15.2 Transformer Connections & Special Transformers
PRC Registered Electrical Engineer REE
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Overview, RA 7920 & Electrical Engineering Ethics
1.1 PRC Board of Electrical Engineering & REE Examination Overview 1.2 Republic Act No. 7920 (New Electrical Engineering Law) & License Classes 1.3 Code of Ethics & Professional Practice for Electrical Engineers
2 Chapter 2: Math — Algebra, Trig & Geometry
2.1 Algebraic Equations, Polynomials & Complex Numbers 2.2 Trigonometry — Identities, Triangles & Spherical Trig 2.3 Analytic & Solid Geometry
3 Chapter 3: Engineering Mathematics — Calculus & Differential Equations
3.1 Differential Calculus, Limits, Derivatives & Applications 3.2 Integral Calculus, Integration Techniques & Area/Volume Applications 3.3 Ordinary Differential Equations & Initial-Value Problems
4 Chapter 4: Engineering Mathematics — Advanced Math & Transform Methods
4.1 Laplace Transforms, Inverse Transforms & Circuit Applications 4.2 Fourier Series, Fourier Transforms & Frequency-Domain Analysis 4.3 Vector Analysis, Linear Algebra, Matrices & Complex Analysis
5 Chapter 5: Engineering Mathematics — Probability, Statistics & Engineering Data Analysis
5.1 Probability Theory, Counting Techniques & Bayes' Theorem 5.2 Engineering Data Analysis I — Descriptive Statistics & Probability Distributions 5.3 Engineering Data Analysis II — Confidence Intervals, Hypothesis Testing & Regression
6 Chapter 6: Engineering Mathematics — Numerical Methods & Analysis
6.1 Numerical Root-Finding & Solution of Linear Systems 6.2 Interpolation, Numerical Integration & Numerical Solution of ODEs
7 Chapter 7: ESAS — Physics, Chemistry & Computer Fundamentals
7.1 Physics for Engineers 7.2 General Chemistry & Materials Science 7.3 Computer Fundamentals, Programming & Data Logic 7.4 Logic Circuits, Switching Theory & Microprocessor Systems
8 Chapter 8: ESAS — Mechanics & Thermal-Fluid Engineering
8.1 Engineering Mechanics — Statics & Dynamics 8.2 Strength of Materials & Mechanics of Deformable Bodies 8.3 Thermal-Fluid Engineering — Thermodynamics & Fluid Mechanics
9 Chapter 9: ESAS — Engineering Economics, Management & Contracts
9.1 Engineering Economics & Depreciation 9.2 Engineering Management & Ethics 9.3 Philippine Electrical Engineering Law, Code & Contracts 9.4 Technopreneurship 101 & Management of Engineering Projects
10 Chapter 10: PEC 1 — Safety, Sizing & Protection
10.1 PEC Fundamentals, Safety Standards & Grounding/Bonding 10.2 Conductor Sizing, Ampacity Adjustment & Voltage Drop 10.3 Overcurrent Protection, Branch Circuit & Feeder Sizing 10.4 Basic Occupational Safety & Health (BOSH) and Electrical Safety Standards
11 Chapter 11: PEC 1 & 2 — Equipment & Utility Systems
11.1 PEC Equipment Installation & Wiring Methods 11.2 Utility Systems, Transformers & Switchgear 11.3 Special Occupancies & Hazardous Locations
12 Chapter 12: Electrical Professional — DC & AC Circuit Fundamentals
12.1 DC Circuit Analysis & Network Theorems 12.2 Single-Phase AC Circuits & Phasor Analysis 12.3 Balanced & Unbalanced Three-Phase AC Circuits
13 Chapter 13: Electrical Professional — EM Fields & Transients
