Study guide

4.3 Transformer Losses, Efficiency, Cooling & Connections

PRC Registered Master Electrician RME

Track your progress as you read

Finished sections get a check mark.

1 Introduction

RME Licensure Examination Overview & RA 7920 Framework How to Use This Study Guide & Build Your Study Plan

2 Chapter 1: DC & AC Circuit Fundamentals

1.1 Ohm's Law & DC Circuit Calculations 1.2 Kirchhoff's Laws & Series-Parallel Network Analysis 1.3 AC Fundamentals: Sine Waves, RMS & Phase Relationships 1.4 AC Circuit Impedance, Reactance & Resonance

3 Chapter 2: AC Power, Three-Phase Systems & DC Generators

2.1 Power in AC Circuits & Power Factor 2.2 Three-Phase Systems: Wye-Delta Configurations & Calculations 2.3 DC Generators: Construction, Types & Characteristics

4 Chapter 3: DC & AC Motors and Starting Methods

3.1 DC Motors: Construction, Types & Speed Control 3.2 AC Induction Motors: Construction, Slip & Synchronous Speed 3.3 Induction Motor Starting Methods

5 Chapter 4: Synchronous Machines & Transformers

4.1 Synchronous Motors & AC Generators (Alternators) 4.2 Transformers: Construction, Turns Ratio & Types 4.3 Transformer Losses, Efficiency, Cooling & Connections

6 Chapter 5: Motor Starters, Control Circuits & Overcurrent Devices

5.1 Motor Starters: DOL, Star-Delta & Autotransformer Starting 5.2 Motor Control Circuits & Overload Protection 5.3 Fuses & Circuit Breakers: Types, Ratings & Applications

7 Chapter 6: Control Devices & Electrical Components

6.1 Contactors, Relays & Other Control Devices 6.2 Electrical Components: Capacitors, Inductors & Resistors 6.3 Semiconductor Devices & Basic Solid-State Components

8 Chapter 7: Maintenance, Test Equipment & RA 7920 Law

7.1 Maintenance & Troubleshooting Practices 7.2 Test Equipment & Electrical Instruments 7.3 RA 7920: RME Law, Scope of Practice & PRC Regulation

9 Chapter 8: PEC Foundations: Scope & General Requirements

8.1 PEC Scope, Definitions & Code Organization (Part 1 vs Part 2) 8.2 General Installation Requirements & Working Space 8.3 Conductor Sizing, Ampacity & Derating 8.4 Overcurrent Protection & Conductor Protection Coordination

10 Chapter 9: Load Calculations & Wiring Methods

9.1 Voltage Drop & Continuous Load Calculations 9.2 Feeders, Load Calculations & Demand Factors 9.3 Wiring Methods: Raceways & Conduit Systems

11 Chapter 10: Cable Systems, Boxes & Wiring Devices

10.1 Wiring Methods: Cable Systems & Flexible Wiring 10.2 Boxes, Enclosures & Fittings 10.3 Wiring Devices, Receptacles & GFCI Protection

12 Chapter 11: Branch Circuits & Services

11.1 Branch Circuits & Multiwire Branch Circuits 11.2 Services & Service Equipment 11.3 Grounding: System & Equipment Grounding

13 Chapter 12: Bonding, Panelboards & Motor Wiring

12.1 Bonding & Grounding Electrode Systems 12.2 Panelboards & Switchboards 12.3 Motor & Generator Wiring, Protection & Disconnects

14 Chapter 13: Motor-Starter Diagrams & Hazardous Locations

13.1 Motor-Starter Wiring Diagrams & Control Symbols 13.2 One-Line Diagrams, Drawing Symbols & Wiring Plans 13.3 Hazardous (Classified) Locations

15 Chapter 14: Special Occupancies, Conditions & Safety

14.1 Special Occupancies (Wet/Damp Locations, Underground Wiring) 14.2 Special Conditions: Emergency Systems & Communications Wiring 14.3 Electrical Safety, PPE & Code-Mandated Working Clearances

16 Chapter 15: Final Review & Next Steps

15.1 RME Exam Strategy, Time Management & Test-Day Tips 15.2 After Passing: PRC Registration, CPD Renewal & Career Paths

4.3 Transformer Losses, Efficiency, Cooling & Connections

Key Takeaways Explain This Topic AI

Core (iron) losses — hysteresis plus eddy-current losses — stay roughly constant with load, while copper (I²R) losses rise with the square of load current

Transformer efficiency = output power divided by input power (output plus core loss plus copper loss); maximum efficiency occurs when copper loss equals core loss

Oil-immersed transformers dissipate heat more effectively than dry-type (air-cooled) units, allowing a higher current rating for a given physical size

Cooling capacity directly sets a transformer's nameplate kVA rating — blocked or degraded cooling forces a real-world derating

Delta-wye is the standard connection for utility distribution transformers because the grounded wye secondary supplies a neutral while the delta primary blocks ground-fault propagation

Last updated: July 2026

  • 4.3 Transformer Losses, Efficiency, Cooling & Connections
  • Core Losses vs. Copper Losses

Every real transformer wastes some input energy as heat rather than delivering it all to the load. These losses fall into two distinct categories that behave very differently with load, and a master electrician must be able to tell them apart to correctly size, load, and troubleshoot a transformer.

Core losses (also called iron losses ) occur in the magnetic core itself and consist of two components:

Hysteresis loss — energy consumed repeatedly magnetizing and demagnetizing the core material as the AC flux reverses direction every half-cycle. It depends on the area of the core material's B-H hysteresis loop and on frequency; using high-grade silicon steel with a narrow hysteresis loop minimizes this loss.

