1 Chapter 1: Overview, RA 7920 & Electrical Engineering Ethics
1.1 PRC Board of Electrical Engineering & REE Examination Overview 1.2 Republic Act No. 7920 (New Electrical Engineering Law) & License Classes 1.3 Code of Ethics & Professional Practice for Electrical Engineers
2 Chapter 2: Math — Algebra, Trig & Geometry
2.1 Algebraic Equations, Polynomials & Complex Numbers 2.2 Trigonometry — Identities, Triangles & Spherical Trig 2.3 Analytic & Solid Geometry
3 Chapter 3: Engineering Mathematics — Calculus & Differential Equations
3.1 Differential Calculus, Limits, Derivatives & Applications 3.2 Integral Calculus, Integration Techniques & Area/Volume Applications 3.3 Ordinary Differential Equations & Initial-Value Problems
4 Chapter 4: Engineering Mathematics — Advanced Math & Transform Methods
4.1 Laplace Transforms, Inverse Transforms & Circuit Applications 4.2 Fourier Series, Fourier Transforms & Frequency-Domain Analysis 4.3 Vector Analysis, Linear Algebra, Matrices & Complex Analysis
5 Chapter 5: Engineering Mathematics — Probability, Statistics & Engineering Data Analysis
5.1 Probability Theory, Counting Techniques & Bayes' Theorem 5.2 Engineering Data Analysis I — Descriptive Statistics & Probability Distributions 5.3 Engineering Data Analysis II — Confidence Intervals, Hypothesis Testing & Regression
6 Chapter 6: Engineering Mathematics — Numerical Methods & Analysis
6.1 Numerical Root-Finding & Solution of Linear Systems 6.2 Interpolation, Numerical Integration & Numerical Solution of ODEs
7 Chapter 7: ESAS — Physics, Chemistry & Computer Fundamentals
7.1 Physics for Engineers 7.2 General Chemistry & Materials Science 7.3 Computer Fundamentals, Programming & Data Logic 7.4 Logic Circuits, Switching Theory & Microprocessor Systems
8 Chapter 8: ESAS — Mechanics & Thermal-Fluid Engineering
8.1 Engineering Mechanics — Statics & Dynamics 8.2 Strength of Materials & Mechanics of Deformable Bodies 8.3 Thermal-Fluid Engineering — Thermodynamics & Fluid Mechanics
9 Chapter 9: ESAS — Engineering Economics, Management & Contracts
9.1 Engineering Economics & Depreciation 9.2 Engineering Management & Ethics 9.3 Philippine Electrical Engineering Law, Code & Contracts 9.4 Technopreneurship 101 & Management of Engineering Projects
10 Chapter 10: PEC 1 — Safety, Sizing & Protection
10.1 PEC Fundamentals, Safety Standards & Grounding/Bonding 10.2 Conductor Sizing, Ampacity Adjustment & Voltage Drop 10.3 Overcurrent Protection, Branch Circuit & Feeder Sizing 10.4 Basic Occupational Safety & Health (BOSH) and Electrical Safety Standards
11 Chapter 11: PEC 1 & 2 — Equipment & Utility Systems
11.1 PEC Equipment Installation & Wiring Methods 11.2 Utility Systems, Transformers & Switchgear 11.3 Special Occupancies & Hazardous Locations
12 Chapter 12: Electrical Professional — DC & AC Circuit Fundamentals
12.1 DC Circuit Analysis & Network Theorems 12.2 Single-Phase AC Circuits & Phasor Analysis 12.3 Balanced & Unbalanced Three-Phase AC Circuits
13 Chapter 13: Electrical Professional — EM Fields & Transients
13.1 Electrostatics, Magnetostatics & Maxwell's Equations 13.2 Electromagnetic Waves & Transmission Line Fields 13.3 First-Order & Second-Order Circuit Transients
