Study guide

14.2 Psychrometrics & Air Conditioning Systems

PRC Mechanical Engineer Licensure Examination MELE

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Licensing Overview, Law & Professional Ethics

1.1 MELE Facts, RA 8495 & Board Organization 1.2 Code of Ethics for Mechanical Engineers & Professional Practice 1.3 Philippine Mechanical Engineering Code (PME Code) Governance & Legal Mandates

2 Chapter 2: Advanced Mathematics & Engineering Statistics

2.1 Differential & Integral Calculus in Engineering Applications 2.2 Differential Equations & Mathematical Modeling 2.3 Applied Engineering Statistics & Quality Control Probability

3 Chapter 3: Engineering Thermodynamics

3.1 Thermodynamic State Postulate, Properties & P-V-T Equations of State 3.2 First Law Analysis for Open & Closed Thermal Systems 3.3 Second Law, Entropy, Exergy & Reversibility Analysis

4 Chapter 4: Fluid Mechanics & Hydraulic Engineering

4.1 Fluid Statics, Manometry, Hydrostatic Force & Buoyancy 4.2 Fluid Kinematics, Dynamics & Bernoulli Equation 4.3 Pipe Flow, Friction Losses & Piping Network Analysis

5 Chapter 5: Heat Transfer & Thermal Systems

5.1 Conduction Heat Transfer & Thermal Insulation Design 5.2 Natural & Forced Convection Heat Transfer Correlations 5.3 Thermal Radiation & Industrial Heat Exchanger Design

6 Chapter 6: Mechanics & Strength of Materials

6.1 Statics & Dynamics of Rigid Bodies & Engineering Linkages 6.2 Normal, Shear & Triaxial Stress-Strain Relationships 6.3 Bending Stresses, Torsion & Column Buckling Analysis

7 Chapter 7: Engineering Economics & Financial Analysis

7.1 Time Value of Money & Cash Flow Equivalence Formulas 7.2 Asset Depreciation, Taxation & Economic Evaluation Methods 7.3 Break-Even Analysis, Payback Period & EOQ Inventory Models

8 Chapter 8: Engineering Materials & Metallurgy

8.1 Ferrous & Non-Ferrous Metals, Alloys & Polymers 8.2 Phase Diagrams, Iron-Carbon System & Heat Treatment 8.3 Mechanical Testing, Fatigue Failure & Fracture Mechanics

9 Chapter 9: Machine Elements & Stress Analysis

9.1 Failure Theories, Static & Fluctuating Stress Design 9.2 Power Transmission Shafts, Keys & Rigid/Flexible Couplings 9.3 Spur, Helical, Bevel & Worm Gear Design Calculations

10 Chapter 10: Power Transmission Components

10.1 Belts, V-Belts, Chains, Wire Ropes & Flywheels 10.2 Rolling Element & Hydrodynamic Journal Bearings 10.3 Mechanical Springs, Clutches & Industrial Brakes

11 Chapter 11: Manufacturing, Fasteners & GD&T

11.1 Threaded Fasteners, Rivets & Welded Joint Analysis 11.2 Manufacturing Processes, Machine Tools & Machining Calculations 11.3 Engineering Drawing, Limits, Fits, Tolerances & GD&T

12 Chapter 12: Power Plants, Boilers & Thermal Power Cycles

12.1 Steam Power Plants & Rankine Cycles 12.2 Steam Generators, Boilers & Combustion Engineering 12.3 Internal Combustion Engines: SI & CI Cycles 12.4 Gas Turbine Power Plants & Combined Cycles

13 Chapter 13: Renewable Energy, Fluid Machinery & Plant Systems

13.1 Hydroelectric, Geothermal & Renewable Energy Power Plants 13.2 Pumps & Hydraulic Machinery 13.3 Air Compressors, Fans & Blowers

14 Chapter 14: Refrigeration, HVAC & Building Mechanical Systems

14.1 Refrigeration Systems, Cycles & Refrigerants 14.2 Psychrometrics & Air Conditioning Systems 14.3 Piping/Ductwork Design, PME Code & Industrial Safety Management

14.2 Psychrometrics & Air Conditioning Systems

Key Takeaways Explain This Topic AI

Psychrometric state parameters (DBT, WBT, DPT, RH, humidity ratio w, enthalpy h) govern air conditioning design under standard atmospheric pressure (101.325 kPa).

