Study guide
18.1 Transmission Line Parameters & Performance Models
PRC Registered Electrical Engineer REE
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Overview, RA 7920 & Electrical Engineering Ethics
1.1 PRC Board of Electrical Engineering & REE Examination Overview 1.2 Republic Act No. 7920 (New Electrical Engineering Law) & License Classes 1.3 Code of Ethics & Professional Practice for Electrical Engineers
2 Chapter 2: Math — Algebra, Trig & Geometry
2.1 Algebraic Equations, Polynomials & Complex Numbers 2.2 Trigonometry — Identities, Triangles & Spherical Trig 2.3 Analytic & Solid Geometry
3 Chapter 3: Engineering Mathematics — Calculus & Differential Equations
3.1 Differential Calculus, Limits, Derivatives & Applications 3.2 Integral Calculus, Integration Techniques & Area/Volume Applications 3.3 Ordinary Differential Equations & Initial-Value Problems
4 Chapter 4: Engineering Mathematics — Advanced Math & Transform Methods
4.1 Laplace Transforms, Inverse Transforms & Circuit Applications 4.2 Fourier Series, Fourier Transforms & Frequency-Domain Analysis 4.3 Vector Analysis, Linear Algebra, Matrices & Complex Analysis
5 Chapter 5: Engineering Mathematics — Probability, Statistics & Engineering Data Analysis
5.1 Probability Theory, Counting Techniques & Bayes' Theorem 5.2 Engineering Data Analysis I — Descriptive Statistics & Probability Distributions 5.3 Engineering Data Analysis II — Confidence Intervals, Hypothesis Testing & Regression
6 Chapter 6: Engineering Mathematics — Numerical Methods & Analysis
6.1 Numerical Root-Finding & Solution of Linear Systems 6.2 Interpolation, Numerical Integration & Numerical Solution of ODEs
7 Chapter 7: ESAS — Physics, Chemistry & Computer Fundamentals
7.1 Physics for Engineers 7.2 General Chemistry & Materials Science 7.3 Computer Fundamentals, Programming & Data Logic 7.4 Logic Circuits, Switching Theory & Microprocessor Systems
8 Chapter 8: ESAS — Mechanics & Thermal-Fluid Engineering
8.1 Engineering Mechanics — Statics & Dynamics 8.2 Strength of Materials & Mechanics of Deformable Bodies 8.3 Thermal-Fluid Engineering — Thermodynamics & Fluid Mechanics
9 Chapter 9: ESAS — Engineering Economics, Management & Contracts
9.1 Engineering Economics & Depreciation 9.2 Engineering Management & Ethics 9.3 Philippine Electrical Engineering Law, Code & Contracts 9.4 Technopreneurship 101 & Management of Engineering Projects
10 Chapter 10: PEC 1 — Safety, Sizing & Protection
10.1 PEC Fundamentals, Safety Standards & Grounding/Bonding 10.2 Conductor Sizing, Ampacity Adjustment & Voltage Drop 10.3 Overcurrent Protection, Branch Circuit & Feeder Sizing 10.4 Basic Occupational Safety & Health (BOSH) and Electrical Safety Standards
11 Chapter 11: PEC 1 & 2 — Equipment & Utility Systems
11.1 PEC Equipment Installation & Wiring Methods 11.2 Utility Systems, Transformers & Switchgear 11.3 Special Occupancies & Hazardous Locations
12 Chapter 12: Electrical Professional — DC & AC Circuit Fundamentals
12.1 DC Circuit Analysis & Network Theorems 12.2 Single-Phase AC Circuits & Phasor Analysis 12.3 Balanced & Unbalanced Three-Phase AC Circuits
13 Chapter 13: Electrical Professional — EM Fields & Transients
13.1 Electrostatics, Magnetostatics & Maxwell's Equations 13.2 Electromagnetic Waves & Transmission Line Fields 13.3 First-Order & Second-Order Circuit Transients
14 Chapter 14: Electrical Professional — Electronics, Industrial Electronics & Communications
14.1 Electronics 1 & 2 — Semiconductor Devices & Analog Circuits 14.2 Electrical Apparatus & Devices — Industrial Electronics & Power Converters 14.3 Fundamentals of Electronic Communications
15 Chapter 15: Electrical Professional — Transformers & DC Machines
15.1 Single-Phase & Three-Phase Transformers 15.2 Transformer Connections & Special Transformers 15.3 DC Generators & DC Motors
16 Chapter 16: Electrical Professional — AC Synchronous & Induction Machinery
16.1 Synchronous Generators (Alternators) 16.2 Synchronous Motors & Special AC Machines 16.3 Three-Phase & Single-Phase Induction Motors
17 Chapter 17: Electrical Professional — Power Plants & Energy Conversion
17.1 Hydroelectric, Thermal & Combined Cycle Power Plants 17.2 Renewable Energy Systems & Geothermal Power Plants 17.3 Power Plant Economics, Load Curves & Energy Conversion
18 Chapter 18: Electrical Professional — Transmission & Distribution
18.1 Transmission Line Parameters & Performance Models 18.2 Mechanical Overhead Line Design, Underground Cables & Insulators 18.3 Distribution Systems, Substation Layouts & Power Flow Control
