6.1 Psychrometric Principles & Air-Conditioning Processes
PE Mechanical Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview, Reference Handbook & Mechanical Engineering Fundamentals
1.1 NCEES PE Mechanical CBT Format, Three Disciplines & Reference Handbook Strategy 1.2 Engineering Economics, Cash Flow & Project Evaluation and Scheduling 1.3 Units, Dimensional Analysis & Physical Constants 1.4 Statics, Dynamics & Mechanical Equilibrium
2 Chapter 2: Mechanical Design & Analysis (Stress, Failure Theories & Components)
2.1 Stress, Strain, Principal Stresses & Combined Loading 2.2 Static Failure Theories for Ductile and Brittle Materials 2.3 Fatigue Analysis, S-N Curves & Fluctuating Stresses 2.4 Pressure Vessels, Column Buckling & Spring Design 2.5 Threaded Fasteners, Welded Connections & Mechanical Joints
3 Chapter 3: Mechanical Power Transmission, Mechanisms & Vibrations
3.1 Shaft Sizing, Torsional Deflection & Critical Speeds 3.2 Spur, Helical, Bevel & Worm Gears and Epicyclic Gear Trains 3.3 Rolling-Element & Journal Bearings, Power Screws, Clutches, Brakes & Flywheels 3.4 Four-Bar Linkages, Cam-Follower Systems & Kinematics 3.5 Single-DOF and 2-DOF Vibrations, Damping & Dynamic Balancing
4 Chapter 4: Thermal & Fluid Systems
4.1 Fluid Statics, Manometry, Submerged Surfaces & Buoyancy 4.2 Incompressible Pipe Flow, Darcy-Weisbach & Minor Losses 4.3 Pump Selection, System Curves, NPSH & Cavitation 4.4 Steady & Transient Conduction, Forced & Natural Convection 4.5 Radiation Heat Transfer, View Factors & Heat Exchanger Sizing (LMTD/NTU)
5 Chapter 5: Power Plants & Energy Conversion Systems
5.1 Thermodynamic Properties, Pure Substances & 1st/2nd Laws 5.2 Vapor Power Cycles (Rankine, Superheat, Reheat & Regeneration) 5.3 Gas Power Cycles (Brayton, Otto, Diesel, Dual & Combined Cycle) 5.4 Combustion Stoichiometry, Flue Gas Analysis & Thermochemistry 5.5 Turbomachinery, Compressible Flow & Nozzles, Renewables & Energy Storage
6 Chapter 6: HVAC & Refrigeration Systems
6.1 Psychrometric Principles & Air-Conditioning Processes 6.2 Cooling & Heating Load Calculations (CLTD/SCL/CLF & Heat Balance) 6.3 Vapor-Compression Refrigeration Cycles & Refrigerant Properties 6.4 Refrigeration Equipment (Compressors, Evaporators, Condensers, Expansion Devices) & Safety Codes 6.5 Air Distribution, Duct Design, Fans & Hydronic Water Networks 6.6 Energy Recovery Devices, HVAC Acoustics & Vibration Isolation
7 Chapter 7: Materials, Manufacturing & Processing
7.1 Ferrous/Non-Ferrous Metals, Polymers, Ceramics & Composites 7.2 Iron-Carbon Equilibrium Phase Diagram & Heat Treatment Processes 7.3 Corrosion, Wear, Creep, Hydrogen Embrittlement & Fracture Mechanics 7.4 Casting, Metal Forming, Forging, Stamping & Powder Metallurgy 7.5 Machining Dynamics, Tool Wear, Welding Metallurgy & Non-Destructive Examination (NDE)
8 Chapter 8: Measurements, Controls, Codes & Engineering Ethics
8.1 Temperature, Pressure, Flow & Strain Transducers and Signal Conditioning 8.2 Feedback Control Loops, PID Tuning, Frequency Response & Stability 8.3 ASME Boiler & Pressure Vessel Code, ASHRAE, OSHA & NFPA Safety Standards 8.4 NCEES Model Rules, Engineering Ethics & Professional Seal Liability
6.1 Psychrometric Principles & Air-Conditioning Processes
Key Takeaways Explain This Topic AI
Moist air obeys Dalton's law of partial pressures ( p = p a + p w p = p_a + p_w p = p a + p w ), where the humidity ratio ω = 0.622 p w p − p w \omega = 0.622 \frac{p_w}{p - p_w} ω = 0.622 p − p w p w quantifies moisture mass per unit mass of dry air.
Sensible heating and cooling occur at a constant humidity ratio ( Δ ω = 0 \Delta \omega = 0 Δ ω = 0 ), governed by the standard air heat rate formula q ˙ s = 1.08 × C F M × Δ T \dot{q}_s = 1.08 \times CFM \times \Delta T q ˙ s = 1.08 × CFM × Δ T in US Customary units ( 1.23 × V ˙ L / s × Δ T 1.23 \times \dot{V}_{L/s} \times \Delta T 1.23 × V ˙ L / s × Δ T in SI units).
Cooling with dehumidification occurs when coil surface temperatures fall below the entering air dew point, characterized by the Apparatus Dew Point (ADP) and coil Bypass Factor ( B F BF BF ).
The total heat transfer rate across any psychrometric process is proportional to the enthalpy difference: q ˙ t = 4.5 × C F M × Δ h \dot{q}_t = 4.5 \times CFM \times \Delta h q ˙ t = 4.5 × CFM × Δ h in US Customary units ( 1.20 × V ˙ L / s × Δ h 1.20 \times \dot{V}_{L/s} \times \Delta h 1.20 × V ˙ L / s × Δ h in SI units), with the Sensible Heat Ratio defined as S H R = q ˙ s / q ˙ t SHR = \dot{q}_s / \dot{q}_t S H R = q ˙ s / q ˙ t .
