Study guide

6.5 Air Distribution, Duct Design, Fans & Hydronic Water Networks

PE Mechanical Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Overview, Reference Handbook & Mechanical Engineering Fundamentals

1.1 NCEES PE Mechanical CBT Format, Three Disciplines & Reference Handbook Strategy 1.2 Engineering Economics, Cash Flow & Project Evaluation and Scheduling 1.3 Units, Dimensional Analysis & Physical Constants 1.4 Statics, Dynamics & Mechanical Equilibrium

2 Chapter 2: Mechanical Design & Analysis (Stress, Failure Theories & Components)

2.1 Stress, Strain, Principal Stresses & Combined Loading 2.2 Static Failure Theories for Ductile and Brittle Materials 2.3 Fatigue Analysis, S-N Curves & Fluctuating Stresses 2.4 Pressure Vessels, Column Buckling & Spring Design 2.5 Threaded Fasteners, Welded Connections & Mechanical Joints

3 Chapter 3: Mechanical Power Transmission, Mechanisms & Vibrations

3.1 Shaft Sizing, Torsional Deflection & Critical Speeds 3.2 Spur, Helical, Bevel & Worm Gears and Epicyclic Gear Trains 3.3 Rolling-Element & Journal Bearings, Power Screws, Clutches, Brakes & Flywheels 3.4 Four-Bar Linkages, Cam-Follower Systems & Kinematics 3.5 Single-DOF and 2-DOF Vibrations, Damping & Dynamic Balancing

4 Chapter 4: Thermal & Fluid Systems

4.1 Fluid Statics, Manometry, Submerged Surfaces & Buoyancy 4.2 Incompressible Pipe Flow, Darcy-Weisbach & Minor Losses 4.3 Pump Selection, System Curves, NPSH & Cavitation 4.4 Steady & Transient Conduction, Forced & Natural Convection 4.5 Radiation Heat Transfer, View Factors & Heat Exchanger Sizing (LMTD/NTU)

5 Chapter 5: Power Plants & Energy Conversion Systems

5.1 Thermodynamic Properties, Pure Substances & 1st/2nd Laws 5.2 Vapor Power Cycles (Rankine, Superheat, Reheat & Regeneration) 5.3 Gas Power Cycles (Brayton, Otto, Diesel, Dual & Combined Cycle) 5.4 Combustion Stoichiometry, Flue Gas Analysis & Thermochemistry 5.5 Turbomachinery, Compressible Flow & Nozzles, Renewables & Energy Storage

6 Chapter 6: HVAC & Refrigeration Systems

6.1 Psychrometric Principles & Air-Conditioning Processes 6.2 Cooling & Heating Load Calculations (CLTD/SCL/CLF & Heat Balance) 6.3 Vapor-Compression Refrigeration Cycles & Refrigerant Properties 6.4 Refrigeration Equipment (Compressors, Evaporators, Condensers, Expansion Devices) & Safety Codes 6.5 Air Distribution, Duct Design, Fans & Hydronic Water Networks 6.6 Energy Recovery Devices, HVAC Acoustics & Vibration Isolation

7 Chapter 7: Materials, Manufacturing & Processing

7.1 Ferrous/Non-Ferrous Metals, Polymers, Ceramics & Composites 7.2 Iron-Carbon Equilibrium Phase Diagram & Heat Treatment Processes 7.3 Corrosion, Wear, Creep, Hydrogen Embrittlement & Fracture Mechanics 7.4 Casting, Metal Forming, Forging, Stamping & Powder Metallurgy 7.5 Machining Dynamics, Tool Wear, Welding Metallurgy & Non-Destructive Examination (NDE)

8 Chapter 8: Measurements, Controls, Codes & Engineering Ethics

8.1 Temperature, Pressure, Flow & Strain Transducers and Signal Conditioning 8.2 Feedback Control Loops, PID Tuning, Frequency Response & Stability 8.3 ASME Boiler & Pressure Vessel Code, ASHRAE, OSHA & NFPA Safety Standards 8.4 NCEES Model Rules, Engineering Ethics & Professional Seal Liability

6.5 Air Distribution, Duct Design, Fans & Hydronic Water Networks

Key Takeaways Explain This Topic AI

Air distribution aerodynamics balances total, static, and velocity pressures ( T P = S P + V P TP = SP + VP TP = SP + V P ), with velocity pressure given by V P = ( V / 4005 ) 2 VP = (V/4005)^2 V P = ( V /4005 ) 2 at standard air density.