19 Chapter 19: Electrical Professional — Power System Analysis
19.1 The Per-Unit System, Base Conversion & Impedance Diagrams 19.2 Symmetrical Components & Unbalanced Fault Analysis 19.3 Load Flow, Economic Dispatch & Power System Stability
20 Chapter 20: Electrical Professional — Protection, Control, Instrumentation & Illumination
20.1 Power System Protection & Protective Relaying 20.2 Industrial Motor Control, Logic Circuits & PLC Automation 20.3 Electrical Instrumentation, Transducers & Measurement Systems 20.4 Illumination Engineering, Lighting Design & Photometrics 20.5 Feedback Control Systems & Research Methods
18.1 Transmission Line Parameters & Performance Models
Key Takeaways Explain This Topic AI
The self GMR ( D s D_s D s ) and mutual GMD ( D m D_m D m ) method reduces multi-conductor transmission lines to equivalent single-conductor inductance L = 2 × 10 − 7 ln ( D m / D s ) H/m L = 2 \times 10^{-7} \ln(D_m / D_s)\ \text{H/m} L = 2 × 1 0 − 7 ln ( D m / D s ) H/m and line-to-neutral capacitance C n = 2 π ϵ 0 ln ( D m / D s c ) F/m C_n = \frac{2\pi \epsilon_0}{\ln(D_m / D_s^c)}\ \text{F/m} C n = l n ( D m / D s c ) 2 π ϵ 0 F/m , with bundling significantly increasing GMR, lowering electric field gradients, and decreasing line reactance.
Transmission line classification by length dictates performance modeling: Short lines ( < 80 km <80\ \text{km} < 80 km ) neglect line capacitance; Medium lines ( 80 – 250 km 80\text{--}250\ \text{km} 80 – 250 km ) utilize lumped Nominal- π \pi π or Nominal- T T T networks; Long lines ( > 250 km >250\ \text{km} > 250 km ) require exact distributed parameter hyperbolic equations ( A = D = cosh γ l A = D = \cosh \gamma l A = D = cosh γ l , B = Z c sinh γ l B = Z_c \sinh \gamma l B = Z c sinh γ l ).
The Ferranti Effect causes no-load or lightly loaded receiving-end line voltage to exceed sending-end voltage ( V R > V S V_R > V_S V R > V S ) on medium and long transmission lines due to line charging current flowing through line series inductance ( V R ≈ V S cos β l V_R \approx \frac{V_S}{\cos \beta l} V R ≈ c o s βl V S ).
Surge Impedance Loading ( SIL = V L − L 2 Z c \text{SIL} = \frac{V_{L-L}^2}{Z_c} SIL = Z c V L − L 2 ) represents the load power at which reactive power generated by line capacitance equals reactive power absorbed by line inductance, yielding a flat voltage profile with zero net reactive power exchange.
Skin effect concentrates alternating current density near the outer conductor surface, increasing AC resistance above DC resistance ( R ac > R dc R_{\text{ac}} > R_{\text{dc}} R ac > R dc ) as frequency, conductor cross-section, and magnetic permeability increase.
Last updated: August 2026
18.1 Transmission Line Parameters & Performance Models
Electric power transmission line theory and steady-state modeling constitute major core subjects on the PRC Registered Electrical Engineer (REE) Licensure Examination . Power transmission lines connect distant generating plants to distribution load centers. Precise analytical modeling of transmission line parameters—resistance ( R R R ), inductance ( L L L ), capacitance ( C C C ), and shunt conductance ( G G G )—is essential for calculating voltage drop, power losses, transient limits, and voltage regulation across high-voltage grid networks.
1. Electrical Transmission Line Parameters
An overhead power transmission line possesses four distributed electrical parameters evenly distributed along its physical length.
Resistance ( R R R )
The DC resistance of a solid cylindrical conductor of length l l l (meters) and cross-sectional area A A A (square meters) is: R dc = ρ l A R_{\text{dc}} = \frac{\rho l}{A} R dc = A ρl
where ρ \rho ρ is the material volume resistivity ( Ω ⋅ m \Omega \cdot \text{m} Ω ⋅ m ). Conductor resistance increases linearly with operating temperature: R T 2 = R T 1 [ 1 + α T 1 ( T 2 − T 1 ) ] = R T 1 ( T 2 + T 0 T 1 + T 0 ) R_{T2} = R_{T1} \left[ 1 + \alpha_{T1} (T_2 - T_1) \right] = R_{T1} \left( \frac{T_2 + T_0}{T_1 + T_0} \right) R T 2 = R T 1 [ 1 + α T 1 ( T 2 − T 1 ) ] = R T 1 ( T 1 + T 0 T 2 + T 0 )
where α T 1 \alpha_{T1} α T 1 is the temperature coefficient of resistance at T 1 T_1 T 1 , and T 0 T_0 T 0 is the inferred absolute zero-resistance temperature ( T 0 = 234.5 ∘ C T_0 = 234.5^\circ\text{C} T 0 = 234. 5 ∘ C for 100 % 100\% 100% IACS copper, T 0 = 228.1 ∘ C T_0 = 228.1^\circ\text{C} T 0 = 228. 1 ∘ C for hard-drawn aluminum).
