19.2 Symmetrical Components & Unbalanced Fault Analysis
PRC Registered Electrical Engineer REE
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Overview, RA 7920 & Electrical Engineering Ethics
1.1 PRC Board of Electrical Engineering & REE Examination Overview 1.2 Republic Act No. 7920 (New Electrical Engineering Law) & License Classes 1.3 Code of Ethics & Professional Practice for Electrical Engineers
2 Chapter 2: Math — Algebra, Trig & Geometry
2.1 Algebraic Equations, Polynomials & Complex Numbers 2.2 Trigonometry — Identities, Triangles & Spherical Trig 2.3 Analytic & Solid Geometry
3 Chapter 3: Engineering Mathematics — Calculus & Differential Equations
3.1 Differential Calculus, Limits, Derivatives & Applications 3.2 Integral Calculus, Integration Techniques & Area/Volume Applications 3.3 Ordinary Differential Equations & Initial-Value Problems
4 Chapter 4: Engineering Mathematics — Advanced Math & Transform Methods
4.1 Laplace Transforms, Inverse Transforms & Circuit Applications 4.2 Fourier Series, Fourier Transforms & Frequency-Domain Analysis 4.3 Vector Analysis, Linear Algebra, Matrices & Complex Analysis
5 Chapter 5: Engineering Mathematics — Probability, Statistics & Engineering Data Analysis
5.1 Probability Theory, Counting Techniques & Bayes' Theorem 5.2 Engineering Data Analysis I — Descriptive Statistics & Probability Distributions 5.3 Engineering Data Analysis II — Confidence Intervals, Hypothesis Testing & Regression
6 Chapter 6: Engineering Mathematics — Numerical Methods & Analysis
6.1 Numerical Root-Finding & Solution of Linear Systems 6.2 Interpolation, Numerical Integration & Numerical Solution of ODEs
7 Chapter 7: ESAS — Physics, Chemistry & Computer Fundamentals
7.1 Physics for Engineers 7.2 General Chemistry & Materials Science 7.3 Computer Fundamentals, Programming & Data Logic 7.4 Logic Circuits, Switching Theory & Microprocessor Systems
8 Chapter 8: ESAS — Mechanics & Thermal-Fluid Engineering
8.1 Engineering Mechanics — Statics & Dynamics 8.2 Strength of Materials & Mechanics of Deformable Bodies 8.3 Thermal-Fluid Engineering — Thermodynamics & Fluid Mechanics
9 Chapter 9: ESAS — Engineering Economics, Management & Contracts
9.1 Engineering Economics & Depreciation 9.2 Engineering Management & Ethics 9.3 Philippine Electrical Engineering Law, Code & Contracts 9.4 Technopreneurship 101 & Management of Engineering Projects
10 Chapter 10: PEC 1 — Safety, Sizing & Protection
10.1 PEC Fundamentals, Safety Standards & Grounding/Bonding 10.2 Conductor Sizing, Ampacity Adjustment & Voltage Drop 10.3 Overcurrent Protection, Branch Circuit & Feeder Sizing 10.4 Basic Occupational Safety & Health (BOSH) and Electrical Safety Standards
11 Chapter 11: PEC 1 & 2 — Equipment & Utility Systems
11.1 PEC Equipment Installation & Wiring Methods 11.2 Utility Systems, Transformers & Switchgear 11.3 Special Occupancies & Hazardous Locations
12 Chapter 12: Electrical Professional — DC & AC Circuit Fundamentals
12.1 DC Circuit Analysis & Network Theorems 12.2 Single-Phase AC Circuits & Phasor Analysis 12.3 Balanced & Unbalanced Three-Phase AC Circuits
13 Chapter 13: Electrical Professional — EM Fields & Transients
13.1 Electrostatics, Magnetostatics & Maxwell's Equations 13.2 Electromagnetic Waves & Transmission Line Fields 13.3 First-Order & Second-Order Circuit Transients
14 Chapter 14: Electrical Professional — Electronics, Industrial Electronics & Communications
14.1 Electronics 1 & 2 — Semiconductor Devices & Analog Circuits 14.2 Electrical Apparatus & Devices — Industrial Electronics & Power Converters 14.3 Fundamentals of Electronic Communications
