Study guide

Masonry, CMU, Mortar, Grout, and Brick Veneer Properties

PE Civil: Structural Exam

Track your progress as you read

Finished sections get a check mark.

1 Exam Identity and Reference Workflow

2026 PE Civil: Structural Identity, Format, and Scoring Electronic Handbook, Design Standards, Units, and Version Control

2 Chapter 2: Gravity and Construction Loads

2.1 Dead Loads and Self-Weight 2.2 Live Loads, Reduction, and Load Placement 2.3 Construction-Stage Loads

3 Environmental Loads

Wind Loads and Pressure Paths Seismic Loads and Lateral Force Distribution Snow, Rain, and Ice Loads

4 Moving, Impact, and Lateral Soil Loads

Vehicular, Crane, and Other Moving Loads Impact and Dynamic Allowances Earth Pressure and Surcharge Loads

5 Chapter 5: Load Paths and Combinations

5.1 Tributary Areas and Complete Vertical/Lateral Load Paths 5.2 Strength and Service Load Combinations

6 Reactions, Diagrams, and Basic Axial Effects

Free-Body Diagrams, Reactions, Shear, and Moment Qualitative Diagrams, Influence Lines, and Critical Placement Axial Tension, Compression, and Deformation

7 Chapter 7: Axial Systems and Shear Effects

7.1 Trusses, Braces, and Column Axial Force 7.2 Shear Stress, Shear Flow, and Built-Up Sections 7.3 One-Way, Two-Way, Punching, and Interface Shear Effects

8 Flexure

Section Properties and Elastic Flexural Stress Beam and Slab Flexural Load Effects Biaxial and Unsymmetrical Flexure

9 Combined Stress and Deflection

Combined Axial and Flexural Stress Principal Stress, Mohr's Circle, and Combined Shear Elastic Deflection Methods

10 Chapter 10: Serviceability, Torsion, and Stability

10.1 Serviceability: Deflection, Drift, Vibration, and Ponding 10.2 Torsion and Warping Effects 10.3 Buckling, Effective Length, and Second-Order Stability

11 Fatigue, Robustness, Thermal, and Bearing Effects

Fatigue and Progressive-Collapse Concepts Thermal Deformation and Bearing/Contact Stress

12 Inspections, Submittals, and Adjacent Facilities

Special Inspections and Verification Duties Shop Drawings, Submittals, RFIs, and Delegated Design Construction Effects on Adjacent Facilities

13 Chapter 13: Temporary Works and Safety

13.1 Formwork, Falsework, Scaffolding, Shoring/Reshoring, Bracing, and Anchorage 13.2 Construction, Roadside, and Work-Zone Safety

14 Soils and Core Concrete Properties

Soil Phase Relationships and Classification Soil Strength, Permeability, and Compressibility Fresh and Hardened Concrete Properties

15 Chapter 15: Prestressed Concrete and Steel Properties

15.1 Reinforced, Precast, Pretensioned, and Post-Tensioned Concrete Materials 15.2 Structural and Cold-Formed Steel Properties 15.3 Steel Toughness, Weldability, Corrosion, and Temperature Effects

16 Timber, Masonry, and Material Conformance

Timber Properties and ASD Design Values Masonry, CMU, Mortar, Grout, and Brick Veneer Properties Concrete and Masonry Test Methods Steel, Timber, and Other Material Specification Conformance

17 Horizontal Members I

Steel Beams and Girders Reinforced Concrete Beams and Slabs Timber and Masonry Horizontal Members

18 Chapter 18: Diaphragms and Vertical Members

18.1 Diaphragms, Collectors, Struts, and Composite Slabs 18.2 Steel Columns and Beam-Columns 18.3 Concrete Columns and Bearing Walls

19 Shear Walls, Trusses, and Frames

Shear Walls and Vertical Lateral Members Trusses and Braced Systems Moment Frames and Stability Systems

20 Composite/Bridge Systems and Bolted Connections

Composite Construction and Structural System Selection Bridge Systems and Load Distribution Bolted Steel Connections

21 Chapter 21: Welded, Embedded, and Anchored Connections

21.1 Welded Steel Connections 21.2 Bearing, Embedded, and Precast Connections 21.3 Anchors, Post-Installed Anchors, and Wood/Masonry Connections

22 Shallow Foundations

Isolated, Spread, and Strip Footings Combined and Strap Footings Mat Foundations and Foundation Slabs

23 Deep Foundations

Driven Piles: Axial Capacity and Settlement Drilled Shafts, Piers, and Caissons Pile Groups, Caps, and Lateral Deep-Foundation Response

24 Chapter 24: Retaining Structures

24.1 Lateral Earth/Water Pressure and Drainage 24.2 Sliding, Overturning, Bearing, and Global Stability 24.3 Concrete Cantilever, Gravity, and Basement Walls 24.4 Sheet-Pile, Anchored, and Mechanically Stabilized Earth Walls

Masonry, CMU, Mortar, Grout, and Brick Veneer Properties

Key Takeaways Explain This Topic AI

Masonry behavior comes from an assembly of units, mortar, grout, reinforcement, connections, and workmanship rather than from unit strength alone

Mortar beds and bonds units, while grout fills designated spaces and develops reinforcement; concrete, mortar, and grout are not interchangeable names

Use net or gross section properties exactly as required by the TMS 402/602-16 design method and the stated grouting pattern

Reinforced masonry relies on compatible reinforcement and grouted cells for tensile force transfer, while unreinforced masonry has limited tensile resistance

Anchored or adhered brick veneer carries its own loads and transfers out-of-plane actions to backing but is not automatically a structural bearing or shear wall

Movement joints, flashing, drainage, ties, shelf support, corrosion protection, and differential movement are part of veneer performance

Last updated: July 2026

Masonry, CMU, Mortar, Grout, and Brick Veneer Properties

Use TMS 402/602-16 with its companion commentaries and IBC 2018 without supplements for a July 2026 exam question. Masonry is an assembly. A high-strength concrete masonry unit does not by itself establish wall strength, and a brick appearance does not establish a structural bearing wall.