Specific humidity ratio is w = 0.622 * (Pv / (P - Pv)) and moist air specific enthalpy is h = 1.006 t + w (2501 + 1.805*t) in kJ/kg of dry air.

Adiabatic mixing of two air streams follows conservation of dry air mass, water vapor mass, and enthalpy: h3 = (m_a1 h1 + m_a2 h2) / (m_a1 + m_a2).

Sensible Heat Factor (SHF = RSH / TRH) dictates the slope of the room process line; cooling coil apparatus dew point (ADP) and bypass factor (BF) determine leaving air conditions.

Last updated: July 2026

14.2 Psychrometrics & Air Conditioning Systems

Psychrometrics is the branch of thermodynamic science concerned with the physical and thermal properties of moist air—a binary mixture of dry air and water vapor. In tropical climates like the Philippines, HVAC engineers must precisely evaluate psychrometric properties to calculate sensible and latent cooling loads, size cooling coils, and ensure indoor thermal comfort.

Psychrometric Parameters & Fundamental Governing Equations

At standard atmospheric pressure ( P = 101.325 kPa P = 101.325 \text{ kPa} P = 101.325 kPa at sea level), the thermodynamic state of moist air is uniquely fixed by any two independent intensive properties.

Dry-Bulb Temperature ( D B T , t DBT, t D BT , t in ∘ C ^\circ\text{C} ∘ C ): The true air temperature measured by a standard thermometer shielded from direct radiation.

Wet-Bulb Temperature ( W B T , t w b WBT, t_{wb} W BT , t w b ​ in ∘ C ^\circ\text{C} ∘ C ): The adiabatic saturation temperature measured by a thermometer covered with a water-wetted wick exposed to rapid air stream motion ( V > 4 m/s V > 4 \text{ m/s} V > 4 m/s ).

Dew-Point Temperature ( D P T , t d p DPT, t_{dp} D PT , t d p ​ in ∘ C ^\circ\text{C} ∘ C ): The saturation temperature corresponding to the partial pressure P v P_v P v ​ of water vapor. Cooling air at constant pressure below its DPT causes moisture condensation.

Partial Vapor Pressure ( P v P_v P v ​ in kPa \text{kPa} kPa ): The partial pressure exerted by water vapor molecules in moist air. Saturated vapor pressure at dry-bulb temperature t t t is designated P s a t ( t ) P_{sat}(t) P s a t ​ ( t ) or P g P_g P g ​ .

Relative Humidity ( R H , ϕ RH, \phi R H , ϕ ): The ratio of partial vapor pressure P v P_v P v ​ to saturation pressure P g P_g P g ​ at dry-bulb temperature t t t : ϕ = P v P g × 100 % \phi = \frac{P_v}{P_g} \times 100\% ϕ = P g ​ P v ​ ​ × 100%

Specific Humidity / Humidity Ratio ( ω \omega ω in kg w / kg d a \text{kg}_{w}/\text{kg}_{da} kg w ​ / kg d a ​ or g w / kg d a \text{g}_{w}/\text{kg}_{da} g w ​ / kg d a ​ ): The mass ratio of water vapor m w m_w m w ​ to dry air m a m_a m a ​ : ω = m w m a = 0.622 P v P − P v \omega = \frac{m_w}{m_a} = 0.622 \frac{P_v}{P - P_v} ω = m a ​ m w ​ ​ = 0.622 P − P v ​ P v ​ ​ where 0.622 = M w M a = 18.015 28.97 0.622 = \frac{M_w}{M_a} = \frac{18.015}{28.97} 0.622 = M a ​ M w ​ ​ = 28.97 18.015 ​ is the ratio of molecular weights of water vapor and dry air.

