Study guide

20.1 Power System Protection & Protective Relaying

PRC Registered Electrical Engineer REE

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Overview, RA 7920 & Electrical Engineering Ethics

1.1 PRC Board of Electrical Engineering & REE Examination Overview 1.2 Republic Act No. 7920 (New Electrical Engineering Law) & License Classes 1.3 Code of Ethics & Professional Practice for Electrical Engineers

2 Chapter 2: Math — Algebra, Trig & Geometry

2.1 Algebraic Equations, Polynomials & Complex Numbers 2.2 Trigonometry — Identities, Triangles & Spherical Trig 2.3 Analytic & Solid Geometry

3 Chapter 3: Engineering Mathematics — Calculus & Differential Equations

3.1 Differential Calculus, Limits, Derivatives & Applications 3.2 Integral Calculus, Integration Techniques & Area/Volume Applications 3.3 Ordinary Differential Equations & Initial-Value Problems

4 Chapter 4: Engineering Mathematics — Advanced Math & Transform Methods

4.1 Laplace Transforms, Inverse Transforms & Circuit Applications 4.2 Fourier Series, Fourier Transforms & Frequency-Domain Analysis 4.3 Vector Analysis, Linear Algebra, Matrices & Complex Analysis

5 Chapter 5: Engineering Mathematics — Probability, Statistics & Engineering Data Analysis

5.1 Probability Theory, Counting Techniques & Bayes' Theorem 5.2 Engineering Data Analysis I — Descriptive Statistics & Probability Distributions 5.3 Engineering Data Analysis II — Confidence Intervals, Hypothesis Testing & Regression

6 Chapter 6: Engineering Mathematics — Numerical Methods & Analysis

6.1 Numerical Root-Finding & Solution of Linear Systems 6.2 Interpolation, Numerical Integration & Numerical Solution of ODEs

7 Chapter 7: ESAS — Physics, Chemistry & Computer Fundamentals

7.1 Physics for Engineers 7.2 General Chemistry & Materials Science 7.3 Computer Fundamentals, Programming & Data Logic 7.4 Logic Circuits, Switching Theory & Microprocessor Systems

8 Chapter 8: ESAS — Mechanics & Thermal-Fluid Engineering

8.1 Engineering Mechanics — Statics & Dynamics 8.2 Strength of Materials & Mechanics of Deformable Bodies 8.3 Thermal-Fluid Engineering — Thermodynamics & Fluid Mechanics

9 Chapter 9: ESAS — Engineering Economics, Management & Contracts

9.1 Engineering Economics & Depreciation 9.2 Engineering Management & Ethics 9.3 Philippine Electrical Engineering Law, Code & Contracts 9.4 Technopreneurship 101 & Management of Engineering Projects

10 Chapter 10: PEC 1 — Safety, Sizing & Protection

10.1 PEC Fundamentals, Safety Standards & Grounding/Bonding 10.2 Conductor Sizing, Ampacity Adjustment & Voltage Drop 10.3 Overcurrent Protection, Branch Circuit & Feeder Sizing 10.4 Basic Occupational Safety & Health (BOSH) and Electrical Safety Standards

11 Chapter 11: PEC 1 & 2 — Equipment & Utility Systems

11.1 PEC Equipment Installation & Wiring Methods 11.2 Utility Systems, Transformers & Switchgear 11.3 Special Occupancies & Hazardous Locations

12 Chapter 12: Electrical Professional — DC & AC Circuit Fundamentals

12.1 DC Circuit Analysis & Network Theorems 12.2 Single-Phase AC Circuits & Phasor Analysis 12.3 Balanced & Unbalanced Three-Phase AC Circuits

13 Chapter 13: Electrical Professional — EM Fields & Transients

13.1 Electrostatics, Magnetostatics & Maxwell's Equations 13.2 Electromagnetic Waves & Transmission Line Fields 13.3 First-Order & Second-Order Circuit Transients