15 Chapter 15: Electrical Professional — Transformers & DC Machines
15.1 Single-Phase & Three-Phase Transformers 15.2 Transformer Connections & Special Transformers 15.3 DC Generators & DC Motors
16 Chapter 16: Electrical Professional — AC Synchronous & Induction Machinery
16.1 Synchronous Generators (Alternators) 16.2 Synchronous Motors & Special AC Machines 16.3 Three-Phase & Single-Phase Induction Motors
17 Chapter 17: Electrical Professional — Power Plants & Energy Conversion
17.1 Hydroelectric, Thermal & Combined Cycle Power Plants 17.2 Renewable Energy Systems & Geothermal Power Plants 17.3 Power Plant Economics, Load Curves & Energy Conversion
18 Chapter 18: Electrical Professional — Transmission & Distribution
18.1 Transmission Line Parameters & Performance Models 18.2 Mechanical Overhead Line Design, Underground Cables & Insulators 18.3 Distribution Systems, Substation Layouts & Power Flow Control
19 Chapter 19: Electrical Professional — Power System Analysis
19.1 The Per-Unit System, Base Conversion & Impedance Diagrams 19.2 Symmetrical Components & Unbalanced Fault Analysis 19.3 Load Flow, Economic Dispatch & Power System Stability
20 Chapter 20: Electrical Professional — Protection, Control, Instrumentation & Illumination
20.1 Power System Protection & Protective Relaying 20.2 Industrial Motor Control, Logic Circuits & PLC Automation 20.3 Electrical Instrumentation, Transducers & Measurement Systems 20.4 Illumination Engineering, Lighting Design & Photometrics 20.5 Feedback Control Systems & Research Methods
19.2 Symmetrical Components & Unbalanced Fault Analysis
Key Takeaways Explain This Topic AI
Any set of three unbalanced phasors resolves into positive-, negative- and zero-sequence sets, with Va0 = (Va + Vb + Vc)/3 and the operator a = 1∠120°.
A three-phase balanced fault uses the positive-sequence network only; single line-to-ground connects all three sequence networks in series and gives Ia1 = Ea/(Z1 + Z2 + Z0).
Line-to-line faults connect positive and negative sequence networks in parallel with no zero-sequence involvement, so LL fault current is about 86.6% of the three-phase value.
Zero-sequence current requires a return path: a delta winding traps it and an ungrounded wye blocks it entirely, which is why transformer connection determines ground-fault current.
Faults ranked by typical frequency of occurrence are single line-to-ground (about 70–80%), line-to-line, double line-to-ground, then three-phase (about 5%), which is nevertheless usually the most severe.
Last updated: August 2026
19.2 Symmetrical Components & Unbalanced Fault Analysis
Balanced three-phase faults are the easy case and account for only about 5% of real faults. The remaining 95% are unbalanced, and the only practical way to analyse them by hand is Fortescue's method of symmetrical components , a core component of Enhanced TOS topic K, Power System Analysis (PRBEE Resolution No. 40, s. 2024 — 9.00% of the examination, 20 of the 100 Electrical Engineering items).
1. The Symmetrical Component Transformation
Any three unbalanced phasors decompose into three balanced sets:
Positive sequence (1) — three equal phasors 120° apart in the normal rotation a a a – b b b – c c c ; this is the only set present in a healthy balanced system;
Negative sequence (2) — three equal phasors 120° apart in the reversed rotation a a a – c c c – b b b ; it produces a counter-rotating field that heats generator rotors, which is why negative-sequence relays exist;
Zero sequence (0) — three equal phasors in phase ; it can flow only where a neutral or ground return path exists.
