12.3 Balanced & Unbalanced Three-Phase AC Circuits

PRC Registered Electrical Engineer REE

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Overview, RA 7920 & Electrical Engineering Ethics

1.1 PRC Board of Electrical Engineering & REE Examination Overview 1.2 Republic Act No. 7920 (New Electrical Engineering Law) & License Classes 1.3 Code of Ethics & Professional Practice for Electrical Engineers

2 Chapter 2: Math — Algebra, Trig & Geometry

2.1 Algebraic Equations, Polynomials & Complex Numbers 2.2 Trigonometry — Identities, Triangles & Spherical Trig 2.3 Analytic & Solid Geometry

3 Chapter 3: Engineering Mathematics — Calculus & Differential Equations

3.1 Differential Calculus, Limits, Derivatives & Applications 3.2 Integral Calculus, Integration Techniques & Area/Volume Applications 3.3 Ordinary Differential Equations & Initial-Value Problems

4 Chapter 4: Engineering Mathematics — Advanced Math & Transform Methods

4.1 Laplace Transforms, Inverse Transforms & Circuit Applications 4.2 Fourier Series, Fourier Transforms & Frequency-Domain Analysis 4.3 Vector Analysis, Linear Algebra, Matrices & Complex Analysis

5 Chapter 5: Engineering Mathematics — Probability, Statistics & Engineering Data Analysis

5.1 Probability Theory, Counting Techniques & Bayes' Theorem 5.2 Engineering Data Analysis I — Descriptive Statistics & Probability Distributions 5.3 Engineering Data Analysis II — Confidence Intervals, Hypothesis Testing & Regression

6 Chapter 6: Engineering Mathematics — Numerical Methods & Analysis

6.1 Numerical Root-Finding & Solution of Linear Systems 6.2 Interpolation, Numerical Integration & Numerical Solution of ODEs

7 Chapter 7: ESAS — Physics, Chemistry & Computer Fundamentals

7.1 Physics for Engineers 7.2 General Chemistry & Materials Science 7.3 Computer Fundamentals, Programming & Data Logic 7.4 Logic Circuits, Switching Theory & Microprocessor Systems

8 Chapter 8: ESAS — Mechanics & Thermal-Fluid Engineering

8.1 Engineering Mechanics — Statics & Dynamics 8.2 Strength of Materials & Mechanics of Deformable Bodies 8.3 Thermal-Fluid Engineering — Thermodynamics & Fluid Mechanics

9 Chapter 9: ESAS — Engineering Economics, Management & Contracts

9.1 Engineering Economics & Depreciation 9.2 Engineering Management & Ethics 9.3 Philippine Electrical Engineering Law, Code & Contracts 9.4 Technopreneurship 101 & Management of Engineering Projects

10 Chapter 10: PEC 1 — Safety, Sizing & Protection

10.1 PEC Fundamentals, Safety Standards & Grounding/Bonding 10.2 Conductor Sizing, Ampacity Adjustment & Voltage Drop 10.3 Overcurrent Protection, Branch Circuit & Feeder Sizing 10.4 Basic Occupational Safety & Health (BOSH) and Electrical Safety Standards

11 Chapter 11: PEC 1 & 2 — Equipment & Utility Systems

11.1 PEC Equipment Installation & Wiring Methods 11.2 Utility Systems, Transformers & Switchgear 11.3 Special Occupancies & Hazardous Locations

12 Chapter 12: Electrical Professional — DC & AC Circuit Fundamentals

12.1 DC Circuit Analysis & Network Theorems 12.2 Single-Phase AC Circuits & Phasor Analysis 12.3 Balanced & Unbalanced Three-Phase AC Circuits

13 Chapter 13: Electrical Professional — EM Fields & Transients

13.1 Electrostatics, Magnetostatics & Maxwell's Equations 13.2 Electromagnetic Waves & Transmission Line Fields 13.3 First-Order & Second-Order Circuit Transients

14 Chapter 14: Electrical Professional — Electronics, Industrial Electronics & Communications

14.1 Electronics 1 & 2 — Semiconductor Devices & Analog Circuits 14.2 Electrical Apparatus & Devices — Industrial Electronics & Power Converters 14.3 Fundamentals of Electronic Communications