14 Chapter 14: Electrical Professional — Electronics, Industrial Electronics & Communications
14.1 Electronics 1 & 2 — Semiconductor Devices & Analog Circuits 14.2 Electrical Apparatus & Devices — Industrial Electronics & Power Converters 14.3 Fundamentals of Electronic Communications
15 Chapter 15: Electrical Professional — Transformers & DC Machines
15.1 Single-Phase & Three-Phase Transformers 15.2 Transformer Connections & Special Transformers 15.3 DC Generators & DC Motors
16 Chapter 16: Electrical Professional — AC Synchronous & Induction Machinery
16.1 Synchronous Generators (Alternators) 16.2 Synchronous Motors & Special AC Machines 16.3 Three-Phase & Single-Phase Induction Motors
17 Chapter 17: Electrical Professional — Power Plants & Energy Conversion
17.1 Hydroelectric, Thermal & Combined Cycle Power Plants 17.2 Renewable Energy Systems & Geothermal Power Plants 17.3 Power Plant Economics, Load Curves & Energy Conversion
18 Chapter 18: Electrical Professional — Transmission & Distribution
18.1 Transmission Line Parameters & Performance Models 18.2 Mechanical Overhead Line Design, Underground Cables & Insulators 18.3 Distribution Systems, Substation Layouts & Power Flow Control
19 Chapter 19: Electrical Professional — Power System Analysis
19.1 The Per-Unit System, Base Conversion & Impedance Diagrams 19.2 Symmetrical Components & Unbalanced Fault Analysis 19.3 Load Flow, Economic Dispatch & Power System Stability
20 Chapter 20: Electrical Professional — Protection, Control, Instrumentation & Illumination
20.1 Power System Protection & Protective Relaying 20.2 Industrial Motor Control, Logic Circuits & PLC Automation 20.3 Electrical Instrumentation, Transducers & Measurement Systems 20.4 Illumination Engineering, Lighting Design & Photometrics 20.5 Feedback Control Systems & Research Methods
20.3 Electrical Instrumentation, Transducers & Measurement Systems
Key Takeaways Explain This Topic AI
Permanent Magnet Moving Coil (PMMC) instruments measure DC quantities with linear deflection ( T d = B N I A T_d = B N I A T d = BN I A ), whereas Moving Iron (MI) instruments measure true RMS AC/DC quantities with non-linear scale characteristics ( T d = 1 2 I 2 d L d θ T_d = \frac{1}{2} I^2 \frac{dL}{d\theta} T d = 2 1 I 2 d θ d L ).
Ammeter measurement range extension requires a low-resistance parallel shunt ( R sh = R m m − 1 R_{\text{sh}} = \frac{R_m}{m - 1} R sh = m − 1 R m , where m = I / I m m = I / I_m m = I / I m ), while voltmeter range extension requires a high-resistance series multiplier ( R s = R m [ m − 1 ] R_s = R_m[m - 1] R s = R m [ m − 1 ] , where m = V / V m m = V / V_m m = V / V m ).
The Two-Wattmeter Method measures total 3-phase 3-wire power under balanced or unbalanced loads: Total Active Power P total = W 1 + W 2 P_{\text{total}} = W_1 + W_2 P total = W 1 + W 2 , Total Reactive Power Q total = 3 ( W 1 − W 2 ) Q_{\text{total}} = \sqrt{3}(W_1 - W_2) Q total = 3 ( W 1 − W 2 ) , and Power Factor cos ϕ = cos [ arctan ( 3 W 1 − W 2 W 1 + W 2 ) ] \cos \phi = \cos \left[ \arctan\left(\sqrt{3} \frac{W_1 - W_2}{W_1 + W_2}\right) \right] cos ϕ = cos [ arctan ( 3 W 1 + W 2 W 1 − W 2 ) ] .