The operator a = 1 ∠ 120 ° = − 0.5 + j 0.866 a = 1\angle 120° = -0.5 + j0.866 a = 1∠120° = − 0.5 + j 0.866 satisfies a 2 = 1 ∠ 240 ° , a 3 = 1 , 1 + a + a 2 = 0 a^{2} = 1\angle 240°, \qquad a^{3} = 1, \qquad 1 + a + a^{2} = 0 a 2 = 1∠240° , a 3 = 1 , 1 + a + a 2 = 0
Synthesis (components to phase quantities): V a = V a 0 + V a 1 + V a 2 V_a = V_{a0} + V_{a1} + V_{a2} V a = V a 0 + V a 1 + V a 2 V b = V a 0 + a 2 V a 1 + a V a 2 V_b = V_{a0} + a^{2}V_{a1} + aV_{a2} V b = V a 0 + a 2 V a 1 + a V a 2 V c = V a 0 + a V a 1 + a 2 V a 2 V_c = V_{a0} + aV_{a1} + a^{2}V_{a2} V c = V a 0 + a V a 1 + a 2 V a 2
Analysis (phase quantities to components): V a 0 = 1 3 ( V a + V b + V c ) V_{a0} = \frac{1}{3}\left(V_a + V_b + V_c\right) V a 0 = 3 1 ( V a + V b + V c ) V a 1 = 1 3 ( V a + a V b + a 2 V c ) V_{a1} = \frac{1}{3}\left(V_a + aV_b + a^{2}V_c\right) V a 1 = 3 1 ( V a + a V b + a 2 V c ) V a 2 = 1 3 ( V a + a 2 V b + a V c ) V_{a2} = \frac{1}{3}\left(V_a + a^{2}V_b + aV_c\right) V a 2 = 3 1 ( V a + a 2 V b + a V c )
Two consequences are examined repeatedly:
In a three-wire system (no neutral), I a + I b + I c = 0 I_a + I_b + I_c = 0 I a + I b + I c = 0 , so zero-sequence current is zero by definition;
In a four-wire system the neutral carries I n = 3 I a 0 I_n = 3I_{a0} I n = 3 I a 0 — the neutral current is three times the zero-sequence current, not equal to it.
2. Sequence Networks
Each sequence has its own network with its own impedance.
Element Z 1 Z_1 Z 1 Z 2 Z_2 Z 2 Z 0 Z_0 Z 0
Synchronous generator X d ′ ′ X_d'' X d ′′ ≈ X d ′ ′ \approx X_d'' ≈ X d ′′ Smallest; typically 0.15 0.15 0.15 – 0.6 × X 1 0.6 \times X_1 0.6 × X 1
Transformer Z T Z_T Z T Z T Z_T Z T Z T Z_T Z T , but path depends on winding connection
Transmission line Z 1 Z_1 Z 1 Z 1 = Z 2 Z_1 = Z_2 Z 1 = Z 2 2 2 2 – 3.5 × Z 1 3.5 \times Z_1 3.5 × Z 1 (ground return path)
For static equipment — lines, cables, transformers — Z 1 = Z 2 Z_1 = Z_2 Z 1 = Z 2 always, because a static device cannot tell the direction of phase rotation. For rotating machines Z 2 ≠ Z 1 Z_2 \ne Z_1 Z 2 = Z 1 in general, though Z 2 ≈ X d ′ ′ Z_2 \approx X_d'' Z 2 ≈ X d ′′ is the usual working assumption.
Zero-sequence line impedance is substantially higher than positive sequence because the return path is the earth and any overhead ground wires, enclosing a much larger flux loop.
Transformer Zero-Sequence Connection Rules
This table is the single most examinable item in the topic:
- Connection Zero-sequence path
- Grounded wye – grounded wye Continuous through the transformer
- Grounded wye – delta Flows on the wye side, circulates and is trapped in the delta; does not pass through
- Delta – delta Blocked on both sides; no external zero-sequence path
- Ungrounded wye – anything Blocked; no zero-sequence current at all
- Grounded wye – delta (as grounding bank) Provides a deliberate zero-sequence source for ground-fault detection
A delta winding is a zero-sequence trap : it gives circulating third-harmonic and zero-sequence currents somewhere to go, which is why a delta tertiary is added to large wye-wye autotransformers.