Adiabatic mixing of two moist air streams follows conservation of dry air mass and enthalpy, forming a mixed state point that lies on the straight line connecting the entering states according to the lever rule: T d b , 3 − T d b , 1 T d b , 2 − T d b , 3 = m ˙ d a , 2 m ˙ d a , 1 \frac{T_{db,3} - T_{db,1}}{T_{db,2} - T_{db,3}} = \frac{\dot{m}_{da,2}}{\dot{m}_{da,1}} T d b , 2 − T d b , 3 T d b , 3 − T d b , 1 = m ˙ d a , 1 m ˙ d a , 2 .
Last updated: August 2026
Psychrometric Principles & Air-Conditioning Processes
Psychrometrics is the branch of thermodynamics dedicated to atmospheric air combined with water vapor. It serves as the foundational core for heating, ventilating, air-conditioning, and refrigeration (HVAC&R) system design. On the NCEES PE Mechanical exam, psychrometric analysis is essential for evaluating air handling unit (AHU) performance, sizing direct expansion (DX) and chilled water cooling coils, determining required supply airflow rates, and analyzing mixing plenums and evaporative coolers.
1. Thermodynamic Properties of Moist Air & Dalton's Law
Atmospheric moist air is treated as a binary mixture of dry air (a pseudo-pure gas with apparent molecular weight M a = 28.966 lbm/lbmol = 28.966 kg/kmol M_a = 28.966\text{ lbm/lbmol} = 28.966\text{ kg/kmol} M a = 28.966 lbm/lbmol = 28.966 kg/kmol ) and water vapor ( M w = 18.015 lbm/lbmol = 18.015 kg/kmol M_w = 18.015\text{ lbm/lbmol} = 18.015\text{ kg/kmol} M w = 18.015 lbm/lbmol = 18.015 kg/kmol ). Under typical HVAC operating ranges (temperatures from − 40 ∘ F -40^\circ\text{F} − 4 0 ∘ F to 140 ∘ F 140^\circ\text{F} 14 0 ∘ F and pressures near atmospheric), both dry air and water vapor behave in close accordance with the ideal gas law ( p V = m R T p V = m R T p V = m RT ). +-----------------------------------------------------------------------------------------+
- | MOIST AIR CONSTITUENTS & DALTON'S LAW |
- | |
- | Total Barometric Pressure: p = p_a + p_w |
- | |
- | - Dry Air Partial Pressure: p_a = \frac{m_a R_a T}{V} |
- | - Water Vapor Partial Press: p_w = \frac{m_w R_w T}{V} |
- | - Standard Atmospheric Press: p = 14.696 psia = 29.921 in. Hg = 101.325 kPa |
- +-----------------------------------------------------------------------------------------+
- Primary Psychrometric Variables
Dry-Bulb Temperature ( T d b T_{db} T d b or T T T ): The true thermodynamic temperature of the moist air mixture measured by an ordinary, unshielded thermometer unaffected by radiation or moisture.
Wet-Bulb Temperature ( T w b T_{wb} T w b or T ∗ T^* T ∗ ): The equilibrium temperature registered by an accurate thermometer whose sensor is covered by a wetted wick and exposed to rapid airflow ( > 900 FPM > 900\text{ FPM} > 900 FPM ). At saturation (100% relative humidity), dry-bulb, wet-bulb, and dew-point temperatures are all identical: T d b = T w b = T d p T_{db} = T_{wb} = T_{dp} T d b = T w b = T d p .
Dew-Point Temperature ( T d p T_{dp} T d p ): The temperature at which water vapor in moist air begins to condense when the mixture is cooled at constant moisture content ( ω = const \omega = \text{const} ω = const ) and constant total pressure ( p = const p = \text{const} p = const ). T d p T_{dp} T d p is strictly a function of the water vapor partial pressure p w p_w p w , satisfying p w = p w s ( T d p ) p_w = p_{ws}(T_{dp}) p w = p w s ( T d p ) , where p w s p_{ws} p w s is the saturation pressure of water.
