20.2 Industrial Motor Control, Logic Circuits & PLC Automation

PRC Registered Electrical Engineer REE

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Overview, RA 7920 & Electrical Engineering Ethics

1.1 PRC Board of Electrical Engineering & REE Examination Overview 1.2 Republic Act No. 7920 (New Electrical Engineering Law) & License Classes 1.3 Code of Ethics & Professional Practice for Electrical Engineers

2 Chapter 2: Math — Algebra, Trig & Geometry

2.1 Algebraic Equations, Polynomials & Complex Numbers 2.2 Trigonometry — Identities, Triangles & Spherical Trig 2.3 Analytic & Solid Geometry

3 Chapter 3: Engineering Mathematics — Calculus & Differential Equations

3.1 Differential Calculus, Limits, Derivatives & Applications 3.2 Integral Calculus, Integration Techniques & Area/Volume Applications 3.3 Ordinary Differential Equations & Initial-Value Problems

4 Chapter 4: Engineering Mathematics — Advanced Math & Transform Methods

4.1 Laplace Transforms, Inverse Transforms & Circuit Applications 4.2 Fourier Series, Fourier Transforms & Frequency-Domain Analysis 4.3 Vector Analysis, Linear Algebra, Matrices & Complex Analysis

5 Chapter 5: Engineering Mathematics — Probability, Statistics & Engineering Data Analysis

5.1 Probability Theory, Counting Techniques & Bayes' Theorem 5.2 Engineering Data Analysis I — Descriptive Statistics & Probability Distributions 5.3 Engineering Data Analysis II — Confidence Intervals, Hypothesis Testing & Regression

6 Chapter 6: Engineering Mathematics — Numerical Methods & Analysis

6.1 Numerical Root-Finding & Solution of Linear Systems 6.2 Interpolation, Numerical Integration & Numerical Solution of ODEs

7 Chapter 7: ESAS — Physics, Chemistry & Computer Fundamentals

7.1 Physics for Engineers 7.2 General Chemistry & Materials Science 7.3 Computer Fundamentals, Programming & Data Logic 7.4 Logic Circuits, Switching Theory & Microprocessor Systems

8 Chapter 8: ESAS — Mechanics & Thermal-Fluid Engineering

8.1 Engineering Mechanics — Statics & Dynamics 8.2 Strength of Materials & Mechanics of Deformable Bodies 8.3 Thermal-Fluid Engineering — Thermodynamics & Fluid Mechanics

9 Chapter 9: ESAS — Engineering Economics, Management & Contracts

9.1 Engineering Economics & Depreciation 9.2 Engineering Management & Ethics 9.3 Philippine Electrical Engineering Law, Code & Contracts 9.4 Technopreneurship 101 & Management of Engineering Projects

10 Chapter 10: PEC 1 — Safety, Sizing & Protection

10.1 PEC Fundamentals, Safety Standards & Grounding/Bonding 10.2 Conductor Sizing, Ampacity Adjustment & Voltage Drop 10.3 Overcurrent Protection, Branch Circuit & Feeder Sizing 10.4 Basic Occupational Safety & Health (BOSH) and Electrical Safety Standards

11 Chapter 11: PEC 1 & 2 — Equipment & Utility Systems

11.1 PEC Equipment Installation & Wiring Methods 11.2 Utility Systems, Transformers & Switchgear 11.3 Special Occupancies & Hazardous Locations

12 Chapter 12: Electrical Professional — DC & AC Circuit Fundamentals

12.1 DC Circuit Analysis & Network Theorems 12.2 Single-Phase AC Circuits & Phasor Analysis 12.3 Balanced & Unbalanced Three-Phase AC Circuits

13 Chapter 13: Electrical Professional — EM Fields & Transients

13.1 Electrostatics, Magnetostatics & Maxwell's Equations 13.2 Electromagnetic Waves & Transmission Line Fields 13.3 First-Order & Second-Order Circuit Transients

14 Chapter 14: Electrical Professional — Electronics, Industrial Electronics & Communications

14.1 Electronics 1 & 2 — Semiconductor Devices & Analog Circuits 14.2 Electrical Apparatus & Devices — Industrial Electronics & Power Converters 14.3 Fundamentals of Electronic Communications

15 Chapter 15: Electrical Professional — Transformers & DC Machines

15.1 Single-Phase & Three-Phase Transformers 15.2 Transformer Connections & Special Transformers 15.3 DC Generators & DC Motors