DC and AC bridge circuits perform precision impedance measurement: Wheatstone bridge for medium resistance, Kelvin Double Bridge for low resistance ( < 1 Ω < 1\ \Omega < 1 Ω , eliminating lead resistance), Maxwell/Hay bridges for inductance, and Schering bridge for capacitance and dielectric dissipation factor ( tan δ \tan \delta tan δ ).
Industrial transducers convert physical parameters into standardized electrical signals: Platinum RTDs (Pt100) exhibit linear positive resistance variation ( R T = R 0 [ 1 + α T ] R_T = R_0[1 + \alpha T] R T = R 0 [ 1 + α T ] ), strain gauges measure mechanical strain via Gauge Factor ( G F = Δ R / R ϵ GF = \frac{\Delta R / R}{\epsilon} GF = ϵ Δ R / R ), and LVDTs provide contactless position feedback.
Last updated: August 2026
20.3 Electrical Instrumentation, Transducers & Measurement Systems
Electrical measuring instruments, meter range extension techniques, bridge networks, 3-phase wattmeter methods, and industrial sensors/transducers form fundamental practical evaluation areas on the PRC Registered Electrical Engineer (REE) Licensure Examination . Power engineers must understand instrument operating mechanisms, sensitivity parameters, measurement error correction, and signal conditioning to perform accurate testing, commissioning, and diagnostic monitoring.
1. Operating Principles of Electrical Measuring Instruments
Measuring instruments convert electromagnetic or electrostatic forces into visual pointer deflections or calibrated digital readout signals.
Meter Movement Operating Comparison
Instrument Type Suitable Quantity Operating Principle Deflecting Torque ( T d T_d T d ) Equation Scale Type Key Advantages & Limitations
PMMC (D'Arsonval) DC Only Interaction of coil current with permanent magnetic field T d = B ⋅ N ⋅ A ⋅ I T_d = B \cdot N \cdot A \cdot I T d = B ⋅ N ⋅ A ⋅ I Strictly Linear (Uniform) High accuracy, high sensitivity, low power consumption. Cannot measure AC (pointer vibrates at 0).
Moving Iron (MI) AC and DC (True RMS) Magnetic repulsion or attraction between iron vanes T d = 1 2 I 2 ( d L d θ ) T_d = \frac{1}{2} I^2 \left( \frac{dL}{d\theta} \right) T d = 2 1 I 2 ( d θ d L ) Non-linear (Square Law, crowded at zero) Robust, inexpensive. Subject to hysteresis errors and frequency variation.
Electrodynamometer AC and DC Force between fixed and moving current-carrying coils T d = I 1 I 2 ( d M d θ ) T_d = I_1 I_2 \left( \frac{dM}{d\theta} \right) T d = I 1 I 2 ( d θ d M ) Non-linear for A/V; Linear for Wattmeter Used as precision Wattmeter ( T d ∝ V I cos ϕ T_d \propto V I \cos \phi T d ∝ V I cos ϕ ) and transfer standard.
Electrostatic AC and DC (Voltage Only) Electrostatic attraction between charged metal plates T d = 1 2 V 2 ( d C d θ ) T_d = \frac{1}{2} V^2 \left( \frac{dC}{d\theta} \right) T d = 2 1 V 2 ( d θ d C ) Non-linear (Square Law) High-voltage voltmeter ( > 1 kV > 1\ \text{kV} > 1 kV ). Draws zero continuous DC current.
2. Meter Movement Range Extension
A basic D'Arsonval PMMC meter movement has a full-scale deflection current I m I_m I m (typically 50 μ A to 10 mA 50\ \mu\text{A} \text{ to } 10\ \text{mA} 50 μ A to 10 mA ) and internal coil resistance R m R_m R m (typically 10 Ω to 1000 Ω 10\ \Omega \text{ to } 1000\ \Omega 10 Ω to 1000 Ω ).
