Study guide
3.3 Induction Motor Starting Methods
PRC Registered Master Electrician RME
Track your progress as you read
Finished sections get a check mark.
1 Introduction
RME Licensure Examination Overview & RA 7920 Framework How to Use This Study Guide & Build Your Study Plan
2 Chapter 1: DC & AC Circuit Fundamentals
1.1 Ohm's Law & DC Circuit Calculations 1.2 Kirchhoff's Laws & Series-Parallel Network Analysis 1.3 AC Fundamentals: Sine Waves, RMS & Phase Relationships 1.4 AC Circuit Impedance, Reactance & Resonance
3 Chapter 2: AC Power, Three-Phase Systems & DC Generators
2.1 Power in AC Circuits & Power Factor 2.2 Three-Phase Systems: Wye-Delta Configurations & Calculations 2.3 DC Generators: Construction, Types & Characteristics
4 Chapter 3: DC & AC Motors and Starting Methods
3.1 DC Motors: Construction, Types & Speed Control 3.2 AC Induction Motors: Construction, Slip & Synchronous Speed 3.3 Induction Motor Starting Methods
5 Chapter 4: Synchronous Machines & Transformers
4.1 Synchronous Motors & AC Generators (Alternators) 4.2 Transformers: Construction, Turns Ratio & Types 4.3 Transformer Losses, Efficiency, Cooling & Connections
6 Chapter 5: Motor Starters, Control Circuits & Overcurrent Devices
5.1 Motor Starters: DOL, Star-Delta & Autotransformer Starting 5.2 Motor Control Circuits & Overload Protection 5.3 Fuses & Circuit Breakers: Types, Ratings & Applications
7 Chapter 6: Control Devices & Electrical Components
6.1 Contactors, Relays & Other Control Devices 6.2 Electrical Components: Capacitors, Inductors & Resistors 6.3 Semiconductor Devices & Basic Solid-State Components
8 Chapter 7: Maintenance, Test Equipment & RA 7920 Law
7.1 Maintenance & Troubleshooting Practices 7.2 Test Equipment & Electrical Instruments 7.3 RA 7920: RME Law, Scope of Practice & PRC Regulation
9 Chapter 8: PEC Foundations: Scope & General Requirements
8.1 PEC Scope, Definitions & Code Organization (Part 1 vs Part 2) 8.2 General Installation Requirements & Working Space 8.3 Conductor Sizing, Ampacity & Derating 8.4 Overcurrent Protection & Conductor Protection Coordination
10 Chapter 9: Load Calculations & Wiring Methods
9.1 Voltage Drop & Continuous Load Calculations 9.2 Feeders, Load Calculations & Demand Factors 9.3 Wiring Methods: Raceways & Conduit Systems
11 Chapter 10: Cable Systems, Boxes & Wiring Devices
10.1 Wiring Methods: Cable Systems & Flexible Wiring 10.2 Boxes, Enclosures & Fittings 10.3 Wiring Devices, Receptacles & GFCI Protection
12 Chapter 11: Branch Circuits & Services
11.1 Branch Circuits & Multiwire Branch Circuits 11.2 Services & Service Equipment 11.3 Grounding: System & Equipment Grounding
13 Chapter 12: Bonding, Panelboards & Motor Wiring
12.1 Bonding & Grounding Electrode Systems 12.2 Panelboards & Switchboards 12.3 Motor & Generator Wiring, Protection & Disconnects
14 Chapter 13: Motor-Starter Diagrams & Hazardous Locations
13.1 Motor-Starter Wiring Diagrams & Control Symbols 13.2 One-Line Diagrams, Drawing Symbols & Wiring Plans 13.3 Hazardous (Classified) Locations
15 Chapter 14: Special Occupancies, Conditions & Safety
14.1 Special Occupancies (Wet/Damp Locations, Underground Wiring) 14.2 Special Conditions: Emergency Systems & Communications Wiring 14.3 Electrical Safety, PPE & Code-Mandated Working Clearances
16 Chapter 15: Final Review & Next Steps
15.1 RME Exam Strategy, Time Management & Test-Day Tips 15.2 After Passing: PRC Registration, CPD Renewal & Career Paths
3.3 Induction Motor Starting Methods
Key Takeaways Explain This Topic AI
Large induction motors need reduced-voltage starting because locked-rotor current (6-8x FLA) causes utility voltage dips and mechanical/thermal stress on the motor and driven equipment.
Direct-On-Line (DOL) starting applies full voltage and delivers full starting torque and current; it is acceptable only for small motors whose inrush does not disturb the system.
Star-delta starting reduces winding voltage to about 58% of line voltage, cutting both starting current and starting torque to roughly one-third of DOL — suitable only for loads that start unloaded or lightly loaded.
Autotransformer starting uses selectable voltage taps to tune the starting current/torque trade-off and reduces line current more effectively than star-delta at a comparable torque, at the cost of bulkier, more expensive equipment.
Transitioning a star-delta starter to the delta (run) connection too early — before the motor nears rated speed — causes a second large transient current and torque spike.