Know each constituent's job

Constituent Structural or construction role Common trap

Concrete masonry unit (CMU) Provides face shells, webs, cells, compression area, and geometry Treating nominal dimensions or gross area as solid concrete

Clay brick or structural unit Provides unit strength, geometry, durability, and bond surface Assuming every brick wythe is veneer or every brick veneer is bearing

Mortar Beds units, accommodates dimensional variation, bonds joints, and transfers local stress Selecting the strongest mortar without considering compatibility and specification

Grout Fills designated cells or cavities and bonds reinforcement to masonry Treating grout as mortar or assuming every cell is grouted

Reinforcement Carries designed tension and contributes to shear or compression behavior Counting a bar whose cell is ungrouted or improperly consolidated

Anchors and ties Transfer out-of-plane veneer or wall forces and accommodate specified movement Using them as gravity support without a designed load path

CMU dimensions are often nominal; actual dimensions account for mortar joints. Hollow units concentrate material in face shells and webs. The design method may use net cross-sectional area, effective area, or transformed properties. Follow TMS notation and the stated grouting layout. A fully grouted wall and a partially grouted wall with the same nominal thickness do not have the same weight, stiffness, or effective section.

Mortar type is selected for the required masonry system, unit absorption, exposure, workability, and structural properties under TMS 402/602-16 and the project specification. More compressive strength is not automatically better bond, water resistance, or movement accommodation. Grout must flow into specified spaces, surround reinforcement, and be placed and consolidated under the construction requirements. Mortar protrusions or debris can block cells and compromise grout continuity.

Reinforced and unreinforced behavior

Masonry is strong in compression but comparatively weak and variable in tension. Unreinforced masonry therefore depends heavily on compression, geometry, axial load, and permitted tensile provisions. It should not be credited with reinforced behavior merely because metal accessories are nearby.

Reinforced masonry uses bars placed in grouted cells or bond beams so tensile forces can transfer through grout and bond into the units and mortar assembly. Bar location matters: moving a bar changes effective depth and moment strength. Lap lengths, cover, cell cleanliness, grout consolidation, and continuity at intersections affect whether the analytical load path exists. The specified masonry compressive strength f'm characterizes the masonry assemblage; it is not the individual CMU strength, mortar cube strength, or grout-cylinder strength.

For walls, distinguish in-plane shear and flexure from out-of-plane pressure response. Axial load can alter flexural behavior and slenderness effects. Openings interrupt wall piers and bond beams, requiring forces to flow through lintels, jamb reinforcement, collectors, and foundations. Material property selection is only the start of system design.

Brick veneer is a facing system

Anchored masonry veneer is attached to backing with anchors or ties and commonly has a cavity. The veneer carries its self-weight to a foundation ledge, shelf angle, or other designed support and transfers out-of-plane wind or seismic pressure through ties to the backing. Ties must have appropriate capacity, spacing, embedment, corrosion protection, and movement capability.

Adhered masonry veneer transfers its weight and out-of-plane forces by bond through the specified setting system to a suitable backing. Its substrate preparation, mortar layers, bond, water management, and installation limits follow IBC 2018 and TMS provisions. “Adhered” does not mean its gravity or environmental load disappears.

Neither type should automatically be counted as part of the structural backing's thickness, bearing capacity, or lateral-force-resisting system. The backing wall or frame remains responsible for assigned building loads unless the structural design explicitly qualifies another role. Conversely, calling veneer nonstructural does not make it harmless: its weight, anchors, eccentricity, support, and falling hazard are structural demands.

Exterior veneer must also accommodate different thermal and moisture movement between brick, CMU, concrete, steel, or wood backing. Shelf angles, soft joints, expansion joints, flashing, weeps, drainage cavities, and water-resistive layers have distinct functions. A rigid tie or blocked cavity can turn normal movement or water into cracking and corrosion.

Worked load-path example

A 12-ft-high structural CMU wall is idealized for preliminary dead load as 8 in ( 0.667 ft ) thick with an equivalent assembly unit weight of 90 pcf . Per foot of wall length,

wCMU = 90(0.667)(12) = 720 lb/ft = 0.72 klf .

A brick veneer weighs 40 psf of wall surface, so its line weight is

wveneer = 40(12) = 480 lb/ft = 0.48 klf .

If both are supported by the same foundation ledge, the preliminary vertical reaction is 0.72 + 0.48 = 1.20 klf , before other loads and factors. If the veneer instead bears on a shelf angle at an elevated floor, its 0.48-klf weight follows the shelf angle and frame load path; it should not be added blindly to the CMU footing line.

For a separate tie illustration, suppose nominal out-of-plane pressure is 30 psf and one tie receives 2.0 ft² of tributary veneer. Its nominal force is 30(2.0) = 60 lb . Final design still uses the prescribed load combinations, tie capacities, spacing limits, embedment, backing connection, and any flexible-anchor provisions. Tributary force alone does not approve a tie layout.

Exam workflow

Identify whether the element is structural masonry, backing, anchored veneer, or adhered veneer. Trace gravity and out-of-plane forces separately. Then select the assembly property, grouting pattern, reinforcement, effective section, and movement details from the exact TMS 402/602-16 and IBC 2018 provisions. This prevents a material label from replacing the actual wall system.