Ammeter Shunt Resistor ( R sh R_{\text{sh}} R sh )
To measure a total line current I > I m I > I_m I > I m , a low-resistance shunt resistor ( R sh R_{\text{sh}} R sh ) is connected in parallel with the meter movement. AMMETER SHUNT RESISTOR EXTENSION
- Line Current I +-----[ Basic Meter Rm, Im ]-----+
- -------------------->| |-----> I
- +-----[ Shunt Resistor Rsh ]-----+
- Ish
Since voltages across parallel branches are equal ( I m R m = I sh R sh I_m R_m = I_{\text{sh}} R_{\text{sh}} I m R m = I sh R sh ) and I sh = I − I m I_{\text{sh}} = I - I_m I sh = I − I m : R sh = I m R m I − I m = R m ( I I m ) − 1 = R m m − 1 R_{\text{sh}} = \frac{I_m R_m}{I - I_m} = \frac{R_m}{\left(\frac{I}{I_m}\right) - 1} = \frac{R_m}{m - 1} R sh = I − I m I m R m = ( I m I ) − 1 R m = m − 1 R m
where m = I I m m = \frac{I}{I_m} m = I m I is the multiplying power of the shunt.
Voltmeter Multiplier Resistor ( R s R_s R s )
To measure a total line voltage V > V m V > V_m V > V m (where V m = I m R m V_m = I_m R_m V m = I m R m ), a high-resistance multiplier resistor ( R s R_s R s ) is connected in series with the meter movement. V = I m ( R m + R s ) ⟹ R s = V I m − R m = R m ( V V m − 1 ) = R m ( m − 1 ) V = I_m (R_m + R_s) \implies R_s = \frac{V}{I_m} - R_m = R_m \left( \frac{V}{V_m} - 1 \right) = R_m (m - 1) V = I m ( R m + R s ) ⟹ R s = I m V − R m = R m ( V m V − 1 ) = R m ( m − 1 )
where m = V V m m = \frac{V}{V_m} m = V m V is the multiplying factor of the series resistor.
3. Bridge Circuits for Impedance & Parameter Measurement
Bridge circuits compare unknown impedances against calibrated precision standards.
DC Bridge Circuits
Wheatstone Bridge : Measures medium resistance ( 1 Ω to 1 M Ω 1\ \Omega \text{ to } 1\ \text{M}\Omega 1 Ω to 1 M Ω ). At balance ( V detector = 0 V_{\text{detector}} = 0 V detector = 0 ): R x = R 2 R 3 R 1 R_x = \frac{R_2 R_3}{R_1} R x = R 1 R 2 R 3
Kelvin Double Bridge : Measures low resistance ( < 1 Ω < 1\ \Omega < 1 Ω , down to 1 μ Ω 1\ \mu\Omega 1 μ Ω ). Eliminates contact resistance and lead wire resistance errors by incorporating twin ratio arms.
AC Bridge Circuits
Maxwell Bridge : Measures medium-Q inductors ( 1 < Q < 10 1 < Q < 10 1 < Q < 10 ) using a parallel RC standard arm ( L x = R 2 R 3 C 4 L_x = R_2 R_3 C_4 L x = R 2 R 3 C 4 , R x = R 2 R 3 R 4 R_x = \frac{R_2 R_3}{R_4} R x = R 4 R 2 R 3 ).
Hay Bridge : Measures high-Q inductors ( Q > 10 Q > 10 Q > 10 ) using a series RC standard arm ( L x = R 2 R 3 C 4 1 + ( 1 / Q ) 2 L_x = \frac{R_2 R_3 C_4}{1 + (1/Q)^2} L x = 1 + ( 1/ Q ) 2 R 2 R 3 C 4 ).
Schering Bridge : Measures unknown capacitance C x = C 2 ( R 4 R 3 ) C_x = C_2 \left(\frac{R_4}{R_3}\right) C x = C 2 ( R 3 R 4 ) and insulation dielectric loss tangent ( tan δ = ω R 4 C 4 \tan \delta = \omega R_4 C_4 tan δ = ω R 4 C 4 ).
