 COP R + 1
EER \text{EER} EER EER 3.41214 \frac{\text{EER}}{3.41214} 3.41214 EER 1.0 1.0 1.0 12 EER \frac{12}{\text{EER}} EER 12 EER 3.41214 + 1 \frac{\text{EER}}{3.41214} + 1 3.41214 EER + 1
kW/ton \text{kW/ton} kW/ton 3.51685 kW/ton \frac{3.51685}{\text{kW/ton}} kW/ton 3.51685 12 kW/ton \frac{12}{\text{kW/ton}} kW/ton 12 1.0 1.0 1.0 3.51685 kW/ton + 1 \frac{3.51685}{\text{kW/ton}} + 1 kW/ton 3.51685 + 1
COP H P \text{COP}_{HP} COP H P COP H P − 1 \text{COP}_{HP} - 1 COP H P − 1 3.41214 × ( COP H P − 1 ) 3.41214 \times (\text{COP}_{HP} - 1) 3.41214 × ( COP H P − 1 ) 3.51685 COP H P − 1 \frac{3.51685}{\text{COP}_{HP} - 1} COP H P − 1 3.51685 1.0 1.0 1.0
5. Part-Load Performance Metrics: AHRI 550/590 IPLV & NPLV
Chillers rarely operate at 100% full design load. Sizing equipment based solely on full-load efficiency overlooks the fact that HVAC systems spend over 85% of their operating hours at part-load conditions (75%, 50%, and 25% capacity) with cooler ambient wet-bulb temperatures.
AHRI Standard 550/590 Rating Formula
The Integrated Part-Load Value (IPLV) for standard conditions ( 44 ∘ F 44^\circ\text{F} 4 4 ∘ F leaving chilled water, entering condenser water relief from 85 ∘ F 85^\circ\text{F} 8 5 ∘ F at 100% down to 65 ∘ F 65^\circ\text{F} 6 5 ∘ F at 25% load) and Non-Standard Part-Load Value (NPLV) are calculated as: +-----------------------------------------------------------------------------------------+
- | AHRI 550/590 PART-LOAD OPERATING WEIGHTINGS |
- +-----------------------------------------------------------------------------------------+
- | Load Point A: 100% Capacity (Weight = 0.010 -> 1% of annual operating hours) |
- | Load Point B: 75% Capacity (Weight = 0.420 -> 42% of annual operating hours) |
- | Load Point C: 50% Capacity (Weight = 0.450 -> 45% of annual operating hours) |
- | Load Point D: 25% Capacity (Weight = 0.120 -> 12% of annual operating hours) |
- | *Notice that 75% and 50% loads dominate 87% of total operational lifecycle! |
- +-----------------------------------------------------------------------------------------+
- IPLV Formula for EER & COP
When metrics are proportional to efficiency (higher is better, like EER or COP): IPLV EER = 0.010 ⋅ A + 0.420 ⋅ B + 0.450 ⋅ C + 0.120 ⋅ D \text{IPLV}_{\text{EER}} = 0.010 \cdot A + 0.420 \cdot B + 0.450 \cdot C + 0.120 \cdot D IPLV EER = 0.010 ⋅ A + 0.420 ⋅ B + 0.450 ⋅ C + 0.120 ⋅ D IPLV COP = 0.010 ⋅ A COP + 0.420 ⋅ B COP + 0.450 ⋅ C COP + 0.120 ⋅ D COP \text{IPLV}_{\text{COP}} = 0.010 \cdot A_{\text{COP}} + 0.420 \cdot B_{\text{COP}} + 0.450 \cdot C_{\text{COP}} + 0.120 \cdot D_{\text{COP}} IPLV COP = 0.010 ⋅ A COP + 0.420 ⋅ B COP + 0.450 ⋅ C COP + 0.120 ⋅ D COP
IPLV Formula for kW/ton (Harmonic Weighting)