Fan Laws govern operational scaling: airflow scales linearly with RPM ( C F M ∝ N CFM \propto N CFM ∝ N ), static pressure quadratically ( S P ∝ N 2 SP \propto N^2 SP ∝ N 2 ), and brake horsepower cubically ( B H P ∝ N 3 BHP \propto N^3 B H P ∝ N 3 ).

The standard hydronic heat transfer equation for water is q ˙ = 500 × G P M × Δ T [BTU/hr] \dot{q} = 500 \times GPM \times \Delta T\text{ [BTU/hr]} q ˙ ​ = 500 × GPM × Δ T [BTU/hr] ( 4.184 × V ˙ L / s × Δ T [kW] 4.184 \times \dot{V}_{L/s} \times \Delta T\text{ [kW]} 4.184 × V ˙ L / s ​ × Δ T [kW] ).

Control valve sizing requires balancing C v C_v C v ​ ( Q = C v Δ P Q = C_v \sqrt{\Delta P} Q = C v ​ Δ P ​ ) and valve authority ( N = Δ P valve Δ P valve + Δ P branch ≥ 0.50 N = \frac{\Delta P_{\text{valve}}}{\Delta P_{\text{valve}} + \Delta P_{\text{branch}}} \ge 0.50 N = Δ P valve ​ + Δ P branch ​ Δ P valve ​ ​ ≥ 0.50 ) to maintain linear temperature modulation.

Cooling tower thermal performance is dictated by Range ( T hot,in − T cold,out T_{\text{hot,in}} - T_{\text{cold,out}} T hot,in ​ − T cold,out ​ ) and Approach ( T cold,out − T w b , amb T_{\text{cold,out}} - T_{wb,\text{amb}} T cold,out ​ − T w b , amb ​ ), with total makeup water compensating for evaporation, drift, and blowdown ( M = E C O C C O C − 1 M = E \frac{COC}{COC - 1} M = E COC − 1 COC ​ ).

Last updated: August 2026

Air Distribution, Duct Design, Fans & Hydronic Water Networks

Fluid distribution networks—both air ductwork and hydronic piping loops—transport thermal energy between central plant equipment and conditioned building zones. Mastering duct sizing, fan performance scaling, chilled water hydronics, control valve authority, and cooling tower thermodynamics is vital for success on the NCEES PE Mechanical exam.

1. Air Distribution Fundamentals & Duct Aerodynamics

Air flowing through a duct system obeys the conservation of energy expressed by Bernoulli's equation in terms of total, static, and velocity pressures: +-----------------------------------------------------------------------------------------+

  • | DUCT SYSTEM PRESSURE RELATIONSHIPS |
  • | |
  • | Total Pressure (TP) = Static Pressure (SP) + Velocity Pressure (VP) |
  • | |
  • | - Static Pressure (SP): Potential energy exerted outward equally in all directions |
  • | on duct walls; measured perpendicular to airflow. |
  • | |
  • | - Velocity Pressure (VP): Kinetic energy of moving air stream; always positive; |
  • | measured parallel to airflow using a pitot tube. |
  • | |
  • | - Standard Air Formula: VP = \left(\frac{V}{4005}\right)^2 \quad [\text{in. w.g.}] |
  • | Where V is velocity in Feet Per Minute (FPM). |
  • | |
  • | - Velocity from VP: V = 4005 \sqrt{VP} \quad [\text{FPM}] |
  • | |
  • | - SI Units: VP = \frac{1}{2} \rho V^2 \quad [\text{Pa}] |
  • +-----------------------------------------------------------------------------------------+
  • Duct Design Methodologies

Equal Friction Method: Sizes all duct sections for a constant friction loss per unit length (typically 0.08 to 0.10 in. w.g. per 100 ft 0.08\text{ to }0.10\text{ in. w.g. per } 100\text{ ft} 0.08 to 0.10 in. w.g. per 100 ft of equivalent duct run). Simple and widely used, but requires manual balancing dampers on shorter branch runs.

