Study guide

10.3 Overcurrent Protection, Branch Circuit & Feeder Sizing

PRC Registered Electrical Engineer REE

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Overview, RA 7920 & Electrical Engineering Ethics

1.1 PRC Board of Electrical Engineering & REE Examination Overview 1.2 Republic Act No. 7920 (New Electrical Engineering Law) & License Classes 1.3 Code of Ethics & Professional Practice for Electrical Engineers

2 Chapter 2: Math — Algebra, Trig & Geometry

2.1 Algebraic Equations, Polynomials & Complex Numbers 2.2 Trigonometry — Identities, Triangles & Spherical Trig 2.3 Analytic & Solid Geometry

3 Chapter 3: Engineering Mathematics — Calculus & Differential Equations

3.1 Differential Calculus, Limits, Derivatives & Applications 3.2 Integral Calculus, Integration Techniques & Area/Volume Applications 3.3 Ordinary Differential Equations & Initial-Value Problems

4 Chapter 4: Engineering Mathematics — Advanced Math & Transform Methods

4.1 Laplace Transforms, Inverse Transforms & Circuit Applications 4.2 Fourier Series, Fourier Transforms & Frequency-Domain Analysis 4.3 Vector Analysis, Linear Algebra, Matrices & Complex Analysis

5 Chapter 5: Engineering Mathematics — Probability, Statistics & Engineering Data Analysis

5.1 Probability Theory, Counting Techniques & Bayes' Theorem 5.2 Engineering Data Analysis I — Descriptive Statistics & Probability Distributions 5.3 Engineering Data Analysis II — Confidence Intervals, Hypothesis Testing & Regression

6 Chapter 6: Engineering Mathematics — Numerical Methods & Analysis

6.1 Numerical Root-Finding & Solution of Linear Systems 6.2 Interpolation, Numerical Integration & Numerical Solution of ODEs

7 Chapter 7: ESAS — Physics, Chemistry & Computer Fundamentals

7.1 Physics for Engineers 7.2 General Chemistry & Materials Science 7.3 Computer Fundamentals, Programming & Data Logic 7.4 Logic Circuits, Switching Theory & Microprocessor Systems

8 Chapter 8: ESAS — Mechanics & Thermal-Fluid Engineering

8.1 Engineering Mechanics — Statics & Dynamics 8.2 Strength of Materials & Mechanics of Deformable Bodies 8.3 Thermal-Fluid Engineering — Thermodynamics & Fluid Mechanics

9 Chapter 9: ESAS — Engineering Economics, Management & Contracts

9.1 Engineering Economics & Depreciation 9.2 Engineering Management & Ethics 9.3 Philippine Electrical Engineering Law, Code & Contracts 9.4 Technopreneurship 101 & Management of Engineering Projects

10 Chapter 10: PEC 1 — Safety, Sizing & Protection

10.1 PEC Fundamentals, Safety Standards & Grounding/Bonding 10.2 Conductor Sizing, Ampacity Adjustment & Voltage Drop 10.3 Overcurrent Protection, Branch Circuit & Feeder Sizing 10.4 Basic Occupational Safety & Health (BOSH) and Electrical Safety Standards

11 Chapter 11: PEC 1 & 2 — Equipment & Utility Systems

11.1 PEC Equipment Installation & Wiring Methods 11.2 Utility Systems, Transformers & Switchgear 11.3 Special Occupancies & Hazardous Locations

12 Chapter 12: Electrical Professional — DC & AC Circuit Fundamentals

12.1 DC Circuit Analysis & Network Theorems 12.2 Single-Phase AC Circuits & Phasor Analysis 12.3 Balanced & Unbalanced Three-Phase AC Circuits

13 Chapter 13: Electrical Professional — EM Fields & Transients

13.1 Electrostatics, Magnetostatics & Maxwell's Equations 13.2 Electromagnetic Waves & Transmission Line Fields 13.3 First-Order & Second-Order Circuit Transients

14 Chapter 14: Electrical Professional — Electronics, Industrial Electronics & Communications

14.1 Electronics 1 & 2 — Semiconductor Devices & Analog Circuits 14.2 Electrical Apparatus & Devices — Industrial Electronics & Power Converters 14.3 Fundamentals of Electronic Communications

15 Chapter 15: Electrical Professional — Transformers & DC Machines

15.1 Single-Phase & Three-Phase Transformers 15.2 Transformer Connections & Special Transformers 15.3 DC Generators & DC Motors