14 Chapter 14: Electrical Professional — Electronics, Industrial Electronics & Communications

14.1 Electronics 1 & 2 — Semiconductor Devices & Analog Circuits 14.2 Electrical Apparatus & Devices — Industrial Electronics & Power Converters 14.3 Fundamentals of Electronic Communications

15 Chapter 15: Electrical Professional — Transformers & DC Machines

15.1 Single-Phase & Three-Phase Transformers 15.2 Transformer Connections & Special Transformers 15.3 DC Generators & DC Motors

16 Chapter 16: Electrical Professional — AC Synchronous & Induction Machinery

16.1 Synchronous Generators (Alternators) 16.2 Synchronous Motors & Special AC Machines 16.3 Three-Phase & Single-Phase Induction Motors

17 Chapter 17: Electrical Professional — Power Plants & Energy Conversion

17.1 Hydroelectric, Thermal & Combined Cycle Power Plants 17.2 Renewable Energy Systems & Geothermal Power Plants 17.3 Power Plant Economics, Load Curves & Energy Conversion

18 Chapter 18: Electrical Professional — Transmission & Distribution

18.1 Transmission Line Parameters & Performance Models 18.2 Mechanical Overhead Line Design, Underground Cables & Insulators 18.3 Distribution Systems, Substation Layouts & Power Flow Control

19 Chapter 19: Electrical Professional — Power System Analysis

19.1 The Per-Unit System, Base Conversion & Impedance Diagrams 19.2 Symmetrical Components & Unbalanced Fault Analysis 19.3 Load Flow, Economic Dispatch & Power System Stability

20 Chapter 20: Electrical Professional — Protection, Control, Instrumentation & Illumination

20.1 Power System Protection & Protective Relaying 20.2 Industrial Motor Control, Logic Circuits & PLC Automation 20.3 Electrical Instrumentation, Transducers & Measurement Systems 20.4 Illumination Engineering, Lighting Design & Photometrics 20.5 Feedback Control Systems & Research Methods

20.1 Power System Protection & Protective Relaying

Key Takeaways Explain This Topic AI

Protective relaying systems must fulfill five fundamental performance criteria: Selectivity (isolating only the faulted grid section without interrupting healthy circuits), Sensitivity (detecting minimal fault currents), Speed (clearing faults rapidly to preserve transient stability), Reliability (Dependability and Security), and Simplicity.

Overcurrent protection (ANSI 50/51) utilizes pickup current I pu = I ct,sec × PS I_{\text{pu}} = I_{\text{ct,sec}} \times \text{PS} I pu ​ = I ct,sec ​ × PS and Time Dial Setting (TDS) to shape inverse operating curves ( t = TDS × 0.14 M 0.02 − 1 t = \text{TDS} \times \frac{0.14}{M^{0.02} - 1} t = TDS × M 0.02 − 1 0.14 ​ for standard inverse curves, where multiple M = I fault,sec / I pu M = I_{\text{fault,sec}} / I_{\text{pu}} M = I fault,sec ​ / I pu ​ ).

Percentage differential protection (ANSI 87) evaluates vector current differences ( I d = ∣ I 1 − I 2 ∣ > k I restraint I_d = |I_1 - I_2| > k I_{\text{restraint}} I d ​ = ∣ I 1 ​ − I 2 ​ ∣ > k I restraint ​ ); transformer differential protection incorporates CT ratio matching, Δ – Y \Delta\text{--}Y Δ – Y phase-shift matrix compensation, and 2nd harmonic restraint ( 15 % – 20 % 15\%\text{--}20\% 15% – 20% ) to prevent false trips during magnetizing inrush.