Wien Bridge : Measures audio signal frequency ( f = 1 2 π R 1 R 2 C 1 C 2 f = \frac{1}{2\pi \sqrt{R_1 R_2 C_1 C_2}} f = 2 π R 1 R 2 C 1 C 2 1 ).
4. Power & Energy Measurement (Two-Wattmeter Method)
The Two-Wattmeter Method measures total active power in any 3-phase 3-wire system (balanced or unbalanced, Wye or Delta). TWO-WATTMETER METHOD SCHEMATIC
- Line A -------------+---[ W1 Current Coil ]-------------------> Load
- | |
- | [ W1 Potential Coil ]
- | |
- Line B -------------|------------+----------------------------> Load
- | |
- | [ W2 Potential Coil ]
- | |
- Line C -------------+---[ W2 Current Coil ]-------------------> Load
Wattmeter Readings under Balanced Load: W 1 = V L I L cos ( 30 ∘ − ϕ ) W_1 = V_L I_L \cos(30^\circ - \phi) W 1 = V L I L cos ( 3 0 ∘ − ϕ ) W 2 = V L I L cos ( 30 ∘ + ϕ ) W_2 = V_L I_L \cos(30^\circ + \phi) W 2 = V L I L cos ( 3 0 ∘ + ϕ )
Total Active Power ( P total P_{\text{total}} P total ) : P total = W 1 + W 2 = 3 V L I L cos ϕ ( Watts ) P_{\text{total}} = W_1 + W_2 = \sqrt{3} V_L I_L \cos \phi \quad (\text{Watts}) P total = W 1 + W 2 = 3 V L I L cos ϕ ( Watts )
Total Reactive Power ( Q total Q_{\text{total}} Q total ) : Q total = 3 ( W 1 − W 2 ) ( VARs ) Q_{\text{total}} = \sqrt{3} (W_1 - W_2) \quad (\text{VARs}) Q total = 3 ( W 1 − W 2 ) ( VARs )
Power Factor Angle ( ϕ \phi ϕ ) & Power Factor ( cos ϕ \cos \phi cos ϕ ) : tan ϕ = 3 ( W 1 − W 2 W 1 + W 2 ) ⟹ cos ϕ = cos [ arctan ( 3 W 1 − W 2 W 1 + W 2 ) ] \tan \phi = \sqrt{3} \left( \frac{W_1 - W_2}{W_1 + W_2} \right) \implies \cos \phi = \cos \left[ \arctan \left( \sqrt{3} \frac{W_1 - W_2}{W_1 + W_2} \right) \right] tan ϕ = 3 ( W 1 + W 2 W 1 − W 2 ) ⟹ cos ϕ = cos [ arctan ( 3 W 1 + W 2 W 1 − W 2 ) ]
Critical Power Factor Conditions:
Unity Power Factor ( ϕ = 0 ∘ \,\phi = 0^\circ ϕ = 0 ∘ ) : W 1 = W 2 > 0 W_1 = W_2 > 0 W 1 = W 2 > 0 .
Power Factor = 0.50 = 0.50 = 0.50 Lagging ( ϕ = 60 ∘ \,\phi = 60^\circ ϕ = 6 0 ∘ ) : W 1 = P total W_1 = P_{\text{total}} W 1 = P total , while W 2 = 0 W_2 = 0 W 2 = 0 .
Power Factor < 0.50 < 0.50 < 0.50 Lagging ( ϕ > 60 ∘ \,\phi > 60^\circ ϕ > 6 0 ∘ ) : W 2 W_2 W 2 reads negative ! To obtain a correct reading, reverse the potential coil leads and subtract W 2 W_2 W 2 ( P total = W 1 − W 2 P_{\text{total}} = W_1 - W_2 P total = W 1 − W 2 ).