Relative Humidity ( ϕ \phi ϕ ): The ratio of the actual water vapor partial pressure p w p_w p w to the saturation pressure p w s p_{ws} p w s at the same dry-bulb temperature: ϕ = ( p w p w s ) T d b × 100 \phi = \left(\frac{p_w}{p_{ws}}\right)_{T_{db}} \times 100 ϕ = ( p w s p w ) T d b × 100
Humidity Ratio / Specific Humidity ( ω \omega ω or W W W ): The ratio of the mass of water vapor ( m w m_w m w ) to the mass of dry air ( m d a m_{da} m d a ): ω = m w m d a = M w p w M a p a = 18.015 28.966 ( p w p − p w ) = 0.622 p w p − p w [ lbm w lbm d a or kg w kg d a ] \omega = \frac{m_w}{m_{da}} = \frac{M_w p_w}{M_a p_a} = \frac{18.015}{28.966} \left(\frac{p_w}{p - p_w}\right) = 0.622 \frac{p_w}{p - p_w} \quad \left[\frac{\text{lbm}_w}{\text{lbm}_{da}} \text{ or } \frac{\text{kg}_w}{\text{kg}_{da}}\right] ω = m d a m w = M a p a M w p w = 28.966 18.015 ( p − p w p w ) = 0.622 p − p w p w [ lbm d a lbm w or kg d a kg w ] In US Customary units, moisture content is frequently expressed in grains of moisture per pound of dry air ( 1 lbm = 7 , 000 grains 1\text{ lbm} = 7,000\text{ grains} 1 lbm = 7 , 000 grains ): W g r = 7 , 000 × ω [ grains w lbm d a ] W_{gr} = 7,000 \times \omega \quad \left[\frac{\text{grains}_w}{\text{lbm}_{da}}\right] W g r = 7 , 000 × ω [ lbm d a grains w ]
Specific Volume ( v v v ): The total volume of the moist air mixture per unit mass of dry air: v = V m d a = R a T p a = R a T p − p w = R a T ( 1 + 1.608 ω ) p [ ft 3 lbm d a or m 3 kg d a ] v = \frac{V}{m_{da}} = \frac{R_a T}{p_a} = \frac{R_a T}{p - p_w} = \frac{R_a T (1 + 1.608\omega)}{p} \quad \left[\frac{\text{ft}^3}{\text{lbm}_{da}} \text{ or } \frac{\text{m}^3}{\text{kg}_{da}}\right] v = m d a V = p a R a T = p − p w R a T = p R a T ( 1 + 1.608 ω ) [ lbm d a ft 3 or kg d a m 3 ] Where R a = 53.35 ft ⋅ lbf / ( lbm ⋅ ∘ R ) = 0.2870 kJ / ( kg ⋅ K ) R_a = 53.35\text{ ft}\cdot\text{lbf}/(\text{lbm}\cdot^\circ\text{R}) = 0.2870\text{ kJ}/(\text{kg}\cdot\text{K}) R a = 53.35 ft ⋅ lbf / ( lbm ⋅ ∘ R ) = 0.2870 kJ / ( kg ⋅ K ) and T T T is absolute temperature ( ∘ R ^\circ\text{R} ∘ R or K \text{K} K ).
Specific Enthalpy ( h h h ): The total thermal energy of the moist air mixture per unit mass of dry air, using 0 ∘ F 0^\circ\text{F} 0 ∘ F (or 0 ∘ C 0^\circ\text{C} 0 ∘ C ) dry air and 32 ∘ F 32^\circ\text{F} 3 2 ∘ F liquid water as reference states:
US Customary Units: h = c p a T d b + ω h g ≈ 0.240 T d b + ω ( 1061 + 0.444 T d b ) [ BTU lbm d a ] h = c_{pa} T_{db} + \omega h_g \approx 0.240 T_{db} + \omega (1061 + 0.444 T_{db}) \quad \left[\frac{\text{BTU}}{\text{lbm}_{da}}\right] h = c p a T d b + ω h g ≈ 0.240 T d b + ω ( 1061 + 0.444 T d b ) [ lbm d a BTU ]
SI Units: h = c p a T d b + ω h g ≈ 1.006 T d b + ω ( 2501 + 1.86 T d b ) [ kJ kg d a ] h = c_{pa} T_{db} + \omega h_g \approx 1.006 T_{db} + \omega (2501 + 1.86 T_{db}) \quad \left[\frac{\text{kJ}}{\text{kg}_{da}}\right] h = c p a T d b + ω h g ≈ 1.006 T d b + ω ( 2501 + 1.86 T d b ) [ kg d a kJ ]
2. Navigating the Standard Psychrometric Chart
The standard sea-level psychrometric chart ( p = 14.696 psia = 101.325 kPa p = 14.696\text{ psia} = 101.325\text{ kPa} p = 14.696 psia = 101.325 kPa ) plots thermodynamic properties on a 2D coordinate system. +-----------------------------------------------------------------------------------------+
- | PSYCHROMETRIC CHART GEOMETRY & AXES |
- | |
- | Humidity Ratio (\omega) / Enthalpy (h) |
- | ^ |
- | | / Constant Volume (v) |
- | | Saturation / |
- | | Curve / |
- | | (\phi=100%)/ Constant Wet-Bulb (T_wb) |
- | | ,-''''' / / & Specific Enthalpy (h) |
- | | _,-' / ,' |
- | | _,-' / ,' |
- | | _,-' / ,' |
- | | _,-' /,' --- Constant Relative |
- | | _,-' /' Humidity (\phi = 50%) |
- | | _,-' / |
- | | _,-' / |
- | | _,-' / |
- | | _,-' / |
- | +----+-----------------------------------+--------------------------------------> |
- | Dew Point (T_dp) Dry-Bulb Temperature (T_db) |
- +-----------------------------------------------------------------------------------------+
- Property Chart Orientation & Geometry
- Dry-Bulb Temperature ( T d b T_{db} T d b ) Vertical lines originating along the horizontal baseline axis
- Humidity Ratio ( ω \omega ω / W W W ) Horizontal lines reading onto the right-hand vertical axis
- Saturation Curve ( ϕ = 100 % \phi = 100\% ϕ = 100% ) Boundary curve along the upper-left envelope of the chart
- Relative Humidity ( ϕ \phi ϕ ) Non-linear curved lines paralleling the outer saturation curve
- Wet-Bulb Temperature ( T w b T_{wb} T w b ) Moderately steep diagonal lines extending downward to the right
- Specific Enthalpy ( h h h ) Diagonal lines nearly parallel to lines of constant wet-bulb temperature
- Specific Volume ( v v v ) Steeply pitched straight diagonal lines
Important
Altitude and Barometric Corrections: Standard psychrometric charts are valid only at sea level ( 14.696 psia = 101.325 kPa 14.696\text{ psia} = 101.325\text{ kPa} 14.696 psia = 101.325 kPa ). At higher elevations (e.g., Denver at 5 , 000 ft 5,000\text{ ft} 5 , 000 ft , p ≈ 12.23 psia p \approx 12.23\text{ psia} p ≈ 12.23 psia ), atmospheric pressure decreases, causing the humidity ratio ω = 0.622 p w p − p w \omega = 0.622 \frac{p_w}{p - p_w} ω = 0.622 p − p w p w and specific volume v v v to increase for the same dry-bulb temperature and dew point. Always use an elevation-corrected chart or Dalton's law formulas when solving non-sea-level problems.