Distance impedance relays (ANSI 21) measure apparent positive-sequence impedance ( Z seen = V / I Z_{\text{seen}} = V / I Z seen ​ = V / I ); 3-zone protection schemes deploy Zone 1 ( 80 % – 90 % 80\%\text{--}90\% 80% – 90% line reach, instantaneous 0 s 0\ \text{s} 0 s ), Zone 2 ( 120 % – 150 % 120\%\text{--}150\% 120% – 150% line reach, 0.2 – 0.4 s 0.2\text{--}0.4\ \text{s} 0.2 – 0.4 s delay), and Zone 3 ( 100 % 100\% 100% line plus adjacent line, 0.6 – 1.0 s 0.6\text{--}1.0\ \text{s} 0.6 – 1.0 s remote backup delay).

Circuit breaker interrupting rating is determined by symmetrical short-circuit current ( I sc = S k 3 V L I_{\text{sc}} = \frac{S_k}{\sqrt{3} V_L} I sc ​ = 3 ​ V L ​ S k ​ ​ ) and asymmetrical peak making current ( I making = 2.55 × I sym, RMS I_{\text{making}} = 2.55 \times I_{\text{sym, RMS}} I making ​ = 2.55 × I sym, RMS ​ ), accounting for maximum DC offset decay time constant τ = L / R \tau = L/R τ = L / R at fault inception.

Last updated: August 2026

20.1 Power System Protection & Protective Relaying

Power system protection, protective relaying coordination, instrument transformer application, and circuit breaker rating constitute major core subjects on the PRC Registered Electrical Engineer (REE) Licensure Examination . Protective relaying systems act as the automated intelligence of electric power networks, continuously detecting abnormal voltage, current, or frequency conditions and isolating faulted apparatus to preserve equipment integrity and grid stability.

  • 1. Fundamentals of Protection & Instrument Transformers
  • Core Protective Relaying Criteria

Every protective relaying scheme must satisfy five essential operational requirements:

Selectivity (Coordination) : Isolates only the minimum faulted portion of the system, keeping healthy feeders energized.

Sensitivity : Operates reliably under minimum fault current conditions (e.g., high-resistance ground faults at light system loading).

Speed : Disconnects short circuits as rapidly as possible to limit thermal/mechanical equipment damage and maintain power system transient stability.

Reliability : Consists of Dependability (certainty of operating when a fault occurs) and Security (certainty of NOT operating when no fault exists).

Simplicity : Minimizes secondary wiring complexity and relay components to reduce failure modes.

Instrument Transformers: CTs and PTs

Protective relays operate on reduced secondary current and voltage signals supplied by Current Transformers (CTs) and Potential Transformers (PTs / VTs) .

Current Transformers (CTs)

Standard secondary current rating is 5 A 5\ \text{A} 5 A (or 1 A 1\ \text{A} 1 A in modern numerical European/IEC standards).

CT Ratio ( N ct N_{\text{ct}} N ct ​ ) : N ct = I primary I secondary N_{\text{ct}} = \frac{I_{\text{primary}}}{I_{\text{secondary}}} N ct ​ = I secondary ​ I primary ​ ​ . For an 800 / 5 A 800/5\ \text{A} 800/5 A CT, N ct = 160 N_{\text{ct}} = 160 N ct ​ = 160 .

ANSI Accuracy Classes (C-Class) : Designates transformer secondary terminal voltage at 20 times nominal secondary current without exceeding 10 % 10\% 10% ratio error. For example, a C400 CT maintains ratio accuracy up to V sec = 400 V V_{\text{sec}} = 400\ \text{V} V sec ​ = 400 V at 20 × 5 A = 100 A 20 \times 5\ \text{A} = 100\ \text{A} 20 × 5 A = 100 A secondary current ( Z burden, max = 400 V 100 A = 4.0 Ω Z_{\text{burden, max}} = \frac{400\ \text{V}}{100\ \text{A}} = 4.0\ \Omega Z burden, max ​ = 100 A 400 V ​ = 4.0 Ω ).