15 Chapter 15: Electrical Professional — Transformers & DC Machines

15.1 Single-Phase & Three-Phase Transformers 15.2 Transformer Connections & Special Transformers 15.3 DC Generators & DC Motors

16 Chapter 16: Electrical Professional — AC Synchronous & Induction Machinery

16.1 Synchronous Generators (Alternators) 16.2 Synchronous Motors & Special AC Machines 16.3 Three-Phase & Single-Phase Induction Motors

17 Chapter 17: Electrical Professional — Power Plants & Energy Conversion

17.1 Hydroelectric, Thermal & Combined Cycle Power Plants 17.2 Renewable Energy Systems & Geothermal Power Plants 17.3 Power Plant Economics, Load Curves & Energy Conversion

18 Chapter 18: Electrical Professional — Transmission & Distribution

18.1 Transmission Line Parameters & Performance Models 18.2 Mechanical Overhead Line Design, Underground Cables & Insulators 18.3 Distribution Systems, Substation Layouts & Power Flow Control

19 Chapter 19: Electrical Professional — Power System Analysis

19.1 The Per-Unit System, Base Conversion & Impedance Diagrams 19.2 Symmetrical Components & Unbalanced Fault Analysis 19.3 Load Flow, Economic Dispatch & Power System Stability

20 Chapter 20: Electrical Professional — Protection, Control, Instrumentation & Illumination

20.1 Power System Protection & Protective Relaying 20.2 Industrial Motor Control, Logic Circuits & PLC Automation 20.3 Electrical Instrumentation, Transducers & Measurement Systems 20.4 Illumination Engineering, Lighting Design & Photometrics 20.5 Feedback Control Systems & Research Methods

12.3 Balanced & Unbalanced Three-Phase AC Circuits

Key Takeaways Explain This Topic AI

In a balanced Wye (Y) connected system, line-to-line voltage is 3 \sqrt{3} 3 ​ times line-to-neutral phase voltage ( V L = 3 V p V_L = \sqrt{3} V_p V L ​ = 3 ​ V p ​ ) leading by 30 ∘ 30^\circ 3 0 ∘ , while line current equals phase current ( I L = I p I_L = I_p I L ​ = I p ​ ).

In a balanced Delta ( Δ \Delta Δ ) connected system, line-to-line voltage equals phase voltage ( V L = V p V_L = V_p V L ​ = V p ​ ), while line current is 3 \sqrt{3} 3 ​ times phase current ( I L = 3 I p I_L = \sqrt{3} I_p I L ​ = 3 ​ I p ​ ) lagging phase current by 30 ∘ 30^\circ 3 0 ∘ .

Total active power in any balanced three-phase load (Wye or Delta) is P 3 ϕ = 3 V L I L cos ⁡ θ = 3 V p I p cos ⁡ θ P_{3\phi} = \sqrt{3} V_L I_L \cos\theta = 3 V_p I_p \cos\theta P 3 ϕ ​ = 3 ​ V L ​ I L ​ cos θ = 3 V p ​ I p ​ cos θ , total reactive power is Q 3 ϕ = 3 V L I L sin ⁡ θ Q_{3\phi} = \sqrt{3} V_L I_L \sin\theta Q 3 ϕ ​ = 3 ​ V L ​ I L ​ sin θ , and apparent power is S 3 ϕ = 3 V L I L S_{3\phi} = \sqrt{3} V_L I_L S 3 ϕ ​ = 3 ​ V L ​ I L ​ .

The Two-Wattmeter Method measures total active power as P = W 1 + W 2 P = W_1 + W_2 P = W 1 ​ + W 2 ​ and total reactive power as Q = 3 ( W 1 − W 2 ) Q = \sqrt{3}(W_1 - W_2) Q = 3 ​ ( W 1 ​ − W 2 ​ ) in any 3-wire three-phase system, with power factor angle θ = arctan ⁡ ( 3 W 1 − W 2 W 1 + W 2 ) \theta = \arctan\left(\sqrt{3}\frac{W_1 - W_2}{W_1 + W_2}\right) θ = arctan ( 3 ​ W 1 ​ + W 2 ​ W 1 ​ − W 2 ​ ​ ) .

