Study guide
14.2 Electrical Apparatus & Devices — Industrial Electronics & Power Converters
PRC Registered Electrical Engineer REE
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Overview, RA 7920 & Electrical Engineering Ethics
1.1 PRC Board of Electrical Engineering & REE Examination Overview 1.2 Republic Act No. 7920 (New Electrical Engineering Law) & License Classes 1.3 Code of Ethics & Professional Practice for Electrical Engineers
2 Chapter 2: Math — Algebra, Trig & Geometry
2.1 Algebraic Equations, Polynomials & Complex Numbers 2.2 Trigonometry — Identities, Triangles & Spherical Trig 2.3 Analytic & Solid Geometry
3 Chapter 3: Engineering Mathematics — Calculus & Differential Equations
3.1 Differential Calculus, Limits, Derivatives & Applications 3.2 Integral Calculus, Integration Techniques & Area/Volume Applications 3.3 Ordinary Differential Equations & Initial-Value Problems
4 Chapter 4: Engineering Mathematics — Advanced Math & Transform Methods
4.1 Laplace Transforms, Inverse Transforms & Circuit Applications 4.2 Fourier Series, Fourier Transforms & Frequency-Domain Analysis 4.3 Vector Analysis, Linear Algebra, Matrices & Complex Analysis
5 Chapter 5: Engineering Mathematics — Probability, Statistics & Engineering Data Analysis
5.1 Probability Theory, Counting Techniques & Bayes' Theorem 5.2 Engineering Data Analysis I — Descriptive Statistics & Probability Distributions 5.3 Engineering Data Analysis II — Confidence Intervals, Hypothesis Testing & Regression
6 Chapter 6: Engineering Mathematics — Numerical Methods & Analysis
6.1 Numerical Root-Finding & Solution of Linear Systems 6.2 Interpolation, Numerical Integration & Numerical Solution of ODEs
7 Chapter 7: ESAS — Physics, Chemistry & Computer Fundamentals
7.1 Physics for Engineers 7.2 General Chemistry & Materials Science 7.3 Computer Fundamentals, Programming & Data Logic 7.4 Logic Circuits, Switching Theory & Microprocessor Systems
8 Chapter 8: ESAS — Mechanics & Thermal-Fluid Engineering
8.1 Engineering Mechanics — Statics & Dynamics 8.2 Strength of Materials & Mechanics of Deformable Bodies 8.3 Thermal-Fluid Engineering — Thermodynamics & Fluid Mechanics
9 Chapter 9: ESAS — Engineering Economics, Management & Contracts
9.1 Engineering Economics & Depreciation 9.2 Engineering Management & Ethics 9.3 Philippine Electrical Engineering Law, Code & Contracts 9.4 Technopreneurship 101 & Management of Engineering Projects
10 Chapter 10: PEC 1 — Safety, Sizing & Protection
10.1 PEC Fundamentals, Safety Standards & Grounding/Bonding 10.2 Conductor Sizing, Ampacity Adjustment & Voltage Drop 10.3 Overcurrent Protection, Branch Circuit & Feeder Sizing 10.4 Basic Occupational Safety & Health (BOSH) and Electrical Safety Standards
11 Chapter 11: PEC 1 & 2 — Equipment & Utility Systems
11.1 PEC Equipment Installation & Wiring Methods 11.2 Utility Systems, Transformers & Switchgear 11.3 Special Occupancies & Hazardous Locations
12 Chapter 12: Electrical Professional — DC & AC Circuit Fundamentals
12.1 DC Circuit Analysis & Network Theorems 12.2 Single-Phase AC Circuits & Phasor Analysis 12.3 Balanced & Unbalanced Three-Phase AC Circuits
13 Chapter 13: Electrical Professional — EM Fields & Transients
13.1 Electrostatics, Magnetostatics & Maxwell's Equations 13.2 Electromagnetic Waves & Transmission Line Fields 13.3 First-Order & Second-Order Circuit Transients
14 Chapter 14: Electrical Professional — Electronics, Industrial Electronics & Communications
14.1 Electronics 1 & 2 — Semiconductor Devices & Analog Circuits 14.2 Electrical Apparatus & Devices — Industrial Electronics & Power Converters 14.3 Fundamentals of Electronic Communications
15 Chapter 15: Electrical Professional — Transformers & DC Machines
15.1 Single-Phase & Three-Phase Transformers 15.2 Transformer Connections & Special Transformers 15.3 DC Generators & DC Motors
16 Chapter 16: Electrical Professional — AC Synchronous & Induction Machinery