Static Regain Method: Sizes duct cross-sections such that the increase in static pressure from velocity reduction at each branch takeoff exactly balances the downstream friction loss of the next section.

Velocity Reduction Method: Arbitrarily steps down velocities along successive downstream branches.

Huebscher Formula for Equivalent Circular Duct Diameter

To convert a rectangular duct with dimensions a a a and b b b (inches) carrying a specified airflow to a circular duct of diameter D e D_e D e ​ having the exact same friction loss per foot : D e = 1.30 ( a ⋅ b ) 0.625 ( a + b ) 0.25 D_e = 1.30 \frac{(a \cdot b)^{0.625}}{(a + b)^{0.25}} D e ​ = 1.30 ( a + b ) 0.25 ( a ⋅ b ) 0.625 ​

2. Fan Types, Fan Laws & System Resistance Curves +-----------------------------------------------------------------------------------------+

  • | CENTRIFUGAL VS. AXIAL FAN CLASSIFICATIONS |
  • | |
  • | CENTRIFUGAL FANS (Air turned 90°): |
  • | - Forward Curved (FC): Squirrel-cage, low speed/low SP; overloading horsepower curve. |
  • | - Backward Inclined (BI) / Airfoil (AF): High efficiency (up to 85%), high SP; |
  • | self-limiting non-overloading power curve. |
  • | - Radial: Rugged, industrial material handling and sawdust collection. |
  • | |
  • | AXIAL FANS (Straight-through flow): |
  • | - Propeller: High volume, low static pressure (< 0.5 in. w.g.); wall exhaust fans. |
  • | - Tubeaxial: Propeller inside cylinder; medium static pressure (< 2.0 in. w.g.). |
  • | - Vaneaxial: Straightening guide vanes convert swirl into static regain; up to 90% eta|
  • +-----------------------------------------------------------------------------------------+

The Affinity Laws for Fans (Fan Laws) +-----------------------------------------------------------------------------------------+

  • | FAN LAWS FORMULATION SUMMARY |
  • | |
  • | LAW 1: SPEED VARIATION (Constant Diameter D and Density \rho) |
  • | - Airflow Rate: \frac{CFM_2}{CFM_1} = \frac{N_2}{N_1} |
  • | - Static Pressure: \frac{SP_2}{SP_1} = \left(\frac{N_2}{N_1}\right)^2 |
  • | - Brake Horsepower: \frac{BHP_2}{BHP_1} = \left(\frac{N_2}{N_1}\right)^3 |
  • | |
  • | LAW 2: DENSITY VARIATION (Constant Diameter D and Speed N) |
  • | - Airflow Rate: CFM_2 = CFM_1 |
  • | - Static Pressure: \frac{SP_2}{SP_1} = \frac{\rho_2}{\rho_1} |
  • | - Brake Horsepower: \frac{BHP_2}{BHP_1} = \frac{\rho_2}{\rho_1} |
  • +-----------------------------------------------------------------------------------------+

Fan Static & Total Efficiency Formulas Air Horsepower (AHP) = C F M × S P 6356 [ HP ] \text{Air Horsepower (AHP)} = \frac{CFM \times SP}{6356} \quad [\text{HP}] Air Horsepower (AHP) = 6356 CFM × SP ​ [ HP ] Fan Static Efficiency ( η f s ) = C F M × S P 6356 × B H P \text{Fan Static Efficiency (}\eta_{fs}\text{)} = \frac{CFM \times SP}{6356 \times BHP} Fan Static Efficiency ( η f s ​ ) = 6356 × B H P CFM × SP ​ Fan Total Efficiency ( η t ) = C F M × T P 6356 × B H P \text{Fan Total Efficiency (}\eta_t\text{)} = \frac{CFM \times TP}{6356 \times BHP} Fan Total Efficiency ( η t ​ ) = 6356 × B H P CFM × TP ​

System Effect Factors (SEF)

Abrupt elbows, transitions, or obstructions located immediately adjacent to fan inlets or outlets disrupt the uniform velocity profile, introducing severe uncalculated pressure losses known as System Effects . SEF must be added to calculated duct friction when selecting fan operating points.