Unbalanced Wye 4-wire systems produce neutral current I N = I A + I B + I C I_N = \mathbf{I}_A + \mathbf{I}_B + \mathbf{I}_C I N ​ = I A ​ + I B ​ + I C ​ , whereas unbalanced 3-wire Wye systems create a neutral shift voltage V n N V_{n N} V n N ​ that distorts phase voltages relative to ground.

Last updated: August 2026

12.3 Balanced & Unbalanced Three-Phase AC Circuits

Three-phase AC power generation, transmission, and utilization dominate industrial power systems due to constant instantaneous power delivery, higher conductor efficiency, and self-starting rotating magnetic fields in AC motors. This section covers balanced and unbalanced Wye ( Y Y Y ) and Delta ( Δ \Delta Δ ) configurations, neutral currents, and power measurement via the Two-Wattmeter Method .

1. Three-Phase Voltage Generation & Phase Sequences

A balanced three-phase AC generator produces three equal sinusoidal phase voltages displaced in time by 120 ∘ 120^\circ 12 0 ∘ ( 2 π / 3 2\pi/3 2 π /3 radians):

Positive (ABC) Phase Sequence: V A N = V p ∠ 0 ∘ \mathbf{V}_{AN} = V_p \angle 0^\circ V A N ​ = V p ​ ∠ 0 ∘ V B N = V p ∠ − 120 ∘ \mathbf{V}_{BN} = V_p \angle -120^\circ V BN ​ = V p ​ ∠ − 12 0 ∘ V C N = V p ∠ − 240 ∘ = V p ∠ + 120 ∘ \mathbf{V}_{CN} = V_p \angle -240^\circ = V_p \angle +120^\circ V CN ​ = V p ​ ∠ − 24 0 ∘ = V p ​ ∠ + 12 0 ∘ Sum of Balanced Phase Voltages: V A N + V B N + V C N = 0 \text{Sum of Balanced Phase Voltages: } \mathbf{V}_{AN} + \mathbf{V}_{BN} + \mathbf{V}_{CN} = 0 Sum of Balanced Phase Voltages: V A N ​ + V BN ​ + V CN ​ = 0

Negative (CBA) Phase Sequence: V A N = V p ∠ 0 ∘ , V B N = V p ∠ + 120 ∘ , V C N = V p ∠ − 120 ∘ \mathbf{V}_{AN} = V_p \angle 0^\circ, \quad \mathbf{V}_{BN} = V_p \angle +120^\circ, \quad \mathbf{V}_{CN} = V_p \angle -120^\circ V A N ​ = V p ​ ∠ 0 ∘ , V BN ​ = V p ​ ∠ + 12 0 ∘ , V CN ​ = V p ​ ∠ − 12 0 ∘

  • 2. Wye ( Y Y Y ) and Delta ( Δ \Delta Δ ) Phase-Line Voltage & Current Relations
  • Balanced Wye ( Y Y Y ) Connection

In a Wye connection, line conductors connect to outer terminals, and neutral ( N N N ) connects to the central star point. BALANCED WYE (Y) CONNECTION

  • Phase A ───────► Line Current I_A
  • │
  • [Z]
  • │
  • Neutral N ───────┼─────── [Z] ─────── Phase B ───► Line Current I_B
  • │
  • [Z]
  • │
  • Phase C ───────► Line Current I_C

Line Voltage vs. Phase Voltage: Line-to-line voltages V A B = V A N − V B N \mathbf{V}_{AB} = \mathbf{V}_{AN} - \mathbf{V}_{BN} V A B ​ = V A N ​ − V BN ​ lead phase-to-neutral voltages by 30 ∘ 30^\circ 3 0 ∘ : V L − L = 3 V L − N ⟹ V A B = 3 V p ∠ + 30 ∘ V_{L-L} = \sqrt{3} V_{L-N} \quad \implies \quad \mathbf{V}_{AB} = \sqrt{3} V_p \angle +30^\circ V L − L ​ = 3 ​ V L − N ​ ⟹ V A B ​ = 3 ​ V p ​ ∠ + 3 0 ∘

  • Line Current vs. Phase Current: Line current equals phase current: I L = I p I_L = I_p I L ​ = I p ​
  • Balanced Delta ( Δ \Delta Δ ) Connection

In a Delta connection, load impedances connect directly across pairs of line phase conductors ( A – B A\text{--}B A – B , B – C B\text{--}C B – C , C – A C\text{--}A C – A ).

