6.3 Vapor-Compression Refrigeration Cycles & Refrigerant Properties
PE Mechanical Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview, Reference Handbook & Mechanical Engineering Fundamentals
1.1 NCEES PE Mechanical CBT Format, Three Disciplines & Reference Handbook Strategy 1.2 Engineering Economics, Cash Flow & Project Evaluation and Scheduling 1.3 Units, Dimensional Analysis & Physical Constants 1.4 Statics, Dynamics & Mechanical Equilibrium
2 Chapter 2: Mechanical Design & Analysis (Stress, Failure Theories & Components)
2.1 Stress, Strain, Principal Stresses & Combined Loading 2.2 Static Failure Theories for Ductile and Brittle Materials 2.3 Fatigue Analysis, S-N Curves & Fluctuating Stresses 2.4 Pressure Vessels, Column Buckling & Spring Design 2.5 Threaded Fasteners, Welded Connections & Mechanical Joints
3 Chapter 3: Mechanical Power Transmission, Mechanisms & Vibrations
3.1 Shaft Sizing, Torsional Deflection & Critical Speeds 3.2 Spur, Helical, Bevel & Worm Gears and Epicyclic Gear Trains 3.3 Rolling-Element & Journal Bearings, Power Screws, Clutches, Brakes & Flywheels 3.4 Four-Bar Linkages, Cam-Follower Systems & Kinematics 3.5 Single-DOF and 2-DOF Vibrations, Damping & Dynamic Balancing
4 Chapter 4: Thermal & Fluid Systems
4.1 Fluid Statics, Manometry, Submerged Surfaces & Buoyancy 4.2 Incompressible Pipe Flow, Darcy-Weisbach & Minor Losses 4.3 Pump Selection, System Curves, NPSH & Cavitation 4.4 Steady & Transient Conduction, Forced & Natural Convection 4.5 Radiation Heat Transfer, View Factors & Heat Exchanger Sizing (LMTD/NTU)
5 Chapter 5: Power Plants & Energy Conversion Systems
5.1 Thermodynamic Properties, Pure Substances & 1st/2nd Laws 5.2 Vapor Power Cycles (Rankine, Superheat, Reheat & Regeneration) 5.3 Gas Power Cycles (Brayton, Otto, Diesel, Dual & Combined Cycle) 5.4 Combustion Stoichiometry, Flue Gas Analysis & Thermochemistry 5.5 Turbomachinery, Compressible Flow & Nozzles, Renewables & Energy Storage
6 Chapter 6: HVAC & Refrigeration Systems
6.1 Psychrometric Principles & Air-Conditioning Processes 6.2 Cooling & Heating Load Calculations (CLTD/SCL/CLF & Heat Balance) 6.3 Vapor-Compression Refrigeration Cycles & Refrigerant Properties 6.4 Refrigeration Equipment (Compressors, Evaporators, Condensers, Expansion Devices) & Safety Codes 6.5 Air Distribution, Duct Design, Fans & Hydronic Water Networks 6.6 Energy Recovery Devices, HVAC Acoustics & Vibration Isolation
7 Chapter 7: Materials, Manufacturing & Processing
7.1 Ferrous/Non-Ferrous Metals, Polymers, Ceramics & Composites 7.2 Iron-Carbon Equilibrium Phase Diagram & Heat Treatment Processes 7.3 Corrosion, Wear, Creep, Hydrogen Embrittlement & Fracture Mechanics 7.4 Casting, Metal Forming, Forging, Stamping & Powder Metallurgy 7.5 Machining Dynamics, Tool Wear, Welding Metallurgy & Non-Destructive Examination (NDE)
8 Chapter 8: Measurements, Controls, Codes & Engineering Ethics
8.1 Temperature, Pressure, Flow & Strain Transducers and Signal Conditioning 8.2 Feedback Control Loops, PID Tuning, Frequency Response & Stability 8.3 ASME Boiler & Pressure Vessel Code, ASHRAE, OSHA & NFPA Safety Standards 8.4 NCEES Model Rules, Engineering Ethics & Professional Seal Liability
6.3 Vapor-Compression Refrigeration Cycles & Refrigerant Properties
Key Takeaways Explain This Topic AI
The standard vapor-compression refrigeration cycle comprises four thermodynamic processes: isentropic compression ( 1 → 2 1 \to 2 1 → 2 ), constant-pressure heat rejection ( 2 → 3 2 \to 3 2 → 3 ), isenthalpic throttling ( 3 → 4 3 \to 4 3 → 4 ), and constant-pressure heat absorption ( 4 → 1 4 \to 1 4 → 1 ).