3. Hydronic Distribution Networks (Chilled & Heating Water) +-----------------------------------------------------------------------------------------+

  • | HYDRONIC PIPING SYSTEM ARCHITECTURES |
  • | |
  • | PRIMARY-SECONDARY DECOUPLED: |
  • | - Primary Loop: Constant flow chillers protected by dedicated primary pumps. |
  • | - Secondary Loop: Variable-speed distribution pumps modulating with zone 2-way valves.|
  • | - Decoupler / Common Pipe: Hydraulic bridge with zero pressure drop separating loops. |
  • | |
  • | VARIABLE PRIMARY FLOW (VPF): |
  • | - Single variable-speed pump set modulates flow across variable-flow chillers. |
  • | - Requires minimum-flow bypass valve to prevent evaporator freezing during low loads. |
  • +-----------------------------------------------------------------------------------------+

The Fundamental Hydronic Equation q ˙ = m ˙ c p Δ T = ( G P M × 8.33 lbm/gal × 60 min/hr ) × 1.0 BTU/lbm ⋅ ∘ F × Δ T \dot{q} = \dot{m} c_p \Delta T = (GPM \times 8.33\text{ lbm/gal} \times 60\text{ min/hr}) \times 1.0\text{ BTU/lbm}\cdot^\circ\text{F} \times \Delta T q ˙ ​ = m ˙ c p ​ Δ T = ( GPM × 8.33 lbm/gal × 60 min/hr ) × 1.0 BTU/lbm ⋅ ∘ F × Δ T q ˙ = 500 × G P M × Δ T [ BTU/hr ] \dot{q} = 500 \times GPM \times \Delta T \quad [\text{BTU/hr}] q ˙ ​ = 500 × GPM × Δ T [ BTU/hr ]

In SI Units (Water ρ = 1000 kg/m 3 , c p = 4.184 kJ/kg ⋅ K \rho = 1000\text{ kg/m}^3, c_p = 4.184\text{ kJ/kg}\cdot\text{K} ρ = 1000 kg/m 3 , c p ​ = 4.184 kJ/kg ⋅ K ): q ˙ = 4.184 × V ˙ L / s × Δ T [ kW ] \dot{q} = 4.184 \times \dot{V}_{L/s} \times \Delta T \quad [\text{kW}] q ˙ ​ = 4.184 × V ˙ L / s ​ × Δ T [ kW ]

For Ethylene/Propylene Glycol mixtures: q ˙ = 500 × S G × c p × G P M × Δ T \dot{q} = 500 \times SG \times c_p \times GPM \times \Delta T q ˙ ​ = 500 × SG × c p ​ × GPM × Δ T .

Hydronic Control Valves & Valve Authority ( N N N )

Valve Flow Coefficient ( C v C_v C v ​ ): The flow rate of 60 ∘ F 60^\circ\text{F} 6 0 ∘ F water in GPM that produces a 1.0 psi 1.0\text{ psi} 1.0 psi pressure drop across a fully open valve: Q = C v Δ P ⟹ Δ P = ( Q C v ) 2 Q = C_v \sqrt{\Delta P} \implies \Delta P = \left(\frac{Q}{C_v}\right)^2 Q = C v ​ Δ P ​ ⟹ Δ P = ( C v ​ Q ​ ) 2

Valve Authority ( N N N ): The ratio of the pressure drop across the fully open control valve to the total pressure drop of the valve plus its associated piping branch: N = Δ P valve, 100% Δ P valve, 100% + Δ P piping branch N = \frac{\Delta P_{\text{valve, 100\%}}}{\Delta P_{\text{valve, 100\%}} + \Delta P_{\text{piping branch}}} N = Δ P valve, 100% ​ + Δ P piping branch ​ Δ P valve, 100% ​ ​

If N < 0.25 N < 0.25 N < 0.25 , the valve loses control authority, distorting linear heat output and causing severe actuator hunting.

