Study guide

5.2 Motor Control Circuits & Overload Protection

PRC Registered Master Electrician RME

Track your progress as you read

Finished sections get a check mark.

1 Introduction

RME Licensure Examination Overview & RA 7920 Framework How to Use This Study Guide & Build Your Study Plan

2 Chapter 1: DC & AC Circuit Fundamentals

1.1 Ohm's Law & DC Circuit Calculations 1.2 Kirchhoff's Laws & Series-Parallel Network Analysis 1.3 AC Fundamentals: Sine Waves, RMS & Phase Relationships 1.4 AC Circuit Impedance, Reactance & Resonance

3 Chapter 2: AC Power, Three-Phase Systems & DC Generators

2.1 Power in AC Circuits & Power Factor 2.2 Three-Phase Systems: Wye-Delta Configurations & Calculations 2.3 DC Generators: Construction, Types & Characteristics

4 Chapter 3: DC & AC Motors and Starting Methods

3.1 DC Motors: Construction, Types & Speed Control 3.2 AC Induction Motors: Construction, Slip & Synchronous Speed 3.3 Induction Motor Starting Methods

5 Chapter 4: Synchronous Machines & Transformers

4.1 Synchronous Motors & AC Generators (Alternators) 4.2 Transformers: Construction, Turns Ratio & Types 4.3 Transformer Losses, Efficiency, Cooling & Connections

6 Chapter 5: Motor Starters, Control Circuits & Overcurrent Devices

5.1 Motor Starters: DOL, Star-Delta & Autotransformer Starting 5.2 Motor Control Circuits & Overload Protection 5.3 Fuses & Circuit Breakers: Types, Ratings & Applications

7 Chapter 6: Control Devices & Electrical Components

6.1 Contactors, Relays & Other Control Devices 6.2 Electrical Components: Capacitors, Inductors & Resistors 6.3 Semiconductor Devices & Basic Solid-State Components

8 Chapter 7: Maintenance, Test Equipment & RA 7920 Law

7.1 Maintenance & Troubleshooting Practices 7.2 Test Equipment & Electrical Instruments 7.3 RA 7920: RME Law, Scope of Practice & PRC Regulation

9 Chapter 8: PEC Foundations: Scope & General Requirements

8.1 PEC Scope, Definitions & Code Organization (Part 1 vs Part 2) 8.2 General Installation Requirements & Working Space 8.3 Conductor Sizing, Ampacity & Derating 8.4 Overcurrent Protection & Conductor Protection Coordination

10 Chapter 9: Load Calculations & Wiring Methods

9.1 Voltage Drop & Continuous Load Calculations 9.2 Feeders, Load Calculations & Demand Factors 9.3 Wiring Methods: Raceways & Conduit Systems

11 Chapter 10: Cable Systems, Boxes & Wiring Devices

10.1 Wiring Methods: Cable Systems & Flexible Wiring 10.2 Boxes, Enclosures & Fittings 10.3 Wiring Devices, Receptacles & GFCI Protection

12 Chapter 11: Branch Circuits & Services

11.1 Branch Circuits & Multiwire Branch Circuits 11.2 Services & Service Equipment 11.3 Grounding: System & Equipment Grounding

13 Chapter 12: Bonding, Panelboards & Motor Wiring

12.1 Bonding & Grounding Electrode Systems 12.2 Panelboards & Switchboards 12.3 Motor & Generator Wiring, Protection & Disconnects

14 Chapter 13: Motor-Starter Diagrams & Hazardous Locations

13.1 Motor-Starter Wiring Diagrams & Control Symbols 13.2 One-Line Diagrams, Drawing Symbols & Wiring Plans 13.3 Hazardous (Classified) Locations

15 Chapter 14: Special Occupancies, Conditions & Safety

14.1 Special Occupancies (Wet/Damp Locations, Underground Wiring) 14.2 Special Conditions: Emergency Systems & Communications Wiring 14.3 Electrical Safety, PPE & Code-Mandated Working Clearances

16 Chapter 15: Final Review & Next Steps

15.1 RME Exam Strategy, Time Management & Test-Day Tips 15.2 After Passing: PRC Registration, CPD Renewal & Career Paths

5.2 Motor Control Circuits & Overload Protection

Key Takeaways Explain This Topic AI

A motor starter has two separate circuits: the power circuit, which carries full motor current, and the control circuit, which carries only the small current needed to operate the contactor coil.

Basic control-circuit elements include a normally open START pushbutton, a normally closed STOP pushbutton, a seal-in (holding) auxiliary contact, and pilot lights that indicate run or trip status.

A thermal overload relay protects against sustained overcurrent — not short circuits — by sensing motor current through heater elements and tripping on an inverse time-current curve.

Overload relays are sized from the motor's nameplate full-load current (FLA) and service factor, typically set between about 115% and 125% of FLA depending on the motor's thermal margin.

Electrical interlocking (cross-wired normally closed auxiliary contacts) and mechanical interlocking (a physical linkage) both prevent two contactors, such as forward and reverse, from closing at the same time.