13.1 Electrostatics, Magnetostatics & Maxwell's Equations 13.2 Electromagnetic Waves & Transmission Line Fields 13.3 First-Order & Second-Order Circuit Transients
14 Chapter 14: Electrical Professional — Electronics, Industrial Electronics & Communications
14.1 Electronics 1 & 2 — Semiconductor Devices & Analog Circuits 14.2 Electrical Apparatus & Devices — Industrial Electronics & Power Converters 14.3 Fundamentals of Electronic Communications
15 Chapter 15: Electrical Professional — Transformers & DC Machines
15.1 Single-Phase & Three-Phase Transformers 15.2 Transformer Connections & Special Transformers 15.3 DC Generators & DC Motors
16 Chapter 16: Electrical Professional — AC Synchronous & Induction Machinery
16.1 Synchronous Generators (Alternators) 16.2 Synchronous Motors & Special AC Machines 16.3 Three-Phase & Single-Phase Induction Motors
17 Chapter 17: Electrical Professional — Power Plants & Energy Conversion
17.1 Hydroelectric, Thermal & Combined Cycle Power Plants 17.2 Renewable Energy Systems & Geothermal Power Plants 17.3 Power Plant Economics, Load Curves & Energy Conversion
18 Chapter 18: Electrical Professional — Transmission & Distribution
18.1 Transmission Line Parameters & Performance Models 18.2 Mechanical Overhead Line Design, Underground Cables & Insulators 18.3 Distribution Systems, Substation Layouts & Power Flow Control
19 Chapter 19: Electrical Professional — Power System Analysis
19.1 The Per-Unit System, Base Conversion & Impedance Diagrams 19.2 Symmetrical Components & Unbalanced Fault Analysis 19.3 Load Flow, Economic Dispatch & Power System Stability
20 Chapter 20: Electrical Professional — Protection, Control, Instrumentation & Illumination
20.1 Power System Protection & Protective Relaying 20.2 Industrial Motor Control, Logic Circuits & PLC Automation 20.3 Electrical Instrumentation, Transducers & Measurement Systems 20.4 Illumination Engineering, Lighting Design & Photometrics 20.5 Feedback Control Systems & Research Methods
15.2 Transformer Connections & Special Transformers
Key Takeaways Explain This Topic AI
Standard three-phase transformer connections (Y-Y, Y-Δ, Δ-Y, Δ-Δ) establish fundamental voltage and current relationships, with Y-Δ and Δ-Y configurations producing a 30° phase shift between HV and LV line voltages.
The Open-Delta (V-V) connection utilizes two single-phase transformers to deliver three-phase power at 57.7% of the capacity of a full Δ-Δ bank (1.732 S₁) with an active utility capability factor of 86.6%.
Scott-T (T-T) connections transform three-phase power into two-phase power (or vice versa) using a main transformer tapped at 50% and a teaser transformer tapped at (√3)/2 ≈ 86.6% of full winding turn count.
Autotransformers transfer power via both inductive and conductive mechanisms, providing higher efficiency, smaller physical footprint, and lower percentage impedance according to S_auto = S_two-winding / (1 - K).
Grounding transformers, such as zig-zag (interconnected star) units, create a stable artificial neutral point on ungrounded 3-wire systems to facilitate zero-sequence fault current return paths for protective relaying.