Skin Effect & Proximity Effect
Skin Effect : Under alternating current (AC), changing magnetic flux linkages inside the conductor generate internal eddy currents that oppose current flow at the conductor core while reinforcing current flow near the outer surface. Consequently, AC current density concentrates near the conductor surface ("skin"). This reduces the effective cross-sectional area, raising AC resistance ( R ac > R dc R_{\text{ac}} > R_{\text{dc}} R ac > R dc ). Skin effect increases with higher supply frequency ( f f f ), larger conductor diameter ( d d d ), higher permeability ( μ \mu μ ), and lower resistivity ( ρ \rho ρ ). At 60 Hz 60\ \text{Hz} 60 Hz , R ac / R dc ≈ 1.02 to 1.08 R_{\text{ac}} / R_{\text{dc}} \approx 1.02 \text{ to } 1.08 R ac / R dc ≈ 1.02 to 1.08 .
Proximity Effect : Alternate magnetic fields produced by adjacent parallel conductors alter the current density distribution across conductor cross-sections, further increasing effective AC line resistance.
2. Inductance of Transmission Lines
Inductance per phase arises from total magnetic flux linkages per unit current, comprising internal flux linkages (inside the conductor body) and external flux linkages (between conductor surface and infinity).
Single Conductor & Internal Inductance
For a solid cylindrical conductor carrying uniform current I I I , the internal inductance per meter is constant regardless of conductor radius: L int = μ 0 8 π = 4 π × 10 − 7 8 π = 1 2 × 10 − 7 H/m = 0.05 mH/km L_{\text{int}} = \frac{\mu_0}{8 \pi} = \frac{4 \pi \times 10^{-7}}{8 \pi} = \frac{1}{2} \times 10^{-7}\ \text{H/m} = 0.05\ \text{mH/km} L int = 8 π μ 0 = 8 π 4 π × 1 0 − 7 = 2 1 × 1 0 − 7 H/m = 0.05 mH/km
Self Geometric Mean Radius (GMR / D s D_s D s ) & Geometric Mean Distance (GMD / D m D_m D m )
Combining internal and external flux linkages yields the total inductance formula using the concept of Self GMR ( D s D_s D s ) and Mutual GMD ( D m D_m D m ) .
Self GMR ( D s D_s D s )
For a solid conductor of radius r r r , the internal inductance is mathematically absorbed into an equivalent fictitious hollow thin-walled conductor of radius D s D_s D s with zero internal flux: D s = r e − 1 / 4 = r e − 0.25 ≈ 0.7788 r D_s = r e^{-1/4} = r e^{-0.25} \approx 0.7788 r D s = r e − 1/4 = r e − 0.25 ≈ 0.7788 r
For multi-strand composite or ACSR conductors, D s D_s D s is determined by taking the n 2 n^2 n 2 -th root of all inter-strand distance products: D s = ∏ i = 1 n ∏ j = 1 n d i j n 2 D_s = \sqrt[n^2]{\prod_{i=1}^n \prod_{j=1}^n d_{ij}} D s = n 2 i = 1 ∏ n j = 1 ∏ n d ij
For a bundled conductor consisting of n n n sub-conductors separated by bundle spacing d d d :
2-conductor bundle: D s b = D s ⋅ d D_s^b = \sqrt{D_s \cdot d} D s b = D s ⋅ d
3-conductor bundle (equilateral triangle): D s b = D s ⋅ d 2 3 D_s^b = \sqrt[3]{D_s \cdot d^2} D s b = 3 D s ⋅ d 2
4-conductor bundle (square arrangement): D s b = D s ⋅ d 3 ⋅ 2 4 = 1.091 D s ⋅ d 3 4 D_s^b = \sqrt[4]{D_s \cdot d^3 \cdot \sqrt{2}} = 1.091 \sqrt[4]{D_s \cdot d^3} D s b = 4 D s ⋅ d 3 ⋅ 2 = 1.091 4 D s ⋅ d 3
Mutual GMD ( D m D_m D m )
For a 3-phase line with phase conductor spacings D a b , D b c , D c a D_{ab}, D_{bc}, D_{ca} D ab , D b c , D c a : D m = D a b D b c D c a 3 D_m = \sqrt[3]{D_{ab} D_{bc} D_{ca}} D m = 3 D ab D b c D c a
If the 3-phase conductors are symmetrically placed at the vertices of an equilateral triangle ( D a b = D b c = D c a = D D_{ab} = D_{bc} = D_{ca} = D D ab = D b c = D c a = D ), then D m = D D_m = D D m = D .
