20.4 Illumination Engineering, Lighting Design & Photometrics
PRC Registered Electrical Engineer REE
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Overview, RA 7920 & Electrical Engineering Ethics
1.1 PRC Board of Electrical Engineering & REE Examination Overview 1.2 Republic Act No. 7920 (New Electrical Engineering Law) & License Classes 1.3 Code of Ethics & Professional Practice for Electrical Engineers
2 Chapter 2: Math — Algebra, Trig & Geometry
2.1 Algebraic Equations, Polynomials & Complex Numbers 2.2 Trigonometry — Identities, Triangles & Spherical Trig 2.3 Analytic & Solid Geometry
3 Chapter 3: Engineering Mathematics — Calculus & Differential Equations
3.1 Differential Calculus, Limits, Derivatives & Applications 3.2 Integral Calculus, Integration Techniques & Area/Volume Applications 3.3 Ordinary Differential Equations & Initial-Value Problems
4 Chapter 4: Engineering Mathematics — Advanced Math & Transform Methods
4.1 Laplace Transforms, Inverse Transforms & Circuit Applications 4.2 Fourier Series, Fourier Transforms & Frequency-Domain Analysis 4.3 Vector Analysis, Linear Algebra, Matrices & Complex Analysis
5 Chapter 5: Engineering Mathematics — Probability, Statistics & Engineering Data Analysis
5.1 Probability Theory, Counting Techniques & Bayes' Theorem 5.2 Engineering Data Analysis I — Descriptive Statistics & Probability Distributions 5.3 Engineering Data Analysis II — Confidence Intervals, Hypothesis Testing & Regression
6 Chapter 6: Engineering Mathematics — Numerical Methods & Analysis
6.1 Numerical Root-Finding & Solution of Linear Systems 6.2 Interpolation, Numerical Integration & Numerical Solution of ODEs
7 Chapter 7: ESAS — Physics, Chemistry & Computer Fundamentals
7.1 Physics for Engineers 7.2 General Chemistry & Materials Science 7.3 Computer Fundamentals, Programming & Data Logic 7.4 Logic Circuits, Switching Theory & Microprocessor Systems
8 Chapter 8: ESAS — Mechanics & Thermal-Fluid Engineering
8.1 Engineering Mechanics — Statics & Dynamics 8.2 Strength of Materials & Mechanics of Deformable Bodies 8.3 Thermal-Fluid Engineering — Thermodynamics & Fluid Mechanics
9 Chapter 9: ESAS — Engineering Economics, Management & Contracts
9.1 Engineering Economics & Depreciation 9.2 Engineering Management & Ethics 9.3 Philippine Electrical Engineering Law, Code & Contracts 9.4 Technopreneurship 101 & Management of Engineering Projects
10 Chapter 10: PEC 1 — Safety, Sizing & Protection
10.1 PEC Fundamentals, Safety Standards & Grounding/Bonding 10.2 Conductor Sizing, Ampacity Adjustment & Voltage Drop 10.3 Overcurrent Protection, Branch Circuit & Feeder Sizing 10.4 Basic Occupational Safety & Health (BOSH) and Electrical Safety Standards
11 Chapter 11: PEC 1 & 2 — Equipment & Utility Systems
11.1 PEC Equipment Installation & Wiring Methods 11.2 Utility Systems, Transformers & Switchgear 11.3 Special Occupancies & Hazardous Locations
12 Chapter 12: Electrical Professional — DC & AC Circuit Fundamentals
12.1 DC Circuit Analysis & Network Theorems 12.2 Single-Phase AC Circuits & Phasor Analysis 12.3 Balanced & Unbalanced Three-Phase AC Circuits
13 Chapter 13: Electrical Professional — EM Fields & Transients
13.1 Electrostatics, Magnetostatics & Maxwell's Equations 13.2 Electromagnetic Waves & Transmission Line Fields 13.3 First-Order & Second-Order Circuit Transients
