Study guide

Concrete and Masonry Test Methods

PE Civil: Structural Exam

Track your progress as you read

Finished sections get a check mark.

1 Exam Identity and Reference Workflow

2026 PE Civil: Structural Identity, Format, and Scoring Electronic Handbook, Design Standards, Units, and Version Control

2 Chapter 2: Gravity and Construction Loads

2.1 Dead Loads and Self-Weight 2.2 Live Loads, Reduction, and Load Placement 2.3 Construction-Stage Loads

3 Environmental Loads

Wind Loads and Pressure Paths Seismic Loads and Lateral Force Distribution Snow, Rain, and Ice Loads

4 Moving, Impact, and Lateral Soil Loads

Vehicular, Crane, and Other Moving Loads Impact and Dynamic Allowances Earth Pressure and Surcharge Loads

5 Chapter 5: Load Paths and Combinations

5.1 Tributary Areas and Complete Vertical/Lateral Load Paths 5.2 Strength and Service Load Combinations

6 Reactions, Diagrams, and Basic Axial Effects

Free-Body Diagrams, Reactions, Shear, and Moment Qualitative Diagrams, Influence Lines, and Critical Placement Axial Tension, Compression, and Deformation

7 Chapter 7: Axial Systems and Shear Effects

7.1 Trusses, Braces, and Column Axial Force 7.2 Shear Stress, Shear Flow, and Built-Up Sections 7.3 One-Way, Two-Way, Punching, and Interface Shear Effects

8 Flexure

Section Properties and Elastic Flexural Stress Beam and Slab Flexural Load Effects Biaxial and Unsymmetrical Flexure

9 Combined Stress and Deflection

Combined Axial and Flexural Stress Principal Stress, Mohr's Circle, and Combined Shear Elastic Deflection Methods

10 Chapter 10: Serviceability, Torsion, and Stability

10.1 Serviceability: Deflection, Drift, Vibration, and Ponding 10.2 Torsion and Warping Effects 10.3 Buckling, Effective Length, and Second-Order Stability

11 Fatigue, Robustness, Thermal, and Bearing Effects

Fatigue and Progressive-Collapse Concepts Thermal Deformation and Bearing/Contact Stress

12 Inspections, Submittals, and Adjacent Facilities

Special Inspections and Verification Duties Shop Drawings, Submittals, RFIs, and Delegated Design Construction Effects on Adjacent Facilities

13 Chapter 13: Temporary Works and Safety

13.1 Formwork, Falsework, Scaffolding, Shoring/Reshoring, Bracing, and Anchorage 13.2 Construction, Roadside, and Work-Zone Safety

14 Soils and Core Concrete Properties

Soil Phase Relationships and Classification Soil Strength, Permeability, and Compressibility Fresh and Hardened Concrete Properties

15 Chapter 15: Prestressed Concrete and Steel Properties

15.1 Reinforced, Precast, Pretensioned, and Post-Tensioned Concrete Materials 15.2 Structural and Cold-Formed Steel Properties 15.3 Steel Toughness, Weldability, Corrosion, and Temperature Effects

16 Timber, Masonry, and Material Conformance

Timber Properties and ASD Design Values Masonry, CMU, Mortar, Grout, and Brick Veneer Properties Concrete and Masonry Test Methods Steel, Timber, and Other Material Specification Conformance

17 Horizontal Members I

Steel Beams and Girders Reinforced Concrete Beams and Slabs Timber and Masonry Horizontal Members

18 Chapter 18: Diaphragms and Vertical Members

18.1 Diaphragms, Collectors, Struts, and Composite Slabs 18.2 Steel Columns and Beam-Columns 18.3 Concrete Columns and Bearing Walls

19 Shear Walls, Trusses, and Frames

Shear Walls and Vertical Lateral Members Trusses and Braced Systems Moment Frames and Stability Systems

20 Composite/Bridge Systems and Bolted Connections

Composite Construction and Structural System Selection Bridge Systems and Load Distribution Bolted Steel Connections

21 Chapter 21: Welded, Embedded, and Anchored Connections

21.1 Welded Steel Connections 21.2 Bearing, Embedded, and Precast Connections 21.3 Anchors, Post-Installed Anchors, and Wood/Masonry Connections

22 Shallow Foundations

Isolated, Spread, and Strip Footings Combined and Strap Footings Mat Foundations and Foundation Slabs

23 Deep Foundations

Driven Piles: Axial Capacity and Settlement Drilled Shafts, Piers, and Caissons Pile Groups, Caps, and Lateral Deep-Foundation Response

24 Chapter 24: Retaining Structures

24.1 Lateral Earth/Water Pressure and Drainage 24.2 Sliding, Overturning, Bearing, and Global Stability 24.3 Concrete Cantilever, Gravity, and Basement Walls 24.4 Sheet-Pile, Anchored, and Mechanically Stabilized Earth Walls

Concrete and Masonry Test Methods

Key Takeaways Explain This Topic AI

Define the lot, sample, specimen, test result, and acceptance criterion separately; one specimen is not automatically one strength test or one accepted placement

Fresh-concrete slump, air, temperature, and unit-weight tests measure different properties and do not directly equal compressive strength

Standard-cured concrete cylinders support strength acceptance, while field-cured cylinders address in-place curing or construction decisions

ACI 318-14 concrete acceptance applies both a rolling average of three consecutive strength tests and an individual low-test limit

Masonry prism strength represents an assembly and is distinct from CMU, mortar, or grout specimen strength

A valid procedure produces a test result; the governing ACI, TMS, IBC, and project criteria determine what that result means for acceptance

Last updated: July 2026

Concrete and Masonry Test Methods

For July 2026, use ACI 318-14 , TMS 402/602-16 , and IBC 2018 without supplements . Referenced test procedures explain how to sample, fabricate, cure, and test; the code and project documents explain acceptance. A perfectly executed test can produce a result that fails acceptance, while an invalid sample cannot establish acceptance merely because its number is high.

