Study guide

Classes of Fire and Extinguishing Media

Fire Officer Examination FOE

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Introduction & Exam Overview

About the Fire Officer Examination How to Use This Study Guide

2 Chapter 2: General Ability - Verbal Reasoning

Fire Service Vocabulary, Synonyms & Antonyms Verbal Analogies and Standard English Grammar Spelling, Correct Usage, Idioms & Punctuation Reading Comprehension and Passage Analysis

3 Chapter 3: General Ability - Analytical & Numerical Reasoning

Deductive Logic and Categorical Syllogisms Spatial Reasoning & Fireground Situational Judgment Data Interpretation: Tables, Graphs & Fire Incident Statistics Fundamental Arithmetic & Hydraulics Flow Rates Ratio, Proportion & Basic Algebra Percentages, Averages & Work/Time Word Problems Geometry, Mensuration & Measurement Conversions

4 Chapter 4: Fire Suppression - Science & Extinguishing Agents

Fire Behavior, Chemistry of Combustion & Fire Tetrahedron Classes of Fire and Extinguishing Media Portable Fire Extinguishers: Types, Ratings, PASS & Maintenance Firefighting Foam: Concentrates, Proportioning & Application Water Supply Systems, Pressure & Fire Hydraulics

5 Chapter 5: Fire Suppression - Operations & Equipment

Pre-Fire Planning, Size-Up & Incident Command System Fire Attack Tactics, Ventilation & Overhaul Salvage Operations, Loss Control & Property Conservation Hose Lines, Nozzles, Ground Ladders & Forcible Entry Fire Apparatus, Pump Operations & Apparatus Positioning Search & Rescue Operations, PPE & SCBA Safety BFP Emergency Medical Services & Special Rescue Operations Hazardous Materials Incident Response & Mitigation

6 Chapter 6: Fire Safety & Prevention - Philippine Fire Code (RA 9514)

Republic Act 9514 (Fire Code of the Philippines 2008) Scope & Principles 2019 Revised IRR Enforcement, Administrative Sanctions & Closure Orders Fire Safety Inspection Certificate (FSIC) & FSEC Requirements Fire Code Fees, Taxes & the Collection of Fire Code Revenues

7 Chapter 7: Fire Safety & Prevention - Codes & Inspection SOPs

Means of Egress Specifications & Fire Protection Systems Philippine Electrical Code & Electrical Fire Hazards Hazardous Materials Classification & High-Risk Occupancies Fire Drills, Evacuation Planning, Fire Brigades & Public Fire Safety Education BFP Citizens Charter & Standard Inspection Procedures

8 Chapter 8: Fire Investigation - Law on Arson & Evidence

Law on Arson in the Philippines: Revised Penal Code Framework Prima Facie Evidence of Arson & Motive Determination Fire Origin & Cause Determination & Burn Patterns Evidence Collection, Chain of Custody & Rights of Accused Rules of Court: Admissibility of Evidence & Investigator Testimony BFP SOPs on Fire and Arson Investigation: Workflow, Reports & Documentation

9 Chapter 9: Administrative Matters - BFP Laws & Rules

Republic Act 6975 (DILG Act of 1990) & Creation of the BFP Republic Act 9263 (BFP Professionalization Act) & Rank Hierarchy Republic Act 9592 & Administrative Disciplinary Rules Civil Service Commission Rules & Code of Ethics (RA 6713)

Classes of Fire and Extinguishing Media

Key Takeaways Explain This Topic AI

Fires are classified into five distinct categories (A, B, C, D, K) based on the physical state and chemical behavior of the involved fuel source.

Water is the primary agent for Class A fires due to its high specific heat capacity and latent heat of vaporization, but it is extremely dangerous on Class C and Class D fires.

Class K fires require wet chemical agents that react with hot cooking oils through saponification, forming a thick alkaline foam blanket to trap vapors.

Dry chemical agents like monoammonium phosphate (ABC) extinguish fire by interrupting the chemical chain reaction and smothering fuel surfaces.

Using water on Class C fires presents severe electrocution hazards, while applying water to Class D metal fires causes thermal decomposition into explosive hydrogen gas.

Last updated: July 2026

Classes of Fire and Extinguishing Media

Effective fire suppression requires selecting the appropriate extinguishing agent for the specific fuel involved. Deploying an incorrect extinguishing media can fail to suppress the fire, worsen fire conditions, cause violent explosions, or result in fatal injuries to fire suppression personnel. Fire protection organizations (including NFPA and international standards bodies) categorize fires into five distinct classes based on fuel characteristics.

The Five Standard Classes of Fire

  • Class Fuel Type & Examples Symbol & Standard Identifier
  • Class A Ordinary combustibles (wood, cloth, paper, rubber, trash, plastics) Green Triangle "A"
  • Class B Flammable/combustible liquids and gases (gasoline, oil, propane, diesel) Red Square "B"
  • Class C Energized electrical equipment (wiring, motors, panels, transformers) Blue Circle "C"
  • Class D Combustible metals (magnesium, titanium, sodium, potassium, lithium) Yellow Star "D"
  • Class K Commercial cooking media (vegetable oils, animal fats, lard, fryers) Black Hexagon "K"
  • Class A: Ordinary Combustibles

Class A fires involve common solid materials such as wood, paper, cloth, rubber, cardboard, and many plastics. These materials burn with ember formation and leave solid ash residue. The primary extinguishment mechanism for Class A fires is thermal cooling to drop the fuel temperature below its ignition point, typically accomplished using water or water-based foam solutions.