Eddy-current loss — circulating currents induced directly in the conductive core material by the changing flux (the same Faraday's-law mechanism that induces voltage in the windings). These circulating currents dissipate energy as I²R heat inside the core itself. Building the core from thin laminations, each insulated with a thin varnish or oxide coating, breaks up the conductive path and sharply reduces eddy-current loss compared to a solid iron core.

Core losses depend only on the applied voltage and frequency — both essentially fixed at rated conditions — so core losses are present continuously whenever the transformer is energized, whether or not it is supplying any load. For this reason, core losses are called constant losses (or no-load losses), and they can be measured directly with an open-circuit test .

Copper losses (also called I²R losses ) are the resistive heating losses in the primary and secondary winding conductors. Because load current flows through both windings, copper losses rise with the square of the load current — double the load current and copper losses quadruple. Copper losses are therefore called variable losses , and they are measured with a short-circuit test .

  • Loss Type Also Called Cause Behavior with Load
  • Core loss Iron loss, no-load loss Hysteresis + eddy currents in the core Roughly constant at all loads
  • Copper loss I²R loss, load loss Winding resistance heating Increases with the square of load current

This distinction matters directly for loading decisions: a lightly loaded transformer wastes proportionally more energy on constant core losses relative to its useful output, while a heavily overloaded transformer suffers rapidly escalating copper losses (and winding heating) that can shorten insulation life well before the nameplate current is exceeded.

Efficiency

Efficiency is the ratio of useful output power delivered to the load, divided by the total input power drawn from the source, expressed as a percentage:

  • Efficiency (%) = (Output Power / Input Power) × 100 = [Output / (Output + Core Loss + Copper Loss)] × 100
  • Worked Example

A distribution transformer delivers 90 kW to its connected load at full rated capacity. At that load, the core loss is 1 kW and the copper loss is 2 kW.

  • Input power = Output + losses = 90 + 1 + 2 = 93 kW
  • Efficiency = (90 / 93) × 100 = 96.77%

Because core loss stays essentially fixed while copper loss grows with the square of load, a transformer's efficiency actually peaks at a specific load point — maximum efficiency occurs at the load where copper loss equals core loss — not necessarily at full rated load. This is a useful design fact: utilities try to size distribution transformers so their typical daily loading sits near this maximum-efficiency point rather than at either extreme.

Cooling Methods

The rate at which a transformer can safely dissipate its core and copper losses as heat directly determines its continuous current-carrying capacity — the nameplate kVA rating . Two broad cooling families are in common use:

Dry-type (air-cooled) transformers rely on natural or forced air circulation over the windings and core, with no liquid coolant. Self-cooled dry-type units are commonly designated AA (air natural, air natural); some add fans for forced-air cooling ( AFA ) to boost their rating. Dry-type units are favored indoors — in commercial and institutional buildings, electrical rooms, and near occupied spaces — because they eliminate the fire and spill risk of liquid coolant, at the cost of a somewhat lower current-carrying capacity for a given physical size compared to oil-immersed units.

Oil-immersed (liquid-filled) transformers submerge the core and windings in mineral oil (or a less-flammable synthetic/natural ester fluid), which serves double duty as both an electrical insulator and a coolant. Because oil circulates heat away far more effectively than air, oil-immersed units can carry substantially more current for a given size than a comparable dry-type unit — common designations include ONAN (oil natural, air natural), ONAF (oil natural, air forced, using fans on the radiators), and OFAF (oil forced, air forced, using pumps and fans). Oil-immersed transformers dominate outdoor utility distribution and substation power transformers, but require fire walls, containment berms, or oil-containment pits, plus periodic oil testing, because of the fire and environmental risk of a large liquid-oil inventory.

Because cooling capability sets the current a transformer can carry without overheating its insulation, undersized or obstructed cooling (blocked vents, low oil level, failed cooling fans) forces a real-world derating of the nameplate kVA — a practical field consideration for a master electrician sizing or troubleshooting a transformer installation.

Three-Phase Connections

Three single-phase transformers (or the three windings of one three-phase unit) can be connected on each side in either a wye (star) or delta configuration, giving four common combinations:

Connection Primary Secondary Common Reason for Use

Wye-Wye (Y-Y) Wye Wye Provides a neutral on both sides for 4-wire service, but prone to third-harmonic voltage distortion and neutral instability unless a grounded neutral or tertiary winding is added

Delta-Delta (Δ-Δ) Delta Delta No neutral needed by the load; can keep running at reduced (about 58%) capacity in an open-delta configuration if one unit fails, favored for industrial 3-wire power supplies

Wye-Delta (Y-Δ) Wye Delta Common at the sending end of a step-down line — the grounded wye primary gives a stable path to ground for lightning and fault protection and simplifies system grounding, while the delta secondary supplies 3-wire industrial power with no neutral needed

Delta-Wye (Δ-Y) Delta Wye The standard connection for utility distribution transformers serving mixed loads — the grounded wye secondary provides a neutral for single-phase, line-to-neutral loads (lighting, receptacles), while the ungrounded delta primary blocks the propagation of secondary ground faults back into the primary system and suppresses third-harmonic currents

For a master electrician, the delta-wye connection is the one most frequently encountered in the field: it is the standard configuration for pole-mounted and pad-mounted distribution transformers that step utility primary voltage down to a grounded, neutral-bearing secondary serving ordinary building loads.