CT Burden ( Z B Z_B Z B ​ ) : Total external impedance connected across secondary terminals, including relay coil impedance, lead wire resistance, and terminal contacts: Z B = R ct,sec + 2 R lead + Z relay Z_B = R_{\text{ct,sec}} + 2 R_{\text{lead}} + Z_{\text{relay}} Z B ​ = R ct,sec ​ + 2 R lead ​ + Z relay ​

CRITICAL REE SAFETY RULE: Never open-circuit the secondary terminals of an energized Current Transformer! Open-circuiting a CT causes infinite secondary impedance, inducing extreme high-voltage spikes ( V = N d Φ d t ≥ 10 kV V = N \frac{d\Phi}{dt} \ge 10\ \text{kV} V = N d t d Φ ​ ≥ 10 kV ) across secondary terminals that cause lethal electric shock and core insulation breakdown.

2. Overcurrent Protection (ANSI 50/51) & Relaying Curves

Overcurrent relays detect phase short circuits and ground faults when current exceeds a predetermined threshold.

ANSI 50 : Instantaneous Overcurrent Relay (operates with no intentional time delay, t < 50 ms t < 50\ \text{ms} t < 50 ms ).

ANSI 51 : AC Inverse Time Overcurrent Relay (operating time decreases non-linearly as fault current magnitude increases).

Relay Pickup & Plug Setting

Plug Setting (PS) : Percentage tap setting on the relay ( 50 % to 200 % 50\% \text{ to } 200\% 50% to 200% in steps of 25 % 25\% 25% for phase relays; 20 % to 80 % 20\% \text{ to } 80\% 20% to 80% for ground relays).

Pickup Current ( I pu I_{\text{pu}} I pu ​ ) : The minimum secondary current required to initiate relay operation: I pu = I ct,sec × PS = 5 A × ( PS % 100 ) I_{\text{pu}} = I_{\text{ct,sec}} \times \text{PS} = 5\ \text{A} \times \left( \frac{\text{PS}\%}{100} \right) I pu ​ = I ct,sec ​ × PS = 5 A × ( 100 PS % ​ )

Primary Pickup Current ( I pu,pri I_{\text{pu,pri}} I pu,pri ​ ) : I pu,pri = I pu × N ct I_{\text{pu,pri}} = I_{\text{pu}} \times N_{\text{ct}} I pu,pri ​ = I pu ​ × N ct ​

Multiple of Pickup Current ( M M M ) M = I fault,sec I pu = I fault,pri I pu,pri M = \frac{I_{\text{fault,sec}}}{I_{\text{pu}}} = \frac{I_{\text{fault,pri}}}{I_{\text{pu,pri}}} M = I pu ​ I fault,sec ​ ​ = I pu,pri ​ I fault,pri ​ ​

Time Dial Setting (TDS / TMS) & Standard Inverse Curves

Relay operating time t t t is calculated using standardized mathematical curves (IEC 60255 / IEEE C37.112):

Curve Type IEC / IEEE Formula for Operating Time t t t (seconds) Application Characteristics

Standard Inverse (SI) t = TDS × ( 0.14 M 0.02 − 1 ) t = \text{TDS} \times \left( \frac{0.14}{M^{0.02} - 1} \right) t = TDS × ( M 0.02 − 1 0.14 ​ ) Standard distribution feeder protection.

Very Inverse (VI) t = TDS × ( 13.5 M − 1 ) t = \text{TDS} \times \left( \frac{13.5}{M - 1} \right) t = TDS × ( M − 1 13.5 ​ ) Lines where fault current drops rapidly with distance.

Extremely Inverse (EI) t = TDS × ( 80 M 2 − 1 ) t = \text{TDS} \times \left( \frac{80}{M^2 - 1} \right) t = TDS × ( M 2 − 1 80 ​ ) Coordinated with power fuses and transformer inrush.