Induction Watt-Hour Meter Energy Calibration Meter Constant K = Revolutions kWh \text{Meter Constant } K = \frac{\text{Revolutions}}{\text{kWh}} Meter Constant K = kWh Revolutions % Error = N actual − N theoretical N theoretical × 100 % \% \text{Error} = \frac{N_{\text{actual}} - N_{\text{theoretical}}}{N_{\text{theoretical}}} \times 100\% % Error = N theoretical N actual − N theoretical × 100%
5. Industrial Sensors & Transducers
Resistance Temperature Detectors (RTDs) : Platinum Pt100 ( R = 100 Ω R = 100\ \Omega R = 100 Ω at 0 ∘ C 0^\circ\text{C} 0 ∘ C , α = 0.00385 Ω / Ω / ∘ C \alpha = 0.00385\ \Omega/\Omega/^\circ\text{C} α = 0.00385 Ω/Ω / ∘ C ). Temperature formula: R T = R 0 [ 1 + α T ] R_T = R_0 [1 + \alpha T] R T = R 0 [ 1 + α T ] . High accuracy and linearity.
Thermocouples : Operates on the Seebeck Effect (voltage generated across dissimilar metal junctions proportional to temperature gradient Δ T \Delta T Δ T ). Types K (Chromel-Alumel), J (Iron-Constantan), T (Copper-Constantan).
Strain Gauges : Piezoresistive sensor measuring mechanical strain ϵ = Δ L L \epsilon = \frac{\Delta L}{L} ϵ = L Δ L . Gauge Factor ( G F GF GF ) : G F = Δ R / R Δ L / L = Δ R / R ϵ GF = \frac{\Delta R / R}{\Delta L / L} = \frac{\Delta R / R}{\epsilon} GF = Δ L / L Δ R / R = ϵ Δ R / R
LVDT (Linear Variable Differential Transformer) : Inductive position transducer producing AC voltage magnitude proportional to core displacement with phase indicating direction.
- Solved Board Exam Examples
- Example 1: Ammeter Shunt & Voltmeter Multiplier Design
Problem: A PMMC meter movement has an internal coil resistance R m = 50 Ω R_m = 50\ \Omega R m = 50 Ω and full-scale deflection current I m = 2 mA I_m = 2\ \text{mA} I m = 2 mA ( 0.002 A 0.002\ \text{A} 0.002 A ). Calculate: (a) Shunt resistance R sh R_{\text{sh}} R sh required to extend the movement to a 0 – 10 A 0\text{--}10\ \text{A} 0 – 10 A ammeter, and (b) Multiplier resistance R s R_s R s required to extend the movement to a 0 – 300 V 0\text{--}300\ \text{V} 0 – 300 V voltmeter.
Solution:
Calculate ammeter shunt resistance ( R sh R_{\text{sh}} R sh ): m = I I m = 10 A 0.002 A = 5000 m = \frac{I}{I_m} = \frac{10\ \text{A}}{0.002\ \text{A}} = 5000 m = I m I = 0.002 A 10 A = 5000 R sh = R m m − 1 = 50 5000 − 1 = 50 4999 = 0.010002 Ω ( 10.002 m Ω ) R_{\text{sh}} = \frac{R_m}{m - 1} = \frac{50}{5000 - 1} = \frac{50}{4999} = 0.010002\ \Omega \quad (10.002\ \text{m}\Omega) R sh = m − 1 R m = 5000 − 1 50 = 4999 50 = 0.010002 Ω ( 10.002 m Ω )