Target design rule: N ≥ 0.50 N \ge 0.50 N ≥ 0.50 (the valve drop should equal or exceed the piping branch drop).

4. Cooling Towers & Condenser Water Systems

Cooling towers reject waste heat from water-cooled chillers to the ambient atmosphere via direct evaporative contact with ambient air. +-----------------------------------------------------------------------------------------+

  • | COOLING TOWER TEMPERATURE RELATIONSHIPS |
  • | |
  • | Hot Water In (T_hot,in) = 95°F |
  • | | |
  • | | <--- Cooling Tower Range = T_hot,in - T_cold,out = 95°F - 85°F = 10°F |
  • | v |
  • | Cold Water Out (T_cold,out) = 85°F |
  • | | |
  • | | <--- Cooling Tower Approach = T_cold,out - T_wb,ambient = 85°F - 78°F = 7°F |
  • | v |
  • | Ambient Wet-Bulb Temp (T_wb) = 78°F |
  • +-----------------------------------------------------------------------------------------+

Key Cooling Tower Performance Metrics:

Range: The temperature drop of the condenser water across the tower: Range = T hot, entering − T cold, leaving \text{Range} = T_{\text{hot, entering}} - T_{\text{cold, leaving}} Range = T hot, entering ​ − T cold, leaving ​

Approach: The temperature difference between the cold water leaving the tower basin and the ambient entering wet-bulb temperature: Approach = T cold, leaving − T w b , ambient \text{Approach} = T_{\text{cold, leaving}} - T_{wb,\text{ambient}} Approach = T cold, leaving ​ − T w b , ambient ​ (Note: The leaving water temperature can NEVER be cooled below the ambient wet-bulb temperature).

Cooling Tower Effectiveness ( η tower \eta_{\text{tower}} η tower ​ ): η tower = Range Range + Approach = T hot − T cold T hot − T w b \eta_{\text{tower}} = \frac{\text{Range}}{\text{Range} + \text{Approach}} = \frac{T_{\text{hot}} - T_{\text{cold}}}{T_{\text{hot}} - T_{wb}} η tower ​ = Range + Approach Range ​ = T hot ​ − T w b ​ T hot ​ − T cold ​ ​

Cooling Tower Water Consumption & Makeup Water

Water lost through heat rejection must be continuously replenished by fresh municipal makeup water ( M M M ): +-----------------------------------------------------------------------------------------+

  • | COOLING TOWER WATER BALANCE |
  • | |
  • | Total Makeup Water (M) = Evaporation Loss (E) + Blowdown (B) + Drift Loss (D) |
  • | |
  • | - Evaporation Rate (E): E \approx 0.0008 \times GPM \times \text{Range} |
  • | Rule of thumb: ~1% of circulating flow per 10°F Range (or ~3 GPM per 100 TR). |
  • | |
  • | - Drift Loss (D): D \approx 0.0002 \text{ to } 0.002 \times GPM |
  • | |
  • | - Cycles of Concentration (COC): Ratio of dissolved solids in basin to makeup: |
  • | COC = \frac{\text{TDS}_{\text{basin}}}{\text{TDS}_{\text{makeup}}} = \frac{M}{B + D}|
  • | |
  • | - Blowdown Rate (B): B = \frac{E}{COC - 1} - D \approx \frac{E}{COC - 1} |
  • | |
  • | - Total Makeup (M): M = E \left(\frac{COC}{COC - 1}\right) |
  • +-----------------------------------------------------------------------------------------+
  • 5. Step-by-Step Worked Engineering Problem
  • Problem Statement

A central chilled water plant features a 500 TR 500\text{ TR} 500 TR water-cooled centrifugal chiller operating with a condenser heat rejection rate of 15 , 000 BTU/hr ⋅ TR 15,000\text{ BTU/hr}\cdot\text{TR} 15 , 000 BTU/hr ⋅ TR .