Last updated: July 2026
Induction Motor Starting Methods
Small induction motors can generally be switched directly across the supply line without issue, but as motor size (horsepower) increases, the current drawn at starting becomes a serious problem. This section covers why large induction motors need reduced-voltage starting and reviews the three starting methods most relevant to the RME exam: Direct-On-Line (DOL), star-delta, and autotransformer starting.
Why Large Motors Need Reduced-Voltage Starting
At the instant of starting, an induction motor's rotor is stationary, so slip = 1 (100%) and the rotor behaves electrically like a short-circuited transformer secondary. This produces locked-rotor current — commonly six to eight times the motor's full-load amps (FLA) — flowing until the rotor accelerates and the effective rotor impedance rises, reducing current draw. For a small motor, this brief high current is easily tolerated by the supply system. For a large motor, however, this inrush current creates several problems:
Voltage dip on the supply system — a large sudden current draw causes a voltage sag that can dim lighting, disturb sensitive electronic equipment, and momentarily affect other motors and loads on the same feeder or nearby utility transformer.
Mechanical stress — the sudden torque surge as the motor accelerates can shock-load couplings, belts, gearboxes, and the driven equipment itself, accelerating wear or causing damage.
Electrical/thermal stress — repeated full-voltage starting subjects windings to high thermal and electromagnetic stress from the strong starting currents, shortening insulation life over many starts.
Utility demand and code requirements — power utilities, and the Philippine Electrical Code (PEC) that the RME exam draws on, often place limits on the starting current a large motor may impose on the distribution system, effectively requiring reduced-voltage starting above a given horsepower threshold so other customers on the same feeder are not disturbed.
Direct-On-Line (DOL) Starting
Direct-On-Line (DOL) starting , also called "across-the-line" starting, connects the motor directly to full line voltage through a contactor, with no voltage reduction at all. It is the simplest and least expensive starting method, requiring only a contactor and overload relay, and it delivers the motor's full starting torque. DOL starting is acceptable for small motors, where the resulting inrush current is small enough in absolute terms that it does not meaningfully disturb the supply system or overstress the driven load, and it remains the default starting method whenever motor size and supply capacity allow it.
Star-Delta (Wye-Delta) Starting
Star-delta starting , also called wye-delta starting, is used on motors whose windings are designed to run normally in a delta configuration at line voltage. During starting, the windings are temporarily reconfigured into a star (wye) connection, which places only 1/root-3 (about 58%) of line voltage across each winding. Because starting current is roughly proportional to applied voltage and starting torque is roughly proportional to the square of applied voltage, this reduced voltage during the star connection cuts the line starting current to roughly one-third of the DOL value — but it also cuts starting torque to roughly one-third of the DOL value. This is the central trade-off of star-delta starting: a large reduction in starting current comes at the cost of a proportionally larger reduction in starting torque, so star-delta starting is only suitable for loads that start with little or no torque demand, such as centrifugal pumps and fans, and is a poor choice for loads that must start already loaded, such as loaded conveyors or crushers.
Transition timing matters: after a preset time, or when the motor approaches roughly 75% to 80% of rated speed, a timer or speed-sensing control switches the windings from star to delta so the motor runs at full line voltage. If this transition happens too early, before the motor has built up sufficient speed, the sudden reconnection to full voltage causes a second large transient current spike and mechanical shock, as the motor is effectively subjected to a second "start" from partial speed. Simple open-transition starters briefly disconnect the motor during the changeover, which worsens this transient; closed-transition starters use transition resistors to bridge the switch and reduce the current spike.
Autotransformer Starting
Autotransformer starting uses a three-phase autotransformer with multiple selectable taps, commonly 50%, 65%, and 80% of line voltage, to apply a reduced voltage to the motor terminals during starting, then switches the motor to full line voltage once it has accelerated. Because the autotransformer's turns ratio reduces current on the supply side by roughly the square of the voltage tap ratio, while the motor itself only "sees" a current reduction proportional to the tap ratio, autotransformer starting can achieve a lower line current draw for a given starting torque than star-delta starting provides at a comparable torque level. Its practical advantages over star-delta are the selectable taps, which let an installer tune the trade-off between starting current and starting torque to match the specific motor and load, and compatibility with motors that are not built with six leads for a star-delta transition. The trade-offs are a bulkier, heavier, and considerably more expensive piece of equipment than a simple star-delta or DOL starter.
Table 3.2 — Comparison of Starting Methods
Starting Method Relative Starting (Line) Current Relative Starting Torque Complexity / Cost Typical Application
Direct-On-Line (DOL) 100% (full locked-rotor current, ~6-8x FLA) 100% Low - simple contactor and overload relay Small motors where inrush is tolerable
Star-Delta (Wye-Delta) ~33% of DOL ~33% of DOL Moderate - needs a 6-lead motor, timer, and multiple contactors Medium/large motors starting unloaded, e.g. fans, centrifugal pumps
Autotransformer ~40-80% of DOL (tap-selectable, reduced by roughly the square of the tap ratio) ~40-80% of DOL (tap-dependent) High - bulky, costly autotransformer with multiple taps Larger motors needing a tunable balance of current and torque, or higher-inertia/higher-torque loads
Understanding this trade-off — lower starting current always comes paired with lower starting torque, whichever reduced-voltage method is chosen — is essential for correctly answering RME exam questions on motor starting selection.