Refrigerating effect ( R E = h 1 − h 4 RE = h_1 - h_4 RE = h 1 − h 4 ) governs refrigerant mass flow rate ( m ˙ = Q ˙ evap / R E \dot{m} = \dot{Q}_{\text{evap}}/RE m ˙ = Q ˙ evap / RE ), while compressor work ( w = h 2 − h 1 w = h_2 - h_1 w = h 2 − h 1 ) determines power requirements ( P = m ˙ w P = \dot{m} w P = m ˙ w ).
Liquid subcooling before the expansion valve increases refrigerating effect with zero additional compressor work, directly boosting cycle COP.
Multi-stage compression with flash intercooling optimizes intermediate pressure ( P int = P evap P cond P_{\text{int}} = \sqrt{P_{\text{evap}} P_{\text{cond}}} P int = P evap P cond ), drastically reducing high-stage compressor discharge temperatures and compressor power.
Absorption refrigeration replaces the mechanical compressor with a chemical absorber, solution pump, and thermal generator, utilizing working fluid pairs such as H 2 O - L i B r H_2O\text{-}LiBr H 2 O - L i B r or N H 3 - H 2 O NH_3\text{-}H_2O N H 3 - H 2 O .
Last updated: August 2026
Vapor-Compression Refrigeration Cycles & Refrigerant Properties
Vapor-compression refrigeration is the primary thermodynamic cycle used in chillers, split-system heat pumps, commercial freezers, and industrial process cooling. Solving refrigeration problems on the NCEES PE Mechanical exam requires fluent tracking of refrigerant properties across Pressure-Enthalpy ( P - h P\text{-}h P - h ) and Temperature-Entropy ( T - s T\text{-}s T - s ) diagrams, calculating performance metrics ( C O P COP COP , E E R EER EER , kW/ton \text{kW/ton} kW/ton ), evaluating subcooling/superheat adjustments, and optimizing multi-stage systems.
1. The Standard Vapor-Compression Refrigeration Cycle +-----------------------------------------------------------------------------------------+
- | STANDARD VAPOR-COMPRESSION CYCLE (P-h DIAGRAM) |
- | |
- | Pressure (P) |
- | ^ Critical Point |
- | | | |
- | | ,-'''''''-. |
- | | P_cond -------+-----------+-------------> [2] Compressor Discharge |
- | | | / [3] q_cond \ [2s] / (Superheated Vapor) |
- | | | +---------------+----------+ |
- | | | |Sat. Liquid |Sat. Vapor |
- | | | h3=h4 | |
- | | P_evap |----+---------------+----------> [1] Evaporator Exit (Superheated Vapor) |
- | | | / [4] q_evap \ / |
- | | v / (Two-Phase Mix) \ / (Isentropic Compression 1->2s) |
- | | +---------------------+-----+ |
- | +------------+---------------------+-----------------------------> Enthalpy (h) |
- | h4 h1 h2s h2 |
- | <----- RE = h1-h4 -----> |
- +-----------------------------------------------------------------------------------------+
The Four Thermodynamic Processes:
Process 1 → 2 1 \to 2 1 → 2 : Vapor Compression (Compressor)
Saturated or slightly superheated refrigerant vapor at low evaporating pressure ( P evap P_{\text{evap}} P evap ) is compressed to high condensing pressure ( P cond P_{\text{cond}} P cond ).