14 Chapter 14: Electrical Professional — Electronics, Industrial Electronics & Communications
14.1 Electronics 1 & 2 — Semiconductor Devices & Analog Circuits 14.2 Electrical Apparatus & Devices — Industrial Electronics & Power Converters 14.3 Fundamentals of Electronic Communications
15 Chapter 15: Electrical Professional — Transformers & DC Machines
15.1 Single-Phase & Three-Phase Transformers 15.2 Transformer Connections & Special Transformers 15.3 DC Generators & DC Motors
16 Chapter 16: Electrical Professional — AC Synchronous & Induction Machinery
16.1 Synchronous Generators (Alternators) 16.2 Synchronous Motors & Special AC Machines 16.3 Three-Phase & Single-Phase Induction Motors
17 Chapter 17: Electrical Professional — Power Plants & Energy Conversion
17.1 Hydroelectric, Thermal & Combined Cycle Power Plants 17.2 Renewable Energy Systems & Geothermal Power Plants 17.3 Power Plant Economics, Load Curves & Energy Conversion
18 Chapter 18: Electrical Professional — Transmission & Distribution
18.1 Transmission Line Parameters & Performance Models 18.2 Mechanical Overhead Line Design, Underground Cables & Insulators 18.3 Distribution Systems, Substation Layouts & Power Flow Control
19 Chapter 19: Electrical Professional — Power System Analysis
19.1 The Per-Unit System, Base Conversion & Impedance Diagrams 19.2 Symmetrical Components & Unbalanced Fault Analysis 19.3 Load Flow, Economic Dispatch & Power System Stability
20 Chapter 20: Electrical Professional — Protection, Control, Instrumentation & Illumination
20.1 Power System Protection & Protective Relaying 20.2 Industrial Motor Control, Logic Circuits & PLC Automation 20.3 Electrical Instrumentation, Transducers & Measurement Systems 20.4 Illumination Engineering, Lighting Design & Photometrics 20.5 Feedback Control Systems & Research Methods
20.4 Illumination Engineering, Lighting Design & Photometrics
Key Takeaways Explain This Topic AI
Fundamental photometric quantities govern light measurement: Luminous Flux ( Φ \Phi Φ , lumens, lm \text{lm} lm ) measures total emitted light energy, Luminous Intensity ( I I I , candelas, cd = lm/sr \text{cd} = \text{lm/sr} cd = lm/sr ) measures directional flux density ( I = d Φ d Ω I = \frac{d\Phi}{d\Omega} I = d Ω d Φ ), Illuminance ( E E E , lux or lm/m 2 \text{lm/m}^2 lm/m 2 ) measures surface incident flux density ( E = d Φ d A E = \frac{d\Phi}{dA} E = d A d Φ ), and Luminous Efficacy ( η \eta η , lm/W \text{lm/W} lm/W ) evaluates electrical conversion efficiency.
Point-by-point illuminance calculations obey the Inverse Square Law ( E N = I d 2 E_N = \frac{I}{d^2} E N = d 2 I ) and Lambert's Cosine Law ( E = I d 2 cos θ = I h 2 cos 3 θ E = \frac{I}{d^2} \cos \theta = \frac{I}{h^2} \cos^3 \theta E = d 2 I cos θ = h 2 I cos 3 θ ), where h h h is luminaire mounting height above the horizontal work plane.
Interior lighting design using the Lumen (Zonal Cavity) Method determines required luminaire fixture count ( N = E ⋅ A n ⋅ Φ lamp ⋅ C U ⋅ L L F N = \frac{E \cdot A}{n \cdot \Phi_{\text{lamp}} \cdot CU \cdot LLF} N = n ⋅ Φ lamp ⋅ C U ⋅ LL F E ⋅ A ) based on Room Cavity Ratio ( RCR = 5 h rc ( L + W ) L ⋅ W \text{RCR} = \frac{5 h_{\text{rc}} (L + W)}{L \cdot W} RCR = L ⋅ W 5 h rc ( L + W ) ), Coefficient of Utilization ( C U CU C U ), and Light Loss Factor ( L L F = L L D × L D D LLF = LLD \times LDD LL F = LL D × L DD ).