Since kW/ton \text{kW/ton} kW/ton is inversely proportional to efficiency (lower is better), the weighted formula must take the harmonic form: IPLV kW/ton = 1 0.010 A + 0.420 B + 0.450 C + 0.120 D \mathbf{\text{IPLV}_{\text{kW/ton}} = \frac{1}{\frac{0.010}{A} + \frac{0.420}{B} + \frac{0.450}{C} + \frac{0.120}{D}}} IPLV kW/ton = A 0.010 + B 0.420 + C 0.450 + D 0.120 1
Where:
A = Efficiency at 100% load [ kW/ton ] A = \text{Efficiency at 100\% load } [\text{kW/ton}] A = Efficiency at 100% load [ kW/ton ]
B = Efficiency at 75% load [ kW/ton ] B = \text{Efficiency at 75\% load } [\text{kW/ton}] B = Efficiency at 75% load [ kW/ton ]
C = Efficiency at 50% load [ kW/ton ] C = \text{Efficiency at 50\% load } [\text{kW/ton}] C = Efficiency at 50% load [ kW/ton ]
D = Efficiency at 25% load [ kW/ton ] D = \text{Efficiency at 25\% load } [\text{kW/ton}] D = Efficiency at 25% load [ kW/ton ]
Exam Trap: Never use linear arithmetic averaging 0.01 A + 0.42 B + 0.45 C + 0.12 D 0.01A + 0.42B + 0.45C + 0.12D 0.01 A + 0.42 B + 0.45 C + 0.12 D for kW/ton \text{kW/ton} kW/ton . That yields an erroneously low power consumption figure. Always use the reciprocal harmonic formula!
6. NCEES Reference Handbook Navigation Tactics
Conversion Factors: Navigate to Section 1: Mathematics & Fundamentals for exact multiplier constants ( 1 TR = 12 , 000 Btu/hr 1\text{ TR} = 12,000\text{ Btu/hr} 1 TR = 12 , 000 Btu/hr , 1 kW = 3 , 412.14 Btu/hr 1\text{ kW} = 3,412.14\text{ Btu/hr} 1 kW = 3 , 412.14 Btu/hr ). Locate the equation COP = Q L / W \text{COP} = Q_L / W COP = Q L / W .
Carnot Cycle Equations: Search "Carnot COP" or "Carnot Efficiency" in Section 7: HVAC & Refrigeration Applications to find T L / ( T H − T L ) T_L / (T_H - T_L) T L / ( T H − T L ) .
AHRI Part-Load Equation: Search "IPLV" or "Part-Load Value" to pull the 0.01 , 0.42 , 0.45 , 0.12 0.01, 0.42, 0.45, 0.12 0.01 , 0.42 , 0.45 , 0.12 weighting coefficients and verify the harmonic kW/ton \text{kW/ton} kW/ton formula.
- 7. Worked Computational Examples
- Example 1: Full Performance & Second Law Analysis of a Centrifugal Chiller
A 400 -Ton 400\text{-Ton} 400 -Ton water-cooled centrifugal chiller operates at design conditions, drawing 208 kW 208\text{ kW} 208 kW of total electrical power. The evaporator produces 44 ∘ F 44^\circ\text{F} 4 4 ∘ F chilled water (refrigerant boils at T evap = 40 ∘ F T_{\text{evap}} = 40^\circ\text{F} T evap = 4 0 ∘ F ), while the condenser receives 85 ∘ F 85^\circ\text{F} 8 5 ∘ F cooling tower water (refrigerant condenses at T cond = 95 ∘ F T_{\text{cond}} = 95^\circ\text{F} T cond = 9 5 ∘ F ).
Calculate: (a) Specific power consumption in kW/ton \text{kW/ton} kW/ton , (b) Full-load COP R \text{COP}_R COP R and EER \text{EER} EER , (c) Maximum theoretical Carnot COP R , Carnot \text{COP}_{R,\text{Carnot}} COP R , Carnot , (d) Second Law efficiency ( η II \eta_{\text{II}} η II ), and (e) Condenser heat rejection rate ( Btu/hr \text{Btu/hr} Btu/hr and Tons of Heat Rejection \text{Tons of Heat Rejection} Tons of Heat Rejection ).