3. Fault Types and Sequence Network Interconnection
- Fault type Network connection Fault current expression
- Three-phase (balanced) Positive sequence only I f = E a Z 1 I_f = \dfrac{E_a}{Z_1} I f = Z 1 E a
Single line-to-ground (SLG) Z 1 Z_1 Z 1 , Z 2 Z_2 Z 2 , Z 0 Z_0 Z 0 in series I a 1 = E a Z 1 + Z 2 + Z 0 I_{a1} = \dfrac{E_a}{Z_1+Z_2+Z_0} I a 1 = Z 1 + Z 2 + Z 0 E a , I a = 3 I a 1 I_a = 3I_{a1} I a = 3 I a 1
Line-to-line (LL) Z 1 Z_1 Z 1 , Z 2 Z_2 Z 2 in parallel ; no zero sequence I a 1 = E a Z 1 + Z 2 I_{a1} = \dfrac{E_a}{Z_1+Z_2} I a 1 = Z 1 + Z 2 E a , I b = − j 3 I a 1 I_b = -j\sqrt{3}\,I_{a1} I b = − j 3 I a 1
Double line-to-ground (DLG) Z 1 Z_1 Z 1 in series with Z 2 ∥ Z 0 Z_2 \parallel Z_0 Z 2 ∥ Z 0 I a 1 = E a Z 1 + Z 2 Z 0 Z 2 + Z 0 I_{a1} = \dfrac{E_a}{Z_1 + \dfrac{Z_2Z_0}{Z_2+Z_0}} I a 1 = Z 1 + Z 2 + Z 0 Z 2 Z 0 E a
Open conductor Series (rather than shunt) network connection Produces negative-sequence current without high fault current
Fault-current arithmetic worth memorising: with Z 1 = Z 2 Z_1 = Z_2 Z 1 = Z 2 , the line-to-line fault current is I L L I 3 ϕ = 3 2 = 0.866 \frac{I_{LL}}{I_{3\phi}} = \frac{\sqrt{3}}{2} = 0.866 I 3 ϕ I LL = 2 3 = 0.866
so an LL fault is always about 86.6% of the three-phase value. A single line-to-ground fault can exceed the three-phase value when Z 0 < Z 1 Z_0 < Z_1 Z 0 < Z 1 , which happens on solidly grounded systems close to a grounded-wye transformer — a genuine engineering result and a favourite examination trap for candidates who assume the three-phase fault is always the worst case.
Faults ranked by frequency of occurrence: SLG 70–80% , LL about 15%, DLG about 10%, and three-phase only about 5% .
4. System Grounding
- Grounding method Ground-fault current Transient overvoltage Typical application
- Solidly grounded Very high Low LV distribution, most utility MV
- Low-resistance grounded Limited to 100–1000 A Moderate Industrial MV systems
- High-resistance grounded Limited to about 5–10 A Moderate Continuous-process plants
- Ungrounded Capacitive only High (arcing ground fault) Legacy systems; increasingly avoided
Neutral grounding impedance Z n Z_n Z n appears in the zero-sequence network as 3 Z n 3Z_n 3 Z n — three times, because the total zero-sequence current 3 I a 0 3I_{a0} 3 I a 0 flows through it. Forgetting the factor of three is the standard error in grounded-neutral fault problems.
- Solved Board Exam Examples
- Example 1: Resolving Unbalanced Line Currents
A four-wire feeder carries I a = 10 ∠ 0 ° I_a = 10\angle 0° I a = 10∠0° A, I b = 10 ∠ 230 ° I_b = 10\angle 230° I b = 10∠230° A and I c = 10 ∠ 130 ° I_c = 10\angle 130° I c = 10∠130° A. Find the zero-sequence current and the neutral current.
Solution. I a 0 = 1 3 ( I a + I b + I c ) I_{a0} = \frac{1}{3}\left(I_a + I_b + I_c\right) I a 0 = 3 1 ( I a + I b + I c )
Converting to rectangular form: 10 ∠ 0 ° = 10 + j 0 10\angle 0° = 10 + j0 10∠0° = 10 + j 0 ; 10 ∠ 230 ° = − 6.428 − j 7.660 10\angle 230° = -6.428 - j7.660 10∠230° = − 6.428 − j 7.660 ; 10 ∠ 130 ° = − 6.428 + j 7.660 10\angle 130° = -6.428 + j7.660 10∠130° = − 6.428 + j 7.660 . ∑ = ( 10 − 6.428 − 6.428 ) + j ( 0 − 7.660 + 7.660 ) = − 2.856 + j 0 \sum = (10 - 6.428 - 6.428) + j(0 - 7.660 + 7.660) = -2.856 + j0 ∑ = ( 10 − 6.428 − 6.428 ) + j ( 0 − 7.660 + 7.660 ) = − 2.856 + j 0 I a 0 = − 2.856 3 = − 0.952 A = 0.952 ∠ 180 ° A I_{a0} = \frac{-2.856}{3} = \boxed{-0.952 \text{ A}} = 0.952\angle 180° \text{ A} I a 0 = 3 − 2.856 = − 0.952 A = 0.952∠180° A
The neutral carries three times this value: I n = 3 I a 0 = 2.856 ∠ 180 ° A I_n = 3I_{a0} = \boxed{2.856\angle 180° \text{ A}} I n = 3 I a 0 = 2.856∠180° A
Had the feeder been three-wire with no neutral or ground return, I a + I b + I c I_a + I_b + I_c I a + I b + I c would be forced to zero and no zero-sequence component could exist at all — a useful sanity check on any set of measured currents.