Solid-state LED luminaires offer high efficacy ( 120 – 200 lm/W 120\text{--}200\ \text{lm/W} 120 – 200 lm/W ), extended operating life ( 50 , 000 + hours 50,000+\ \text{hours} 50 , 000 + hours ), excellent Color Rendering Index ( CRI ≥ 80 – 90 \text{CRI} \ge 80\text{--}90 CRI ≥ 80 – 90 ), and controllable Correlated Color Temperature (CCT, 2700 K to 6500 K 2700\text{K} \text{ to } 6500\text{K} 2700 K to 6500 K ) compared to legacy fluorescent, metal halide, and high-pressure sodium sources.
Energy-conscious lighting design enforces mandatory Lighting Power Density (LPD, W/m 2 \text{W/m}^2 W/m 2 ) limits established by the Philippine Green Building Code and PEC guidelines (e.g. commercial office LPD target ≤ 8.0 W/m 2 \le 8.0\ \text{W/m}^2 ≤ 8.0 W/m 2 ), integrating daylighting sensors and automated occupancy controls.
Last updated: August 2026
20.4 Illumination Engineering, Lighting Design & Photometrics
Illumination engineering, photometric laws, indoor/outdoor lighting design calculations, light source technologies, and energy efficiency standards represent core practical topics evaluated on the PRC Registered Electrical Engineer (REE) Licensure Examination . Electrical engineers must design lighting systems that deliver optimal visual comfort, glare control, uniform illuminance, and color rendering while adhering to energy efficiency codes (Philippine Green Building Code and PEC guidelines).
1. Fundamentals of Photometry & Light Quantities
Photometry measures light in terms of human visual perception (standard CIE eye response curve peaking at λ = 555 nm \lambda = 555\ \text{nm} λ = 555 nm in the green-yellow spectrum, where 1 Watt of monochromatic radiant power = 683 lumens 1\ \text{Watt of monochromatic radiant power} = 683\ \text{lumens} 1 Watt of monochromatic radiant power = 683 lumens ).
Core Photometric Definitions & Units
Photometric Quantity Symbol SI Unit Mathematical Definition Physical Description
Luminous Flux Φ \Phi Φ or F F F Lumen ( lm \text{lm} lm ) Φ = ∫ 380 780 K ( λ ) P ( λ ) d λ \Phi = \int_{380}^{780} K(\lambda) P(\lambda) d\lambda Φ = ∫ 380 780 K ( λ ) P ( λ ) d λ Total visible light energy emitted by a light source per second.
Luminous Intensity I I I Candela ( cd \text{cd} cd ) I = d Φ d Ω I = \frac{d\Phi}{d\Omega} I = d Ω d Φ Luminous flux emitted per unit solid angle Ω \Omega Ω (steradians, sr \text{sr} sr ) in a specific direction.
Illuminance E E E Lux ( lx = lm/m 2 \text{lx} = \text{lm/m}^2 lx = lm/m 2 ) E = d Φ d A E = \frac{d\Phi}{dA} E = d A d Φ Luminous flux density striking a surface area A A A . ( 1 foot-candle, fc = 10.764 lx 1\ \text{foot-candle, fc} = 10.764\ \text{lx} 1 foot-candle, fc = 10.764 lx ).
Luminance (Brightness) L L L Candela/ m 2 \text{m}^2 m 2 ( cd/m 2 \text{cd/m}^2 cd/m 2 or nit) L = d I d A cos θ L = \frac{dI}{dA \cos \theta} L = d A c o s θ d I Luminous intensity emitted or reflected per unit projected area in a given direction.
Luminous Efficacy η \eta η Lumens/Watt ( lm/W \text{lm/W} lm/W ) η = Φ total P electrical \eta = \frac{\Phi_{\text{total}}}{P_{\text{electrical}}} η = P electrical Φ total Efficiency of converting electrical power input into visible light flux.