Last updated: August 2026
- 15.2 Transformer Connections & Special Transformers
- Standard Three-Phase Bank Configurations
Three-phase power transformation can be accomplished using either a single 3-phase transformer unit or three identical single-phase transformers connected in a 3-phase bank. The four primary three-phase winding configurations are Star-Star (Y-Y) , Delta-Delta ( Δ \Delta Δ - Δ \Delta Δ ) , Star-Delta (Y- Δ \Delta Δ ) , and Delta-Star ( Δ \Delta Δ -Y) . THREE-PHASE WINDING CONNECTIONS & LINE/PHASE RELATIONS
- STAR (Y) CONNECTION DELTA (Δ) CONNECTION
- Phase A Phase A
- │ ┌─┐
- █ Winding ███│ Winding
- │ ███│
- Neutral├──────┐ Phase B│ └─┐Phase C
- │ │ ┌─────┼───┼─────┐
- █ █ │ ███ │ ███
- │ │ │ ███ │ ███
- Phase B Phase C └─────┼───┘ │
- └─────────┘
- V_Line = √3 · V_Phase V_Line = V_Phase
- I_Line = I_Phase I_Line = √3 · I_Phase
- Summary of Voltage, Current & Phase Relationships
Winding Connection Line-to-Phase Voltage Line-to-Phase Current Neutral Availability Primary/Secondary Phase Shift
Star-Star (Y-Y) V L = 3 V P V_L = \sqrt{3} V_P V L = 3 V P I L = I P I_L = I_P I L = I P Yes (4-wire system) 0 ∘ 0^\circ 0 ∘ (or 180 ∘ 180^\circ 18 0 ∘ )
Delta-Delta ( Δ \Delta Δ - Δ \Delta Δ ) V L = V P V_L = V_P V L = V P I L = 3 I P I_L = \sqrt{3} I_P I L = 3 I P No (3-wire system) 0 ∘ 0^\circ 0 ∘ (or 180 ∘ 180^\circ 18 0 ∘ )
Star-Delta (Y- Δ \Delta Δ ) V L 1 = 3 V P 1 , V L 2 = V P 2 V_{L1} = \sqrt{3} V_{P1}, V_{L2} = V_{P2} V L 1 = 3 V P 1 , V L 2 = V P 2 I L 1 = I P 1 , I L 2 = 3 I P 2 I_{L1} = I_{P1}, I_{L2} = \sqrt{3} I_{P2} I L 1 = I P 1 , I L 2 = 3 I P 2 Primary side only ± 30 ∘ \pm 30^\circ ± 3 0 ∘ phase shift
Delta-Star ( Δ \Delta Δ -Y) V L 1 = V P 1 , V L 2 = 3 V P 2 V_{L1} = V_{P1}, V_{L2} = \sqrt{3} V_{P2} V L 1 = V P 1 , V L 2 = 3 V P 2 I L 1 = 3 I P 1 , I L 2 = I P 2 I_{L1} = \sqrt{3} I_{P1}, I_{L2} = I_{P2} I L 1 = 3 I P 1 , I L 2 = I P 2 Secondary side only ± 30 ∘ \pm 30^\circ ± 3 0 ∘ phase shift
Technical Features of Bank Configurations
Star-Star (Y-Y) :
Requires minimum insulation per phase ( V P = V L / 3 V_P = V_L / \sqrt{3} V P = V L / 3 ), making it economical for extra-high voltage (EHV) systems.
Disadvantage : Oscillating neutral phenomenon and severe 3rd harmonic voltage distortion under unbalanced loads unless neutrals are grounded or a tertiary delta winding is added.
Delta-Delta ( Δ \Delta Δ - Δ \Delta Δ ) :
Excellent for high-current, lower-voltage applications. Traps 3rd harmonic currents within the closed delta loop, preventing voltage distortion.
Can continue operating at reduced capacity in Open-Delta (V-V) if one single-phase unit breaks down.
Star-Delta (Y- Δ \Delta Δ ) :
Standard choice for step-down high-voltage transmission substations . The primary Y neutral can be grounded to stabilize line voltages against lightning surges.
Delta-Star ( Δ \Delta Δ -Y) :
Standard choice for step-up generation substations and commercial distribution systems ( 400 / 230 V 400/230\text{ V} 400/230 V or 480 / 277 V 480/277\text{ V} 480/277 V ). The secondary Y neutral provides a 4-wire service to supply both 3-phase motor loads and single-phase lighting/receptacle loads.
Vector Groups & Standard 30 ∘ 30^\circ 3 0 ∘ Phase Shift
According to IEEE/ANSI standards, in Y- Δ \Delta Δ and Δ \Delta Δ -Y transformers, high-voltage line voltage leads low-voltage line voltage by 30 ∘ 30^\circ 3 0 ∘ for positive phase sequence ( A − B − C A-B-C A − B − C ). In European IEC notation, vector groups such as Dy11 ( 30 ∘ 30^\circ 3 0 ∘ lead) and Dy1 ( 30 ∘ 30^\circ 3 0 ∘ lag) designate phase displacements on a 12-hour clock dial ( 11 × 30 ∘ = 330 ∘ ≡ + 30 ∘ 11 \times 30^\circ = 330^\circ \equiv +30^\circ 11 × 3 0 ∘ = 33 0 ∘ ≡ + 3 0 ∘ ).