Solution:
Specific Power Consumption: kW/ton = W ˙ electric Capacity [Tons] = 208 kW 400 Tons = 0.520 kW/ton \text{kW/ton} = \frac{\dot{W}_{\text{electric}}}{\text{Capacity [Tons]}} = \frac{208\text{ kW}}{400\text{ Tons}} = \mathbf{0.520\text{ kW/ton}} kW/ton = Capacity [Tons] W ˙ electric = 400 Tons 208 kW = 0.520 kW/ton
Actual COP R \text{COP}_R COP R and EER \text{EER} EER : COP R = 3.51685 kW/ton = 3.51685 0.520 = 6.763 \text{COP}_R = \frac{3.51685}{\text{kW/ton}} = \frac{3.51685}{0.520} = \mathbf{6.763} COP R = kW/ton 3.51685 = 0.520 3.51685 = 6.763 EER = 3.41214 × COP R = 3.41214 × 6.763 = 23.077 Btu/(W ⋅ hr) \text{EER} = 3.41214 \times \text{COP}_R = 3.41214 \times 6.763 = \mathbf{23.077\text{ Btu/(W}\cdot\text{hr)}} EER = 3.41214 × COP R = 3.41214 × 6.763 = 23.077 Btu/(W ⋅ hr) Check: EER = 12 kW/ton = 12 0.520 = 23.077 Btu/(W ⋅ hr) ✓ \text{Check: } \text{EER} = \frac{12}{\text{kW/ton}} = \frac{12}{0.520} = 23.077\text{ Btu/(W}\cdot\text{hr)} \quad \checkmark Check: EER = kW/ton 12 = 0.520 12 = 23.077 Btu/(W ⋅ hr) ✓
Carnot Maximum Theoretical COP: Convert refrigerant temperatures to absolute Rankine: T L = 40 ∘ F + 459.67 = 499.67 ∘ R T_L = 40^\circ\text{F} + 459.67 = 499.67^\circ\text{R} T L = 4 0 ∘ F + 459.67 = 499.6 7 ∘ R T H = 95 ∘ F + 459.67 = 554.67 ∘ R T_H = 95^\circ\text{F} + 459.67 = 554.67^\circ\text{R} T H = 9 5 ∘ F + 459.67 = 554.6 7 ∘ R COP R , Carnot = T L T H − T L = 499.67 554.67 − 499.67 = 499.67 55.0 = 9.085 \text{COP}_{R,\text{Carnot}} = \frac{T_L}{T_H - T_L} = \frac{499.67}{554.67 - 499.67} = \frac{499.67}{55.0} = \mathbf{9.085} COP R , Carnot = T H − T L T L = 554.67 − 499.67 499.67 = 55.0 499.67 = 9.085
Second Law Efficiency ( η II \eta_{\text{II}} η II ): η II = COP R COP R , Carnot = 6.763 9.085 = 0.7444 = 74.44 % \eta_{\text{II}} = \frac{\text{COP}_R}{\text{COP}_{R,\text{Carnot}}} = \frac{6.763}{9.085} = 0.7444 = \mathbf{74.44\%} η II = COP R , Carnot COP R = 9.085 6.763 = 0.7444 = 74.44%
Condenser Heat Rejection Rate: Q ˙ cooling = 400 Tons × 12 , 000 Btu/(hr ⋅ Ton) = 4 , 800 , 000 Btu/hr \dot{Q}_{\text{cooling}} = 400\text{ Tons} \times 12,000\text{ Btu/(hr}\cdot\text{Ton)} = 4,800,000\text{ Btu/hr} Q ˙ cooling = 400 Tons × 12 , 000 Btu/(hr ⋅ Ton) = 4 , 800 , 000 Btu/hr W ˙ in = 208 kW × 3 , 412.14 Btu/(kW ⋅ hr) = 709 , 725 Btu/hr \dot{W}_{\text{in}} = 208\text{ kW} \times 3,412.14\text{ Btu/(kW}\cdot\text{hr)} = 709,725\text{ Btu/hr} W ˙ in = 208 kW × 3 , 412.14 Btu/(kW ⋅ hr) = 709 , 