3. Core Psychrometric Air-Conditioning Processes
Every HVAC cycle decomposes into basic linear or multi-step psychrometric transformations on the chart. +-----------------------------------------------------------------------------------------+
- | SUMMARY OF CORE PSYCHROMETRIC PROCESSES |
- | |
- | [2] Humidification Only (\Delta T_db = 0, \omega \uparrow) |
- | ^ |
- | [6] Evaporative Cooling | [1] Sensible Heating |
- | (Adiabatic Saturation) | (\omega = const, T_db \uparrow) |
- | \ | / |
- | \ | / |
- | \ | / |
- | <---------------------- [0] ----------------------> |
- | / State Point \ |
- | / | \ |
- | / | \ |
- | [4] Cooling & Dehumidification | [5] Chemical Dehumidification |
- | (T_db \downarrow, \omega \downarrow) v (T_db \uparrow, \omega \downarrow) |
- | [3] Dehumidification Only (\Delta T_db = 0, \omega \downarrow) |
- +-----------------------------------------------------------------------------------------+
- 1. Sensible Heating and Cooling
Sensible processes occur when moist air passes over a heating or cooling coil whose surface temperature remains above the dew-point temperature of the entering air ( T surface > T d p T_{\text{surface}} > T_{dp} T surface > T d p ). Moisture is neither added nor removed ( Δ ω = 0 \Delta \omega = 0 Δ ω = 0 ). q ˙ s = m ˙ d a c p a Δ T = ( ρ ⋅ C F M ⋅ 60 ) c p a Δ T \dot{q}_s = \dot{m}_{da} c_{pa} \Delta T = (\rho \cdot CFM \cdot 60) c_{pa} \Delta T q ˙ s = m ˙ d a c p a Δ T = ( ρ ⋅ CFM ⋅ 60 ) c p a Δ T
Applying standard sea-level air properties ( ρ = 0.075 lbm/ft 3 \rho = 0.075\text{ lbm/ft}^3 ρ = 0.075 lbm/ft 3 , c p a = 0.240 BTU/lbm ⋅ ∘ F c_{pa} = 0.240\text{ BTU/lbm}\cdot^\circ\text{F} c p a = 0.240 BTU/lbm ⋅ ∘ F ): q ˙ s = ( 0.075 ) ( 60 ) ( 0.240 ) × C F M × Δ T = 1.08 × C F M × Δ T [ BTU/hr ] \dot{q}_s = (0.075)(60)(0.240) \times CFM \times \Delta T = 1.08 \times CFM \times \Delta T \quad [\text{BTU/hr}] q ˙ s = ( 0.075 ) ( 60 ) ( 0.240 ) × CFM × Δ T = 1.08 × CFM × Δ T [ BTU/hr ]
In SI units ( ρ = 1.204 kg/m 3 \rho = 1.204\text{ kg/m}^3 ρ = 1.204 kg/m 3 , c p a = 1.006 kJ/kg ⋅ K c_{pa} = 1.006\text{ kJ/kg}\cdot\text{K} c p a = 1.006 kJ/kg ⋅ K ): q ˙ s = ( 1.204 ) ( 1.006 ) × V ˙ L / s × Δ T = 1.23 × V ˙ L / s × Δ T [ W ] \dot{q}_s = (1.204)(1.006) \times \dot{V}_{L/s} \times \Delta T = 1.23 \times \dot{V}_{L/s} \times \Delta T \quad [\text{W}] q ˙ s = ( 1.204 ) ( 1.006 ) × V ˙ L / s × Δ T = 1.23 × V ˙ L / s × Δ T [ W ]
2. Cooling and Dehumidification
When air passes over a cooling coil whose effective surface temperature is below the entering air dew point ( T coil < T d p T_{\text{coil}} < T_{dp} T coil < T d p ), moisture condenses out of the air stream. The process line on the psychrometric chart curves downward and leftward toward the Apparatus Dew Point (ADP) , which represents the effective coil surface temperature on the saturation curve ( ϕ = 100 % \phi = 100\% ϕ = 100% ). +-----------------------------------------------------------------------------------------+
- | COIL BYPASS FACTOR & APPARATUS DEW POINT |
- | |