16 Chapter 16: Electrical Professional — AC Synchronous & Induction Machinery

16.1 Synchronous Generators (Alternators) 16.2 Synchronous Motors & Special AC Machines 16.3 Three-Phase & Single-Phase Induction Motors

17 Chapter 17: Electrical Professional — Power Plants & Energy Conversion

17.1 Hydroelectric, Thermal & Combined Cycle Power Plants 17.2 Renewable Energy Systems & Geothermal Power Plants 17.3 Power Plant Economics, Load Curves & Energy Conversion

18 Chapter 18: Electrical Professional — Transmission & Distribution

18.1 Transmission Line Parameters & Performance Models 18.2 Mechanical Overhead Line Design, Underground Cables & Insulators 18.3 Distribution Systems, Substation Layouts & Power Flow Control

19 Chapter 19: Electrical Professional — Power System Analysis

19.1 The Per-Unit System, Base Conversion & Impedance Diagrams 19.2 Symmetrical Components & Unbalanced Fault Analysis 19.3 Load Flow, Economic Dispatch & Power System Stability

20 Chapter 20: Electrical Professional — Protection, Control, Instrumentation & Illumination

20.1 Power System Protection & Protective Relaying 20.2 Industrial Motor Control, Logic Circuits & PLC Automation 20.3 Electrical Instrumentation, Transducers & Measurement Systems 20.4 Illumination Engineering, Lighting Design & Photometrics 20.5 Feedback Control Systems & Research Methods

20.2 Industrial Motor Control, Logic Circuits & PLC Automation

Key Takeaways Explain This Topic AI

Reduced-voltage starting methods restrict induction motor inrush currents during acceleration: Wye-Delta ( Y– Δ \text{Y}\text{--}\Delta Y – Δ ) starting reduces line current and starting torque to 1 3 \frac{1}{3} 3 1 ​ ( 33.3 % 33.3\% 33.3% ) of Direct-On-Line (DOL) values ( I start, Y = 1 3 I start, Δ I_{\text{start, Y}} = \frac{1}{3} I_{\text{start, }\Delta} I start, Y ​ = 3 1 ​ I start, Δ ​ , T start, Y = 1 3 T start, Δ T_{\text{start, Y}} = \frac{1}{3} T_{\text{start, }\Delta} T start, Y ​ = 3 1 ​ T start, Δ ​ ).

Autotransformer starters (Korndorfer method) utilize voltage taps x x x ( 50 % 50\% 50% , 65 % 65\% 65% , or 80 % 80\% 80% ), reducing motor voltage to x V L x V_L x V L ​ , motor starting current to x I DOL x I_{\text{DOL}} x I DOL ​ , starting torque to x 2 T DOL x^2 T_{\text{DOL}} x 2 T DOL ​ , and line starting current to x 2 I DOL x^2 I_{\text{DOL}} x 2 I DOL ​ .

Variable Frequency Drives (VFDs) control AC motor rotational speed ( N s = 120 f P N_s = \frac{120 f}{P} N s ​ = P 120 f ​ ) by maintaining a constant Volts-per-Hertz ratio ( V / f = constant V/f = \text{constant} V / f = constant ) below base frequency, limiting inrush current to 100 % – 150 % 100\%\text{--}150\% 100% – 150% of rated current while developing full rated torque.

Industrial hardwired motor control circuits deploy Start/Stop pushbuttons, seal-in holding contacts, series Thermal Overload Relay (TOR) normally closed contacts, and electrical/mechanical interlocking to prevent simultaneous energization of opposing contactors.

Programmable Logic Controllers (PLCs) execute a cyclic 4-stage scan sequence: Input Scan (reading physical sensor inputs into memory), Logic Execution Scan (evaluating Ladder Diagram or Function Block program logic), Output Scan (updating output modules), and System Diagnostics/Overhead.

Last updated: August 2026

20.2 Industrial Motor Control, Logic Circuits & PLC Automation

Industrial motor control systems, magnetic contactors, reduced-voltage starting topologies, and Programmable Logic Controllers (PLCs) form vital practical components of the PRC Registered Electrical Engineer (REE) Licensure Examination . Three-phase induction motors drive the vast majority of industrial loads (pumps, compressors, conveyors, fans). Electrical engineers must design control circuits that safely start, stop, reverse, speed-control, and protect electric motors while complying with Philippine Electrical Code (PEC) guidelines.