Inductance Equations
Single-Phase Two-Wire Line : L loop = 4 × 10 − 7 ln ( D D s ) H/m = 0.921 log 10 ( D D s ) mH/km L_{\text{loop}} = 4 \times 10^{-7} \ln\left( \frac{D}{D_s} \right)\ \text{H/m} = 0.921 \log_{10}\left( \frac{D}{D_s} \right)\ \text{mH/km} L loop = 4 × 1 0 − 7 ln ( D s D ) H/m = 0.921 lo g 10 ( D s D ) mH/km
Three-Phase Line (Transposed Conductor Configuration) : L = 2 × 10 − 7 ln ( D m D s ) H/m/phase = 0.4605 log 10 ( D m D s ) mH/km/phase L = 2 \times 10^{-7} \ln\left( \frac{D_m}{D_s} \right)\ \text{H/m/phase} = 0.4605 \log_{10}\left( \frac{D_m}{D_s} \right)\ \text{mH/km/phase} L = 2 × 1 0 − 7 ln ( D s D m ) H/m/phase = 0.4605 lo g 10 ( D s D m ) mH/km/phase Inductive Reactance: X L = 2 π f L ( Ω / km ) \text{Inductive Reactance: } X_L = 2 \pi f L \quad (\Omega/\text{km}) Inductive Reactance: X L = 2 π f L ( Ω/ km )
REE Exam Rule: Transposition of line conductors at regular physical intervals along the line route equalizes mutual inductances among phases, preventing unbalanced induced phase voltage drops.
3. Capacitance of Transmission Lines
Electric potential differences between parallel energized conductors establish an electrostatic field. Transmission line capacitance per unit length is defined by electric charge per unit potential difference ( C = q / V C = q / V C = q / V ).
Single-Phase & Three-Phase Line-to-Neutral Capacitance
For a 3-phase transposed line with mutual GMD D m D_m D m and conductor outer radius r r r : C n = 2 π ϵ 0 ln ( D m r ) = 2 π ( 8.854 × 10 − 12 ) ln ( D m r ) F/m/phase = 0.0556 ln ( D m r ) μ F/km/phase C_n = \frac{2 \pi \epsilon_0}{\ln\left( \frac{D_m}{r} \right)} = \frac{2 \pi (8.854 \times 10^{-12})}{\ln\left( \frac{D_m}{r} \right)}\ \text{F/m/phase} = \frac{0.0556}{\ln\left( \frac{D_m}{r} \right)}\ \mu\text{F/km/phase} C n = ln ( r D m ) 2 π ϵ 0 = ln ( r D m ) 2 π ( 8.854 × 1 0 − 12 ) F/m/phase = ln ( r D m ) 0.0556 μ F/km/phase
For bundled conductors, the capacitive self GMR is D s c = r D_s^c = r D s c = r (using physical radius r r r , not 0.7788 r 0.7788r 0.7788 r !):
2-conductor bundle: D s c b = r ⋅ d D_s^{cb} = \sqrt{r \cdot d} D s c b = r ⋅ d
4-conductor bundle: D s c b = 1.091 r ⋅ d 3 4 D_s^{cb} = 1.091 \sqrt[4]{r \cdot d^3} D s c b = 1.091 4 r ⋅ d 3 Line Charging Current: I c = ω C n V LN = 2 π f C n ( V L − L 3 ) ( A/phase ) \text{Line Charging Current: } I_c = \omega C_n V_{\text{LN}} = 2 \pi f C_n \left( \frac{V_{L-L}}{\sqrt{3}} \right) \quad (\text{A/phase}) Line Charging Current: I c = ω C n V LN = 2 π f C n ( 3 V L − L ) ( A/phase )
Effect of Earth / Ground (Method of Image Charges)
The presence of the conducting earth plane increases line-to-neutral capacitance. Using fictitious image conductors placed at depth h h h below ground level: C n , earth = 2 π ϵ 0 ln ( D m r ⋅ 1 + ( D m 2 h ) 2 ) C_{n,\text{earth}} = \frac{2 \pi \epsilon_0}{\ln\left( \frac{D_m}{r \cdot \sqrt{1 + \left( \frac{D_m}{2h} \right)^2}} \right)} C n , earth = ln ( r ⋅ 1 + ( 2 h D m ) 2 D m ) 2 π ϵ 0
Because tower heights h ≫ D m h \gg D_m h ≫ D m , earth proximity increases capacitance by less than 1 % – 2 % 1\%\text{--}2\% 1% – 2% , which is often neglected in standard overhead line calculations.