Last updated: July 2026

Power Circuit vs. Control Circuit

Every motor starter contains two electrically separate circuits that a Registered Master Electrician must be able to tell apart on a wiring diagram:

Power circuit — Carries the full motor current, from line through the contactor's main contacts and the overload relay's current-sensing elements to the motor. Conductors are sized for the motor's full-load current (FLA); this is the circuit covered in 5.1's DOL, star-delta, and autotransformer wiring.

Control circuit — Carries only the small current (often well under 1 A) needed to energize the contactor coil. It may run at line voltage or, more commonly on larger equipment, at a reduced voltage — commonly 24 V or 120 V — supplied by a control transformer stepped down from the power circuit. Conductors here are sized for the coil and pilot-device load, not for motor current.

Mixing these two up on a diagram is a common exam trap: the pushbuttons and pilot lights of the control circuit never carry the motor's running current, no matter how large the motor is.

Basic Control-Circuit Elements

A standard control circuit for a DOL starter contains:

START pushbutton — normally open (NO); pressing it momentarily completes the coil circuit.

STOP pushbutton — normally closed (NC); pressing it opens the coil circuit and drops out the contactor. STOP is wired in series ahead of START so that a stop command always overrides a start command.

Seal-in (holding) contact — an auxiliary NO contact on the contactor itself, wired in parallel with the START pushbutton. Once the contactor picks up, this contact closes and holds the coil circuit energized after the operator releases START — this is why a momentary pushbutton can start a motor that then keeps running.

Overload contact — a normally closed auxiliary contact from the overload relay, wired in series in the coil circuit, described in more detail below.

Pilot lights — typically a RUN light wired across the seal-in contact (or an auxiliary contact) to show the motor is running, and sometimes a separate TRIPPED or fault light wired from the overload relay's alarm contact.

Thermal Overload Relays: How They Protect the Motor

A thermal overload relay protects the motor winding insulation from damage caused by sustained overcurrent — a jammed conveyor, a partially seized bearing, single-phasing, or simply an undersized motor for its load. It does this by continuously sensing motor current, most commonly through small heater elements connected in series with each phase in the power circuit. As current flows through a heater, it heats a bimetallic strip (or, in electronic overload relays, a current sensor feeds a microprocessor that models the same heating behavior). The hotter the strip gets, the more it bends, until — at a current and time combination set by the relay's design — it trips a normally closed contact in the control circuit, dropping out the contactor coil.

This is fundamentally a time-current response, not an instantaneous one: a small overcurrent takes a long time to trip the relay, while a large overcurrent trips it quickly. Overload relays are rated by trip class — Class 10, 20, or 30 — indicating the maximum number of seconds the relay allows before tripping at 6× the relay's current setting. Class 10 trips fastest (within about 10 seconds), suiting motors with little thermal margin; Class 20 and Class 30 allow progressively longer starting times for high-inertia loads such as large fans or crushers.

Sizing an overload relay starts from the motor nameplate full-load current (FLA) , never from horsepower alone. Where the nameplate service factor is 1.15 or higher (or the motor is marked for no more than 40°C temperature rise), overload relays are commonly set up to about 125% of FLA; motors with a 1.0 service factor or less thermal margin are typically set closer to 115% of FLA. Setting the relay too low causes nuisance tripping during normal operation; setting it too high defeats the protection and risks cooking the winding insulation long before the relay ever trips.

Overload Protection vs. Short-Circuit Protection

It is critical not to confuse these two protection functions:

  • Overload Protection Short-Circuit / Fault Protection
  • Device Thermal or electronic overload relay Fuse or circuit breaker (see 5.3)

Guards against Sustained overcurrent from mechanical overload, a stalled rotor, or single-phasing Sudden, very large fault currents from a short circuit or ground fault

  • Response speed Slow, time-delayed — seconds to minutes Fast, often within a fraction of a second
  • Typical trip current About 1.15–1.25× FLA and up Many times FLA — fault-level currents

An overload relay is deliberately slow so that it can ride through normal starting inrush without tripping; it is not built to interrupt a short-circuit-level fault safely, and it carries no interrupting rating for that purpose. That job belongs to the fuse or breaker upstream, sized and rated for interrupting fault current — the subject of the next section.

Interlocking

Interlocking prevents a control action that would create an unsafe or damaging condition — most commonly, preventing a forward contactor and a reverse contactor from closing at the same time, which would short two line phases together through both sets of contacts. Two forms are used, often together:

Electrical interlock — a normally closed auxiliary contact from the forward contactor is wired in series with the reverse contactor's coil circuit, and vice versa. If forward is engaged, its auxiliary contact opens the reverse coil circuit, so reverse simply cannot pick up until forward drops out.

Mechanical interlock — a physical lever or latch links the two contactors so that if one is mechanically closed, it blocks the armature of the other from closing, regardless of what the control wiring is doing.

Reversing starters, and any application with two contactors that must never close together, use both electrical and mechanical interlocking as a belt-and-suspenders safeguard — one protects against a wiring fault, the other against a welded or stuck contact that electrical logic alone could not catch.