1. Industrial Motor Starting Techniques & Performance Comparisons

Direct-On-Line (DOL) starting of large 3-phase induction motors causes massive inrush current ( 500 % to 800 % 500\% \text{ to } 800\% 500% to 800% of full-load current), creating severe line voltage dips that disturb neighboring facility loads. Reduced-voltage starting limits starting current to acceptable utility limits.

Comparison of Motor Starting Methods

Starting Method Motor Terminal Voltage ( V m V_m V m ​ ) Motor Starting Current ( I m I_m I m ​ ) Line Starting Current ( I line I_{\text{line}} I line ​ ) Starting Torque ( T start T_{\text{start}} T start ​ ) Key Applications & Characteristics

Direct-On-Line (DOL) 100 % ( V L ) 100\% \ (V_L) 100% ( V L ​ ) 100 % ( I DOL ) 100\% \ (I_{\text{DOL}}) 100% ( I DOL ​ ) 100 % ( I DOL ) 100\% \ (I_{\text{DOL}}) 100% ( I DOL ​ ) 100 % ( T DOL ) 100\% \ (T_{\text{DOL}}) 100% ( T DOL ​ ) Small motors ( < 7.5 kW / 10 HP < 7.5\ \text{kW} / 10\ \text{HP} < 7.5 kW /10 HP ). Simple, maximum starting torque, high current surge.

Wye-Delta ( Y– Δ \text{Y}\text{--}\Delta Y – Δ ) 57.7 % ( V L 3 ) 57.7\% \ \left(\frac{V_L}{\sqrt{3}}\right) 57.7% ( 3 ​ V L ​ ​ ) 33.3 % ( I DOL 3 ) 33.3\% \ \left(\frac{I_{\text{DOL}}}{3}\right) 33.3% ( 3 I DOL ​ ​ ) 33.3 % ( I DOL 3 ) 33.3\% \ \left(\frac{I_{\text{DOL}}}{3}\right) 33.3% ( 3 I DOL ​ ​ ) 33.3 % ( T DOL 3 ) 33.3\% \ \left(\frac{T_{\text{DOL}}}{3}\right) 33.3% ( 3 T DOL ​ ​ ) Motors started under light/no-load conditions. Requires 6-terminal motor; low cost.

Autotransformer (Korndorfer) x ⋅ V L x \cdot V_L x ⋅ V L ​ ( x = 0.50 , 0.65 , 0.80 x = 0.50, 0.65, 0.80 x = 0.50 , 0.65 , 0.80 ) x ⋅ I DOL x \cdot I_{\text{DOL}} x ⋅ I DOL ​ x 2 ⋅ I DOL x^2 \cdot I_{\text{DOL}} x 2 ⋅ I DOL ​ x 2 ⋅ T DOL x^2 \cdot T_{\text{DOL}} x 2 ⋅ T DOL ​ Large high-inertia industrial drives. Smooth acceleration, Korndorfer transition eliminates current spike.

Primary Resistor x ⋅ V L x \cdot V_L x ⋅ V L ​ ( x < 1.0 x < 1.0 x < 1.0 ) x ⋅ I DOL x \cdot I_{\text{DOL}} x ⋅ I DOL ​ x ⋅ I DOL x \cdot I_{\text{DOL}} x ⋅ I DOL ​ x 2 ⋅ T DOL x^2 \cdot T_{\text{DOL}} x 2 ⋅ T DOL ​ Smooth acceleration; power dissipated as heat in series resistors.

Soft Starter (SCR) Ramped V m V_m V m ​ ( 0 to V L 0 \text{ to } V_L 0 to V L ​ ) 200 % to 350 % 200\% \text{ to } 350\% 200% to 350% rated 200 % to 350 % 200\% \text{ to } 350\% 200% to 350% rated Adjustable ramp Solid-state voltage ramping via antiparallel SCRs. Eliminates mechanical shock.

Variable Frequency Drive (VFD) Variable V V V ( V / f = const V/f = \text{const} V / f = const ) 100 % to 150 % 100\% \text{ to } 150\% 100% to 150% rated 100 % to 150 % 100\% \text{ to } 150\% 100% to 150% rated 100 % to 150 % 100\% \text{ to } 150\% 100% to 150% rated Full speed and torque control. Maximum efficiency, zero line surge.