4. Two-Port ABCD Parameter Representation & Transmission Line Models
A transmission line is modeled as a passive linear two-port network relating sending-end voltage/current ( V S , I S V_S, I_S V S , I S ) to receiving-end voltage/current ( V R , I R V_R, I_R V R , I R ): [ V S I S ] = [ A B C D ] [ V R I R ] \begin{bmatrix} V_S \\ I_S \end{bmatrix} = \begin{bmatrix} A & B \\ C & D \end{bmatrix} \begin{bmatrix} V_R \\ I_R \end{bmatrix} [ V S I S ] = [ A C B D ] [ V R I R ] V S = A V R + B I R I S = C V R + D I R \begin{aligned} V_S &= A V_R + B I_R \\ I_S &= C V_R + D I_R \end{aligned} V S I S = A V R + B I R = C V R + D I R
Fundamental Properties of ABCD Matrix:
- Reciprocity : A D − B C = 1 A D - B C = 1 A D − BC = 1
- Symmetry (for identical sending and receiving ends): A = D A = D A = D
Units : A A A and D D D are dimensionless; B B B has units of Ohms ( Ω \Omega Ω ); C C C has units of Siemens ( S \text{S} S ).
Classification of Transmission Lines by Length
Line Model Length ( l l l ) Operating Voltage Shunt Capacitance ( Y Y Y ) Handling ABCD Parameter Matrix
Short Line l < 80 km l < 80\ \text{km} l < 80 km ( < 50 miles < 50\ \text{miles} < 50 miles ) < 20 kV < 20\ \text{kV} < 20 kV Completely neglected ( Y = 0 Y = 0 Y = 0 ) [ 1 Z 0 1 ] \begin{bmatrix} 1 & Z \\ 0 & 1 \end{bmatrix} [ 1 0 Z 1 ]
Medium Line (Nominal- π \pi π ) 80 ≤ l ≤ 250 km 80 \le l \le 250\ \text{km} 80 ≤ l ≤ 250 km 20 to 100 kV 20 \text{ to } 100\ \text{kV} 20 to 100 kV Lumped half at each end ( Y / 2 Y/2 Y /2 ) [ 1 + Y Z 2 Z Y ( 1 + Y Z 4 ) 1 + Y Z 2 ] \begin{bmatrix} 1 + \frac{Y Z}{2} & Z \\ Y \left(1 + \frac{Y Z}{4}\right) & 1 + \frac{Y Z}{2} \end{bmatrix} [ 1 + 2 Y Z Y ( 1 + 4 Y Z ) Z 1 + 2 Y Z ]
Medium Line (Nominal- T T T ) 80 ≤ l ≤ 250 km 80 \le l \le 250\ \text{km} 80 ≤ l ≤ 250 km 20 to 100 kV 20 \text{ to } 100\ \text{kV} 20 to 100 kV Lumped total Y Y Y at middle branch [ 1 + Y Z 2 Z ( 1 + Y Z 4 ) Y 1 + Y Z 2 ] \begin{bmatrix} 1 + \frac{Y Z}{2} & Z \left(1 + \frac{Y Z}{4}\right) \\ Y & 1 + \frac{Y Z}{2} \end{bmatrix} [ 1 + 2 Y Z Y Z ( 1 + 4 Y Z ) 1 + 2 Y Z ]
Long Line l > 250 km l > 250\ \text{km} l > 250 km ( > 150 miles > 150\ \text{miles} > 150 miles ) > 100 kV > 100\ \text{kV} > 100 kV Rigorous distributed parameters [ cosh ( γ l ) Z c sinh ( γ l ) 1 Z c sinh ( γ l ) cosh ( γ l ) ] \begin{bmatrix} \cosh(\gamma l) & Z_c \sinh(\gamma l) \\ \frac{1}{Z_c} \sinh(\gamma l) & \cosh(\gamma l) \end{bmatrix} [ cosh ( γ l ) Z c 1 sinh ( γ l ) Z c sinh ( γ l ) cosh ( γ l ) ]
where:
Z = z ⋅ l = ( r + j ω l ) l Z = z \cdot l = (r + j \omega l) l Z = z ⋅ l = ( r + jω l ) l is total line series impedance ( Ω \Omega Ω ).
Y = y ⋅ l = ( g + j ω c ) l Y = y \cdot l = (g + j \omega c) l Y = y ⋅ l = ( g + jω c ) l is total line shunt admittance ( S \text{S} S ).
γ = z y = α + j β \gamma = \sqrt{z y} = \alpha + j \beta γ = zy = α + j β is the complex wave propagation constant ( α \alpha α attenuation constant in nepers/km, β \beta β phase constant in rad/km).
Z c = z y ≈ L C Z_c = \sqrt{\frac{z}{y}} \approx \sqrt{\frac{L}{C}} Z c = y z ≈ C L is characteristic impedance / surge impedance ( Ω \Omega Ω ).