16 Chapter 16: Electrical Professional — AC Synchronous & Induction Machinery

16.1 Synchronous Generators (Alternators) 16.2 Synchronous Motors & Special AC Machines 16.3 Three-Phase & Single-Phase Induction Motors

17 Chapter 17: Electrical Professional — Power Plants & Energy Conversion

17.1 Hydroelectric, Thermal & Combined Cycle Power Plants 17.2 Renewable Energy Systems & Geothermal Power Plants 17.3 Power Plant Economics, Load Curves & Energy Conversion

18 Chapter 18: Electrical Professional — Transmission & Distribution

18.1 Transmission Line Parameters & Performance Models 18.2 Mechanical Overhead Line Design, Underground Cables & Insulators 18.3 Distribution Systems, Substation Layouts & Power Flow Control

19 Chapter 19: Electrical Professional — Power System Analysis

19.1 The Per-Unit System, Base Conversion & Impedance Diagrams 19.2 Symmetrical Components & Unbalanced Fault Analysis 19.3 Load Flow, Economic Dispatch & Power System Stability

20 Chapter 20: Electrical Professional — Protection, Control, Instrumentation & Illumination

20.1 Power System Protection & Protective Relaying 20.2 Industrial Motor Control, Logic Circuits & PLC Automation 20.3 Electrical Instrumentation, Transducers & Measurement Systems 20.4 Illumination Engineering, Lighting Design & Photometrics 20.5 Feedback Control Systems & Research Methods

10.3 Overcurrent Protection, Branch Circuit & Feeder Sizing

Key Takeaways Explain This Topic AI

Overcurrent protective devices (OCPD)—including molded-case circuit breakers (MCCB) and time-delay fuses—protect conductors and equipment against sustained overloads and high-magnitude short-circuit fault currents.

PEC Rule 2.40.1.4(D) enforces strict maximum OCPD ratings for small copper conductors: 2.0 mm² (14 AWG) requires 15 A max, 3.5 mm² (12 AWG) requires 20 A max, and 5.5 mm² (10 AWG) requires 30 A max.

For OCPDs rated 800 A or less, PEC permits the 'next higher standard rating rule', allowing the OCPD rating to exceed the conductor ampacity to the next standard device size, provided the circuit does not supply multi-outlet branch receptacles.

Feeder load calculations apply standard demand factors (PEC Table 2.20.3.3) to raw connected loads: dwelling general lighting applies 100% on the first 3,000 VA, 35% from 3,001 to 120,000 VA, and 25% on the remainder.

Service entrance neutral conductors are sized to carry the maximum unbalanced load, with a permitted 70% demand factor (0.70) applied to the portion of neutral current exceeding 200 A for linear loads.

Last updated: August 2026

  • 10.3 Overcurrent Protection, Branch Circuit & Feeder Sizing
  • 1. Overcurrent Protection Fundamentals: Overload vs. Short-Circuit Faults

An overcurrent is any current in excess of the rated equipment capacity or conductor ampacity. Overcurrents stem from two distinct physical phenomena:

Overload Current: An operating condition where current exceeds normal full-load rating but remains confined to normal conductor paths (e.g., plugging too many appliances into one circuit or overloading an electric motor). Overloads produce slow, cumulative thermal heating.

Short-Circuit / Ground-Fault Current: An abnormal, low-impedance electrical path resulting from insulation breakdown or direct phase-to-phase / phase-to-ground contact. Fault currents can jump to thousands of Amperes within milliseconds, creating intense electromagnetic forces and explosive thermal energy. Fault Current: I sc = V source Z transformer + Z feeder ≫ I load \text{Fault Current: } I_{\text{sc}} = \frac{V_{\text{source}}}{Z_{\text{transformer}} + Z_{\text{feeder}}} \gg I_{\text{load}} Fault Current: I sc ​ = Z transformer ​ + Z feeder ​ V source ​ ​ ≫ I load ​

Overcurrent Protective Device (OCPD) Types

Molded-Case Circuit Breakers (MCCB): Features a dual tripping mechanism: a thermal bimetallic element for inverse-time overload protection and a magnetic solenoid / trip coil for instantaneous short-circuit protection.

