Study guide
13.2 One-Line Diagrams, Drawing Symbols & Wiring Plans
PRC Registered Master Electrician RME
Track your progress as you read
Finished sections get a check mark.
1 Introduction
RME Licensure Examination Overview & RA 7920 Framework How to Use This Study Guide & Build Your Study Plan
2 Chapter 1: DC & AC Circuit Fundamentals
1.1 Ohm's Law & DC Circuit Calculations 1.2 Kirchhoff's Laws & Series-Parallel Network Analysis 1.3 AC Fundamentals: Sine Waves, RMS & Phase Relationships 1.4 AC Circuit Impedance, Reactance & Resonance
3 Chapter 2: AC Power, Three-Phase Systems & DC Generators
2.1 Power in AC Circuits & Power Factor 2.2 Three-Phase Systems: Wye-Delta Configurations & Calculations 2.3 DC Generators: Construction, Types & Characteristics
4 Chapter 3: DC & AC Motors and Starting Methods
3.1 DC Motors: Construction, Types & Speed Control 3.2 AC Induction Motors: Construction, Slip & Synchronous Speed 3.3 Induction Motor Starting Methods
5 Chapter 4: Synchronous Machines & Transformers
4.1 Synchronous Motors & AC Generators (Alternators) 4.2 Transformers: Construction, Turns Ratio & Types 4.3 Transformer Losses, Efficiency, Cooling & Connections
6 Chapter 5: Motor Starters, Control Circuits & Overcurrent Devices
5.1 Motor Starters: DOL, Star-Delta & Autotransformer Starting 5.2 Motor Control Circuits & Overload Protection 5.3 Fuses & Circuit Breakers: Types, Ratings & Applications
7 Chapter 6: Control Devices & Electrical Components
6.1 Contactors, Relays & Other Control Devices 6.2 Electrical Components: Capacitors, Inductors & Resistors 6.3 Semiconductor Devices & Basic Solid-State Components
8 Chapter 7: Maintenance, Test Equipment & RA 7920 Law
7.1 Maintenance & Troubleshooting Practices 7.2 Test Equipment & Electrical Instruments 7.3 RA 7920: RME Law, Scope of Practice & PRC Regulation
9 Chapter 8: PEC Foundations: Scope & General Requirements
8.1 PEC Scope, Definitions & Code Organization (Part 1 vs Part 2) 8.2 General Installation Requirements & Working Space 8.3 Conductor Sizing, Ampacity & Derating 8.4 Overcurrent Protection & Conductor Protection Coordination
10 Chapter 9: Load Calculations & Wiring Methods
9.1 Voltage Drop & Continuous Load Calculations 9.2 Feeders, Load Calculations & Demand Factors 9.3 Wiring Methods: Raceways & Conduit Systems
11 Chapter 10: Cable Systems, Boxes & Wiring Devices
10.1 Wiring Methods: Cable Systems & Flexible Wiring 10.2 Boxes, Enclosures & Fittings 10.3 Wiring Devices, Receptacles & GFCI Protection
12 Chapter 11: Branch Circuits & Services
11.1 Branch Circuits & Multiwire Branch Circuits 11.2 Services & Service Equipment 11.3 Grounding: System & Equipment Grounding
13 Chapter 12: Bonding, Panelboards & Motor Wiring
12.1 Bonding & Grounding Electrode Systems 12.2 Panelboards & Switchboards 12.3 Motor & Generator Wiring, Protection & Disconnects
14 Chapter 13: Motor-Starter Diagrams & Hazardous Locations
13.1 Motor-Starter Wiring Diagrams & Control Symbols 13.2 One-Line Diagrams, Drawing Symbols & Wiring Plans 13.3 Hazardous (Classified) Locations
15 Chapter 14: Special Occupancies, Conditions & Safety
14.1 Special Occupancies (Wet/Damp Locations, Underground Wiring) 14.2 Special Conditions: Emergency Systems & Communications Wiring 14.3 Electrical Safety, PPE & Code-Mandated Working Clearances
16 Chapter 15: Final Review & Next Steps
15.1 RME Exam Strategy, Time Management & Test-Day Tips 15.2 After Passing: PRC Registration, CPD Renewal & Career Paths
13.2 One-Line Diagrams, Drawing Symbols & Wiring Plans
Key Takeaways Explain This Topic AI
RA 7920 Section 19 lists drawing symbols and wiring plans as explicit RME exam content, alongside motor-starter diagrams.
A one-line diagram traces power flow from the utility service point through the main disconnect and distribution equipment down to major feeders and loads using simplified single-line notation.
Floor plans use standardized symbols for receptacles, switches (single-pole, three-way, four-way), light outlets, junction boxes, and panelboards; home run arrows with circuit numbers connect a floor plan to its panel schedule.
Hash marks crossing a conductor line on a drawing indicate how many individual conductors are routed together in that run.
A riser diagram is a vertical one-line diagram showing feeder distribution rising through every floor of a multi-story building.