Voltage Regulation & Transmission Efficiency
Percentage Voltage Regulation (%VR) : % VR = ∣ V S A ∣ − ∣ V R ∣ ∣ V R ∣ × 100 % \% \text{VR} = \frac{\left| \frac{V_S}{A} \right| - |V_R|}{|V_R|} \times 100\% % VR = ∣ V R ∣ A V S − ∣ V R ∣ × 100%
Transmission Efficiency ( η \eta η ) : η = P R , 3-phase P S , 3-phase × 100 % = 3 ∣ V R ∣ ∣ I R ∣ cos ϕ R 3 ∣ V S ∣ ∣ I S ∣ cos ϕ S × 100 % \eta = \frac{P_{R,\text{3-phase}}}{P_{S,\text{3-phase}}} \times 100\% = \frac{3 |V_R| |I_R| \cos \phi_R}{3 |V_S| |I_S| \cos \phi_S} \times 100\% η = P S , 3-phase P R , 3-phase × 100% = 3∣ V S ∣∣ I S ∣ cos ϕ S 3∣ V R ∣∣ I R ∣ cos ϕ R × 100%
- 5. Ferranti Effect & Surge Impedance Loading (SIL)
- Ferranti Effect
When a medium or long transmission line operates under no-load ( I R = 0 I_R = 0 I R = 0 ) or very light load, the receiving-end voltage rises significantly above the sending-end voltage ( V R > V S V_R > V_S V R > V S ). This voltage rise is called the Ferranti Effect .
Physical Cause:
The line's distributed charging current I c = Y V R I_c = Y V_R I c = Y V R flows through the line's series inductive reactance X L X_L X L . The voltage drop across series inductance leads receiving-end voltage by 90 ∘ 90^\circ 9 0 ∘ , creating a boosting voltage component in phase with V S V_S V S .
Mathematical Derivation:
For an un-loaded long line ( I R = 0 I_R = 0 I R = 0 ), V S = V R cosh ( γ l ) V_S = V_R \cosh(\gamma l) V S = V R cosh ( γ l ) . For a lossless line ( α = 0 , γ = j β \alpha = 0, \gamma = j\beta α = 0 , γ = j β ): V S = V R cos ( β l ) ⟹ V R = V S cos ( β l ) V_S = V_R \cos(\beta l) \implies V_R = \frac{V_S}{\cos(\beta l)} V S = V R cos ( βl ) ⟹ V R = cos ( βl ) V S
Expanding cos ( β l ) ≈ 1 − β 2 l 2 2 \cos(\beta l) \approx 1 - \frac{\beta^2 l^2}{2} cos ( βl ) ≈ 1 − 2 β 2 l 2 yields the approximate receiving-end voltage rise: V R ≈ V S ( 1 + ω 2 l 2 L C 2 ) ⟹ Δ V = V R − V S ≈ V S ω 2 l 2 L C 2 V_R \approx V_S \left( 1 + \frac{\omega^2 l^2 L C}{2} \right) \implies \Delta V = V_R - V_S \approx \frac{V_S \omega^2 l^2 L C}{2} V R ≈ V S ( 1 + 2 ω 2 l 2 L C ) ⟹ Δ V = V R − V S ≈ 2 V S ω 2 l 2 L C
Mitigation: Connect shunt reactors (inductive coils) at receiving-end substations to absorb leading capacitive VARs under light-load conditions.
Surge Impedance Loading (SIL)
Surge Impedance Loading (SIL) is the active power delivered by a transmission line when its load impedance equals its characteristic surge impedance ( Z L = Z c Z_L = Z_c Z L = Z c ): SIL = ( V L − L , rated ) 2 Z c ( MW ) \text{SIL} = \frac{\left( V_{L-L,\text{rated}} \right)^2}{Z_c} \quad (\text{MW}) SIL = Z c ( V L − L , rated ) 2 ( MW )
For typical overhead AC transmission lines, Z c ≈ 377 Ω to 400 Ω Z_c \approx 377\ \Omega \text{ to } 400\ \Omega Z c ≈ 377 Ω to 400 Ω . For underground power cables, Z c ≈ 40 Ω to 60 Ω Z_c \approx 40\ \Omega \text{ to } 60\ \Omega Z c ≈ 40 Ω to 60 Ω .
Operational Significance of SIL:
Load = SIL = \text{SIL} = SIL : Reactive power generated by line capacitance ( Q C = I 2 X C Q_C = I^2 X_C Q C = I 2 X C ) exactly balances reactive power absorbed by line inductance ( Q L = I 2 X L Q_L = I^2 X_L Q L = I 2 X L ). The line has a flat voltage profile ( ∣ V ( x ) ∣ = V R = V S |V(x)| = V_R = V_S ∣ V ( x ) ∣ = V R = V S ), unity power factor everywhere, and zero net reactive power exchange with grid terminals.
Load > SIL > \text{SIL} > SIL : Line acts as net inductor ( Q L > Q C Q_L > Q_C Q L > Q C ), requiring reactive power support; receiving voltage drops ( V R < V S V_R < V_S V R < V S ).
Load < SIL < \text{SIL} < SIL : Line acts as net capacitor ( Q C > Q L Q_C > Q_L Q C > Q L ), generating excess reactive power; receiving voltage rises ( V R > V S V_R > V_S V R > V S , Ferranti effect).