Solid Angle ( Ω \Omega Ω ): The 3D spatial angle subtended by a surface area A A A at radius r r r : Ω = A r 2 \Omega = \frac{A}{r^2} Ω = r 2 A steradians ( sr \text{sr} sr ). A complete sphere subtends Ω sphere = 4 π ≈ 12.57 sr \Omega_{\text{sphere}} = 4 \pi \approx 12.57\ \text{sr} Ω sphere = 4 π ≈ 12.57 sr . Thus, a uniform point source of 1 candela 1\ \text{candela} 1 candela emits 4 π lumens 4\pi\ \text{lumens} 4 π lumens total flux.
- 2. Laws of Illumination & Point-by-Point Calculations
- Inverse Square Law of Illumination
Illuminance E E E on a surface perpendicular to light rays varies directly as luminous intensity I I I and inversely as the square of distance d d d from a point source: E N = I d 2 ( Lux ) E_N = \frac{I}{d^2} \quad (\text{Lux}) E N = d 2 I ( Lux )
Lambert's Cosine Law of Illumination
When light strikes a flat surface at an angle θ \theta θ relative to the surface normal, illuminance E E E is proportional to the cosine of the angle of incidence: E = I d 2 cos θ E = \frac{I}{d^2} \cos \theta E = d 2 I cos θ POINT-BY-POINT ILLUMINATION GEOMETRY
- Lamp Source (I candelas)
- |
- | \
- | \
- Mounting Height h | \ Distance d = h / cos(θ)
- | \
- | θ \
- v v
- ----+-------+-------+----- Horizontal Work Plane
- O P
- x (Offset)
- Illuminance Formula for Horizontal Work Plane ( E h E_h E h )
For a luminaire mounted at height h h h above a work plane, illumination at point P P P located at horizontal offset distance x x x from directly below the lamp: d = h 2 + x 2 , cos θ = h d = h h 2 + x 2 d = \sqrt{h^2 + x^2}, \quad \cos \theta = \frac{h}{d} = \frac{h}{\sqrt{h^2 + x^2}} d = h 2 + x 2 , cos θ = d h = h 2 + x 2 h E h = I d 2 cos θ = I ( h 2 + x 2 ) 2 ( h h 2 + x 2 ) = I ⋅ h ( h 2 + x 2 ) 3 / 2 = I h 2 cos 3 θ E_h = \frac{I}{d^2} \cos \theta = \frac{I}{\left(\sqrt{h^2 + x^2}\right)^2} \left( \frac{h}{\sqrt{h^2 + x^2}} \right) = \frac{I \cdot h}{(h^2 + x^2)^{3/2}} = \frac{I}{h^2} \cos^3 \theta E h = d 2 I cos θ = ( h 2 + x 2 ) 2 I ( h 2 + x 2 h ) = ( h 2 + x 2 ) 3/2 I ⋅ h = h 2 I cos 3 θ
3. Interior Lighting Design & The Lumen (Zonal Cavity) Method
The Lumen Method calculates the average uniform illuminance E E E across an interior horizontal work plane ( 0.75 m 0.75\ \text{m} 0.75 m above finished floor).
Fundamental Lumen Method Equations Φ total, required = E × A C U × L L F \Phi_{\text{total, required}} = \frac{E \times A}{CU \times LLF} Φ total, required = C U × LL F E × A N fixtures = E × A n × Φ lamp × C U × L L F N_{\text{fixtures}} = \frac{E \times A}{n \times \Phi_{\text{lamp}} \times CU \times LLF} N fixtures = n × Φ lamp × C U × LL F E × A
where:
E E E = target average illuminance (lux, lx \text{lx} lx ).
A A A = total floor area ( L × W L \times W L × W , m 2 \text{m}^2 m 2 ).
n n n = number of lamps per luminaire fixture.
Φ lamp \Phi_{\text{lamp}} Φ lamp = initial luminous flux output per lamp (lumens, lm \text{lm} lm ).
C U CU C U = Coefficient of Utilization (fraction of lamp lumens reaching work plane, ranging from 0.30 to 0.75 0.30 \text{ to } 0.75 0.30 to 0.75 ).