Ideal Compression (Isentropic, s 1 = s 2 s s_1 = s_{2s} s 1 = s 2 s ): w s = h 2 s − h 1 w_{s} = h_{2s} - h_1 w s = h 2 s − h 1
Actual Compression with Isentropic Efficiency ( η c \eta_c η c ): η c = h 2 s − h 1 h 2 − h 1 ⟹ h 2 = h 1 + h 2 s − h 1 η c \eta_c = \frac{h_{2s} - h_1}{h_2 - h_1} \implies h_2 = h_1 + \frac{h_{2s} - h_1}{\eta_c} η c = h 2 − h 1 h 2 s − h 1 ⟹ h 2 = h 1 + η c h 2 s − h 1 w comp, actual = h 2 − h 1 w_{\text{comp, actual}} = h_2 - h_1 w comp, actual = h 2 − h 1
Process 2 → 3 2 \to 3 2 → 3 : Heat Rejection (Condenser)
Superheated vapor enters the condenser, desuperheats, condenses at constant temperature and pressure ( T cond , P cond T_{\text{cond}}, P_{\text{cond}} T cond , P cond ), and is subcooled before exiting: q cond = h 2 − h 3 [ BTU/lbm or kJ/kg ] q_{\text{cond}} = h_2 - h_3 \quad [\text{BTU/lbm or kJ/kg}] q cond = h 2 − h 3 [ BTU/lbm or kJ/kg ]
Process 3 → 4 3 \to 4 3 → 4 : Throttling / Expansion (Expansion Valve)
High-pressure subcooled or saturated liquid undergoes adiabatic, irreversible throttling across an expansion valve (TXV/EEV) or capillary tube to evaporator pressure ( P evap P_{\text{evap}} P evap ).
Constant Enthalpy (Isenthalpic): h 4 = h 3 h_4 = h_3 h 4 = h 3
As pressure drops below the saturation curve, a portion of the liquid flashes into vapor (Flash Gas Fraction x 4 = h 4 − h f h f g x_4 = \frac{h_4 - h_f}{h_{fg}} x 4 = h f g h 4 − h f ).
Process 4 → 1 4 \to 1 4 → 1 : Heat Absorption (Evaporator)
Low-pressure two-phase mixture absorbs heat from the conditioned space or chilled water stream, boiling at constant pressure ( P evap P_{\text{evap}} P evap ) until fully vaporized and superheated: R E = q evap = h 1 − h 4 = h 1 − h 3 [ BTU/lbm or kJ/kg ] RE = q_{\text{evap}} = h_1 - h_4 = h_1 - h_3 \quad [\text{BTU/lbm or kJ/kg}] RE = q evap = h 1 − h 4 = h 1 − h 3 [ BTU/lbm or kJ/kg ]
2. Key Cycle Performance Parameters +-----------------------------------------------------------------------------------------+
- | REFRIGERATION CYCLE FORMULAS SUMMARY |
- | |
- | - Refrigerating Effect: RE = h_1 - h_4 = h_1 - h_3 [BTU/lbm or kJ/kg] |
- | - Refrigerant Mass Flow: \dot{m} = \frac{\dot{Q}_{\text{evap}}}{RE} [lbm/min, kg/s]|
- | - Compressor Work: w_{\text{comp}} = h_2 - h_1 [BTU/lbm or kJ/kg] |
- | - Compressor Power: P_{\text{comp}} = \dot{m} (h_2 - h_1)[BTU/hr, kW, HP] |
| - Condenser Heat Rejection: \dot{Q}_{\text{cond}} = \dot{m} (h_2 - h_3) = \dot{Q}_{\text{evap}} + P_{\text{comp}}|
- | - Coefficient of Perf (Ref):COP_R = \frac{RE}{w_{\text{comp}}} = \frac{h_1 - h_4}{h_2 - h_1}|
- | - Coefficient of Perf (HP): COP_{HP} = \frac{q_{\text{cond}}}{w_{\text{comp}}} = COP_R + 1|
- | - Energy Efficiency Ratio: EER = 3.412 \times COP_R [BTU/(W·hr)] |
- | - Specific Power: \text{kW/ton} = \frac{3.517}{COP_R} = \frac{12}{EER} |
- +-----------------------------------------------------------------------------------------+
- Units of Refrigeration Capacity