- | Saturation Curve |
- | ,-' |
- | ,' |
- | ,' [ADP] (T_adp, \omega_adp) |
- | / \ |
- | / \______ [Leaving Air Point: 2] (T_db,2, \omega_2) |
- | / \ |
- | / \______ [Entering Air Point: 1] (T_db,1, \omega_1) |
- | / |
- +-----------------------------------------------------------------------------------------+
Bypass Factor ( B F BF BF ): The fraction of total airflow that passes through the cooling coil completely unconditioned: B F = T d b , 2 − T A D P T d b , 1 − T A D P = ω 2 − ω A D P ω 1 − ω A D P = h 2 − h A D P h 1 − h A D P BF = \frac{T_{db,2} - T_{ADP}}{T_{db,1} - T_{ADP}} = \frac{\omega_2 - \omega_{ADP}}{\omega_1 - \omega_{ADP}} = \frac{h_2 - h_{ADP}}{h_1 - h_{ADP}} BF = T d b , 1 − T A D P T d b , 2 − T A D P = ω 1 − ω A D P ω 2 − ω A D P = h 1 − h A D P h 2 − h A D P
Contact Factor ( C F CF CF ): The fraction of total air that comes into direct contact with the coil surface and achieves thermal equilibrium at the ADP: C F = 1 − B F CF = 1 - BF CF = 1 − BF
3. Latent Heat and Total Heat Equations
Latent Heat Transfer Rate (Moisture Addition or Removal): q ˙ L = m ˙ d a h f g Δ ω = ( 0.075 ) ( 60 ) ( 1076 ) × C F M × Δ ω = 4840 × C F M × Δ ω [ BTU/hr ] \dot{q}_L = \dot{m}_{da} h_{fg} \Delta \omega = (0.075)(60)(1076) \times CFM \times \Delta \omega = 4840 \times CFM \times \Delta \omega \quad [\text{BTU/hr}] q ˙ L = m ˙ d a h f g Δ ω = ( 0.075 ) ( 60 ) ( 1076 ) × CFM × Δ ω = 4840 × CFM × Δ ω [ BTU/hr ] When moisture is given in grains per pound of dry air ( W g r W_{gr} W g r ): q ˙ L = 4840 7000 × C F M × Δ W g r ≈ 0.69 × C F M × Δ W g r [ BTU/hr ] \dot{q}_L = \frac{4840}{7000} \times CFM \times \Delta W_{gr} \approx 0.69 \times CFM \times \Delta W_{gr} \quad [\text{BTU/hr}] q ˙ L = 7000 4840 × CFM × Δ W g r ≈ 0.69 × CFM × Δ W g r [ BTU/hr ]
Total Heat Transfer Rate (Enthalpy Method): q ˙ t = q ˙ s + q ˙ L = m ˙ d a Δ h = ( 0.075 ) ( 60 ) × C F M × Δ h = 4.5 × C F M × Δ h [ BTU/hr ] \dot{q}_t = \dot{q}_s + \dot{q}_L = \dot{m}_{da} \Delta h = (0.075)(60) \times CFM \times \Delta h = 4.5 \times CFM \times \Delta h \quad [\text{BTU/hr}] q ˙ t = q ˙ s + q ˙ L = m ˙ d a Δ h = ( 0.075 ) ( 60 ) × CFM × Δ h = 4.5 × CFM × Δ h [ BTU/hr ] In SI units: q ˙ t = 1.20 × V ˙ L / s × Δ h [ W ] \dot{q}_t = 1.20 \times \dot{V}_{L/s} \times \Delta h \quad [\text{W}] q ˙ t = 1.20 × V ˙ L / s × Δ h [ W ]
4. Sensible Heat Ratio (SHR)
The ratio of sensible heat removal rate to total heat removal rate: S H R = q ˙ s q ˙ t = q ˙ s q ˙ s + q ˙ L SHR = \frac{\dot{q}_s}{\dot{q}_t} = \frac{\dot{q}_s}{\dot{q}_s + \dot{q}_L} S H R = q ˙ t q ˙ s = q ˙ s + q ˙ L q ˙ s
Room Sensible Heat Ratio (RSHR): q ˙ s , room q ˙ t , room \frac{\dot{q}_{s,\text{room}}}{\dot{q}_{t,\text{room}}} q ˙ t , room q ˙ s , room , defining the slope of the condition line between the supply air state and the room design state.
Grand Sensible Heat Ratio (GSHR): q ˙ s , total q ˙ t , total \frac{\dot{q}_{s,\text{total}}}{\dot{q}_{t,\text{total}}} q ˙ t , total q ˙ s , total , defining the slope of the process line across the central cooling coil.