Dual-Element Time-Delay Fuses: Utilizes a low-melting spring-loaded solder joint for overload protection (allowing transient motor start-up surges without blowing) and a high-interrupting silver/copper fuse link for fast short-circuit clearing.

Standard Ampere Ratings of OCPDs (PEC Section 2.40.1.6)

Standard circuit breaker and fuse ratings recognized by PEC are: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000, 6000 Amperes .

  • 2. Small Conductor Overcurrent Rules & Next Standard Rating Provision
  • Small Conductor Protection Limits (PEC Section 2.40.1.4(D))

To prevent physical thermal degradation of small copper branch circuit conductors, the PEC imposes absolute upper limits on upstream overcurrent protection, regardless of higher insulation temperature ratings ( 75 ∘ C 75^\circ\text{C} 7 5 ∘ C or 90 ∘ C 90^\circ\text{C} 9 0 ∘ C ):

  • Conductor Size Material Maximum Overcurrent Protection Rating
  • 2.0 mm 2 2.0\text{ mm}^2 2.0 mm 2 (14 AWG) Copper 15 Amperes
  • 3.5 mm 2 3.5\text{ mm}^2 3.5 mm 2 (12 AWG) Copper 20 Amperes
  • 5.5 mm 2 5.5\text{ mm}^2 5.5 mm 2 (10 AWG) Copper 30 Amperes
  • The "Next Standard Rating Rule" (PEC Section 2.40.1.4(B))

For conductors rated 800 Amperes or less , if the calculated allowable ampacity of a conductor does not correspond to a standard OCPD ampere rating listed in PEC 2.40.1.6, the next higher standard OCPD rating is permitted, provided all three of the following conditions are satisfied:

  • The conductor does not supply a multi-outlet branch circuit feeding receptacle outlets;
  • The conductor ampacity does not correspond to a standard OCPD size;

The rating of the OCPD chosen does not exceed 800 Amperes .

Example: A feeder conductor has a derated allowable ampacity of 142 A 142\text{ A} 142 A . The standard OCPD ratings near this value are 125 A 125\text{ A} 125 A and 150 A 150\text{ A} 150 A . Under PEC 2.40.1.4(B), a 150 A circuit breaker is permitted to protect the 142 A 142\text{ A} 142 A conductor.

  • 3. Branch Circuit Load Calculations (Dwelling & Commercial Units)
  • General Lighting Load Densities (PEC Table 2.20.2.3)

Branch circuit design begins by converting floor space into apparent power using floor area unit load factors based on outside building dimensions:

  • Occupancy Type Unit General Lighting Load Factor
  • Dwelling Units (Residential) 24 VA/m 2 24\text{ VA/m}^2 24 VA/m 2 (or 3 VA/ft 2 3\text{ VA/ft}^2 3 VA/ft 2 )
  • Office Buildings 28 VA/m 2 28\text{ VA/m}^2 28 VA/m 2 (or 3.5 VA/ft 2 3.5\text{ VA/ft}^2 3.5 VA/ft 2 )

Schools / Educational Institutions 24 VA/m 2 24\text{ VA/m}^2 24 VA/m 2 (or 3 VA/ft 2 3\text{ VA/ft}^2 3 VA/ft 2 )

  • Hospitals / Medical Facilities 16 VA/m 2 16\text{ VA/m}^2 16 VA/m 2 (or 2 VA/ft 2 2\text{ VA/ft}^2 2 VA/ft 2 )
  • Stores / Retail Commercial 24 VA/m 2 24\text{ VA/m}^2 24 VA/m 2 (or 3 VA/ft 2 3\text{ VA/ft}^2 3 VA/ft 2 )
  • Mandatory Residential Branch Circuits (PEC Section 2.10.1.11)

For every residential dwelling unit, the PEC mandates the following minimum small appliance and laundry circuits in addition to general lighting circuits:

Small Appliance Branch Circuits: Minimum of two (2) 20-Ampere circuits ( 3.5 mm 2 3.5\text{ mm}^2 3.5 mm 2 wire) rated at 1 , 500 VA 1,500\text{ VA} 1 , 500 VA each for kitchen, pantry, and dining room receptacles.

Laundry Branch Circuit: Minimum of one (1) 20-Ampere circuit ( 3.5 mm 2 3.5\text{ mm}^2 3.5 mm 2 wire) rated at 1 , 500 VA 1,500\text{ VA} 1 , 500 VA for laundry room receptacles.