Ton of Refrigeration (TR): The rate of heat absorption required to melt 2 , 000 lbm 2,000\text{ lbm} 2 , 000 lbm ( 1 ton 1\text{ ton} 1 ton ) of ice at 32 ∘ F 32^\circ\text{F} 3 2 ∘ F in 24 hours 24\text{ hours} 24 hours ( h i f = 144 BTU/lbm h_{if} = 144\text{ BTU/lbm} h i f = 144 BTU/lbm ): 1 TR = 2000 lbm × 144 BTU/lbm 24 hr = 12 , 000 BTU/hr = 200 BTU/min = 3.517 kW = 4.714 HP 1\text{ TR} = \frac{2000\text{ lbm} \times 144\text{ BTU/lbm}}{24\text{ hr}} = 12,000\text{ BTU/hr} = 200\text{ BTU/min} = 3.517\text{ kW} = 4.714\text{ HP} 1 TR = 24 hr 2000 lbm × 144 BTU/lbm = 12 , 000 BTU/hr = 200 BTU/min = 3.517 kW = 4.714 HP
Carnot Maximum (Theoretical Limit) COP
For an ideal reversible Carnot refrigeration cycle operating between low temperature T L T_L T L ( T evap T_{\text{evap}} T evap ) and high temperature T H T_H T H ( T cond T_{\text{cond}} T cond ) in absolute units ( ∘ R ^\circ\text{R} ∘ R or K \text{K} K ): C O P R , Carnot = T L T H − T L COP_{R,\text{Carnot}} = \frac{T_L}{T_H - T_L} CO P R , Carnot = T H − T L T L C O P H P , Carnot = T H T H − T L = C O P R , Carnot + 1 COP_{HP,\text{Carnot}} = \frac{T_H}{T_H - T_L} = COP_{R,\text{Carnot}} + 1 CO P H P , Carnot = T H − T L T H = CO P R , Carnot + 1
3. Parametric Sensitivity & Real-World Deviations +-----------------------------------------------------------------------------------------+
- | EFFECTS OF SUBCOOLING AND SUPERHEATING |
- | |
- | SUBCOOLING (State 3 -> 3'): |
- | - Decreases liquid enthalpy entering throttling valve (h_3' < h_3). |
- | - Shifts state 4 to the left (h_4' = h_3' < h_4), reducing flash gas fraction. |
- | - Increases Refrigerating Effect: \Delta RE = h_3 - h_3'. |
- | - Requires ZERO additional compressor work -> DIRECT COP INCREASE. |
- | |
- | SUPERHEATING (State 1' -> 1): |
- | - Useful Superheat (in Evaporator): Increases RE; slight increase in work. |
- | - Parasitic Superheat (in Suction Line): Does not contribute to cooling; increases |
- | specific volume (v_1 \uparrow), reducing compressor mass flow and degrading COP. |
- | - Protects compressor against liquid slugging and mechanical damage. |
- +-----------------------------------------------------------------------------------------+
Operating Shift Evaporator Capacity ( Q ˙ evap \dot{Q}_{\text{evap}} Q ˙ evap ) Compressor Work ( w comp w_{\text{comp}} w comp ) Cycle C O P COP COP Discharge Temp ( T 2 T_2 T 2 )
Increase Evaporator Temp ( T e v a p ↑ T_{evap} \uparrow T e v a p ↑ ) Increases Decreases Increases Decreases
Decrease Evaporator Temp ( T e v a p ↓ T_{evap} \downarrow T e v a p ↓ ) Decreases Increases Decreases Increases
Increase Condenser Temp ( T c o n d ↑ T_{cond} \uparrow T co n d ↑ ) Decreases Increases Decreases Increases
Decrease Condenser Temp ( T c o n d ↓ T_{cond} \downarrow T co n d ↓ ) Increases Decreases Increases Decreases
- Add Liquid Subcooling Increases Unchanged Increases Unchanged
- 4. Multi-Stage Compression, Economizers & Cascade Systems
When temperature lifts exceed 70 ∘ F 70^\circ\text{F} 7 0 ∘ F to 100 ∘ F 100^\circ\text{F} 10 0 ∘ F (e.g., in low-temperature refrigeration or heat pump operation at − 20 ∘ F -20^\circ\text{F} − 2 0 ∘ F ambient), single-stage systems suffer severe penalties: pressure ratios exceed 8 : 1 8:1 8 : 1 , compressor volumetric efficiency plunges, and discharge temperatures cause lubricating oil breakdown. +-----------------------------------------------------------------------------------------+