4. Adiabatic Mixing of Two Air Streams
In standard air handling systems, outdoor ventilation air (Stream 1) mixes adiabatically with recirculated return air (Stream 2) to produce mixed air (Stream 3) entering the conditioning coils. +-----------------------------------------------------------------------------------------+
- | ADIABATIC AIR STREAM MIXING SCHEMATIC |
- | |
- | Outdoor Air (Stream 1) ---> [ MIXING ] ---> Mixed Air (Stream 3) |
- | (m_1, T_1, \omega_1, h_1) [ PLENUM ] (m_3 = m_1 + m_2, T_3, \omega_3, h_3) |
- | Return Air (Stream 2) ---> [ ] |
- | (m_2, T_2, \omega_2, h_2) |
- +-----------------------------------------------------------------------------------------+
Conservation Governing Equations:
Dry Air Mass Balance: m ˙ d a , 3 = m ˙ d a , 1 + m ˙ d a , 2 \dot{m}_{da,3} = \dot{m}_{da,1} + \dot{m}_{da,2} m ˙ d a , 3 = m ˙ d a , 1 + m ˙ d a , 2
Energy Balance: m ˙ d a , 1 h 1 + m ˙ d a , 2 h 2 = m ˙ d a , 3 h 3 ⟹ h 3 = m ˙ d a , 1 h 1 + m ˙ d a , 2 h 2 m ˙ d a , 1 + m ˙ d a , 2 \dot{m}_{da,1} h_1 + \dot{m}_{da,2} h_2 = \dot{m}_{da,3} h_3 \implies h_3 = \frac{\dot{m}_{da,1} h_1 + \dot{m}_{da,2} h_2}{\dot{m}_{da,1} + \dot{m}_{da,2}} m ˙ d a , 1 h 1 + m ˙ d a , 2 h 2 = m ˙ d a , 3 h 3 ⟹ h 3 = m ˙ d a , 1 + m ˙ d a , 2 m ˙ d a , 1 h 1 + m ˙ d a , 2 h 2
Moisture Balance: m ˙ d a , 1 ω 1 + m ˙ d a , 2 ω 2 = m ˙ d a , 3 ω 3 ⟹ ω 3 = m ˙ d a , 1 ω 1 + m ˙ d a , 2 ω 2 m ˙ d a , 1 + m ˙ d a , 2 \dot{m}_{da,1} \omega_1 + \dot{m}_{da,2} \omega_2 = \dot{m}_{da,3} \omega_3 \implies \omega_3 = \frac{\dot{m}_{da,1} \omega_1 + \dot{m}_{da,2} \omega_2}{\dot{m}_{da,1} + \dot{m}_{da,2}} m ˙ d a , 1 ω 1 + m ˙ d a , 2 ω 2 = m ˙ d a , 3 ω 3 ⟹ ω 3 = m ˙ d a , 1 + m ˙ d a , 2 m ˙ d a , 1 ω 1 + m ˙ d a , 2 ω 2
Dry-Bulb Temperature Approximation (Volumetric Basis): T d b , 3 ≈ C F M 1 T d b , 1 + C F M 2 T d b , 2 C F M 1 + C F M 2 T_{db,3} \approx \frac{CFM_1 T_{db,1} + CFM_2 T_{db,2}}{CFM_1 + CFM_2} T d b , 3 ≈ CF M 1 + CF M 2 CF M 1 T d b , 1 + CF M 2 T d b , 2
The Psychrometric Lever Rule
The mixed state point (Point 3) lies on the straight line connecting Point 1 and Point 2 on the psychrometric chart. The line segment lengths are inversely proportional to the mass flow rates: Distance ( 1 − 3 ) Distance ( 1 − 2 ) = m ˙ d a , 2 m ˙ d a , 1 + m ˙ d a , 2 = C F M 2 C F M 3 \frac{\text{Distance }(1-3)}{\text{Distance }(1-2)} = \frac{\dot{m}_{da,2}}{\dot{m}_{da,1} + \dot{m}_{da,2}} = \frac{CFM_2}{CFM_3} Distance ( 1 − 2 ) Distance ( 1 − 3 ) = m ˙ d a , 1 + m ˙ d a , 2 m ˙ d a , 2 = CF M 3 CF M 2 T d b , 3 − T d b , 1 T d b , 2 − T d b , 3 = m ˙ d a , 2 m ˙ d a , 1 \frac{T_{db,3} - T_{db,1}}{T_{db,2} - T_{db,3}} = \frac{\dot{m}_{da,2}}{\dot{m}_{da,1}} T d b , 2 − T d b , 3 T d b , 3 − T d b , 1 = m ˙ d a , 1 m ˙ d a , 2
5. Evaporative Cooling (Adiabatic Saturation)
In direct evaporative cooling (swamp coolers), unsaturated air passes through a wetted porous medium without external heat transfer ( q ˙ = 0 \dot{q} = 0 q ˙ = 0 ).
The sensible heat of the air stream provides the latent heat required to vaporize the liquid water.
Thermodynamic Path: The process moves upward and leftward along a constant wet-bulb temperature / constant enthalpy line ( T w b = const T_{wb} = \text{const} T w b = const , h ≈ const h \approx \text{const} h ≈ const ).
Outcome: Dry-bulb temperature decreases ( T d b ↓ T_{db} \downarrow T d b ↓ ), while humidity ratio increases ( ω ↑ \omega \uparrow ω ↑ ) and relative humidity increases ( ϕ ↑ \phi \uparrow ϕ ↑ ).
Direct Evaporative Saturation Effectiveness ( ϵ evap \epsilon_{\text{evap}} ϵ evap ): ϵ evap = T d b , in − T d b , out T d b , in − T w b , in \epsilon_{\text{evap}} = \frac{T_{db,\text{in}} - T_{db,\text{out}}}{T_{db,\text{in}} - T_{wb,\text{in}}} ϵ evap = T d b , in − T w b , in T d b , in − T d b , out
Indirect Evaporative Cooling: Primary air passes through dry channels of a heat exchanger while secondary air is cooled evaporatively in adjacent wet channels, providing sensible cooling at constant moisture content ( ω = const \omega = \text{const} ω = const ) without adding humidity to the supply air.
- 6. Step-by-Step Worked Engineering Problem
- Problem Statement
An air handling unit (AHU) serves a commercial office zone. The space design condition is 75.0 ∘ F T d b 75.0^\circ\text{F } T_{db} 75. 0 ∘ F T d b and 50 % RH 50\%\text{ RH} 50% RH ( h room = 28.10 BTU/lbm d a , ω room = 0.00925 lbm/lbm d a h_{\text{room}} = 28.10\text{ BTU/lbm}_{da}, \omega_{\text{room}} = 0.00925\text{ lbm/lbm}_{da} h room = 28.10 BTU/lbm d a , ω room = 0.00925 lbm/lbm d a ). The total supply airflow rate is 12 , 000 CFM 12,000\text{ CFM} 12 , 000 CFM .