Bathroom Branch Circuit: Minimum of one (1) 20-Ampere circuit for bathroom receptacles.

4. Feeder Load Sizing & Standard Demand Factors

Because all electrical loads in a facility never operate simultaneously at full rating, PEC Part 1 permits applying demand factors to calculate feeder and service entrance sizing. Demand Load = Connected Load × Demand Factor \text{Demand Load} = \text{Connected Load} \times \text{Demand Factor} Demand Load = Connected Load × Demand Factor

General Lighting Feeder Demand Factors (PEC Table 2.20.3.3)

For dwelling units, general lighting and small appliance loads are summed, and demand factors are applied in tiers:

  • Tier Portion of Total Calculated Lighting Load Demand Factor ( K demand K_{\text{demand}} K demand ​ )
  • First 3,000 VA or less 100% (1.00)
  • From 3,001 VA to 120,000 VA 35% (0.35)
  • Remainder over 120,000 VA 25% (0.25)
  • Feeder Demand Factors for Special Loads

Electric Clothes Dryers: 5 , 000 VA 5,000\text{ VA} 5 , 000 VA or nameplate rating (whichever is larger). Demand factor is 100% for 1 to 4 dryers.

Household Electric Ranges / Cooking Appliances: Sized using PEC Table 2.20.3.16. For a single household range rated up to 12 kW 12\text{ kW} 12 kW , the feeder demand load is 8 kW 8\text{ kW} 8 kW ( 8 , 000 VA 8,000\text{ VA} 8 , 000 VA ).

Motor Loads (PEC 4.30.2.4): Feeder conductors supplying multiple motors must be sized for 125% of the full-load current (FLA) of the largest motor plus the sum of full-load currents of all other motors on the feeder: I motor feeder = 1.25 × I FLA, largest + ∑ I FLA, others I_{\text{motor feeder}} = 1.25 \times I_{\text{FLA, largest}} + \sum I_{\text{FLA, others}} I motor feeder ​ = 1.25 × I FLA, largest ​ + ∑ I FLA, others ​

5. Service Entrance Neutral Sizing & Unbalanced Load Reduction

The service entrance neutral conductor carries the maximum unbalanced load resulting from line-to-neutral loads.

The 200-Ampere Neutral Load Reduction Rule (PEC Section 2.20.3.22)

For 3-wire single-phase or 4-wire 3-phase systems supplying linear loads, a demand factor of 70% (0.70) is permitted for that portion of the unbalanced neutral load that exceeds 200 Amperes : I neutral, demand = 200 A + 0.70 × ( I unbalanced − 200 A ) ( for I unbalanced > 200 A ) I_{\text{neutral, demand}} = 200\text{ A} + 0.70 \times (I_{\text{unbalanced}} - 200\text{ A}) \quad (\text{for } I_{\text{unbalanced}} > 200\text{ A}) I neutral, demand ​ = 200 A + 0.70 × ( I unbalanced ​ − 200 A ) ( for I unbalanced ​ > 200 A )

Critical Harmonic Restriction: The 70% neutral reduction factor is strictly prohibited on 4-wire 3-phase circuits supplying non-linear electronic loads (fluorescent/LED lighting, data processing equipment, variable frequency drives). In non-linear systems, third-harmonic (180 Hz) currents do not cancel out in the neutral; they add arithmetically, causing neutral currents that can exceed phase currents ( I neutral ≈ 3 × I phase I_{\text{neutral}} \approx \sqrt{3} \times I_{\text{phase}} I neutral ​ ≈ 3 ​ × I phase ​ ).

6. Interrupting Capacity (AIC) & Short-Circuit Current Ratings (SCCR)

Every overcurrent protective device must have an Ampere Interrupting Capacity (AIC) rating equal to or greater than the maximum available fault current at its line terminals. Transformer Available Short-Circuit Current: I sc, max = I FLA, secondary % Z / 100 \text{Transformer Available Short-Circuit Current: } I_{\text{sc, max}} = \frac{I_{\text{FLA, secondary}}}{\%Z / 100} Transformer Available Short-Circuit Current: I sc, max ​ = % Z /100 I FLA, secondary ​ ​

Where % Z \%Z % Z is the transformer percent impedance (typically 2.5 % 2.5\% 2.5% to 5.75 % 5.75\% 5.75% for distribution transformers). Standard breaker AIC ratings are 10 kAIC, 14 kAIC, 22 kAIC, 42 kAIC, and 65 kAIC . Installing a 10 kAIC breaker at a main panel where available fault current is 18 kAIC violates PEC 1.10.1.9 and creates severe arc-flash/explosion risks.