Class B: Flammable Liquids and Gases

Class B fires involve flammable liquids (flash point < 100 ∘ F / 37.8 ∘ C < 100^\circ\text{F} / 37.8^\circ\text{C} < 10 0 ∘ F /37. 8 ∘ C like gasoline, acetone, and benzene), combustible liquids (flash point ≥ 100 ∘ F \ge 100^\circ\text{F} ≥ 10 0 ∘ F like diesel fuel, kerosene, and mineral spirits), and flammable gases (propane, natural gas/methane, butane). Class B fires burn at the liquid surface vapor layer or gas discharge point and do not produce deep-seated embers. Extinguishment mechanisms focus on smothering (excluding oxygen), vapor suppression , or chemical chain inhibition .

Class C: Energized Electrical Equipment

Class C fires involve energized electrical wiring, breaker panels, electric motors, transformers, and electronic appliances. Class C is a hazard classification rather than a fuel type; the burning material itself is typically Class A plastic or Class B insulation oil. The essential requirement for a Class C extinguishing agent is electrical non-conductivity . Once the electrical circuit is de-energized, the fire reclassifies into its underlying fuel class (Class A or Class B).

Class D: Combustible Metals

Class D fires involve combustible reactive metals such as magnesium, titanium, zirconium, sodium, lithium, and potassium. Burning metals generate extreme heat (often exceeding 2 , 000 ∘ F– 5 , 000 ∘ F / 1 , 100 ∘ C– 2 , 700 ∘ C 2,000^\circ\text{F}\text{--}5,000^\circ\text{F} / 1,100^\circ\text{C}\text{--}2,700^\circ\text{C} 2 , 00 0 ∘ F – 5 , 00 0 ∘ F /1 , 10 0 ∘ C – 2 , 70 0 ∘ C ) and react violently with conventional extinguishing agents. Suppressing Class D fires requires specialized dry powders designed to crust over the metal and exclude oxygen without decomposing.

Class K: Commercial Cooking Media

Class K fires involve vegetable oils, animal fats, and commercial kitchen fryers. Modern high-efficiency commercial cooking appliances retain heat for prolonged periods, and modern vegetable oils have high autoignition temperatures ( 600 ∘ F– 700 ∘ F 600^\circ\text{F}\text{--}700^\circ\text{F} 60 0 ∘ F – 70 0 ∘ F ). Class K fires require wet chemical agents capable of executing saponification —a chemical reaction that converts hot fats into an alkaline soap foam blanket.

Extinguishing Media & Their Chemical Mechanisms

Extinguishing Agent Dominant Mechanism Target Classes Primary Applications & Operational Notes

Water ( H 2 O H_2O H 2 ​ O ) Thermal Cooling Class A Highest heat absorption capacity (specific heat = 1.0 BTU/lb ∘ F 1.0\text{ BTU/lb}^\circ\text{F} 1.0 BTU/lb ∘ F ; latent heat of vaporization = 970 BTU/lb 970\text{ BTU/lb} 970 BTU/lb ). Expands 1,700 times into steam at 212 ∘ F 212^\circ\text{F} 21 2 ∘ F ( 100 ∘ C 100^\circ\text{C} 10 0 ∘ C ).

Firefighting Foam (AFFF/AR-AFFF) Smothering & Vapor Barrier Class B, Class A Forms an aqueous film over liquid fuels to prevent vapor release, seal fuel surfaces, and cool substrate. AR-AFFF is required for polar solvents (alcohols).

Dry Chemical (Monoammonium Phosphate) Chain Breaking & Smothering Class A, B, C Multi-purpose "ABC" dry chemical coating fuel surfaces and capturing free radicals. Corrosive to sensitive electronics.

Carbon Dioxide ( C O 2 CO_2 C O 2 ​ ) Oxygen Displacement & Cooling Class B, C Non-conductive, residue-free inert gas ( 1.5 × 1.5\times 1.5 × heavier than air). Discharges as cold vapor/snow ( − 110 ∘ F -110^\circ\text{F} − 11 0 ∘ F ). Requires caution in confined spaces (asphyxiation risk).

Clean Agents (FM-200 / Novec 1230) Chemical Inhibition & Cooling Class A, B, C Halocarbon and inert gas substitutes for Halon. Electrically non-conductive, leaves no residue, safe for data centers and delicate instruments.

Wet Chemical (Potassium Acetate/Citrate) Saponification & Cooling Class K, Class A Discharged as a fine mist; reacts with hot fatty acids to form a heavy soap foam layer that smothers flames and prevents re-ignition.

Special Dry Powder (MET-L-X / Lith-X) Smothering & Heat Absorption Class D Sodium chloride or graphite-based powders applied via scoop or low-velocity extinguisher to form an airtight thermal crust over reactive burning metals.

  • Agent Compatibility & Critical Hazard Warnings
  • 1. Water Hazards on Class C & Class D Fires

Class C Hazard: Applying water or water-based streams to energized electrical equipment creates a direct electrical conductor back to the hose nozzle, leading to severe or fatal shock/electrocution to the firefighter.

Class D Hazard: Applying water to burning combustible metals (e.g., magnesium) causes a rapid hydrolysis reaction, violently breaking water into hydrogen gas ( H 2 H_2 H 2 ​ ) and oxygen ( O 2 O_2 O 2 ​ ), resulting in explosive reactions and intense metal spattering.

2. Water Hazards on Class B & Class K Fires

Class B Slop-Over / Boil-Over: Applying solid water streams into hot, burning viscous oils causes water to sink below the oil, rapidly flash into steam (expanding 1,700-fold), and violently eject burning hot oil out of the container.

Class K Mist Requirement: Applying high-velocity water or incorrect agents to kitchen fryers causes explosive steam eruptions, scattering burning grease across the room. Class K wet chemical extinguishers must use low-velocity mist nozzles.