- | TWO-STAGE SYSTEM WITH FLASH TANK ECONOMIZER |
- | |
- | +---> [ High-Stage Comp ] ---> [ Condenser ]---+
- | | |
- | [ Low-Stage Comp ] ---> [ Flash Tank ]-+ |
- | ^ (P_int) | |
- | | +---> [ Economizer TXV ] <---------------------+
- | | | |
- | [ Evaporator ] <----------------------------- [ Main TXV ] |
- +-----------------------------------------------------------------------------------------+
Optimum Intermediate Pressure ( P int P_{\text{int}} P int ):
For a two-stage system operating between P evap P_{\text{evap}} P evap and P cond P_{\text{cond}} P cond , the theoretical optimum interstage pressure that equalizes pressure ratios and minimizes total compressor power is: P int = P evap P cond P_{\text{int}} = \sqrt{P_{\text{evap}} P_{\text{cond}}} P int = P evap P cond
Cascade Refrigeration Systems
For ultra-low temperature applications ( − 40 ∘ F -40^\circ\text{F} − 4 0 ∘ F to − 120 ∘ F -120^\circ\text{F} − 12 0 ∘ F ), two completely isolated refrigeration circuits with different refrigerants are thermally coupled through an intermediate cascade condenser-evaporator :
High-Temperature Loop: Uses medium-pressure refrigerant (e.g., R-134a or R-404A).
Low-Temperature Loop: Uses high-pressure, ultra-low boiling point refrigerant (e.g., R-23 or R-508B).
Energy Balance on Cascade Heat Exchanger: m ˙ l o w ( h dis,low − h liquid,low ) = m ˙ h i g h ( h vap,high − h liquid,high ) \dot{m}_{low} (h_{\text{dis,low}} - h_{\text{liquid,low}}) = \dot{m}_{high} (h_{\text{vap,high}} - h_{\text{liquid,high}}) m ˙ l o w ( h dis,low − h liquid,low ) = m ˙ hi g h ( h vap,high − h liquid,high )
5. Absorption Refrigeration Cycles
Absorption refrigeration utilizes thermal energy (steam, natural gas flame, waste heat, solar thermal) rather than mechanical work to drive the refrigeration cycle. +-----------------------------------------------------------------------------------------+
- | ABSORPTION REFRIGERATION CYCLE SCHEMATIC |
- | |
- | High-Temp Heat (Q_gen) ---> [ GENERATOR ] ---> Refrigerant Vapor |
- | | | |
- | Weak Sol. | +---------v---------+ |
- | v | CONDENSER | |
- | [ HEAT EXCH ] +---------+---------+ |
- | ^ | |
- | Rich Sol. | v |
- | | +---------+---------+ |
- | Heat Rejected (Q_abs) <---- [ ABSORBER ] | EXPANSION | |
- | ^ +---------+---------+ |
- | | | |
- | Pump Work | v |
- | | +---------+---------+ |
- | [ SOLUTION ] | EVAPORATOR | |
- | [ PUMP ] +---------+---------+ |
- | ^ |
- | Cooling Load (Q_evap) --+ |
- +-----------------------------------------------------------------------------------------+
Common Working Fluid Pairs:
Water-Lithium Bromide ( H 2 O - L i B r H_2O\text{-}LiBr H 2 O - L i B r ): Water is the refrigerant; Lithium Bromide is the absorbent. Non-toxic, high efficiency, but limited to above-freezing applications ( T evap > 38 ∘ F T_{\text{evap}} > 38^\circ\text{F} T evap > 3 8 ∘ F ) due to water freezing and risk of LiBr salt crystallization at high concentrations.