Mathematical Formulations

Wye-Delta ( Y– Δ \,\text{Y}\text{--}\Delta Y – Δ ) Starting:

When connected in Delta (run mode), phase voltage equals line voltage ( V phase , Δ = V L V_{\text{phase},\Delta} = V_L V phase , Δ ​ = V L ​ ) and line current is I line , Δ = 3 I phase , Δ = 3 V L Z st I_{\text{line},\Delta} = \sqrt{3} I_{\text{phase},\Delta} = \frac{\sqrt{3} V_L}{Z_{\text{st}}} I line , Δ ​ = 3 ​ I phase , Δ ​ = Z st ​ 3 ​ V L ​ ​ .

During Wye starting, phase voltage is V phase , Y = V L 3 V_{\text{phase},Y} = \frac{V_L}{\sqrt{3}} V phase , Y ​ = 3 ​ V L ​ ​ , so phase current is I phase , Y = V L 3 Z st I_{\text{phase},Y} = \frac{V_L}{\sqrt{3} Z_{\text{st}}} I phase , Y ​ = 3 ​ Z st ​ V L ​ ​ . Line current equals phase current: I line , Y = V L 3 Z st = 1 3 ( 3 V L Z st ) = 1 3 I line , Δ I_{\text{line},Y} = \frac{V_L}{\sqrt{3} Z_{\text{st}}} = \frac{1}{3} \left( \frac{\sqrt{3} V_L}{Z_{\text{st}}} \right) = \frac{1}{3} I_{\text{line},\Delta} I line , Y ​ = 3 ​ Z st ​ V L ​ ​ = 3 1 ​ ( Z st ​ 3 ​ V L ​ ​ ) = 3 1 ​ I line , Δ ​ Starting Torque: T start ∝ V phase 2 ⟹ T start , Y = ( 1 3 ) 2 T start , Δ = 1 3 T start , Δ \text{Starting Torque: } T_{\text{start}} \propto V_{\text{phase}}^2 \implies T_{\text{start},Y} = \left( \frac{1}{\sqrt{3}} \right)^2 T_{\text{start},\Delta} = \frac{1}{3} T_{\text{start},\Delta} Starting Torque: T start ​ ∝ V phase 2 ​ ⟹ T start , Y ​ = ( 3 ​ 1 ​ ) 2 T start , Δ ​ = 3 1 ​ T start , Δ ​

Autotransformer (Korndorfer) Starting:

For an autotransformer tap ratio x x x (where x = 0.50 , 0.65 , 0.80 x = 0.50, 0.65, 0.80 x = 0.50 , 0.65 , 0.80 ):

  • Motor terminal voltage: V m = x V L V_m = x V_L V m ​ = x V L ​
  • Motor starting current: I m = x I DOL I_m = x I_{\text{DOL}} I m ​ = x I DOL ​

Transformer primary line current (by power equality V L I line = V m I m V_L I_{\text{line}} = V_m I_m V L ​ I line ​ = V m ​ I m ​ ): I line = x ( V m V L ) I DOL = x 2 I DOL I_{\text{line}} = x \left( \frac{V_m}{V_L} \right) I_{\text{DOL}} = x^2 I_{\text{DOL}} I line ​ = x ( V L ​ V m ​ ​ ) I DOL ​ = x 2 I DOL ​

  • Motor starting torque: T start = x 2 T DOL T_{\text{start}} = x^2 T_{\text{DOL}} T start ​ = x 2 T DOL ​
  • 2. Hardwired Relay Logic & Motor Control Circuits

Elementary ladder diagrams represent control circuits using standard IEEE/NEMA symbols.

Standard Forward-Reverse Motor Starter Circuit FORWARD / REVERSE MOTOR CONTROL LADDER DIAGRAM

  • L1 |---[ STOP ]---+-+---[ F-START ]---+---[ R-NC ]---( F COIL )---+---[ TOR ]---| N
  • | | | | |
  • | | +---[ F-NO ]-----+ |
  • | | |
  • | +-----[ R-START ]---+---[ F-NC ]---( R COIL )----+
  • | | |
  • | +---[ R-NO ]-----+

Essential Control Elements:

Stop Pushbutton : Normally Closed (NC) contact connected in series with the entire control circuit.

Start Pushbutton : Normally Open (NO) momentary contact.