Line Voltage vs. Phase Voltage: Line voltage equals phase load voltage: V L = V p V_L = V_p V L ​ = V p ​

Line Current vs. Phase Current: Line current is 3 \sqrt{3} 3 ​ times phase current and lags phase current by 30 ∘ 30^\circ 3 0 ∘ (for positive sequence): I L = 3 I p ⟹ I A = I A B − I C A = 3 I p ∠ − 30 ∘ I_L = \sqrt{3} I_p \quad \implies \quad \mathbf{I}_A = \mathbf{I}_{AB} - \mathbf{I}_{CA} = \sqrt{3} I_p \angle -30^\circ I L ​ = 3 ​ I p ​ ⟹ I A ​ = I A B ​ − I C A ​ = 3 ​ I p ​ ∠ − 3 0 ∘

Wye-Delta Impedance Equivalence

To convert a balanced Delta load to an equivalent Wye load for per-phase single-line analysis: Z Y = Z Δ 3 \mathbf{Z}_Y = \frac{\mathbf{Z}_\Delta}{3} Z Y ​ = 3 Z Δ ​ ​

3. Three-Phase Power Formulas & Complex Power

For any balanced three-phase load (whether Wye or Delta connected), the total power expressions are identical when written in terms of line quantities ( V L , I L V_L, I_L V L ​ , I L ​ ):

Power Quantity Formula (Line Values) Formula (Phase Values) Unit

Total Active Power ( P 3 ϕ P_{3\phi} P 3 ϕ ​ ) P 3 ϕ = 3 V L I L cos ⁡ θ P_{3\phi} = \sqrt{3} V_L I_L \cos\theta P 3 ϕ ​ = 3 ​ V L ​ I L ​ cos θ P 3 ϕ = 3 V p I p cos ⁡ θ P_{3\phi} = 3 V_p I_p \cos\theta P 3 ϕ ​ = 3 V p ​ I p ​ cos θ Watts (W / kW)

Total Reactive Power ( Q 3 ϕ Q_{3\phi} Q 3 ϕ ​ ) Q 3 ϕ = 3 V L I L sin ⁡ θ Q_{3\phi} = \sqrt{3} V_L I_L \sin\theta Q 3 ϕ ​ = 3 ​ V L ​ I L ​ sin θ Q 3 ϕ = 3 V p I p sin ⁡ θ Q_{3\phi} = 3 V_p I_p \sin\theta Q 3 ϕ ​ = 3 V p ​ I p ​ sin θ VAR / kVAR

Total Apparent Power ( S 3 ϕ S_{3\phi} S 3 ϕ ​ ) S 3 ϕ = 3 V L I L = P 3 ϕ 2 + Q 3 ϕ 2 S_{3\phi} = \sqrt{3} V_L I_L = \sqrt{P_{3\phi}^2 + Q_{3\phi}^2} S 3 ϕ ​ = 3 ​ V L ​ I L ​ = P 3 ϕ 2 ​ + Q 3 ϕ 2 ​ ​ S 3 ϕ = 3 V p I p S_{3\phi} = 3 V_p I_p S 3 ϕ ​ = 3 V p ​ I p ​ VA / kVA

where θ \theta θ is the impedance phase angle of individual phase load Z p = ∣ Z p ∣ ∠ θ \mathbf{Z}_p = |Z_p| \angle \theta Z p ​ = ∣ Z p ​ ∣∠ θ .