725 Btu/hr Q ˙ cond = Q ˙ cooling + W ˙ in = 4 , 800 , 000 + 709 , 725 = 5 , 509 , 725 Btu/hr \dot{Q}_{\text{cond}} = \dot{Q}_{\text{cooling}} + \dot{W}_{\text{in}} = 4,800,000 + 709,725 = \mathbf{5,509,725\text{ Btu/hr}} Q ˙ cond = Q ˙ cooling + W ˙ in = 4 , 800 , 000 + 709 , 725 = 5 , 509 , 725 Btu/hr Tons of Heat Rejection = 5 , 509 , 725 12 , 000 = 459.14 THR ( HRR = 1.148 ) \text{Tons of Heat Rejection} = \frac{5,509,725}{12,000} = \mathbf{459.14\text{ THR}} \quad (\text{HRR} = 1.148) Tons of Heat Rejection = 12 , 000 5 , 509 , 725 = 459.14 THR ( HRR = 1.148 )
Example 2: AHRI 550/590 IPLV Calculation for Variable-Speed Chiller
A variable-speed magnetic-bearing centrifugal chiller undergoes AHRI 550/590 certified performance testing, recording the following specific power values across four test points:
- A A A (100% Load): 0.580 kW/ton 0.580\text{ kW/ton} 0.580 kW/ton
- B B B (75% Load): 0.460 kW/ton 0.460\text{ kW/ton} 0.460 kW/ton
- C C C (50% Load): 0.380 kW/ton 0.380\text{ kW/ton} 0.380 kW/ton
- D D D (25% Load): 0.440 kW/ton 0.440\text{ kW/ton} 0.440 kW/ton
Calculate: (a) The Integrated Part-Load Value ( IPLV \text{IPLV} IPLV ) in kW/ton \text{kW/ton} kW/ton , and (b) The equivalent IPLV \text{IPLV} IPLV expressed in EER \text{EER} EER .
Solution:
IPLV in kW/ton \text{kW/ton} kW/ton via Harmonic Summation: IPLV kW/ton = 1 0.010 A + 0.420 B + 0.450 C + 0.120 D \text{IPLV}_{\text{kW/ton}} = \frac{1}{\frac{0.010}{A} + \frac{0.420}{B} + \frac{0.450}{C} + \frac{0.120}{D}} IPLV kW/ton = A 0.010 + B 0.420 + C 0.450 + D 0.120 1 0.010 0.580 = 0.01724 \frac{0.010}{0.580} = 0.01724 0.580 0.010 = 0.01724 0.420 0.460 = 0.91304 \frac{0.420}{0.460} = 0.91304 0.460 0.420 = 0.91304 0.450 0.380 = 1.18421 \frac{0.450}{0.380} = 1.18421 0.380 0.450 = 1.18421 0.120 0.440 = 0.27273 \frac{0.120}{0.440} = 0.27273 0.440 0.120 = 0.27273 ∑ = 0.01724 + 0.91304 + 1.18421 + 0.27273 = 2.38722 \sum = 0.01724 + 0.91304 + 1.18421 + 0.27273 = 2.38722 ∑ = 0.01724 + 0.91304 + 1.18421 + 0.27273 = 2.38722 IPLV kW/ton = 1 2.38722 = 0.4189 kW/ton \text{IPLV}_{\text{kW/ton}} = \frac{1}{2.38722} = \mathbf{0.4189\text{ kW/ton}} IPLV kW/ton = 2.38722 1 = 0.4189 kW/ton
Equivalent IPLV in EER \text{EER} EER : IPLV EER = 12 IPLV kW/ton = 12 0.4189 = 28.646 Btu/(W ⋅ hr) \text{IPLV}_{\text{EER}} = \frac{12}{\text{IPLV}_{\text{kW/ton}}} = \frac{12}{0.4189} = \mathbf{28.646\text{ Btu/(W}\cdot\text{hr)}} IPLV EER = IPLV kW/ton 12 = 0.4189 12 = 28.646 Btu/(W ⋅ hr)