Outdoor Air (OA): 3 , 000 CFM 3,000\text{ CFM} 3 , 000 CFM at 95.0 ∘ F T d b 95.0^\circ\text{F } T_{db} 95. 0 ∘ F T d b and 76.0 ∘ F T w b 76.0^\circ\text{F } T_{wb} 76. 0 ∘ F T w b ( h OA = 39.40 BTU/lbm d a , ω OA = 0.01480 lbm/lbm d a h_{\text{OA}} = 39.40\text{ BTU/lbm}_{da}, \omega_{\text{OA}} = 0.01480\text{ lbm/lbm}_{da} h OA = 39.40 BTU/lbm d a , ω OA = 0.01480 lbm/lbm d a ).
Return Air (RA): 9 , 000 CFM 9,000\text{ CFM} 9 , 000 CFM at room conditions ( 75.0 ∘ F T d b , 50 % RH 75.0^\circ\text{F } T_{db}, 50\%\text{ RH} 75. 0 ∘ F T d b , 50% RH ).
The mixed air enters a chilled water cooling coil with an Apparatus Dew Point (ADP) of 52.0 ∘ F 52.0^\circ\text{F} 52. 0 ∘ F ( h ADP = 21.40 BTU/lbm d a , ω ADP = 0.00820 lbm/lbm d a h_{\text{ADP}} = 21.40\text{ BTU/lbm}_{da}, \omega_{\text{ADP}} = 0.00820\text{ lbm/lbm}_{da} h ADP = 21.40 BTU/lbm d a , ω ADP = 0.00820 lbm/lbm d a ) and a Bypass Factor ( B F BF BF ) of 0.12 0.12 0.12 .
Calculate:
The mixed air dry-bulb temperature ( T d b , m T_{db,m} T d b , m ), enthalpy ( h m h_m h m ), and humidity ratio ( ω m \omega_m ω m ).
The leaving air dry-bulb temperature ( T d b , L T_{db,L} T d b , L ) and enthalpy ( h L h_L h L ).
The total cooling coil capacity required in Tons of Refrigeration (TR).
The coil Sensible Heat Ratio (SHR). +-----------------------------------------------------------------------------------------+
- | AHU COIL CALCULATION SCHEMATIC |
- | |
- | OA: 3,000 CFM, 95°F ----> [ MIXING ] |
- | [ PLENUM ] ---> MIXED AIR ---> [ COOLING COIL ] ---> SUPPLY |
- | RA: 9,000 CFM, 75°F ----> [ ] (T_m, h_m) [ ADP = 52°F ] (T_L, h_L)|
- | [ BF = 0.12 ] |
- +-----------------------------------------------------------------------------------------+
- Step 1: Mixed Air Properties
Fraction of Outdoor Air: x O A = 3 , 000 12 , 000 = 0.25 x_{OA} = \frac{3,000}{12,000} = 0.25 x O A = 12 , 000 3 , 000 = 0.25 , Fraction of Return Air: x R A = 9 , 000 12 , 000 = 0.75 x_{RA} = \frac{9,000}{12,000} = 0.75 x R A = 12 , 000 9 , 000 = 0.75 . T d b , m = x O A T d b , O A + x R A T d b , R A = ( 0.25 ) ( 95.0 ∘ F ) + ( 0.75 ) ( 75.0 ∘ F ) = 23.75 + 56.25 = 80.0 ∘ F T_{db,m} = x_{OA} T_{db,OA} + x_{RA} T_{db,RA} = (0.25)(95.0^\circ\text{F}) + (0.75)(75.0^\circ\text{F}) = 23.75 + 56.25 = 80.0^\circ\text{F} T d b , m = x O A T d b , O A + x R A T d b , R A = ( 0.25 ) ( 95. 0 ∘ F ) + ( 0.75 ) ( 75. 0 ∘ F ) = 23.75 + 56.25 = 80. 0 ∘ F h m = x O A h O A + x R A h R A = ( 0.25 ) ( 39.40 ) + ( 0.75 ) ( 28.10 ) = 9.85 + 21.075 = 30.925 BTU/lbm d a h_m = x_{OA} h_{OA} + x_{RA} h_{RA} = (0.25)(39.40) + (0.75)(28.10) = 9.85 + 21.075 = 30.925\text{ BTU/lbm}_{da} h m = x O A h O A + x R A h R A = ( 0.25 ) ( 39.40 ) + ( 0.75 ) ( 28.10 ) = 9.85 + 21.075 = 30.925 BTU/lbm d a ω m = ( 0.25 ) ( 0.01480 ) + ( 0.75 ) ( 0.00925 ) = 0.00370 + 0.0069375 = 0.010638 lbm/lbm d a \omega_m = (0.25)(0.01480) + (0.75)(0.00925) = 0.00370 + 0.0069375 = 0.010638\text{ lbm/lbm}_{da} ω m = ( 0.25 ) ( 0.01480 ) + ( 0.75 ) ( 0.00925 ) = 0.00370 + 0.0069375 = 0.010638 lbm/lbm d a