4. Unbalanced Three-Phase Systems & Neutral Current Analysis

When load impedances across phases are unequal ( Z A ≠ Z B ≠ Z C \mathbf{Z}_A \neq \mathbf{Z}_B \neq \mathbf{Z}_C Z A ​  = Z B ​  = Z C ​ ), symmetry breaks.

Unbalanced 4-Wire Wye Systems

In a 4-wire Wye system with a solidly grounded neutral, phase voltages remain balanced at V p V_p V p ​ . Line currents equal individual phase load currents: I A = V A N Z A , I B = V B N Z B , I C = V C N Z C \mathbf{I}_A = \frac{\mathbf{V}_{AN}}{\mathbf{Z}_A}, \quad \mathbf{I}_B = \frac{\mathbf{V}_{BN}}{\mathbf{Z}_B}, \quad \mathbf{I}_C = \frac{\mathbf{V}_{CN}}{\mathbf{Z}_C} I A ​ = Z A ​ V A N ​ ​ , I B ​ = Z B ​ V BN ​ ​ , I C ​ = Z C ​ V CN ​ ​

Neutral return current I N \mathbf{I}_N I N ​ is the phasor sum of line currents: I N = I A + I B + I C \mathbf{I}_N = \mathbf{I}_A + \mathbf{I}_B + \mathbf{I}_C I N ​ = I A ​ + I B ​ + I C ​

Board Exam Fact: In a balanced 4-wire system, I N = 0 \mathbf{I}_N = 0 I N ​ = 0 . Unbalance creates non-zero neutral return current, increasing neutral conductor heating.

Unbalanced 3-Wire Wye Systems (Neutral Shift Voltage)

When an ungrounded Wye load is unbalanced, the load neutral point n n n shifts away from the source neutral point N N N . The Neutral Shift Voltage V n N \mathbf{V}_{nN} V n N ​ is calculated via Millman's Theorem: V n N = Y A V A N + Y B V B N + Y C V C N Y A + Y B + Y C \mathbf{V}_{nN} = \frac{\mathbf{Y}_A \mathbf{V}_{AN} + \mathbf{Y}_B \mathbf{V}_{BN} + \mathbf{Y}_C \mathbf{V}_{CN}}{\mathbf{Y}_A + \mathbf{Y}_B + \mathbf{Y}_C} V n N ​ = Y A ​ + Y B ​ + Y C ​ Y A ​ V A N ​ + Y B ​ V BN ​ + Y C ​ V CN ​ ​

Actual phase voltages across load impedances become distorted: V a n = V A N − V n N , V b n = V B N − V n N , V c n = V C N − V n N \mathbf{V}_{an} = \mathbf{V}_{AN} - \mathbf{V}_{nN}, \quad \mathbf{V}_{bn} = \mathbf{V}_{BN} - \mathbf{V}_{nN}, \quad \mathbf{V}_{cn} = \mathbf{V}_{CN} - \mathbf{V}_{nN} V an ​ = V A N ​ − V n N ​ , V bn ​ = V BN ​ − V n N ​ , V c n ​ = V CN ​ − V n N ​

5. Three-Phase Power Measurement: The Two-Wattmeter Method

Blondel's Theorem proves that total power in an N N N -wire system can be measured using ( N − 1 ) (N-1) ( N − 1 ) wattmeters. For any 3-wire three-phase system (balanced or unbalanced, Wye or Delta), two wattmeters suffice. TWO-WATTMETER METHOD SCHEMATIC

  • Phase A ───────┬───[ Current Coil W1 ]───────────► Load
  • │
  • [ Potential Coil W1 ]
  • │
  • Phase B ───────┴─────────────────────────────────► Load
  • │
  • [ Potential Coil W2 ]
  • │
  • Phase C ───────┬───[ Current Coil W2 ]───────────► Load
  • Wattmeter Readings & Equations

For a balanced load with line voltage V L V_L V L ​ , line current I L I_L I L ​ , and power factor angle θ \theta θ : W 1 = V L I L cos ⁡ ( 30 ∘ − θ ) W_1 = V_L I_L \cos(30^\circ - \theta) W 1 ​ = V L ​ I L ​ cos ( 3 0 ∘ − θ ) W 2 = V L I L cos ⁡ ( 30 ∘ + θ ) W_2 = V_L I_L \cos(30^\circ + \theta) W 2 ​ = V L ​ I L ​ cos ( 3 0 ∘ + θ )