16.1 Synchronous Generators (Alternators) 16.2 Synchronous Motors & Special AC Machines 16.3 Three-Phase & Single-Phase Induction Motors
17 Chapter 17: Electrical Professional — Power Plants & Energy Conversion
17.1 Hydroelectric, Thermal & Combined Cycle Power Plants 17.2 Renewable Energy Systems & Geothermal Power Plants 17.3 Power Plant Economics, Load Curves & Energy Conversion
18 Chapter 18: Electrical Professional — Transmission & Distribution
18.1 Transmission Line Parameters & Performance Models 18.2 Mechanical Overhead Line Design, Underground Cables & Insulators 18.3 Distribution Systems, Substation Layouts & Power Flow Control
19 Chapter 19: Electrical Professional — Power System Analysis
19.1 The Per-Unit System, Base Conversion & Impedance Diagrams 19.2 Symmetrical Components & Unbalanced Fault Analysis 19.3 Load Flow, Economic Dispatch & Power System Stability
20 Chapter 20: Electrical Professional — Protection, Control, Instrumentation & Illumination
20.1 Power System Protection & Protective Relaying 20.2 Industrial Motor Control, Logic Circuits & PLC Automation 20.3 Electrical Instrumentation, Transducers & Measurement Systems 20.4 Illumination Engineering, Lighting Design & Photometrics 20.5 Feedback Control Systems & Research Methods
14.2 Electrical Apparatus & Devices — Industrial Electronics & Power Converters
Key Takeaways Explain This Topic AI
Electrical Apparatus & Devices and Industrial Electronics form topic E of the Enhanced TOS Electrical Engineering subject, weighted 2.25% of the exam and 5 of the 100 items.
An SCR latches on once gated and turns off only when its anode current falls below the holding current, which is why DC choppers need forced commutation but AC circuits self-commutate.
A single-phase fully controlled bridge delivers Vdc = (2Vm/π)·cos α, so the output reverses polarity for firing angles beyond 90° and the converter inverts.
A three-phase full-wave controlled bridge gives Vdc = (3√2·VLL/π)·cos α = 1.35·VLL·cos α at zero firing delay.
A VFD holds constant volts-per-hertz below base speed to keep flux and torque constant, then operates in field weakening above base speed at reduced torque.
Last updated: August 2026
14.2 Electrical Apparatus & Devices — Industrial Electronics & Power Converters
Topic E of the Electrical Engineering subject in the PRC Enhanced Table of Specifications (PRBEE Resolution No. 40, s. 2024 ) is Electrical Apparatus & Devices, Industrial Electronics , weighted 2.25% of the whole examination and 5 of the 100 Electrical Engineering items . The 2011 syllabus carried the same material as Electronic Power Equipment and Components & Devices . This is the electronics that actually sits in an electrical engineer's switchroom: drives, soft starters, UPS systems and rectifier banks.
1. The Thyristor Family
Device Structure Control Turn-off
SCR (silicon controlled rectifier) 4-layer PNPN, 3 terminals Gate pulse triggers ON Only when I A < I H I_A < I_H I A < I H (holding current)
- TRIAC Bidirectional, 3 terminals Gate, either polarity At each current zero
- DIAC Bidirectional, 2 terminals Breakover voltage At current zero
- GTO Gate turn-off thyristor Positive pulse ON, negative pulse OFF Gate controlled
- IGBT MOS gate, bipolar output Gate voltage Gate controlled, fully
The defining SCR behaviour: a gate pulse latches the device on, after which the gate loses all control. Turn-off requires the anode current to fall below the holding current . In AC circuits this happens naturally at each current zero ( natural or line commutation ); in DC circuits an auxiliary circuit must force the current to zero ( forced commutation ). This single fact explains most SCR examination items.
Latching current is the minimum anode current needed to latch the device on at turn-on; holding current is the minimum needed to keep it on. Latching current is always the larger of the two.
2. Controlled Rectifiers (AC to DC)
Delaying the SCR firing angle α \alpha α from the natural commutation point reduces the average output.