- Solved Board Exam Examples
- Example 1: Inductance & Reactance of a 3-Phase Bundled Line
Problem: A 3-phase, 60 Hz 60\ \text{Hz} 60 Hz transposed transmission line rated at 230 kV 230\ \text{kV} 230 kV has horizontal conductor spacing D a b = 6.0 m D_{ab} = 6.0\ \text{m} D ab = 6.0 m , D b c = 6.0 m D_{bc} = 6.0\ \text{m} D b c = 6.0 m , and D c a = 12.0 m D_{ca} = 12.0\ \text{m} D c a = 12.0 m . Each phase consists of a 2-conductor bundle spaced d = 0.45 m d = 0.45\ \text{m} d = 0.45 m apart. Each sub-conductor has an outside radius r = 1.5 cm r = 1.5\ \text{cm} r = 1.5 cm . Calculate: (a) Mutual GMD D m D_m D m , (b) Bundled self GMR D s b D_s^b D s b , (c) Line inductance per phase per km, and (d) Total inductive reactance per phase for a 100 km 100\ \text{km} 100 km line.
Solution:
Calculate mutual GMD ( D m D_m D m ): D m = D a b D b c D c a 3 = 6.0 × 6.0 × 12.0 3 = 432 3 = 7.5595 m D_m = \sqrt[3]{D_{ab} D_{bc} D_{ca}} = \sqrt[3]{6.0 \times 6.0 \times 12.0} = \sqrt[3]{432} = 7.5595\ \text{m} D m = 3 D ab D b c D c a = 3 6.0 × 6.0 × 12.0 = 3 432 = 7.5595 m
Calculate single conductor self GMR ( D s D_s D s ): D s = 0.7788 × r = 0.7788 × 0.015 m = 0.011682 m D_s = 0.7788 \times r = 0.7788 \times 0.015\ \text{m} = 0.011682\ \text{m} D s = 0.7788 × r = 0.7788 × 0.015 m = 0.011682 m
Calculate bundled conductor self GMR ( D s b D_s^b D s b ): D s b = D s ⋅ d = 0.011682 × 0.45 = 0.0052569 = 0.072504 m D_s^b = \sqrt{D_s \cdot d} = \sqrt{0.011682 \times 0.45} = \sqrt{0.0052569} = 0.072504\ \text{m} D s b = D s ⋅ d = 0.011682 × 0.45 = 0.0052569 = 0.072504 m
Calculate line inductance per km ( L L L ): L = 2 × 10 − 7 ln ( D m D s b ) × 1000 = 2 × 10 − 4 ln ( 7.5595 0.072504 ) = 2 × 10 − 4 ln ( 104.263 ) = 0.9294 mH/km/phase L = 2 \times 10^{-7} \ln\left( \frac{D_m}{D_s^b} \right) \times 1000 = 2 \times 10^{-4} \ln\left( \frac{7.5595}{0.072504} \right) = 2 \times 10^{-4} \ln(104.263) = 0.9294\ \text{mH/km/phase} L = 2 × 1 0 − 7 ln ( D s b D m ) × 1000 = 2 × 1 0 − 4 ln ( 0.072504 7.5595 ) = 2 × 1 0 − 4 ln ( 104.263 ) = 0.9294 mH/km/phase
Calculate total inductive reactance for 100 km 100\ \text{km} 100 km ( X L X_L X L ): X L = 2 π f L × 100 = 2 π × 60 × ( 0.9294 × 10 − 3 ) × 100 = 35.04 Ω X_L = 2 \pi f L \times 100 = 2 \pi \times 60 \times (0.9294 \times 10^{-3}) \times 100 = 35.04\ \Omega X L = 2 π f L × 100 = 2 π × 60 × ( 0.9294 × 1 0 − 3 ) × 100 = 35.04 Ω
Example 2: Medium Transmission Line Nominal- π \pi π Performance
Problem: A 3-phase, 138 kV 138\ \text{kV} 138 kV , 60 Hz 60\ \text{Hz} 60 Hz , 150 km 150\ \text{km} 150 km transmission line delivers 50 MW 50\ \text{MW} 50 MW at 0.85 0.85 0.85 power factor lagging to a 138 kV 138\ \text{kV} 138 kV load. Line series impedance per phase is Z = 20 + j 60 Ω Z = 20 + j 60\ \Omega Z = 20 + j 60 Ω , and line shunt admittance per phase is Y = j 5.0 × 10 − 4 S Y = j 5.0 \times 10^{-4}\ \text{S} Y = j 5.0 × 1 0 − 4 S . Using the Nominal- π \pi π model, determine: (a) ABCD parameters, (b) Sending-end line-to-line voltage V S , L − L V_{S,L-L} V S , L − L , and (c) Percentage voltage regulation.