Sum and Difference Relations

Total Active Power ( P 3 ϕ P_{3\phi} P 3 ϕ ​ ): P 3 ϕ = W 1 + W 2 = V L I L [ cos ⁡ ( 30 ∘ − θ ) + cos ⁡ ( 30 ∘ + θ ) ] = 3 V L I L cos ⁡ θ P_{3\phi} = W_1 + W_2 = V_L I_L \left[ \cos(30^\circ - \theta) + \cos(30^\circ + \theta) \right] = \sqrt{3} V_L I_L \cos\theta P 3 ϕ ​ = W 1 ​ + W 2 ​ = V L ​ I L ​ [ cos ( 3 0 ∘ − θ ) + cos ( 3 0 ∘ + θ ) ] = 3 ​ V L ​ I L ​ cos θ

Total Reactive Power ( Q 3 ϕ Q_{3\phi} Q 3 ϕ ​ ): Q 3 ϕ = 3 ( W 1 − W 2 ) = 3 V L I L [ cos ⁡ ( 30 ∘ − θ ) − cos ⁡ ( 30 ∘ + θ ) ] = 3 V L I L sin ⁡ θ Q_{3\phi} = \sqrt{3} (W_1 - W_2) = \sqrt{3} V_L I_L \left[ \cos(30^\circ - \theta) - \cos(30^\circ + \theta) \right] = \sqrt{3} V_L I_L \sin\theta Q 3 ϕ ​ = 3 ​ ( W 1 ​ − W 2 ​ ) = 3 ​ V L ​ I L ​ [ cos ( 3 0 ∘ − θ ) − cos ( 3 0 ∘ + θ ) ] = 3 ​ V L ​ I L ​ sin θ

Power Factor Angle ( θ \theta θ ) & Power Factor ( PF \text{PF} PF ): tan ⁡ θ = 3 ( W 1 − W 2 W 1 + W 2 ) ⟹ PF = cos ⁡ [ arctan ⁡ ( 3 W 1 − W 2 W 1 + W 2 ) ] \tan\theta = \sqrt{3} \left( \frac{W_1 - W_2}{W_1 + W_2} \right) \quad \implies \quad \text{PF} = \cos\left[ \arctan\left( \sqrt{3} \frac{W_1 - W_2}{W_1 + W_2} \right) \right] tan θ = 3 ​ ( W 1 ​ + W 2 ​ W 1 ​ − W 2 ​ ​ ) ⟹ PF = cos [ arctan ( 3 ​ W 1 ​ + W 2 ​ W 1 ​ − W 2 ​ ​ ) ]

Key Wattmeter Reading Cases:

Load Condition / Power Factor W 1 W_1 W 1 ​ vs. W 2 W_2 W 2 ​ Relationship Interpretation

Unity Power Factor ( PF = 1.0 , θ = 0 ∘ \text{PF} = 1.0, \theta = 0^\circ PF = 1.0 , θ = 0 ∘ ) W 1 = W 2 > 0 W_1 = W_2 > 0 W 1 ​ = W 2 ​ > 0 Both wattmeters read identical positive values.

PF = 0.866 ( θ = 30 ∘ ) \text{PF} = 0.866 \quad (\theta = 30^\circ) PF = 0.866 ( θ = 3 0 ∘ ) W 1 = 2 W 2 W_1 = 2 W_2 W 1 ​ = 2 W 2 ​ One wattmeter reads double the other.

PF = 0.500 ( θ = 60 ∘ ) \text{PF} = 0.500 \quad (\theta = 60^\circ) PF = 0.500 ( θ = 6 0 ∘ ) W 1 > 0 , W 2 = 0 W_1 > 0, \quad W_2 = 0 W 1 ​ > 0 , W 2 ​ = 0 One wattmeter reads total 3-phase power; the other reads zero.