L L F LLF LL F = Light Loss Factor (Maintenance Factor M F MF MF ) = L L D × L D D × R S D D ≈ 0.70 to 0.85 LLD \times LDD \times RSDD \approx 0.70 \text{ to } 0.85 LL D × L DD × RS DD ≈ 0.70 to 0.85 .
- L L D LLD LL D = Lamp Lumen Depreciation
- L D D LDD L DD = Luminaire Dirt Depreciation
- Room Cavity Ratio (RCR)
The Coefficient of Utilization ( C U CU C U ) depends on room proportions quantified by the Room Cavity Ratio (RCR) : RCR = 5 h rc ( L + W ) L × W \text{RCR} = \frac{5 h_{\text{rc}} (L + W)}{L \times W} RCR = L × W 5 h rc ( L + W )
where h rc h_{\text{rc}} h rc is room cavity height (vertical distance from luminaire mounting height to the work plane).
Luminaire Spacing & Layout Rules
Maximum Spacing ( S max S_{\max} S m a x ) : S max ≤ ( S / M H ) × h rc S_{\max} \le (S/MH) \times h_{\text{rc}} S m a x ≤ ( S / M H ) × h rc , where S / M H S/MH S / M H is luminaire spacing-to-mounting-height ratio ( 1.0 to 1.5 1.0 \text{ to } 1.5 1.0 to 1.5 ).
Distance from Wall ( S wall S_{\text{wall}} S wall ) : S wall = S 2 S_{\text{wall}} = \frac{S}{2} S wall = 2 S (or S 3 \frac{S}{3} 3 S alongside desks).
- 4. Light Sources, Color Metrics & Energy Efficiency
- Comparison of Commercial Lighting Technologies
Lamp Technology Efficacy ( lm/W \text{lm/W} lm/W ) Average Life (Hours) Color Rendering Index ( R a R_a R a ) Correlated Color Temp (CCT, K) Typical Industrial / Commercial Uses
Incandescent / Halogen 10 to 18 10 \text{ to } 18 10 to 18 1 , 000 to 2 , 000 1,000 \text{ to } 2,000 1 , 000 to 2 , 000 100 100 100 2700 to 3000 K 2700 \text{ to } 3000\text{K} 2700 to 3000 K (Warm) Legacy residential accent lighting. Extremely inefficient.
Linear Fluorescent (T8/T5) 75 to 105 75 \text{ to } 105 75 to 105 15 , 000 to 24 , 000 15,000 \text{ to } 24,000 15 , 000 to 24 , 000 80 to 88 80 \text{ to } 88 80 to 88 3000 K to 6500 K 3000\text{K} \text{ to } 6500\text{K} 3000 K to 6500 K Legacy office troffers and commercial strip fixtures.
Metal Halide (MH) 75 to 115 75 \text{ to } 115 75 to 115 10 , 000 to 20 , 000 10,000 \text{ to } 20,000 10 , 000 to 20 , 000 65 to 90 65 \text{ to } 90 65 to 90 3000 K to 4500 K 3000\text{K} \text{ to } 4500\text{K} 3000 K to 4500 K High-bay industrial plants, sports stadiums.
High-Pressure Sodium (HPS) 90 to 140 90 \text{ to } 140 90 to 140 24 , 000 to 30 , 000 24,000 \text{ to } 30,000 24 , 000 to 30 , 000 20 to 25 20 \text{ to } 25 20 to 25 1900 K to 2100 K 1900\text{K} \text{ to } 2100\text{K} 1900 K to 2100 K (Yellow) Outdoor roadway, perimeter security. Poor color rendering.
Solid-State LED 120 to 200 + 120 \text{ to } 200+ 120 to 200 + 50 , 000 to 100 , 000 + 50,000 \text{ to } 100,000+ 50 , 000 to 100 , 000 + 80 to 98 80 \text{ to } 98 80 to 98 2700 K to 6500 K 2700\text{K} \text{ to } 6500\text{K} 2700 K to 6500 K Modern standard across all indoor/outdoor applications.