Step 2: Leaving Air Conditions from Coil Bypass Factor T d b , L = T A D P + B F ( T d b , m − T A D P ) = 52.0 ∘ F + 0.12 ( 80.0 ∘ F − 52.0 ∘ F ) = 52.0 + 0.12 ( 28.0 ) = 55.36 ∘ F T_{db,L} = T_{ADP} + BF(T_{db,m} - T_{ADP}) = 52.0^\circ\text{F} + 0.12(80.0^\circ\text{F} - 52.0^\circ\text{F}) = 52.0 + 0.12(28.0) = 55.36^\circ\text{F} T d b , L = T A D P + BF ( T d b , m − T A D P ) = 52. 0 ∘ F + 0.12 ( 80. 0 ∘ F − 52. 0 ∘ F ) = 52.0 + 0.12 ( 28.0 ) = 55.3 6 ∘ F h L = h A D P + B F ( h m − h A D P ) = 21.40 + 0.12 ( 30.925 − 21.40 ) = 21.40 + 0.12 ( 9.525 ) = 22.543 BTU/lbm d a h_L = h_{ADP} + BF(h_m - h_{ADP}) = 21.40 + 0.12(30.925 - 21.40) = 21.40 + 0.12(9.525) = 22.543\text{ BTU/lbm}_{da} h L = h A D P + BF ( h m − h A D P ) = 21.40 + 0.12 ( 30.925 − 21.40 ) = 21.40 + 0.12 ( 9.525 ) = 22.543 BTU/lbm d a ω L = ω A D P + B F ( ω m − ω A D P ) = 0.00820 + 0.12 ( 0.010638 − 0.00820 ) = 0.008493 lbm/lbm d a \omega_L = \omega_{ADP} + BF(\omega_m - \omega_{ADP}) = 0.00820 + 0.12(0.010638 - 0.00820) = 0.008493\text{ lbm/lbm}_{da} ω L = ω A D P + BF ( ω m − ω A D P ) = 0.00820 + 0.12 ( 0.010638 − 0.00820 ) = 0.008493 lbm/lbm d a
Step 3: Total Cooling Coil Capacity q ˙ t = 4.5 × C F M × ( h m − h L ) = 4.5 × 12 , 000 × ( 30.925 − 22.543 ) = 54 , 000 × 8.382 = 452 , 628 BTU/hr \dot{q}_t = 4.5 \times CFM \times (h_m - h_L) = 4.5 \times 12,000 \times (30.925 - 22.543) = 54,000 \times 8.382 = 452,628\text{ BTU/hr} q ˙ t = 4.5 × CFM × ( h m − h L ) = 4.5 × 12 , 000 × ( 30.925 − 22.543 ) = 54 , 000 × 8.382 = 452 , 628 BTU/hr Cooling Capacity in TR = 452 , 628 BTU/hr 12 , 000 BTU/hr ⋅ TR = 37.72 TR \text{Cooling Capacity in TR} = \frac{452,628\text{ BTU/hr}}{12,000\text{ BTU/hr}\cdot\text{TR}} = 37.72\text{ TR} Cooling Capacity in TR = 12 , 000 BTU/hr ⋅ TR 452 , 628 BTU/hr = 37.72 TR
Step 4: Sensible Coil Capacity & SHR q ˙ s = 1.08 × C F M × ( T d b , m − T d b , L ) = 1.08 × 12 , 000 × ( 80.0 − 55.36 ) = 12 , 960 × 24.64 = 319 , 334 BTU/hr \dot{q}_s = 1.08 \times CFM \times (T_{db,m} - T_{db,L}) = 1.08 \times 12,000 \times (80.0 - 55.36) = 12,960 \times 24.64 = 319,334\text{ BTU/hr} q ˙ s = 1.08 × CFM × ( T d b , m − T d b , L ) = 1.08 × 12 , 000 × ( 80.0 − 55.36 ) = 12 , 960 × 24.64 = 319 , 334 BTU/hr S H R = q ˙ s q ˙ t = 319 , 334 452 , 628 = 0.7055 ≈ 0.71 SHR = \frac{\dot{q}_s}{\dot{q}_t} = \frac{319,334}{452,628} = 0.7055 \approx 0.71 S H R = q ˙ t q ˙ s = 452 , 628 319 , 334 = 0.7055 ≈ 0.71
7. Common Exam Traps & PE Pro-Tips
Trap 1 — Using Standard Air Multipliers at High Elevation: The constants 1.08 1.08 1.08 , 4840 4840 4840 , and 4.5 4.5 4.5 are valid only at standard sea-level air density ( ρ = 0.075 lbm/ft 3 \rho = 0.075\text{ lbm/ft}^3 ρ = 0.075 lbm/ft 3 , p = 14.696 psia p = 14.696\text{ psia} p = 14.696 psia ). At non-standard altitudes, you must calculate mass flow directly using m ˙ = ρ V ˙ = p V ˙ R a T \dot{m} = \rho \dot{V} = \frac{p \dot{V}}{R_a T} m ˙ = ρ V ˙ = R a T p V ˙ and apply q ˙ s = m ˙ c p Δ T \dot{q}_s = \dot{m} c_p \Delta T q ˙ s = m ˙ c p Δ T and q ˙ t = m ˙ Δ h \dot{q}_t = \dot{m} \Delta h q ˙ t = m ˙ Δ h .
Trap 2 — Misinterpreting Apparatus Dew Point Location: The Apparatus Dew Point (ADP) is always located on the saturation curve ( ϕ = 100 % \phi = 100\% ϕ = 100% ). It represents the effective coil surface temperature if the coil had a bypass factor of zero ( B F = 0 BF = 0 BF = 0 ). Leaving air dry-bulb is always higher than the ADP whenever B F > 0 BF > 0 BF > 0 .
Trap 3 — Mixing Moisture Units: When computing latent heat with humidity ratio ω \omega ω in lbm w / lbm d a \text{lbm}_w/\text{lbm}_{da} lbm w / lbm d a , use the 4840 4840 4840 constant. When using moisture in grains per pound ( W g r W_{gr} W g r ), use the 0.69 0.69 0.69 constant ( 4840 / 7000 = 0.691 4840 / 7000 = 0.691 4840/7000 = 0.691 ).