Ammonia-Water ( N H 3 - H 2 O NH_3\text{-}H_2O N H 3 - H 2 O ): Ammonia is the refrigerant; Water is the absorbent. Enables sub-freezing operation down to − 40 ∘ F -40^\circ\text{F} − 4 0 ∘ F , but requires a distillation column / rectifier to remove residual water vapor from the ammonia stream.
Performance Metric ( C O P abs COP_{\text{abs}} CO P abs ): C O P abs = Q ˙ evap Q ˙ gen + W pump ≈ Q ˙ evap Q ˙ gen COP_{\text{abs}} = \frac{\dot{Q}_{\text{evap}}}{\dot{Q}_{\text{gen}} + W_{\text{pump}}} \approx \frac{\dot{Q}_{\text{evap}}}{\dot{Q}_{\text{gen}}} CO P abs = Q ˙ gen + W pump Q ˙ evap ≈ Q ˙ gen Q ˙ evap
Typical single-effect C O P abs ≈ 0.65 – 0.75 COP_{\text{abs}} \approx 0.65\text{--}0.75 CO P abs ≈ 0.65 – 0.75 ; double-effect steam chillers achieve C O P abs ≈ 1.1 – 1.2 COP_{\text{abs}} \approx 1.1\text{--}1.2 CO P abs ≈ 1.1 – 1.2 .
- 6. Step-by-Step Worked Engineering Problem
- Problem Statement
An R-134a vapor-compression refrigeration system operates with an evaporator saturation temperature of 10.0 ∘ F 10.0^\circ\text{F} 10. 0 ∘ F ( P evap = 26.65 psia P_{\text{evap}} = 26.65\text{ psia} P evap = 26.65 psia ) and a condenser saturation temperature of 100.0 ∘ F 100.0^\circ\text{F} 100. 0 ∘ F ( P cond = 138.93 psia P_{\text{cond}} = 138.93\text{ psia} P cond = 138.93 psia ). The cooling load is 15.0 TR 15.0\text{ TR} 15.0 TR .
Refrigerant leaves the evaporator superheated by 10.0 ∘ F 10.0^\circ\text{F} 10. 0 ∘ F (at 20.0 ∘ F , h 1 = 106.50 BTU/lbm , s 1 = 0.2265 BTU/lbm ⋅ ∘ R 20.0^\circ\text{F}, h_1 = 106.50\text{ BTU/lbm}, s_1 = 0.2265\text{ BTU/lbm}\cdot^\circ\text{R} 20. 0 ∘ F , h 1 = 106.50 BTU/lbm , s 1 = 0.2265 BTU/lbm ⋅ ∘ R ).
The compressor has an isentropic efficiency of η c = 0.82 \eta_c = 0.82 η c = 0.82 . (At P cond = 138.93 psia P_{\text{cond}} = 138.93\text{ psia} P cond = 138.93 psia and s 2 s = 0.2265 s_{2s} = 0.2265 s 2 s = 0.2265 , ideal isentropic enthalpy h 2 s = 119.50 BTU/lbm h_{2s} = 119.50\text{ BTU/lbm} h 2 s = 119.50 BTU/lbm ).
Liquid leaves the condenser subcooled by 10.0 ∘ F 10.0^\circ\text{F} 10. 0 ∘ F (at 90.0 ∘ F , h 3 = 41.50 BTU/lbm 90.0^\circ\text{F}, h_3 = 41.50\text{ BTU/lbm} 90. 0 ∘ F , h 3 = 41.50 BTU/lbm ).
Calculate:
The Refrigerating Effect ( R E RE RE ).