Color Quality Metrics
Color Rendering Index (CRI / R a R_a R a ) : Measures how accurately a light source renders item colors relative to natural daylight ( 0 to 100 0 \text{ to } 100 0 to 100 ). Office work requires CRI ≥ 80 \text{CRI} \ge 80 CRI ≥ 80 ; inspection areas require CRI ≥ 90 \text{CRI} \ge 90 CRI ≥ 90 .
Correlated Color Temperature (CCT) : Color appearance of emitted light in Kelvin ( 2700 K 2700\text{K} 2700 K Warm White, 4000 K 4000\text{K} 4000 K Neutral White, 6500 K 6500\text{K} 6500 K Daylight).
Lighting Power Density (LPD) & Green Building Code LPD = Total Connected Lighting Power (Watts) Total Building Area ( m 2 ) ( W/m 2 ) \text{LPD} = \frac{\text{Total Connected Lighting Power (Watts)}}{\text{Total Building Area } (\text{m}^2)} \quad (\text{W/m}^2) LPD = Total Building Area ( m 2 ) Total Connected Lighting Power (Watts) ( W/m 2 )
Philippine Green Building Code Limits : Office Space ≤ 8.1 W/m 2 \le 8.1\ \text{W/m}^2 ≤ 8.1 W/m 2 , Educational Facilities ≤ 9.4 W/m 2 \le 9.4\ \text{W/m}^2 ≤ 9.4 W/m 2 , Industrial Plant ≤ 10.5 W/m 2 \le 10.5\ \text{W/m}^2 ≤ 10.5 W/m 2 .
- Solved Board Exam Examples
- Example 1: Point-by-Point Illuminance Calculation
Problem: A luminaire with uniform luminous intensity I = 3 , 200 cd I = 3,200\ \text{cd} I = 3 , 200 cd is mounted 4.0 m 4.0\ \text{m} 4.0 m above a horizontal floor. Calculate illuminance on the floor: (a) Directly below the luminaire ( E 0 E_0 E 0 ), and (b) At a point P P P located 3.0 m 3.0\ \text{m} 3.0 m horizontally away from the point directly below the luminaire.
Solution:
Calculate illuminance directly below the lamp ( E 0 E_0 E 0 , θ = 0 ∘ \theta = 0^\circ θ = 0 ∘ ): E 0 = I h 2 = 3200 ( 4.0 ) 2 = 3200 16 = 200.0 Lux E_0 = \frac{I}{h^2} = \frac{3200}{(4.0)^2} = \frac{3200}{16} = 200.0\ \text{Lux} E 0 = h 2 I = ( 4.0 ) 2 3200 = 16 3200 = 200.0 Lux
Calculate slant distance d d d and angle θ \theta θ to point P P P ( x = 3.0 m x = 3.0\ \text{m} x = 3.0 m ): d = h 2 + x 2 = 4.0 2 + 3.0 2 = 16 + 9 = 25 = 5.0 m d = \sqrt{h^2 + x^2} = \sqrt{4.0^2 + 3.0^2} = \sqrt{16 + 9} = \sqrt{25} = 5.0\ \text{m} d = h 2 + x 2 = 4. 0 2 + 3. 0 2 = 16 + 9 = 25 = 5.0 m cos θ = h d = 4.0 5.0 = 0.80 \cos \theta = \frac{h}{d} = \frac{4.0}{5.0} = 0.80 cos θ = d h = 5.0 4.0 = 0.80
Calculate horizontal illuminance at point P P P ( E h E_h E h ): E h = I d 2 cos θ = 3200 5.0 2 × 0.80 = 3200 25 × 0.80 = 128.0 × 0.80 = 102.4 Lux E_h = \frac{I}{d^2} \cos \theta = \frac{3200}{5.0^2} \times 0.80 = \frac{3200}{25} \times 0.80 = 128.0 \times 0.80 = 102.4\ \text{Lux} E h = d 2 I cos θ = 5. 0 2 3200 × 0.80 = 25 3200 × 0.80 = 128.0 × 0.80 = 102.4 Lux
Example 2: Complete Office Lumen Method Lighting Design
Problem: An open-plan commercial office space measuring 15 m 15\ \text{m} 15 m long by 10 m 10\ \text{m} 10 m wide requires a target average illuminance E = 500 Lux E = 500\ \text{Lux} E = 500 Lux on work planes 0.75 m 0.75\ \text{m} 0.75 m above the floor. Recessed LED troffer luminaires ( 2 × 20 W 2 \times 20\ \text{W} 2 × 20 W lamps producing 2 , 400 lm 2,400\ \text{lm} 2 , 400 lm per lamp) are selected. Given C U = 0.65 CU = 0.65 C U = 0.65 and L L F = 0.80 LLF = 0.80 LL F = 0.80 , determine: (a) Total required lumens, (b) Required number of LED luminaires N N N , (c) Proposed grid layout, and (d) Total Lighting Power Density ( LPD \,\text{LPD} LPD ).