PF < 0.500 ( θ > 60 ∘ ) \text{PF} < 0.500 \quad (\theta > 60^\circ) PF < 0.500 ( θ > 6 0 ∘ ) W 1 > 0 , W 2 < 0 W_1 > 0, \quad W_2 < 0 W 1 ​ > 0 , W 2 ​ < 0 W 2 W_2 W 2 ​ drops below zero (potential coil leads must be reversed).

  • Solved Board Exam Examples
  • Example 1: Balanced Delta Load Analysis

Problem: A balanced 3-phase Delta-connected load with impedance Z Δ = 18 + j 24 Ω \mathbf{Z}_\Delta = 18 + j 24\ \Omega Z Δ ​ = 18 + j 24 Ω per phase is connected to a 440 V 440\ \text{V} 440 V , 60 Hz 60\ \text{Hz} 60 Hz 3-phase supply. Calculate: (a) phase current I p I_p I p ​ , (b) line current I L I_L I L ​ , (c) total active power P 3 ϕ P_{3\phi} P 3 ϕ ​ , and (d) total reactive power Q 3 ϕ Q_{3\phi} Q 3 ϕ ​ .

Solution:

Calculate phase impedance magnitude ∣ Z p ∣ |Z_p| ∣ Z p ​ ∣ and phase angle θ \theta θ : ∣ Z p ∣ = 18 2 + 24 2 = 324 + 576 = 900 = 30 Ω |Z_p| = \sqrt{18^2 + 24^2} = \sqrt{324 + 576} = \sqrt{900} = 30\ \Omega ∣ Z p ​ ∣ = 1 8 2 + 2 4 2 ​ = 324 + 576 ​ = 900 ​ = 30 Ω θ = arctan ⁡ ( 24 18 ) = 53.13 ∘ ⟹ cos ⁡ θ = 0.60 , sin ⁡ θ = 0.80 \theta = \arctan\left(\frac{24}{18}\right) = 53.13^\circ \implies \cos\theta = 0.60, \quad \sin\theta = 0.80 θ = arctan ( 18 24 ​ ) = 53.1 3 ∘ ⟹ cos θ = 0.60 , sin θ = 0.80

In Delta connection, V p = V L = 440 V V_p = V_L = 440\ \text{V} V p ​ = V L ​ = 440 V . Compute phase current I p I_p I p ​ : I p = V p ∣ Z p ∣ = 440 30 = 14.67 A I_p = \frac{V_p}{|Z_p|} = \frac{440}{30} = 14.67\ \text{A} I p ​ = ∣ Z p ​ ∣ V p ​ ​ = 30 440 ​ = 14.67 A

Compute line current I L I_L I L ​ for Delta connection: I L = 3 I p = 3 × 14.67 = 1.73205 × 14.67 = 25.40 A I_L = \sqrt{3} I_p = \sqrt{3} \times 14.67 = 1.73205 \times 14.67 = 25.40\ \text{A} I L ​ = 3 ​ I p ​ = 3 ​ × 14.67 = 1.73205 × 14.67 = 25.40 A

Compute Total 3-Phase Active and Reactive Power: P 3 ϕ = 3 V L I L cos ⁡ θ = 3 × 440 × 25.40 × 0.60 = 11 , 616 W = 11.62 kW P_{3\phi} = \sqrt{3} V_L I_L \cos\theta = \sqrt{3} \times 440 \times 25.40 \times 0.60 = 11,616\ \text{W} = 11.62\ \text{kW} P 3 ϕ ​ = 3 ​ V L ​ I L ​ cos θ = 3 ​ × 440 × 25.40 × 0.60 = 11 , 616 W = 11.62 kW Q 3 ϕ = 3 V L I L sin ⁡ θ = 3 × 440 × 25.40 × 0.80 = 15 , 488 VAR = 15.49 kVAR Q_{3\phi} = \sqrt{3} V_L I_L \sin\theta = \sqrt{3} \times 440 \times 25.40 \times 0.80 = 15,488\ \text{VAR} = 15.49\ \text{kVAR} Q 3 ϕ ​ = 3 ​ V L ​ I L ​ sin θ = 3 ​ × 440 × 25.40 × 0.80 = 15 , 488 VAR = 15.49 kVAR