Separate five levels of information

A lot or placement is the quantity of material represented under the sampling plan.

A sample is material obtained at a specified time and manner from that lot.

A specimen is an individual cylinder, prism, cube, or other prepared test piece.

A test result may be the required average of multiple companion specimens.

An acceptance decision compares one or more test results with code and specification criteria.

Skipping a level causes common errors. Two concrete cylinders from one sample tested at one age may form one strength test; they do not automatically represent two independent placements. A masonry prism is assembled from units and mortar and possibly grout, so its result is not an individual unit result.

Fresh concrete field tests

Obtain a representative sample and identify truck or batch, location, time, mixture, and test personnel. Then use the appropriate procedure:

  • Test Primary information What it does not prove alone
  • Slump Consistency under the test conditions 28-day strength or water-cement ratio by itself
  • Air content Entrained or total air under the method Freeze-thaw durability without other requirements
  • Concrete temperature Placement temperature at sampling Adequate curing for the following days
  • Unit weight Density; supports yield and gravimetric air calculations Member capacity

Strength cylinders Compressive strength at test age after prescribed curing Exact in-place strength at every location

Slump is not a direct strength test. A slump outside the specified range may trigger rejection, adjustment, resampling, or engineering disposition under the project rules, but it should not be converted into an invented f'c . Similarly, excessive or insufficient air can affect durability and strength even when slump appears acceptable. Record water or admixture added at the site because sampling time relative to adjustment matters.

Concrete cylinders and strength acceptance

Standard-cured cylinders are made, stored initially, transported, and laboratory-cured under prescribed conditions to evaluate the concrete mixture for acceptance. Field-cured cylinders are stored with or near the structure to evaluate curing effectiveness or support construction decisions such as form removal when permitted. A low field-cured result and a low standard-cured result point to different questions; do not average them together.

Under ACI 318-14, a strength test for a given class and age is the prescribed average of companion cylinders from the same sample—commonly at least two 6×12-in cylinders or at least three 4×8-in cylinders. Check the exact provision and stated specimen set. First discard or investigate only under authorized criteria; never delete a low break merely to improve an average.

For specified strength f'c ≤ 5,000 psi , the strength level is acceptable when both conditions hold:

every average of any three consecutive strength tests is at least f'c ; and

no individual strength test is more than 500 psi below f'c .

For f'c > 5,000 psi , the individual lower limit uses 0.90f'c rather than subtracting 500 psi. These checks address strength-test statistics; fresh properties and construction conformance remain separate.

Worked rolling acceptance check

A concrete class has f'c = 4,000 psi . Its first three strength-test results are 4,200, 4,000, and 3,800 psi. Their average is

(4,200 + 4,000 + 3,800)/3 = 4,000 psi .

Every individual result is at least 4,000 - 500 = 3,500 psi , so this three-test window satisfies both stated strength criteria.

  • The next result is 3,400 psi. The new consecutive-three average is
  • (4,000 + 3,800 + 3,400)/3 = 3,733 psi ,

which is below 4,000 psi. The 3,400-psi individual result is also below 3,500 psi. Both conditions fail, triggering the ACI-required response and investigation; it does not automatically prove every cubic inch of the member has 3,400-psi strength. Follow the code's low-strength evaluation process rather than declaring immediate demolition or unconditional acceptance.

Masonry sampling and prisms

TMS 402/602-16 permits specified masonry compressive strength f'm to be established by the method allowed for the project, such as the unit-strength method or prism testing. The unit-strength method combines qualifying unit strength with the prescribed mortar information through the code provisions; it is not a simple multiplication. A prism test uses a representative masonry assemblage constructed, cured, prepared, and tested under the referenced procedure, including the required geometry correction where applicable.

Unit tests characterize CMU or brick. Grout specimens characterize grout. Mortar property tests, field consistency observations, and prism tests serve different purposes. Mortar removed from a wall or sampled in the field does not necessarily have the same geometry, curing, or acceptance meaning as laboratory qualification specimens. Never compare unlike specimen results to one numerical limit without checking the referenced method.

A masonry conformance workflow is: confirm approved unit, mortar, grout, and reinforcement requirements; verify sampling frequency and locations; observe proportioning and placement; create and identify specimens; protect and cure them; test at the specified age; then compare the correct result with the applicable TMS/IBC acceptance route. If a result is low, check records, sampling validity, affected extent, and authorized investigation options.

Exam closeout

Ask what property was actually measured, what material volume the sample represents, how many specimens form one test, and which criterion controls. Keep field-control actions separate from final acceptance. This disciplined chain prevents a slump value, a single cylinder, or a CMU coupon from being treated as a complete structural verdict.