Open-Delta (V-V) Connection Analysis
When one single-phase transformer in a 3-phase Δ \Delta Δ - Δ \Delta Δ bank is removed due to failure or maintenance, the remaining two single-phase transformers can continue delivering balanced 3-phase power in an Open-Delta (V-V) connection. OPEN-DELTA (V-V) TRANSFORMER BANK TOPOLOGY
- Phase A ───────────────┐
- │
- ──┴──
- T1 │ │ Primary Winding
- ──┬──
- Phase B ───────────────┼───┐
- │ │
- ──┴── │
- T2 │ │ Primary Winding
- ──┬── │
- Phase C ───────────────┴───┘ (Third transformer T3 removed!)
- Derivation of V-V Bank Rating & Utility Factor
Let S 1 = V P I P S_1 = V_P I_P S 1 = V P I P be the kVA rating of one single-phase transformer. In a full Δ \Delta Δ - Δ \Delta Δ bank of three units, the total capacity is: S Δ − Δ = 3 S 1 S_{\Delta-\Delta} = 3 S_1 S Δ − Δ = 3 S 1
In the Open-Delta (V-V) bank, line current I L I_L I L cannot exceed the rated phase current I P I_P I P of an individual transformer winding ( I L = I P I_L = I_P I L = I P ). The total 3-phase apparent power delivered by the two transformers is: S V − V = 3 V L I L = 3 V P I P = 3 S 1 ≈ 1.732 S 1 S_{V-V} = \sqrt{3} V_L I_L = \sqrt{3} V_P I_P = \sqrt{3} S_1 \approx 1.732 S_1 S V − V = 3 V L I L = 3 V P I P = 3 S 1 ≈ 1.732 S 1
1. Open-Delta Bank Capacity Ratio: S V − V S Δ − Δ = 3 S 1 3 S 1 = 1 3 = 0.577 = 57.7 % \frac{S_{V-V}}{S_{\Delta-\Delta}} = \frac{\sqrt{3} S_1}{3 S_1} = \frac{1}{\sqrt{3}} = 0.577 = 57.7\% S Δ − Δ S V − V = 3 S 1 3 S 1 = 3 1 = 0.577 = 57.7%
The Open-Delta bank delivers 57.7% of the full 3-phase Δ \Delta Δ - Δ \Delta Δ rating.
2. Utility Capability Factor (Operating Efficiency of Installed Units): Utility Factor = Open-Delta Capacity Total Nameplate Rating of 2 Installed Transformers = 3 S 1 2 S 1 = 3 2 = 0.866 = 86.6 % \text{Utility Factor} = \frac{\text{Open-Delta Capacity}}{\text{Total Nameplate Rating of 2 Installed Transformers}} = \frac{\sqrt{3} S_1}{2 S_1} = \frac{\sqrt{3}}{2} = 0.866 = 86.6\% Utility Factor = Total Nameplate Rating of 2 Installed Transformers Open-Delta Capacity = 2 S 1 3 S 1 = 2 3 = 0.866 = 86.6%
The two installed transformers can only be loaded up to 86.6% of their combined rating ( 2 S 1 2 S_1 2 S 1 ) without thermal overload.
Transformer Power Factor in V-V Bank
When an Open-Delta bank supplies a balanced 3-phase load operating at power factor cos ϕ \cos \phi cos ϕ , the individual phase currents in the two transformers are shifted by 30 ∘ 30^\circ 3 0 ∘ relative to their phase voltages. Consequently, the operating power factors of the two individual transformers are unequal: cos ϕ 1 = cos ( ϕ − 30 ∘ ) , cos ϕ 2 = cos ( ϕ + 30 ∘ ) \cos \phi_1 = \cos(\phi - 30^\circ), \quad \cos \phi_2 = \cos(\phi + 30^\circ) cos ϕ 1 = cos ( ϕ − 3 0 ∘ ) , cos ϕ 2 = cos ( ϕ + 3 0 ∘ )
Even if the load operates at unity power factor ( cos ϕ = 1.0 \cos \phi = 1.0 cos ϕ = 1.0 ), both transformers operate at cos 30 ∘ = 0.866 \cos 30^\circ = 0.866 cos 3 0 ∘ = 0.866 power factor (one leading, one lagging).