  • Solved Practice Examples
  • Example 1: Dwelling Unit Feeder Load Calculation

Problem: A residential single-family dwelling unit in Quezon City has a total floor area of 200 m 2 200\text{ m}^2 200 m 2 . The connected loads include:

General Lighting: 200 m 2 × 24 VA/m 2 = 4 , 800 VA 200\text{ m}^2 \times 24\text{ VA/m}^2 = 4,800\text{ VA} 200 m 2 × 24 VA/m 2 = 4 , 800 VA

Two (2) Small Appliance Circuits: 2 × 1 , 500 VA = 3 , 000 VA 2 \times 1,500\text{ VA} = 3,000\text{ VA} 2 × 1 , 500 VA = 3 , 000 VA

  • One (1) Laundry Circuit: 1 , 500 VA 1,500\text{ VA} 1 , 500 VA
  • Electric Range: 10 , 000 VA 10,000\text{ VA} 10 , 000 VA (nameplate)
  • Electric Water Heater: 3 , 000 VA 3,000\text{ VA} 3 , 000 VA (non-continuous)

Calculate the net calculated feeder demand load in VA and the minimum 230 V service disconnect main breaker size.

Solution:

Sum Lighting and Appliance Loads: Total Lighting + Small Appliance + Laundry = 4 , 800 + 3 , 000 + 1 , 500 = 9 , 300 VA \text{Total Lighting + Small Appliance + Laundry} = 4,800 + 3,000 + 1,500 = 9,300\text{ VA} Total Lighting + Small Appliance + Laundry = 4 , 800 + 3 , 000 + 1 , 500 = 9 , 300 VA

Apply Table 2.20.3.3 General Lighting Demand Factors:

First 3 , 000 VA 3,000\text{ VA} 3 , 000 VA at 100 % : 3 , 000 × 1.00 = 3 , 000 VA 100\%: 3,000 \times 1.00 = 3,000\text{ VA} 100% : 3 , 000 × 1.00 = 3 , 000 VA

Remaining ( 9 , 300 − 3 , 000 ) = 6 , 300 VA (9,300 - 3,000) = 6,300\text{ VA} ( 9 , 300 − 3 , 000 ) = 6 , 300 VA at 35 % : 6 , 300 × 0.35 = 2 , 205 VA 35\%: 6,300 \times 0.35 = 2,205\text{ VA} 35% : 6 , 300 × 0.35 = 2 , 205 VA

Subtotal Demand Lighting Load = 3 , 000 + 2 , 205 = 5 , 205 VA 3,000 + 2,205 = 5,205\text{ VA} 3 , 000 + 2 , 205 = 5 , 205 VA

Add Special Appliances with Demand Factors:

  • Electric Range (PEC Table 2.20.3.16 for single 10 kW range): 8 , 000 VA 8,000\text{ VA} 8 , 000 VA
  • Water Heater (100% demand): 3 , 000 VA 3,000\text{ VA} 3 , 000 VA

Total Calculated Net Feeder Demand Load: Total Net Demand Load = 5 , 205 + 8 , 000 + 3 , 000 = 16 , 205 VA \text{Total Net Demand Load} = 5,205 + 8,000 + 3,000 = 16,205\text{ VA} Total Net Demand Load = 5 , 205 + 8 , 000 + 3 , 000 = 16 , 205 VA

Calculate Service Entrance Current at 230 V: I service = 16 , 205 VA 230 V = 70.46 Amperes I_{\text{service}} = \frac{16,205\text{ VA}}{230\text{ V}} = 70.46\text{ Amperes} I service ​ = 230 V 16 , 205 VA ​ = 70.46 Amperes

Select Main Circuit Breaker Rating:

The calculated load is 70.46 A 70.46\text{ A} 70.46 A . The next higher standard main circuit breaker rating per PEC 2.40.1.6 is 80 Amperes (or 100 Amperes standard service disconnect minimum per PEC 2.30.6.10).

Loading diagram... Complete Feeder & Service Entrance Load Sizing Architecture

Feeder Demand Load Distribution for a Standard Dwelling Unit (16,205 VA Total)