Coordination Time Interval (CTI): When coordinating series relays along a distribution feeder, a selective time margin CTI ≈ 0.30 to 0.40 seconds \text{CTI} \approx 0.30 \text{ to } 0.40\ \text{seconds} CTI ≈ 0.30 to 0.40 seconds is maintained between downstream feeder relays and upstream main circuit breaker relays to account for breaker clearing time and relay overshoot.

3. Differential Protection (ANSI 87) & Transformer Relaying

Differential relays operate on the unit protection principle : current entering a protected zone must equal current exiting under normal or external fault conditions.

Percentage Differential Relay Principle PERCENTAGE DIFFERENTIAL RELAY SCHEMATIC (ANSI 87)

  • Line In I1 Line Out I2
  • ------------[ CT1 ]-------------------[ CT2 ]-------------
  • | |
  • i1 i2
  • | |
  • +----[ Restraint Coil ]---+
  • |
  • [ Operating Coil ] (Id = |i1 - i2|)
  • |
  • ==== Ground

Differential Operating Current ( I d I_d I d ​ ) : I d = ∣ i 1 − i 2 ∣ I_d = |i_1 - i_2| I d ​ = ∣ i 1 ​ − i 2 ​ ∣

Restraint Current ( I restraint I_{\text{restraint}} I restraint ​ ) : I restraint = ∣ i 1 ∣ + ∣ i 2 ∣ 2 I_{\text{restraint}} = \frac{|i_1| + |i_2|}{2} I restraint ​ = 2 ∣ i 1 ​ ∣ + ∣ i 2 ​ ∣ ​

Trip Condition : Relay trips when operating current exceeds the percentage restraint slope k k k ( 15 % to 40 % 15\% \text{ to } 40\% 15% to 40% ): I d > k ⋅ I restraint + I 0 I_d > k \cdot I_{\text{restraint}} + I_0 I d ​ > k ⋅ I restraint ​ + I 0 ​

Transformer Differential Protection Challenges

Ratio Mismatch : Primary and secondary transformer full-load currents differ due to transformation ratio N 1 / N 2 N_1 / N_2 N 1 ​ / N 2 ​ . CT ratios N ct1 N_{\text{ct1}} N ct1 ​ and N ct2 N_{\text{ct2}} N ct2 ​ are chosen so secondary currents i 1 i_1 i 1 ​ and i 2 i_2 i 2 ​ match closely under rated load.

Phase Shift in Δ – Y \Delta\text{--}Y Δ – Y Transformers : A Δ – Y \Delta\text{--}Y Δ – Y transformer introduces a 30 ∘ 30^\circ 3 0 ∘ phase shift between primary and secondary line currents. In electromechanical protection, CTs on the Δ \Delta Δ side are connected in Y \text{Y} Y , and CTs on the Y \text{Y} Y side are connected in Δ \Delta Δ to cancel the 30 ∘ 30^\circ 3 0 ∘ shift and supply 3 \sqrt{3} 3 ​ current magnitude compensation. Numerical relays perform phase shift compensation via software matrix multiplication.

Magnetizing Inrush Current : Energizing a transformer creates high transient inrush current (up to 8 – 12 × I rated 8\text{--}12 \times I_{\text{rated}} 8 – 12 × I rated ​ ) that flows only through the primary winding, producing false differential current. Inrush current contains a high 2nd harmonic component ( 15 % – 20 % 15\%\text{--}20\% 15% – 20% of fundamental). Numerical relays use 2nd harmonic blocking to prevent false tripping during energization.

4. Distance Protection (ANSI 21) & Transmission Line Protection

Distance (impedance) relays protect high-voltage transmission lines by measuring the ratio of secondary line voltage to line current: Z seen = V relay I relay = z line × d Z_{\text{seen}} = \frac{V_{\text{relay}}}{I_{\text{relay}}} = z_{\text{line}} \times d Z seen ​ = I relay ​ V relay ​ ​ = z line ​ × d

where z line z_{\text{line}} z line ​ is positive-sequence impedance per km, and d d d is distance to the fault.