The refrigerant mass flow rate ( m ˙ \dot{m} m ˙ ) in lbm/min \text{lbm/min} lbm/min .
The actual compressor work ( w actual w_{\text{actual}} w actual ) and required shaft power ( P comp P_{\text{comp}} P comp ) in HP \text{HP} HP .
The rate of condenser heat rejection ( Q ˙ cond \dot{Q}_{\text{cond}} Q ˙ cond ) in BTU/hr \text{BTU/hr} BTU/hr .
The Coefficient of Performance ( C O P R COP_R CO P R ) and E E R EER EER . +-----------------------------------------------------------------------------------------+
- | R-134a CYCLE CALCULATION STEPS |
- | |
- | State 1 (Evap Exit): P1 = 26.65 psia, T1 = 20°F ---> h1 = 106.50 BTU/lbm |
- | State 2s (Ideal Comp): P2 = 138.93 psia, s2s = s1 ---> h2s = 119.50 BTU/lbm |
- | State 3 (Cond Exit): P3 = 138.93 psia, T3 = 90°F ---> h3 = 41.50 BTU/lbm |
- | State 4 (Exp Valve): h4 = h3 ---> h4 = 41.50 BTU/lbm |
- +-----------------------------------------------------------------------------------------+
Step 1: Refrigerating Effect ( R E RE RE ) R E = h 1 − h 4 = 106.50 − 41.50 = 65.00 BTU/lbm RE = h_1 - h_4 = 106.50 - 41.50 = 65.00\text{ BTU/lbm} RE = h 1 − h 4 = 106.50 − 41.50 = 65.00 BTU/lbm
Step 2: Mass Flow Rate ( m ˙ \dot{m} m ˙ ) Q ˙ evap = 15.0 TR × 200 BTU/min ⋅ TR = 3 , 000 BTU/min = 180 , 000 BTU/hr \dot{Q}_{\text{evap}} = 15.0\text{ TR} \times 200\text{ BTU/min}\cdot\text{TR} = 3,000\text{ BTU/min} = 180,000\text{ BTU/hr} Q ˙ evap = 15.0 TR × 200 BTU/min ⋅ TR = 3 , 000 BTU/min = 180 , 000 BTU/hr m ˙ = Q ˙ evap R E = 3 , 000 BTU/min 65.00 BTU/lbm = 46.154 lbm/min \dot{m} = \frac{\dot{Q}_{\text{evap}}}{RE} = \frac{3,000\text{ BTU/min}}{65.00\text{ BTU/lbm}} = 46.154\text{ lbm/min} m ˙ = RE Q ˙ evap = 65.00 BTU/lbm 3 , 000 BTU/min = 46.154 lbm/min
Step 3: Actual Compressor Enthalpy and Power w s = h 2 s − h 1 = 119.50 − 106.50 = 13.00 BTU/lbm w_s = h_{2s} - h_1 = 119.50 - 106.50 = 13.00\text{ BTU/lbm} w s = h 2 s − h 1 = 119.50 − 106.50 = 13.00 BTU/lbm w actual = w s η c = 13.00 0.82 = 15.854 BTU/lbm w_{\text{actual}} = \frac{w_s}{\eta_c} = \frac{13.00}{0.82} = 15.854\text{ BTU/lbm} w actual = η c w s = 0.82 13.00 = 15.854 BTU/lbm h 2 = h 1 + w actual = 106.50 + 15.854 = 122.354 BTU/lbm h_2 = h_1 + w_{\text{actual}} = 106.50 + 15.854 = 122.354\text{ BTU/lbm} h 2 = h 1 + w actual = 106.50 + 15.854 = 122.354 BTU/lbm P comp = m ˙ w actual = ( 46.154 lbm/min ) × ( 15.854 BTU/lbm ) = 731.73 BTU/min P_{\text{comp}} = \dot{m} w_{\text{actual}} = (46.154\text{ lbm/min}) \times (15.854\text{ BTU/lbm}) = 731.73\text{ BTU/min} P comp = m ˙ w actual = ( 46.154 lbm/min ) × ( 15.854 BTU/lbm ) = 731.73 BTU/min P comp = 731.73 BTU/min 42.418 BTU/min ⋅ HP = 17.25 HP ( 12.86 kW ) P_{\text{comp}} = \frac{731.73\text{ BTU/min}}{42.418\text{ BTU/min}\cdot\text{HP}} = 17.25\text{ HP} \quad (12.86\text{ kW}) P comp = 42.418 BTU/min ⋅ HP 731.73 BTU/min = 17.25 HP ( 12.86 kW )