Example 2: Two-Wattmeter Method Analysis

Problem: Two wattmeters connected to measure power in a 230 V 230\ \text{V} 230 V , 3-phase balanced system yield readings of W 1 = 8000 W W_1 = 8000\ \text{W} W 1 ​ = 8000 W and W 2 = 4000 W W_2 = 4000\ \text{W} W 2 ​ = 4000 W . Calculate: (a) total active power P 3 ϕ P_{3\phi} P 3 ϕ ​ , (b) total reactive power Q 3 ϕ Q_{3\phi} Q 3 ϕ ​ , (c) load power factor PF \text{PF} PF , and (d) line current I L I_L I L ​ .

Solution:

Calculate total active power P 3 ϕ P_{3\phi} P 3 ϕ ​ : P 3 ϕ = W 1 + W 2 = 8000 + 4000 = 12 , 000 W = 12 kW P_{3\phi} = W_1 + W_2 = 8000 + 4000 = 12,000\ \text{W} = 12\ \text{kW} P 3 ϕ ​ = W 1 ​ + W 2 ​ = 8000 + 4000 = 12 , 000 W = 12 kW

Calculate total reactive power Q 3 ϕ Q_{3\phi} Q 3 ϕ ​ : Q 3 ϕ = 3 ( W 1 − W 2 ) = 3 × ( 8000 − 4000 ) = 1.73205 × 4000 = 6928.2 VAR = 6.93 kVAR Q_{3\phi} = \sqrt{3} (W_1 - W_2) = \sqrt{3} \times (8000 - 4000) = 1.73205 \times 4000 = 6928.2\ \text{VAR} = 6.93\ \text{kVAR} Q 3 ϕ ​ = 3 ​ ( W 1 ​ − W 2 ​ ) = 3 ​ × ( 8000 − 4000 ) = 1.73205 × 4000 = 6928.2 VAR = 6.93 kVAR

Calculate tangent of phase angle θ \theta θ and power factor: tan ⁡ θ = Q 3 ϕ P 3 ϕ = 6928.2 12 , 000 = 0.57735 ⟹ θ = arctan ⁡ ( 0.57735 ) = 30 ∘ \tan\theta = \frac{Q_{3\phi}}{P_{3\phi}} = \frac{6928.2}{12,000} = 0.57735 \quad \implies \quad \theta = \arctan(0.57735) = 30^\circ tan θ = P 3 ϕ ​ Q 3 ϕ ​ ​ = 12 , 000 6928.2 ​ = 0.57735 ⟹ θ = arctan ( 0.57735 ) = 3 0 ∘ PF = cos ⁡ ( 30 ∘ ) = 3 2 ≈ 0.8660 \text{PF} = \cos(30^\circ) = \frac{\sqrt{3}}{2} \approx 0.8660 PF = cos ( 3 0 ∘ ) = 2 3 ​ ​ ≈ 0.8660

Calculate line current I L I_L I L ​ from active power formula: P 3 ϕ = 3 V L I L cos ⁡ θ ⟹ I L = P 3 ϕ 3 V L cos ⁡ θ P_{3\phi} = \sqrt{3} V_L I_L \cos\theta \quad \implies \quad I_L = \frac{P_{3\phi}}{\sqrt{3} V_L \cos\theta} P 3 ϕ ​ = 3 ​ V L ​ I L ​ cos θ ⟹ I L ​ = 3 ​ V L ​ cos θ P 3 ϕ ​ ​ I L = 12 , 000 3 × 230 × 0.8660 = 12 , 000 345.0 = 34.78 A I_L = \frac{12,000}{\sqrt{3} \times 230 \times 0.8660} = \frac{12,000}{345.0} = 34.78\ \text{A} I L ​ = 3 ​ × 230 × 0.8660 12 , 000 ​ = 345.0 12 , 000 ​ = 34.78 A

Loading diagram... Three-Phase Wye/Delta Relations and Two-Wattmeter Measurement