Relay Characteristics on R-X Complex Plane

Plain Impedance Relay : Circular characteristic centered at the origin ( ∣ Z seen ∣ < Z set |Z_{\text{seen}}| < Z_{\text{set}} ∣ Z seen ​ ∣ < Z set ​ ). Non-directional; requires additional directional element.

Mho Relay : Circular characteristic passing through the origin. Inherently directional; ideal for long high-voltage transmission lines.

Reactance Relay : Horizontal line characteristic on R-X plane ( X seen < X set X_{\text{seen}} < X_{\text{set}} X seen ​ < X set ​ ). Resists fault arc resistance ( R arc R_{\text{arc}} R arc ​ ); used for short lines and ground fault protection.

Three-Zone Distance Protection Scheme

Zone Reach Setting Operating Time Functional Purpose

Zone 1 80 % to 90 % 80\% \text{ to } 90\% 80% to 90% of protected line length Instantaneous ( 0 s 0\ \text{s} 0 s delay) Primary instantaneous line protection without overlapping far substation.

Zone 2 100 % 100\% 100% of line + 20 % to 50 % + 20\% \text{ to } 50\% + 20% to 50% of shortest adjacent line Time-delayed ( 0.20 to 0.40 s 0.20 \text{ to } 0.40\ \text{s} 0.20 to 0.40 s ) Covers remaining 10 % – 20 % 10\%\text{--}20\% 10% – 20% of line and acts as local backup.

Zone 3 100 % 100\% 100% of line + 100 % + 100\% + 100% of adjacent line Time-delayed ( 0.60 to 1.00 s 0.60 \text{ to } 1.00\ \text{s} 0.60 to 1.00 s ) Remote backup protection for adjacent lines and substations.

5. Circuit Breakers & Short-Circuit Interrupting Capacity

Circuit breakers interrupt heavy fault currents under extreme arc plasma conditions ( > 5000 ∘ C > 5000^\circ\text{C} > 500 0 ∘ C ).

Arc Quenching Media

Vacuum Circuit Breakers (VCB) : Used in medium-voltage distribution ( 4.16 kV to 34.5 kV 4.16\ \text{kV} \text{ to } 34.5\ \text{kV} 4.16 kV to 34.5 kV ). High dielectric recovery rate, zero fire hazard.

Sulfur Hexafluoride (SF6) Breakers : Used in high-voltage transmission ( 69 kV to 500 kV 69\ \text{kV} \text{ to } 500\ \text{kV} 69 kV to 500 kV ). Superior electronegative gas that rapidly absorbs free electrons during current zero crossing.

Asymmetrical Fault Current & Making Capacity

Total short-circuit current contains an AC symmetrical component I sym, RMS I_{\text{sym, RMS}} I sym, RMS ​ and a decaying DC offset i dc ( t ) i_{\text{dc}}(t) i dc ​ ( t ) : ∋ fault ( t ) = 2 I sym, RMS [ cos ⁡ ( ω t + α − θ ) − e − t / τ cos ⁡ ( α − θ ) ] \ni_{\text{fault}}(t) = \sqrt{2} I_{\text{sym, RMS}} \left[ \cos(\omega t + \alpha - \theta) - e^{-t/\tau} \cos(\alpha - \theta) \right] ∋ fault ​ ( t ) = 2 ​ I sym, RMS ​ [ cos ( ω t + α − θ ) − e − t / τ cos ( α − θ ) ]

where τ = L R = X 2 π f R \tau = \frac{L}{R} = \frac{X}{2 \pi f R} τ = R L ​ = 2 π f R X ​ is the DC attenuation time constant.