Step 4: Condenser Heat Rejection Rate Q ˙ cond = m ˙ ( h 2 − h 3 ) = ( 46.154 lbm/min ) × ( 122.354 − 41.50 ) = 46.154 × 80.854 = 3 , 731.73 BTU/min \dot{Q}_{\text{cond}} = \dot{m} (h_2 - h_3) = (46.154\text{ lbm/min}) \times (122.354 - 41.50) = 46.154 \times 80.854 = 3,731.73\text{ BTU/min} Q ˙ cond = m ˙ ( h 2 − h 3 ) = ( 46.154 lbm/min ) × ( 122.354 − 41.50 ) = 46.154 × 80.854 = 3 , 731.73 BTU/min Q ˙ cond = 3 , 731.73 × 60 = 223 , 904 BTU/hr \dot{Q}_{\text{cond}} = 3,731.73 \times 60 = 223,904\text{ BTU/hr} Q ˙ cond = 3 , 731.73 × 60 = 223 , 904 BTU/hr
(Note: Q ˙ cond = Q ˙ evap + P comp = 180 , 000 + ( 731.73 × 60 ) = 223 , 904 BTU/hr \dot{Q}_{\text{cond}} = \dot{Q}_{\text{evap}} + P_{\text{comp}} = 180,000 + (731.73 \times 60) = 223,904\text{ BTU/hr} Q ˙ cond = Q ˙ evap + P comp = 180 , 000 + ( 731.73 × 60 ) = 223 , 904 BTU/hr balances exactly).
Step 5: System COP and EER C O P R = R E w actual = 65.00 BTU/lbm 15.854 BTU/lbm = 4.10 COP_R = \frac{RE}{w_{\text{actual}}} = \frac{65.00\text{ BTU/lbm}}{15.854\text{ BTU/lbm}} = 4.10 CO P R = w actual RE = 15.854 BTU/lbm 65.00 BTU/lbm = 4.10 E E R = 3.412 × C O P R = 3.412 × 4.10 = 13.99 BTU/W ⋅ hr EER = 3.412 \times COP_R = 3.412 \times 4.10 = 13.99\text{ BTU/W}\cdot\text{hr} EER = 3.412 × CO P R = 3.412 × 4.10 = 13.99 BTU/W ⋅ hr
7. Common Exam Traps & PE Pro-Tips
Trap 1 — Carnot COP Temperature Scale: Carnot equations require absolute temperatures ( ∘ R = ∘ F + 459.67 ^\circ\text{R} = ^\circ\text{F} + 459.67 ∘ R = ∘ F + 459.67 or K = ∘ C + 273.15 \text{K} = ^\circ\text{C} + 273.15 K = ∘ C + 273.15 ). Using ∘ F ^\circ\text{F} ∘ F or ∘ C ^\circ\text{C} ∘ C will produce completely incorrect results.
Trap 2 — Throttling Process is Isenthalpic ( h = const h = \text{const} h = const ), NOT Isentropic ( s ≠ const s \neq \text{const} s = const ): The expansion valve is highly irreversible, generating entropy ( Δ s > 0 \Delta s > 0 Δ s > 0 ) while preserving enthalpy ( h 3 = h 4 h_3 = h_4 h 3 = h 4 ).
Trap 3 — Isentropic Efficiency Direction: Remember that compressor isentropic efficiency is defined as η c = w s / w actual \eta_c = w_s / w_{\text{actual}} η c = w s / w actual , which ensures actual power input is always greater than ideal isentropic work.