If the load power factor drops to 0.50 0.50 0.50 lagging ( ϕ = 60 ∘ \phi = 60^\circ ϕ = 6 0 ∘ ), transformer T2 operates at cos ( 60 ∘ + 30 ∘ ) = cos 90 ∘ = 0 \cos(60^\circ + 30^\circ) = \cos 90^\circ = 0 cos ( 6 0 ∘ + 3 0 ∘ ) = cos 9 0 ∘ = 0 power factor, delivering zero active power while transformer T1 supplies the entire active load power!
Scott-T (T-T) Winding Connection
The Scott-T (or T-T) connection converts a 3-phase system into a 2-phase system (or vice versa) using two special single-phase transformers: the Main Transformer and the Teaser Transformer . SCOTT-T (T-T) TRANSFORMER VECTOR SCHEMATIC
- Phase A (Apex)
- │
- │ Teaser Transformer (Tapped at 86.6% = √3/2)
- │
- ▼
- Phase B ───────█████─────── Phase C
- ▲ ▲
- └───── 50% Tap ─────┘
- Main Transformer
- Winding Specifications & Vector Derivations
Main Transformer : Connected across lines B and C of the 3-phase system ( V B C = V L V_{BC} = V_L V BC = V L ). The primary winding has N p N_p N p turns and features a precise 50% center tap .
Teaser Transformer : Connected between line phase A and the 50% center tap of the main transformer.
From the 3-phase equilateral voltage triangle, the altitude from phase A to the midpoint of line B-C is: V teaser = V L sin 60 ∘ = 3 2 V L ≈ 0.866 V L V_{\text{teaser}} = V_L \sin 60^\circ = \frac{\sqrt{3}}{2} V_L \approx 0.866 V_L V teaser = V L sin 6 0 ∘ = 2 3 V L ≈ 0.866 V L
To achieve equal primary voltage per turn and balanced orthogonal two-phase secondary voltages ( 90 ∘ 90^\circ 9 0 ∘ phase shift), the primary winding of the teaser transformer must be tapped at 3 2 ≈ 86.6 % \frac{\sqrt{3}}{2} \approx 86.6\% 2 3 ≈ 86.6% of total main turns ( N teaser = 0.866 N p N_{\text{teaser}} = 0.866 N_p N teaser = 0.866 N p ).
Autotransformers: Conductive vs. Inductive Power Transfer
An autotransformer is a single-winding transformer in which a portion of the same continuous winding is common to both the high-voltage (HV) and low-voltage (LV) circuits. AUTOTRANSFORMER VOLTAGE AND CURRENT FLOW
- I_H ───► ┌───────────┐ Common Winding Portion
- V_H (Input) │ Primary │ (Series Winding N_se)
- └─────┬─────┘
- ──────────────────────────────┼───────────► I_L (Output)
- │
- ┌─────┴─────┐ Common Winding (N_c)
- │ Secondary │ Current = I_L - I_H
- └─────┬─────┘
- ──────────────────────────────┴───────────► Neutral
- Transformation Ratio ( K K K )
Let V H V_H V H be the higher terminal voltage and V L V_L V L be the lower terminal voltage. The autotransformer ratio is defined as: K = V L V H < 1 K = \frac{V_L}{V_H} < 1 K = V H V L < 1
Apparent Power Capacity Advantage
When a standard two-winding transformer of rating S two-winding S_{\text{two-winding}} S two-winding is reconnected as an autotransformer, its effective output kVA capacity increases dramatically according to: S auto = S two-winding 1 − K S_{\text{auto}} = \frac{S_{\text{two-winding}}}{1 - K} S auto = 1 − K S two-winding
Division of Transferred Power
Power transferred from primary to secondary side in an autotransformer occurs via two distinct physical mechanisms: Total Transferred Power: S auto = P ind + P cond \text{Total Transferred Power: } S_{\text{auto}} = P_{\text{ind}} + P_{\text{cond}} Total Transferred Power: S auto = P ind + P cond
Inductively Transferred Power ( P ind P_{\text{ind}} P ind ) (via magnetic flux coupling through core): P ind = ( 1 − K ) S auto = S two-winding P_{\text{ind}} = (1 - K) S_{\text{auto}} = S_{\text{two-winding}} P ind = ( 1 − K ) S auto = S two-winding
Conductively Transferred Power ( P cond P_{\text{cond}} P cond ) (via direct electrical connection): P cond = K S auto P_{\text{cond}} = K S_{\text{auto}} P cond = K S auto
Quantitative Advantages & Isolation Hazard
Copper Saving : Weight of copper in auto Weight of copper in 2-winding = 1 − K \frac{\text{Weight of copper in auto}}{\text{Weight of copper in 2-winding}} = 1 - K Weight of copper in 2-winding Weight of copper in auto = 1 − K .