Solution:
Calculate Nominal- π \pi π ABCD parameters: A = D = 1 + Y Z 2 = 1 + ( j 5.0 × 10 − 4 ) ( 20 + j 60 ) 2 = 1 + − 0.03 + j 0.01 2 = 0.985 + j 0.005 = 0.98501 ∠ 0.291 ∘ A = D = 1 + \frac{Y Z}{2} = 1 + \frac{(j 5.0 \times 10^{-4})(20 + j 60)}{2} = 1 + \frac{-0.03 + j 0.01}{2} = 0.985 + j 0.005 = 0.98501 \angle 0.291^\circ A = D = 1 + 2 Y Z = 1 + 2 ( j 5.0 × 1 0 − 4 ) ( 20 + j 60 ) = 1 + 2 − 0.03 + j 0.01 = 0.985 + j 0.005 = 0.98501∠0.29 1 ∘ B = Z = 20 + j 60 Ω = 63.2455 ∠ 71.565 ∘ Ω B = Z = 20 + j 60\ \Omega = 63.2455 \angle 71.565^\circ\ \Omega B = Z = 20 + j 60 Ω = 63.2455∠71.56 5 ∘ Ω
Receiving-end line-to-neutral voltage and current: V R = 138 , 000 3 = 79 , 674.3 ∠ 0 ∘ V V_R = \frac{138,000}{\sqrt{3}} = 79,674.3 \angle 0^\circ\ \text{V} V R = 3 138 , 000 = 79 , 674.3∠ 0 ∘ V I R = 50 × 10 6 3 × 138 , 000 × 0.85 = 246.06 ∠ − 31.788 ∘ A = ( 209.15 − j 129.62 ) A I_R = \frac{50 \times 10^6}{\sqrt{3} \times 138,000 \times 0.85} = 246.06 \angle -31.788^\circ\ \text{A} = (209.15 - j 129.62)\ \text{A} I R = 3 × 138 , 000 × 0.85 50 × 1 0 6 = 246.06∠ − 31.78 8 ∘ A = ( 209.15 − j 129.62 ) A
Calculate sending-end voltage ( V S = A V R + B I R V_S = A V_R + B I_R V S = A V R + B I R ): A V R = ( 0.985 + j 0.005 ) ( 79 , 674.3 ) = 78 , 479.2 + j 398.37 V A V_R = (0.985 + j 0.005)(79,674.3) = 78,479.2 + j 398.37\ \text{V} A V R = ( 0.985 + j 0.005 ) ( 79 , 674.3 ) = 78 , 479.2 + j 398.37 V B I R = ( 63.2455 ∠ 71.565 ∘ ) ( 246.06 ∠ − 31.788 ∘ ) = 15 , 562.2 ∠ 39.777 ∘ = 11 , 960.0 + j 9 , 956.8 V B I_R = (63.2455 \angle 71.565^\circ)(246.06 \angle -31.788^\circ) = 15,562.2 \angle 39.777^\circ = 11,960.0 + j 9,956.8\ \text{V} B I R = ( 63.2455∠71.56 5 ∘ ) ( 246.06∠ − 31.78 8 ∘ ) = 15 , 562.2∠39.77 7 ∘ = 11 , 960.0 + j 9 , 956.8 V V S = ( 78 , 479.2 + 11 , 960.0 ) + j ( 398.37 + 9 , 956.8 ) = 90 , 439.2 + j 10 , 355.2 V = 91 , 029.7 ∠ 6.536 ∘ V V_S = (78,479.2 + 11,960.0) + j (398.37 + 9,956.8) = 90,439.2 + j 10,355.2\ \text{V} = 91,029.7 \angle 6.536^\circ\ \text{V} V S = ( 78 , 479.2 + 11 , 960.0 ) + j ( 398.37 + 9 , 956.8 ) = 90 , 439.2 + j 10 , 355.2 V = 91 , 029.7∠6.53 6 ∘ V V S , L − L = 91 , 029.7 × 3 = 157 , 668.2 V = 157.67 kV V_{S,L-L} = 91,029.7 \times \sqrt{3} = 157,668.2\ \text{V} = 157.67\ \text{kV} V S , L − L = 91 , 029.7 × 3 = 157 , 668.2 V = 157.67 kV
Calculate Voltage Regulation (%VR): % VR = ∣ V S ∣ ∣ A ∣ − ∣ V R ∣ ∣ V R ∣ × 100 % = 91 , 029.7 0.98501 − 79 , 674.3 79 , 674.3 × 100 % = 92 , 415.0 − 79 , 674.3 79 , 674.3 × 100 % = 15.99 % \% \text{VR} = \frac{\frac{|V_S|}{|A|} - |V_R|}{|V_R|} \times 100\% = \frac{\frac{91,029.7}{0.98501} - 79,674.3}{79,674.3} \times 100\% = \frac{92,415.0 - 79,674.3}{79,674.3} \times 100\% = 15.99\% % VR = ∣ V R ∣ ∣ A ∣ ∣ V S ∣ − ∣ V R ∣ × 100% = 79 , 674.3 0.98501 91 , 029.7 − 79 , 674.3 × 100% = 79 , 674.3 92 , 415.0 − 79 , 674.3 × 100% = 15.99%