Last updated: July 2026
13.2 One-Line Diagrams, Drawing Symbols & Wiring Plans
RA 7920 Section 19 also lists "drawing symbols and wiring plans" among the specific content the Board of Electrical Engineering may test. Where Section 13.1 covered the diagrams that describe how a single piece of equipment is controlled, this section covers the diagrams that describe how an entire building's electrical system is laid out — the drawings an RME reads before ever picking up a tool, and the drawings a PRC or local building official checks the finished installation against.
Reading a One-Line (Single-Line) Diagram
A one-line diagram represents an entire electrical distribution system — including three-phase circuits — using a single line for each conductor group instead of drawing every individual conductor. It trades physical detail for logical clarity: it shows how power flows from the utility service, through the main disconnecting means, through distribution equipment, down to the major feeders and loads, without cluttering the drawing with every wire, box, and fitting a floor plan would show.
Reading a one-line diagram is a top-to-bottom (or left-to-right) exercise in following power flow:
Utility service point — where the utility's conductors connect to the building.
Utility meter.
Main disconnecting means — the service disconnect and its overcurrent protection.
Distribution equipment — switchboards, distribution panelboards, or motor control centers fed from the main.
Sub-feeders — conductors leaving distribution equipment toward branch panelboards, transformers, or large individual loads.
Branch panelboards and major loads — where feeders terminate at final overcurrent protection or connect directly to equipment such as large motors or generators.
An RME uses a one-line diagram to verify that overcurrent device ratings, conductor sizes, and equipment ratings are coordinated correctly from the service down to each load — the same review a PRC-registered electrical engineer would rely on when specifying the system, and the same drawing a building inspector references during a rough-in or final inspection.
Standard One-Line Diagram Symbols
- Symbol Represents
- Circle with two loops or "windings" Transformer
- Rectangle with a diagonal or an "X" Circuit breaker
- Small zig-zag line, or a triangle pointing to a line Fuse
- A line crossed by an angled blade Disconnect switch
- Circle containing "M" Motor
- Circle containing "G" Generator
- Three short parallel lines decreasing in length Ground / grounding electrode connection
Because different design offices use slightly different symbol libraries, every set of drawings should include a legend/symbol schedule on the cover or general-notes sheet. An RME's first move on an unfamiliar drawing set — and a habit the exam expects — is to check the legend before assuming a symbol's meaning.
Loading diagram... One-Line Diagram Power Flow
Architectural / Electrical Floor-Plan Symbols
Floor plans, unlike one-line diagrams, show the physical location of devices as they will actually be installed in the building.
- Symbol Represents
- Circle with two short parallel marks Duplex receptacle outlet
- "S" Single-pole switch
- "S3" Three-way switch
- "S4" Four-way switch
- Circle (often with an "X" or shading inside) Ceiling-mounted light outlet
- Square or circle with "J" Junction box
- Rectangle labeled "P" or "PNL" Panelboard
Arrow drawn from a device toward a panel, with a circuit number alongside it Home run — the point where a branch circuit's conductors leave the visible run and travel back to a specific panelboard and breaker
The home run arrow is one of the most exam-relevant floor-plan symbols, because it is where a floor plan and a panel schedule connect. The circuit number written beside the arrow (for example, "3-5" for circuits 3 and 5 on a shared home run) tells the reader exactly which breaker positions in which panelboard feed that run.
Conductor Counts and Hash Marks
Where several branch-circuit conductors travel together in the same raceway between two points, drawings use short perpendicular tick (hash) marks crossing the line to indicate how many individual conductors are in that run — for example, three hash marks across a line typically mean three conductors are routed together (such as two hots and a shared neutral, or a hot, a neutral, and a ground). A line drawn with no hash marks is read by the default convention stated in the drawing's legend, commonly a simple two-conductor circuit. An RME must count hash marks carefully rather than assume a run is a simple single circuit, especially on plans showing multiwire branch circuits sharing a neutral between two ungrounded conductors.
Riser Diagrams for Multi-Story Buildings
A riser diagram is a specialized one-line diagram drawn vertically to represent a multi-story building, with the service entrance at the bottom (or top) and each floor's distribution equipment shown at its corresponding level. It shows feeder sizes and routing as they rise through the building — typically through electrical closets or shafts stacked floor to floor — to each floor's distribution panelboard, and from there to that floor's branch panelboards. Riser diagrams let an RME or inspector quickly see feeder sizing and overcurrent coordination for the whole building's vertical distribution without needing a separate one-line diagram for every floor.
RME Scenarios
Tracing a home run. A finish electrician needs to identify which breaker controls a specific receptacle discovered dead during a service call. Reading the floor plan, the RME follows the visible branch-circuit wiring back to the home run arrow, notes the circuit number written beside it, and cross-references the panel schedule for the panelboard the arrow points to, confirming the exact breaker position without opening every device along the run.
Verifying as-built conditions. During a final inspection walk-through, an RME compares the approved one-line diagram against the field-installed equipment: is the installed transformer's kVA rating what the one-line specifies, does the main disconnect's ampere rating match, are sub-feeders landed on the panelboards the riser diagram shows, and has any field change — a substituted panel, an added sub-panel — been reflected as a documented as-built revision rather than left unrecorded. This comparison is a routine and heavily tested RME responsibility, because an installation that silently deviates from its approved drawings can fail inspection even when the physical work itself is sound.