Example 2: Single Line-to-Ground Fault Current
At a bus, Z 1 = j 0.15 Z_1 = j0.15 Z 1 = j 0.15 pu, Z 2 = j 0.15 Z_2 = j0.15 Z 2 = j 0.15 pu and Z 0 = j 0.05 Z_0 = j0.05 Z 0 = j 0.05 pu on a 100 MVA, 13.8 kV base. Find the SLG fault current in amperes and compare it with the three-phase fault.
Solution. For an SLG fault the sequence networks are in series: I a 1 = 1.0 j ( 0.15 + 0.15 + 0.05 ) = 1.0 j 0.35 = − j 2.857 pu I_{a1} = \frac{1.0}{j(0.15 + 0.15 + 0.05)} = \frac{1.0}{j0.35} = -j2.857 \text{ pu} I a 1 = j ( 0.15 + 0.15 + 0.05 ) 1.0 = j 0.35 1.0 = − j 2.857 pu I a = 3 I a 1 = 8.571 pu I_a = 3I_{a1} = 8.571 \text{ pu} I a = 3 I a 1 = 8.571 pu I b a s e = 100 3 ( 13.8 ) = 4.184 kA ⟹ I a = 8.571 × 4.184 = 35.86 kA I_{base} = \frac{100}{\sqrt{3}(13.8)} = 4.184 \text{ kA} \implies I_a = 8.571 \times 4.184 = \boxed{35.86 \text{ kA}} I ba se = 3 ( 13.8 ) 100 = 4.184 kA ⟹ I a = 8.571 × 4.184 = 35.86 kA
The three-phase fault gives 1.0 / 0.15 = 6.667 1.0/0.15 = 6.667 1.0/0.15 = 6.667 pu = 27.89 = 27.89 = 27.89 kA. Because Z 0 < Z 1 Z_0 < Z_1 Z 0 < Z 1 , the ground fault is 28% more severe than the three-phase fault — precisely the case that defeats the "three-phase is always worst" assumption.
Example 3: Line-to-Line Fault Ratio
For a machine with Z 1 = Z 2 = j 0.20 Z_1 = Z_2 = j0.20 Z 1 = Z 2 = j 0.20 pu, find the ratio of line-to-line fault current to three-phase fault current.
Solution. I 3 ϕ = 1.0 0.20 = 5.0 pu I_{3\phi} = \frac{1.0}{0.20} = 5.0 \text{ pu} I 3 ϕ = 0.20 1.0 = 5.0 pu
For the LL fault, I a 1 = 1.0 j ( 0.20 + 0.20 ) = − j 2.5 I_{a1} = \dfrac{1.0}{j(0.20+0.20)} = -j2.5 I a 1 = j ( 0.20 + 0.20 ) 1.0 = − j 2.5 pu, and the faulted phase current is I b = − j 3 I a 1 ⟹ ∣ I b ∣ = 3 ( 2.5 ) = 4.330 pu I_b = -j\sqrt{3}\,I_{a1} \implies |I_b| = \sqrt{3}(2.5) = 4.330 \text{ pu} I b = − j 3 I a 1 ⟹ ∣ I b ∣ = 3 ( 2.5 ) = 4.330 pu I L L I 3 ϕ = 4.330 5.0 = 0.866 \frac{I_{LL}}{I_{3\phi}} = \frac{4.330}{5.0} = \boxed{0.866} I 3 ϕ I LL = 5.0 4.330 = 0.866
This √3/2 ratio holds whenever Z 1 = Z 2 Z_1 = Z_2 Z 1 = Z 2 , independent of the actual impedance values.