Condenser water circulation rate = 1 , 500 GPM = 1,500\text{ GPM} = 1 , 500 GPM .

Entering cooling tower hot water temperature = 95.0 ∘ F = 95.0^\circ\text{F} = 95. 0 ∘ F .

Ambient air conditions: 90.0 ∘ F T d b 90.0^\circ\text{F } T_{db} 90. 0 ∘ F T d b ​ and 78.0 ∘ F T w b 78.0^\circ\text{F } T_{wb} 78. 0 ∘ F T w b ​ .

Leaving cooling tower cold water temperature = 85.0 ∘ F = 85.0^\circ\text{F} = 85. 0 ∘ F .

Water treatment operates at C O C = 4.0 COC = 4.0 COC = 4.0 Cycles of Concentration. Drift loss is 0.001 × G P M 0.001 \times GPM 0.001 × GPM .

Calculate:

The cooling tower Range, Approach, and Effectiveness.

The evaporation rate ( E E E ) in GPM \text{GPM} GPM .

The required blowdown rate ( B B B ) in GPM \text{GPM} GPM .

The total municipal makeup water requirement ( M M M ) in GPM \text{GPM} GPM .

If the cooling tower fan motor is upgraded from 1 , 200 RPM 1,200\text{ RPM} 1 , 200 RPM to 1 , 400 RPM 1,400\text{ RPM} 1 , 400 RPM , calculate the percentage increase in fan Brake Horsepower ( B H P BHP B H P ). +-----------------------------------------------------------------------------------------+

  • | CENTRAL PLANT CALCULATION STEPS |
  • | |
  • | Range = 95.0°F - 85.0°F = 10.0°F |
  • | Approach = 85.0°F - 78.0°F = 7.0°F |
  • +-----------------------------------------------------------------------------------------+

Step 1: Range, Approach & Effectiveness Range = 95.0 − 85.0 = 10.0 ∘ F \text{Range} = 95.0 - 85.0 = 10.0^\circ\text{F} Range = 95.0 − 85.0 = 10. 0 ∘ F Approach = 85.0 − 78.0 = 7.0 ∘ F \text{Approach} = 85.0 - 78.0 = 7.0^\circ\text{F} Approach = 85.0 − 78.0 = 7. 0 ∘ F η tower = Range Range + Approach = 10.0 10.0 + 7.0 = 10.0 17.0 = 0.5882 ⟹ 58.8 % \eta_{\text{tower}} = \frac{\text{Range}}{\text{Range} + \text{Approach}} = \frac{10.0}{10.0 + 7.0} = \frac{10.0}{17.0} = 0.5882 \implies 58.8\% η tower ​ = Range + Approach Range ​ = 10.0 + 7.0 10.0 ​ = 17.0 10.0 ​ = 0.5882 ⟹ 58.8%

Step 2: Evaporation Loss Rate ( E E E )

Total Heat Rejected: Q ˙ cond = 500 TR × 15 , 000 BTU/hr ⋅ TR = 7 , 500 , 000 BTU/hr \dot{Q}_{\text{cond}} = 500\text{ TR} \times 15,000\text{ BTU/hr}\cdot\text{TR} = 7,500,000\text{ BTU/hr} Q ˙ ​ cond ​ = 500 TR × 15 , 000 BTU/hr ⋅ TR = 7 , 500 , 000 BTU/hr .

Using latent heat of vaporization ( h f g ≈ 1 , 000 BTU/lbm h_{fg} \approx 1,000\text{ BTU/lbm} h f g ​ ≈ 1 , 000 BTU/lbm ): E = Q ˙ cond h f g × 8.33 lbm/gal × 60 min/hr = 7 , 500 , 000 1000 × 500 = 15.0 GPM E = \frac{\dot{Q}_{\text{cond}}}{h_{fg} \times 8.33\text{ lbm/gal} \times 60\text{ min/hr}} = \frac{7,500,000}{1000 \times 500} = 15.0\text{ GPM} E = h f g ​ × 8.33 lbm/gal × 60 min/hr Q ˙ ​ cond ​ ​ = 1000 × 500 7 , 500 , 000 ​ = 15.0 GPM

(Verification with rule of thumb: E = 0.0008 × 1500 × 10 = 12.0 – 15.0 GPM E = 0.0008 \times 1500 \times 10 = 12.0\text{--}15.0\text{ GPM} E = 0.0008 × 1500 × 10 = 12.0 – 15.0 GPM ).