Peak Making Current ( I making I_{\text{making}} I making ​ ):

The maximum peak current occurring at the first half-cycle ( t ≈ 10 ms t \approx 10\ \text{ms} t ≈ 10 ms at 60 Hz 60\ \text{Hz} 60 Hz ) under maximum DC offset: I making = 2.55 × I sym, RMS ( Peak Amperes ) I_{\text{making}} = 2.55 \times I_{\text{sym, RMS}} \quad (\text{Peak Amperes}) I making ​ = 2.55 × I sym, RMS ​ ( Peak Amperes )

Short-Circuit Symmetrical Breaking Duty ( I sc I_{\text{sc}} I sc ​ ): I sc = S fault, 3-phase 3 × V line, nominal ( kA RMS ) I_{\text{sc}} = \frac{S_{\text{fault, 3-phase}}}{\sqrt{3} \times V_{\text{line, nominal}}} \quad (\text{kA RMS}) I sc ​ = 3 ​ × V line, nominal ​ S fault, 3-phase ​ ​ ( kA RMS )

  • Solved Board Exam Examples
  • Example 1: Overcurrent Relay Pickup & Operating Time Calculation

Problem: A 13.8 kV 13.8\ \text{kV} 13.8 kV distribution feeder is protected by an inverse time overcurrent relay (ANSI 51) connected through an 800 / 5 A 800/5\ \text{A} 800/5 A CT. The relay plug setting is PS = 125 % \text{PS} = 125\% PS = 125% and the Time Dial Setting is TDS = 4 \text{TDS} = 4 TDS = 4 . If a 3-phase fault produces a primary short-circuit current I fault = 6 , 000 A I_{\text{fault}} = 6,000\ \text{A} I fault ​ = 6 , 000 A , calculate using the Standard Inverse curve ( t = TDS × 0.14 M 0.02 − 1 t = \text{TDS} \times \frac{0.14}{M^{0.02} - 1} t = TDS × M 0.02 − 1 0.14 ​ ): (a) Relay pickup current I pu I_{\text{pu}} I pu ​ , (b) Primary pickup current, (c) Multiple of pickup current M M M , and (d) Relay operating time t t t .

Solution:

Calculate secondary pickup current ( I pu I_{\text{pu}} I pu ​ ): I pu = 5 A × 1.25 = 6.25 A I_{\text{pu}} = 5\ \text{A} \times 1.25 = 6.25\ \text{A} I pu ​ = 5 A × 1.25 = 6.25 A

Calculate primary pickup current ( I pu,pri I_{\text{pu,pri}} I pu,pri ​ ): N ct = 800 5 = 160 ⟹ I pu,pri = 6.25 A × 160 = 1 , 000 A N_{\text{ct}} = \frac{800}{5} = 160 \implies I_{\text{pu,pri}} = 6.25\ \text{A} \times 160 = 1,000\ \text{A} N ct ​ = 5 800 ​ = 160 ⟹ I pu,pri ​ = 6.25 A × 160 = 1 , 000 A

Calculate multiple of pickup current ( M M M ): M = I fault,pri I pu,pri = 6 , 000 A 1 , 000 A = 6.0 M = \frac{I_{\text{fault,pri}}}{I_{\text{pu,pri}}} = \frac{6,000\ \text{A}}{1,000\ \text{A}} = 6.0 M = I pu,pri ​ I fault,pri ​ ​ = 1 , 000 A 6 , 000 A ​ = 6.0

Calculate relay operating time t t t for TDS = 4 \text{TDS} = 4 TDS = 4 : M 0.02 = ( 6.0 ) 0.02 = 1.03643 M^{0.02} = (6.0)^{0.02} = 1.03643 M 0.02 = ( 6.0 ) 0.02 = 1.03643 t = 4 × ( 0.14 1.03643 − 1 ) = 4 × ( 0.14 0.03643 ) = 4 × 3.843 = 15.37 seconds t = 4 \times \left( \frac{0.14}{1.03643 - 1} \right) = 4 \times \left( \frac{0.14}{0.03643} \right) = 4 \times 3.843 = 15.37\ \text{seconds} t = 4 × ( 1.03643 − 1 0.14 ​ ) = 4 × ( 0.03643 0.14 ​ ) = 4 × 3.843 = 15.37 seconds