Single-phase half-wave controlled: V d c = V m 2 π ( 1 + cos α ) V_{dc} = \frac{V_m}{2\pi}\left(1 + \cos\alpha\right) V d c = 2 π V m ( 1 + cos α )
Single-phase fully controlled bridge (continuous conduction): V d c = 2 V m π cos α V_{dc} = \frac{2V_m}{\pi}\cos\alpha V d c = π 2 V m cos α
Three-phase full-wave (six-pulse) fully controlled bridge: V d c = 3 2 V L L π cos α = 1.35 V L L cos α V_{dc} = \frac{3\sqrt{2}\,V_{LL}}{\pi}\cos\alpha = 1.35\,V_{LL}\cos\alpha V d c = π 3 2 V LL cos α = 1.35 V LL cos α
Three consequences are examinable:
At α = 0 \alpha = 0 α = 0 the converter behaves as an uncontrolled diode bridge;
For α > 90 ° \alpha > 90° α > 90° with an inductive source of EMF, V d c V_{dc} V d c goes negative — power flows from the DC side back to the AC line and the converter operates in the inversion mode, which is how a regenerative drive returns braking energy;
Displacement power factor for a fully controlled converter is approximately cos α \cos\alpha cos α , so deep phase control means poor power factor — the reason large rectifier installations need harmonic filters and reactive compensation.
- 3. Choppers, Inverters and AC Controllers
- DC Chopper (DC to DC)
With duty cycle D = t o n / T D = t_{on}/T D = t o n / T : V o = D V s (buck) , V o = V s 1 − D (boost) , V o = D V s 1 − D (buck-boost) V_o = D\,V_s \quad \text{(buck)}, \qquad V_o = \frac{V_s}{1-D} \quad \text{(boost)}, \qquad V_o = \frac{D\,V_s}{1-D} \quad \text{(buck-boost)} V o = D V s (buck) , V o = 1 − D V s (boost) , V o = 1 − D D V s (buck-boost)
Inverter (DC to AC)
Converts DC to AC of controllable magnitude and frequency. Voltage source inverters dominate motor drives. Output waveform quality ranks square wave < modified sine < sinusoidal PWM , and the modulation index sets the fundamental amplitude: m a = V control V carrier , V o 1 ( peak ) = m a V d c 2 ( m a ≤ 1 ) m_a = \frac{V_{\text{control}}}{V_{\text{carrier}}}, \qquad V_{o1(\text{peak})} = m_a\frac{V_{dc}}{2} \quad (m_a \le 1) m a = V carrier V control , V o 1 ( peak ) = m a 2 V d c ( m a ≤ 1 )
Raising the switching frequency pushes harmonics higher, where they are easier to filter, at the cost of greater switching loss.
AC Voltage Controller and Cycloconverter
An AC voltage controller uses back-to-back SCRs (or a TRIAC) to vary rms voltage at constant frequency — the basis of the soft starter and of resistive heating control. A cycloconverter converts directly from a fixed AC frequency to a lower variable frequency without a DC link, used in very large low-speed drives such as cement mills.
- Converter Input Output Typical application
- Rectifier AC DC Battery charging, DC drives, UPS front end
- Chopper DC DC Traction, DC motor speed control
- Inverter DC AC VFD output stage, solar PV, UPS output
- AC controller AC AC, same f f f Soft starter, light dimming, heater control
- Cycloconverter AC AC, lower f f f Large low-speed mill drives
- 4. Variable-Frequency Drives and Soft Starters
A VFD is a rectifier, a DC link and a PWM inverter in series. Below base speed it holds the volts-per-hertz ratio constant so that air-gap flux — and hence available torque — stays constant: V f = constant ⟹ ϕ ≈ V 4.44 f N = constant \frac{V}{f} = \text{constant} \qquad \Longrightarrow \qquad \phi \approx \frac{V}{4.44\,f\,N} = \text{constant} f V = constant ⟹ ϕ ≈ 4.44 f N V = constant
For a 460 V, 60 Hz motor the ratio is 460 / 60 = 7.67 460/60 = 7.67 460/60 = 7.67 V/Hz, so 30 Hz operation requires 230 V. Above base speed the voltage cannot rise further, so V / f V/f V / f falls, flux weakens, and the drive enters the constant-power field-weakening region with torque falling as 1 / f 1/f 1/ f .