Step 3: Blowdown Rate ( B B B ) Drift Loss D = 0.001 × 1 , 500 GPM = 1.5 GPM \text{Drift Loss } D = 0.001 \times 1,500\text{ GPM} = 1.5\text{ GPM} Drift Loss D = 0.001 × 1 , 500 GPM = 1.5 GPM B = E C O C − 1 − D = 15.0 GPM 4.0 − 1 − 1.5 = 15.0 3 − 1.5 = 5.0 − 1.5 = 3.5 GPM B = \frac{E}{COC - 1} - D = \frac{15.0\text{ GPM}}{4.0 - 1} - 1.5 = \frac{15.0}{3} - 1.5 = 5.0 - 1.5 = 3.5\text{ GPM} B = COC − 1 E ​ − D = 4.0 − 1 15.0 GPM ​ − 1.5 = 3 15.0 ​ − 1.5 = 5.0 − 1.5 = 3.5 GPM

Step 4: Total Makeup Water ( M M M ) M = E + B + D = 15.0 + 3.5 + 1.5 = 20.0 GPM M = E + B + D = 15.0 + 3.5 + 1.5 = 20.0\text{ GPM} M = E + B + D = 15.0 + 3.5 + 1.5 = 20.0 GPM

(Verification: M = E × C O C C O C − 1 = 15.0 × 4 3 = 20.0 GPM M = E \times \frac{COC}{COC-1} = 15.0 \times \frac{4}{3} = 20.0\text{ GPM} M = E × COC − 1 COC ​ = 15.0 × 3 4 ​ = 20.0 GPM ).

Step 5: Fan Law Scaling for Brake Horsepower

Speed ratio: N 2 N 1 = 1400 1200 = 1.1667 \frac{N_2}{N_1} = \frac{1400}{1200} = 1.1667 N 1 ​ N 2 ​ ​ = 1200 1400 ​ = 1.1667 . B H P 2 B H P 1 = ( N 2 N 1 ) 3 = ( 1.1667 ) 3 = 1.5879 \frac{BHP_2}{BHP_1} = \left(\frac{N_2}{N_1}\right)^3 = (1.1667)^3 = 1.5879 B H P 1 ​ B H P 2 ​ ​ = ( N 1 ​ N 2 ​ ​ ) 3 = ( 1.1667 ) 3 = 1.5879 Percentage Increase = ( 1.5879 − 1 ) × 100 % = 58.8 % \text{Percentage Increase} = (1.5879 - 1) \times 100\% = 58.8\% Percentage Increase = ( 1.5879 − 1 ) × 100% = 58.8%

6. Common Exam Traps & PE Pro-Tips

Trap 1 — Fan Law 3 Cubed Power Scaling: Increasing fan speed by just 20 % 20\% 20% ( 1.20 1.20 1.20 ) increases electrical power draw by 72.8 % 72.8\% 72.8% ( 1.20 3 = 1.728 1.20^3 = 1.728 1.2 0 3 = 1.728 ). Never assume linear power scaling!

Trap 2 — Fan Laws Do Not Apply to Duct Resistance Alterations: The Fan Laws relate performance changes on the same system resistance curve when fan speed is modified. If a damper is closed or duct geometry changes, the system curve itself shifts, and you must find the intersection of the new system curve with the fan curve.

Trap 3 — Cooling Tower Approach Limit: Remember that no cooling tower, regardless of size or airflow, can cool water below the ambient wet-bulb temperature . If an exam question claims leaving water is colder than ambient wet-bulb, the scenario violates the Second Law of Thermodynamics.