Holding (Seal-In) Contact : NO auxiliary contact of contactor ( F -NO F\text{-NO} F -NO or R -NO R\text{-NO} R -NO ) connected in parallel across the Start button to maintain coil energization after button release.

Electrical Interlocking : NC contact of Forward contactor ( F -NC F\text{-NC} F -NC ) wired in series with Reverse coil ( R R R ), and vice versa. Prevents shorting two line phases if both pushbuttons are pressed simultaneously.

Thermal Overload Relay (TOR) : NC contact ( 95 – 96 95\text{--}96 95 – 96 ) placed in series with contactor coils. Opens automatically when sustained motor overcurrent causes bimetallic strip bending.

3. Programmable Logic Controllers (PLCs)

A Programmable Logic Controller (PLC) is a ruggedized industrial digital computer that continuously monitors input signals from sensors/switches, executes a stored control program, and actuates output devices (contactors, solenoids, indicator lamps).

PLC Hardware Architecture

CPU (Central Processing Unit) : Microprocessor executing system firmware and user ladder logic.

Input Module : Converts field AC/DC signals ( 24 V DC , 120 V AC 24\ \text{V DC}, 120\ \text{V AC} 24 V DC , 120 V AC ) into internal logic voltages using optocouplers for electrical noise isolation.

Output Module : Drives field loads via relays, triacs, or solid-state transistors.

Power Supply : Converts plant AC voltage into regulated 24 V DC 24\ \text{V DC} 24 V DC bus power.

The Four-Stage PLC Scan Cycle PLC SCAN CYCLE REPEAT LOOP

  • +-------------------------------------------------------------------+
  • | |
  • v |
  • +----------+ +---------------+ +-----------+ +-----------+
  • | 1. Input | ------> | 2. Logic Exec | ------> | 3. Output | ----> | 4. System |
  • | Scan | | (Program) | | Scan | | Overhead |
  • +----------+ +---------------+ +-----------+ +-----------+

Input Scan : CPU reads state of physical input terminals and updates the Input Image Table memory.

Logic Execution Scan : CPU executes ladder rungs sequentially from top to bottom, evaluating conditions using Input Image Table values and updating the Output Image Table .

Output Scan : CPU writes Output Image Table states simultaneously to physical output module terminals.

System Diagnostics / Overhead : Performs self-testing, communication servicing, and watchdog timer reset.

PLC Scan Time ( T scan T_{\text{scan}} T scan ​ ): Total duration required to complete one full cycle (typically 1 to 20 milliseconds 1 \text{ to } 20\ \text{milliseconds} 1 to 20 milliseconds ). High-speed events occurring faster than T scan T_{\text{scan}} T scan ​ require hardware interrupt inputs.

IEC 61131-3 Programming Languages

Ladder Diagram (LD) : Graphical language mimicking hardwired relay logic rungs.

Function Block Diagram (FBD) : Graphical blocks representing logic functions (AND, OR, TON, PID).

Structured Text (ST) : High-level block-structured text language (similar to Pascal/C).

Instruction List (IL) : Low-level assembly-like language.

Sequential Function Chart (SFC) : Flowchart-based state machine programming.

Standard PLC Timers & Counters

Timer On-Delay (TON) : Output turns ON after input rung remains continuous for Preset Time ( P T PT PT ).

Timer Off-Delay (TOF) : Output turns OFF after input rung goes false for Preset Time ( P T PT PT ).

Retentive Timer (RTO) : Retains accumulated time ( A C C ACC A CC ) even if input rung turns false; requires explicit Reset ( R S T RST RST ) instruction.

Count Up (CTU) / Count Down (CTD) : Increments/decrements accumulated count on false-to-true rung transitions.

  • Solved Board Exam Examples
  • Example 1: Wye-Delta Starter Currents & Torque Calculation

Problem: A 3 3 3 -phase, 460 V 460\ \text{V} 460 V , 60 Hz 60\ \text{Hz} 60 Hz , 50 HP 50\ \text{HP} 50 HP squirrel-cage induction motor has a rated full-load current of 65 A 65\ \text{A} 65 A and a Direct-On-Line (DOL) starting current of 420 A 420\ \text{A} 420 A with a starting torque of 280 N ⋅ m 280\ \text{N}\cdot\text{m} 280 N ⋅ m . Calculate: (a) Line starting current under Wye-Delta starting, (b) Motor starting torque under Wye-Delta starting, and (c) Percentage reduction in starting line current compared to DOL.