Synchronous speed follows the frequency directly: N s = 120 f P N_s = \frac{120f}{P} N s = P 120 f
A soft starter , by contrast, only ramps voltage at fixed 60 Hz. It limits starting current but reduces starting torque with the square of the voltage, so it cannot start a high-inertia load that a VFD handles easily. T s t T s t , full = ( V applied V rated ) 2 \frac{T_{st}}{T_{st,\text{full}}} = \left(\frac{V_{\text{applied}}}{V_{\text{rated}}}\right)^{2} T s t , full T s t = ( V rated V applied ) 2
5. Harmonics from Converter Loads
Non-linear converter loads draw non-sinusoidal current. A p p p -pulse converter generates characteristic harmonics of order h = k p ± 1 , k = 1 , 2 , 3 , … h = kp \pm 1, \qquad k = 1, 2, 3, \dots h = k p ± 1 , k = 1 , 2 , 3 , …
so a six-pulse drive produces the 5th, 7th, 11th and 13th harmonics, while a twelve-pulse arrangement cancels the 5th and 7th and starts at the 11th. Total harmonic distortion and true power factor follow: T H D I = ∑ h ≥ 2 I h 2 I 1 , P F true = cos θ 1 1 + T H D I 2 THD_I = \frac{\sqrt{\sum_{h \ge 2} I_h^{2}}}{I_1}, \qquad PF_{\text{true}} = \frac{\cos\theta_1}{\sqrt{1 + THD_I^{2}}} T H D I = I 1 ∑ h ≥ 2 I h 2 , P F true = 1 + T H D I 2 cos θ 1
The distortion factor term is why a drive with near-unity displacement factor can still present a true power factor well below unity, and why triplen (3rd, 9th, 15th) harmonics from single-phase electronic loads add arithmetically in the neutral of a four-wire system, sometimes forcing an oversized neutral conductor.
- Solved Board Exam Examples
- Example 1: Three-Phase Controlled Rectifier Output
A six-pulse fully controlled bridge is supplied from a 460 V line-to-line, 60 Hz source and fired at α = 30 ° \alpha = 30° α = 30° . Find the average DC output voltage.
Solution. V d c = 1.35 V L L cos α = 1.35 ( 460 ) cos 30 ° = 621 ( 0.8660 ) = 537.8 V V_{dc} = 1.35\,V_{LL}\cos\alpha = 1.35(460)\cos 30° = 621(0.8660) = \boxed{537.8 \text{ V}} V d c = 1.35 V LL cos α = 1.35 ( 460 ) cos 30° = 621 ( 0.8660 ) = 537.8 V
At α = 0 \alpha = 0 α = 0 the same bridge would deliver 621 V; at α = 90 ° \alpha = 90° α = 90° the average output is zero; beyond 90° it goes negative and the converter inverts.
Example 2: Constant Volts-per-Hertz Operation
A 460 V, 60 Hz, 4-pole induction motor is driven by a VFD at 45 Hz. Find the applied voltage under constant V/f control and the new synchronous speed.
Solution. The rated ratio is V f = 460 60 = 7.667 V/Hz \frac{V}{f} = \frac{460}{60} = 7.667 \text{ V/Hz} f V = 60 460 = 7.667 V/Hz V 45 = 7.667 × 45 = 345 V V_{45} = 7.667 \times 45 = \boxed{345 \text{ V}} V 45 = 7.667 × 45 = 345 V N s = 120 ( 45 ) 4 = 1350 rpm N_s = \frac{120(45)}{4} = \boxed{1350 \text{ rpm}} N s = 4 120 ( 45 ) = 1350 rpm
Because flux is preserved, the motor develops full rated torque at 1350 rpm — the property that distinguishes a VFD from a soft starter.
Example 3: Soft Starter Torque Penalty
A soft starter limits the applied voltage to 65% of rated during starting. What fraction of full-voltage starting torque remains?
Solution. Starting torque varies with the square of the applied voltage: T s t T s t , full = ( 0.65 ) 2 = 0.4225 or 42.25 % \frac{T_{st}}{T_{st,\text{full}}} = (0.65)^{2} = \boxed{0.4225 \text{ or } 42.25\%} T s t , full T s t = ( 0.65 ) 2 = 0.4225 or 42.25%