Example 2: Transformer Differential Relay CT Rating & Mismatch

Problem: A 3 3 3 -phase, 30 MVA 30\ \text{MVA} 30 MVA , 115 kV / 13.8 kV 115\ \text{kV} / 13.8\ \text{kV} 115 kV /13.8 kV , Δ – Y \Delta\text{--}Y Δ – Y power transformer is protected by percentage differential relays. CTs on the 115 kV 115\ \text{kV} 115 kV Δ \Delta Δ side are connected in Y \text{Y} Y , and CTs on the 13.8 kV 13.8\ \text{kV} 13.8 kV Y \text{Y} Y side are connected in Δ \Delta Δ . Standard CT ratios available are 200 / 5 A 200/5\ \text{A} 200/5 A on the high-voltage side and 1500 / 5 A 1500/5\ \text{A} 1500/5 A on the low-voltage side. Calculate CT secondary currents under rated full load and determine any current mismatch.

Solution:

Calculate full-load primary line currents on high-voltage (HV) and low-voltage (LV) sides: I HV, rated = 30 × 10 6 3 × 115 , 000 = 150.61 A I_{\text{HV, rated}} = \frac{30 \times 10^6}{\sqrt{3} \times 115,000} = 150.61\ \text{A} I HV, rated ​ = 3 ​ × 115 , 000 30 × 1 0 6 ​ = 150.61 A I LV, rated = 30 × 10 6 3 × 13 , 800 = 1 , 255.11 A I_{\text{LV, rated}} = \frac{30 \times 10^6}{\sqrt{3} \times 13,800} = 1,255.11\ \text{A} I LV, rated ​ = 3 ​ × 13 , 800 30 × 1 0 6 ​ = 1 , 255.11 A

Calculate CT secondary currents entering relay restraint coils:

HV Side ( Δ \,\Delta Δ transformer side, Y \text{Y} Y -connected CTs) : i sec, HV = 150.61 × ( 5 200 ) = 3.765 A i_{\text{sec, HV}} = 150.61 \times \left( \frac{5}{200} \right) = 3.765\ \text{A} i sec, HV ​ = 150.61 × ( 200 5 ​ ) = 3.765 A

LV Side ( Y \,Y Y transformer side, Δ \Delta Δ -connected CTs) :

Line current exiting Δ \Delta Δ -connected CT secondary contains a 3 \sqrt{3} 3 ​ factor: i sec, LV = 1 , 255.11 × ( 5 1500 ) × 3 = 4.184 × 1.73205 = 7.247 A i_{\text{sec, LV}} = 1,255.11 \times \left( \frac{5}{1500} \right) \times \sqrt{3} = 4.184 \times 1.73205 = 7.247\ \text{A} i sec, LV ​ = 1 , 255.11 × ( 1500 5 ​ ) × 3 ​ = 4.184 × 1.73205 = 7.247 A

Evaluate differential mismatch current: Mismatch Current I d = ∣ 7.247 − 3.765 ∣ = 3.482 A \text{Mismatch Current } I_d = |7.247 - 3.765| = 3.482\ \text{A} Mismatch Current I d ​ = ∣7.247 − 3.765∣ = 3.482 A

Conclusion: Numerical relays apply internal digital scaling factors ( a HV = 1.0 , a LV = 0.5195 a_{\text{HV}} = 1.0, a_{\text{LV}} = 0.5195 a HV ​ = 1.0 , a LV ​ = 0.5195 ) to balance secondary currents perfectly to 3.765 A 3.765\ \text{A} 3.765 A , eliminating spill current under normal full-load operation.

Loading diagram... Power System Protective Relaying Scheme & Circuit Breaker Workflow

Relay Operating Time (Seconds) Across Overcurrent Curves at TDS = 1.0 for Multiples M=5 and M=10