Solution:

Calculate line starting current under Wye-Delta starting ( I start, Y I_{\text{start, Y}} I start, Y ​ ): I start, Y = 1 3 I DOL = 420 A 3 = 140.0 A I_{\text{start, Y}} = \frac{1}{3} I_{\text{DOL}} = \frac{420\ \text{A}}{3} = 140.0\ \text{A} I start, Y ​ = 3 1 ​ I DOL ​ = 3 420 A ​ = 140.0 A

Calculate motor starting torque under Wye-Delta starting ( T start, Y T_{\text{start, Y}} T start, Y ​ ): T start, Y = 1 3 T DOL = 280 N ⋅ m 3 = 93.33 N ⋅ m T_{\text{start, Y}} = \frac{1}{3} T_{\text{DOL}} = \frac{280\ \text{N}\cdot\text{m}}{3} = 93.33\ \text{N}\cdot\text{m} T start, Y ​ = 3 1 ​ T DOL ​ = 3 280 N ⋅ m ​ = 93.33 N ⋅ m

Calculate percentage reduction in line current: % Reduction = ( 1 − 1 3 ) × 100 % = 66.67 % \% \text{Reduction} = \left( 1 - \frac{1}{3} \right) \times 100\% = 66.67\% % Reduction = ( 1 − 3 1 ​ ) × 100% = 66.67%

Example 2: Autotransformer Starter Tap Calculation

Problem: A 2300 V 2300\ \text{V} 2300 V , 3 3 3 -phase induction motor draws a DOL starting current of 1 , 200 A 1,200\ \text{A} 1 , 200 A from the line. The facility distribution system limits starting line current to a maximum of 500 A 500\ \text{A} 500 A . Determine: (a) The maximum allowable autotransformer voltage tap x x x , and (b) The resulting starting torque as a percentage of DOL starting torque.

Solution:

Use autotransformer line current equation ( I line = x 2 I DOL I_{\text{line}} = x^2 I_{\text{DOL}} I line ​ = x 2 I DOL ​ ): x 2 I DOL ≤ 500 A ⟹ x 2 ( 1200 ) = 500 x^2 I_{\text{DOL}} \le 500\ \text{A} \implies x^2 (1200) = 500 x 2 I DOL ​ ≤ 500 A ⟹ x 2 ( 1200 ) = 500 x 2 = 500 1200 = 0.41667 ⟹ x = 0.41667 = 0.6455 ( 64.55 % x^2 = \frac{500}{1200} = 0.41667 \implies x = \sqrt{0.41667} = 0.6455 \quad (64.55\% x 2 = 1200 500 ​ = 0.41667 ⟹ x = 0.41667 ​ = 0.6455 ( 64.55%

Select nearest standard lower autotransformer tap: x standard = 0.65 ( 65 % tap yields I line = ( 0.65 ) 2 × 1200 = 507 A ) x_{\text{standard}} = 0.65 \quad (65\%\text{ tap yields } I_{\text{line}} = (0.65)^2 \times 1200 = 507\ \text{A}) x standard ​ = 0.65 ( 65% tap yields I line ​ = ( 0.65 ) 2 × 1200 = 507 A ) To strictly respect the 500 A 500\ \text{A} 500 A limit, select the 50 % 50\% 50% tap ( x = 0.50 x = 0.50 x = 0.50 ): I line, 50% = ( 0.50 ) 2 × 1200 = 300 A I_{\text{line, 50\%}} = (0.50)^2 \times 1200 = 300\ \text{A} I line, 50% ​ = ( 0.50 ) 2 × 1200 = 300 A

Calculate starting torque percentage for 50 % 50\% 50% tap: T start = x 2 T DOL = ( 0.50 ) 2 T DOL = 0.25 T DOL ( 25.0 % of DOL torque ) T_{\text{start}} = x^2 T_{\text{DOL}} = (0.50)^2 T_{\text{DOL}} = 0.25 T_{\text{DOL}} \quad (25.0\%\text{ of DOL torque}) T start ​ = x 2 T DOL ​ = ( 0.50 ) 2 T DOL ​ = 0.25 T DOL ​ ( 25.0% of DOL torque )

Loading diagram... Industrial Motor Starting Topology & PLC Automation Scan Workflow

Motor Line Starting Current (% FLC) and Starting Torque (% FLT) Across Starting Methods