Solution:
Calculate total floor area ( A A A ): A = 15 m × 10 m = 150 m 2 A = 15\ \text{m} \times 10\ \text{m} = 150\ \text{m}^2 A = 15 m × 10 m = 150 m 2
Calculate total required lumens ( Φ required \Phi_{\text{required}} Φ required ): Φ required = E × A C U × L L F = 500 × 150 0.65 × 0.80 = 75 , 000 0.52 = 144 , 230.77 lumens \Phi_{\text{required}} = \frac{E \times A}{CU \times LLF} = \frac{500 \times 150}{0.65 \times 0.80} = \frac{75,000}{0.52} = 144,230.77\ \text{lumens} Φ required = C U × LL F E × A = 0.65 × 0.80 500 × 150 = 0.52 75 , 000 = 144 , 230.77 lumens
Calculate lumen output per fixture ( 2 lamps × 2400 lm = 4800 lm/fixture 2 \text{ lamps} \times 2400\ \text{lm} = 4800\ \text{lm/fixture} 2 lamps × 2400 lm = 4800 lm/fixture ): N = 144 , 230.77 4800 = 30.048 ⟹ 30 Luminaires N = \frac{144,230.77}{4800} = 30.048 \implies 30\ \text{Luminaires} N = 4800 144 , 230.77 = 30.048 ⟹ 30 Luminaires
Propose fixture grid layout ( N length × N width N_{\text{length}} \times N_{\text{width}} N length × N width ):
Along length ( 15 m 15\ \text{m} 15 m ): 6 6 6 luminaires (spacing S L = 15 6 = 2.5 m S_L = \frac{15}{6} = 2.5\ \text{m} S L = 6 15 = 2.5 m ).
Along width ( 10 m 10\ \text{m} 10 m ): 5 5 5 luminaires (spacing S W = 10 5 = 2.0 m S_W = \frac{10}{5} = 2.0\ \text{m} S W = 5 10 = 2.0 m ).
Total fixtures = 6 × 5 = 30 fixtures 6 \times 5 = 30\ \text{fixtures} 6 × 5 = 30 fixtures .
Calculate connected electrical power and Lighting Power Density (LPD): Power per fixture = 2 × 20 W = 40 W \text{Power per fixture} = 2 \times 20\ \text{W} = 40\ \text{W} Power per fixture = 2 × 20 W = 40 W Total Connected Power = 30 × 40 W = 1 , 200 Watts \text{Total Connected Power} = 30 \times 40\ \text{W} = 1,200\ \text{Watts} Total Connected Power = 30 × 40 W = 1 , 200 Watts LPD = 1200 W 150 m 2 = 8.00 W/m 2 \text{LPD} = \frac{1200\ \text{W}}{150\ \text{m}^2} = 8.00\ \text{W/m}^2 LPD = 150 m 2 1200 W = 8.00 W/m 2
Conclusion: LPD of 8.00 W/m 2 8.00\ \text{W/m}^2 8.00 W/m 2 strictly satisfies the Philippine Green Building Code limit of ≤ 8.1 W/m 2 \le 8.1\ \text{W/m}^2 ≤ 8.1 W/m 2 .