Higher Efficiency : Internal I 2 R I^2 R I 2 R losses decrease because only a fraction ( 1 − K ) (1-K) ( 1 − K ) of power is transformed inductively.
Lower Percentage Impedance : Results in superior voltage regulation, but increases available short-circuit fault current ( I sc = I rated / Z pu I_{\text{sc}} = I_{\text{rated}} / Z_{\text{pu}} I sc = I rated / Z pu ).
FATAL ISOLATION HAZARD : Primary and secondary circuits are electrically tied together. A break in the common winding exposes low-voltage load equipment to full high-voltage potentials, requiring solid neutral grounding.
Voltage Tap Changers
To compensate for line voltage drops caused by varying load currents along power distribution feeders, transformers are equipped with tap changers on their high-voltage windings (where current is lower, minimizing arc erosion).
No-Load Tap Changers (NLTC / Off-Circuit Tap Changers) : Tap setting can only be manually adjusted while the transformer is completely de-energized. Typically provides ± 2.5 % \pm 2.5\% ± 2.5% and ± 5.0 % \pm 5.0\% ± 5.0% voltage adjustments.
On-Load Tap Changers (OLTC) : Adjusts tap positions dynamically while carrying full load current. Employs selector switches and diverter switches with transition resistors or reactors to prevent breaking load current or short-circuiting adjacent tap turns during tap transitions.
Grounding Transformers (Zig-Zag Connection)
Utility distribution systems fed by Δ \Delta Δ -connected transformer secondaries lack a physical neutral conductor. To establish a stable neutral point on an ungrounded 3-phase 3-wire network, a Grounding Transformer is installed. ZIG-ZAG (INTERCONNECTED STAR) GROUNDING TRANSFORMER
- Phase A Phase B Phase C
- │ │ │
- ███ a1 ███ b1 ███ c1
- │ │ │
- ███ c2 ███ a2 ███ b2
- └───────────────────┼───────────────────┘
- │
- ▼ Ground Neutral (N)
- Operating Principle of Zig-Zag (Interconnected Star) Winding
Each phase limb contains two equal winding sections wound in opposite directions on different core limbs ( a 1 , c 2 ; b 1 , a 2 ; c 1 , b 2 a_1, c_2; b_1, a_2; c_1, b_2 a 1 , c 2 ; b 1 , a 2 ; c 1 , b 2 ).
Normal Balanced Conditions (Positive/Negative Sequence) : Equal opposing currents in each limb cancel magnetizing flux, presenting extremely high magnetizing impedance and drawing negligible no-load current.
Ground Fault Conditions (Zero Sequence I 0 I_0 I 0 ) : Zero-sequence fault currents flow in phase through all three lines simultaneously. The opposing winding arrangement allows zero-sequence current to pass through with very low impedance , providing a safe path to ground and enabling protective relays to clear phase-to-ground faults.