Calculate voltmeter multiplier resistance ( R s R_s R s ): V m = I m R m = 0.002 × 50 = 0.10 V V_m = I_m R_m = 0.002 \times 50 = 0.10\ \text{V} V m = I m R m = 0.002 × 50 = 0.10 V m v = V V m = 300 V 0.10 V = 3000 m_v = \frac{V}{V_m} = \frac{300\ \text{V}}{0.10\ \text{V}} = 3000 m v = V m V = 0.10 V 300 V = 3000 R s = R m ( m v − 1 ) = 50 × ( 3000 − 1 ) = 50 × 2999 = 149 , 950 Ω = 149.95 k Ω R_s = R_m (m_v - 1) = 50 \times (3000 - 1) = 50 \times 2999 = 149,950\ \Omega = 149.95\ \text{k}\Omega R s = R m ( m v − 1 ) = 50 × ( 3000 − 1 ) = 50 × 2999 = 149 , 950 Ω = 149.95 k Ω
Example 2: Two-Wattmeter 3-Phase Power Factor Determination
Problem: Two wattmeters connected to measure power in a 3 3 3 -phase, 460 V 460\ \text{V} 460 V balanced system yield readings W 1 = 9 , 200 W W_1 = 9,200\ \text{W} W 1 = 9 , 200 W and W 2 = 3 , 400 W W_2 = 3,400\ \text{W} W 2 = 3 , 400 W . Calculate: (a) Total active power P total P_{\text{total}} P total , (b) Total reactive power Q total Q_{\text{total}} Q total , (c) Load power factor cos ϕ \cos \phi cos ϕ , and (d) Line current I L I_L I L .
Solution:
Calculate total active power ( P total P_{\text{total}} P total ): P total = W 1 + W 2 = 9200 + 3400 = 12 , 600 W = 12.60 kW P_{\text{total}} = W_1 + W_2 = 9200 + 3400 = 12,600\ \text{W} = 12.60\ \text{kW} P total = W 1 + W 2 = 9200 + 3400 = 12 , 600 W = 12.60 kW
Calculate total reactive power ( Q total Q_{\text{total}} Q total ): Q total = 3 ( W 1 − W 2 ) = 3 ( 9200 − 3400 ) = 1.73205 × 5800 = 10 , 045.9 VAR = 10.05 kVAR Q_{\text{total}} = \sqrt{3} (W_1 - W_2) = \sqrt{3} (9200 - 3400) = 1.73205 \times 5800 = 10,045.9\ \text{VAR} = 10.05\ \text{kVAR} Q total = 3 ( W 1 − W 2 ) = 3 ( 9200 − 3400 ) = 1.73205 × 5800 = 10 , 045.9 VAR = 10.05 kVAR
Calculate power factor angle ϕ \phi ϕ and power factor cos ϕ \cos \phi cos ϕ : tan ϕ = Q total P total = 10 , 045.9 12 , 600 = 0.79729 \tan \phi = \frac{Q_{\text{total}}}{P_{\text{total}}} = \frac{10,045.9}{12,600} = 0.79729 tan ϕ = P total Q total = 12 , 600 10 , 045.9 = 0.79729 ϕ = arctan ( 0.79729 ) = 38.563 ∘ \phi = \arctan(0.79729) = 38.563^\circ ϕ = arctan ( 0.79729 ) = 38.56 3 ∘ Power Factor cos ϕ = cos ( 38.563 ∘ ) = 0.7819 ( 78.19 % lagging ) \text{Power Factor } \cos \phi = \cos(38.563^\circ) = 0.7819 \quad (78.19\%\text{ lagging}) Power Factor cos ϕ = cos ( 38.56 3 ∘ ) = 0.7819 ( 78.19% lagging )
Calculate line current ( I L I_L I L ): P total = 3 V L I L cos ϕ ⟹ I L = 12 , 600 3 × 460 × 0.7819 = 12 , 600 622.95 = 20.23 A P_{\text{total}} = \sqrt{3} V_L I_L \cos \phi \implies I_L = \frac{12,600}{\sqrt{3} \times 460 \times 0.7819} = \frac{12,600}{622.95} = 20.23\ \text{A} P total = 3 V L I L cos ϕ ⟹ I L = 3 × 460 × 0.7819 12 , 600 = 622.95 12 , 600 = 20.23 A