Specific Enthalpy ( h h h in kJ/kg d a \text{kJ/kg}_{da} kJ/kg d a ​ ): Total thermal energy of moist air per kilogram of dry air: h = c p a t + ω ( h f g , 0 + c p v t ) = 1.006 t + ω ( 2501 + 1.805 t ) ( kJ/kg d a h = c_{pa} t + \omega (h_{fg,0} + c_{pv} t) = 1.006 t + \omega (2501 + 1.805 t) \quad (\text{kJ/kg}_{da} h = c p a ​ t + ω ( h f g , 0 ​ + c p v ​ t ) = 1.006 t + ω ( 2501 + 1.805 t ) ( kJ/kg d a ​ where c p a = 1.006 kJ/kg ⋅ ∘ C c_{pa} = 1.006 \text{ kJ/kg}\cdot^\circ\text{C} c p a ​ = 1.006 kJ/kg ⋅ ∘ C , h f g , 0 = 2501 kJ/kg h_{fg,0} = 2501 \text{ kJ/kg} h f g , 0 ​ = 2501 kJ/kg (latent heat of vaporization at 0 ∘ C 0^\circ\text{C} 0 ∘ C ), and c p v = 1.805 kJ/kg ⋅ ∘ C c_{pv} = 1.805 \text{ kJ/kg}\cdot^\circ\text{C} c p v ​ = 1.805 kJ/kg ⋅ ∘ C .

Specific Volume ( v v v in m 3 / kg d a \text{m}^3/\text{kg}_{da} m 3 / kg d a ​ ): Volume of moist air mixture per unit mass of dry air: v = R a T P − P v = 0.28704 ( t + 273.15 ) P − P v ( m 3 / kg d a v = \frac{R_a T}{P - P_v} = \frac{0.28704 (t + 273.15)}{P - P_v} \quad (\text{m}^3/\text{kg}_{da} v = P − P v ​ R a ​ T ​ = P − P v ​ 0.28704 ( t + 273.15 ) ​ ( m 3 / kg d a ​

Psychrometric Parameter Symbol Unit Governing Formula Key Physical Meaning

Dry-Bulb Temperature D B T , t DBT, t D BT , t ∘ C ^\circ\text{C} ∘ C Thermometer reading Sensible heat indicator

Wet-Bulb Temperature W B T , t w b WBT, t_{wb} W BT , t w b ​ ∘ C ^\circ\text{C} ∘ C Wet-wick reading Total enthalpy indicator

Dew-Point Temperature D P T , t d p DPT, t_{dp} D PT , t d p ​ ∘ C ^\circ\text{C} ∘ C P s a t ( t d p ) = P v P_{sat}(t_{dp}) = P_v P s a t ​ ( t d p ​ ) = P v ​ Condensation onset threshold

Humidity Ratio ω \omega ω kg w / kg d a \text{kg}_w/\text{kg}_{da} kg w ​ / kg d a ​ ω = 0.622 P v P − P v \omega = 0.622 \frac{P_v}{P - P_v} ω = 0.622 P − P v ​ P v ​ ​ Absolute moisture content

Relative Humidity ϕ \phi ϕ % \% % ϕ = P v P g × 100 % \phi = \frac{P_v}{P_g} \times 100\% ϕ = P g ​ P v ​ ​ × 100% Degree of saturation

Moist Air Enthalpy h h h kJ/kg d a \text{kJ/kg}_{da} kJ/kg d a ​ h = 1.006 t + ω ( 2501 + 1.805 t ) h = 1.006 t + \omega (2501 + 1.805 t) h = 1.006 t + ω ( 2501 + 1.805 t ) Total heat content

Basic Psychrometric Processes

Sensible Heating: Horizontal movement to the right on psychrometric chart ( D B T ↑ DBT \uparrow D BT ↑ , ω = const \omega = \text{const} ω = const ). Q ˙ s = m ˙ a c p a ( t 2 − t 1 ) = m ˙ a ( 1.006 ) ( t 2 − t 1 ) ( kW ) \dot{Q}_s = \dot{m}_a c_{pa} (t_2 - t_1) = \dot{m}_a (1.006) (t_2 - t_1) \quad (\text{kW}) Q ˙ ​ s ​ = m ˙ a ​ c p a ​ ( t 2 ​ − t 1 ​ ) = m ˙ a ​ ( 1.006 ) ( t 2 ​ − t 1 ​ ) ( kW )

Sensible Cooling: Horizontal movement to the left ( D B T ↓ DBT \downarrow D BT ↓ , ω = const \omega = \text{const} ω = const ). Q ˙ s = m ˙ a c p a ( t 1 − t 2 ) ( kW ) \dot{Q}_s = \dot{m}_a c_{pa} (t_1 - t_2) \quad (\text{kW}) Q ˙ ​ s ​ = m ˙ a ​ c p a ​ ( t 1 ​ − t 2 ​ ) ( kW )

Cooling & Dehumidification: Standard tropical air conditioning process. Air passes over a cooling coil maintained below its dew point ( t surface < D P T t_{\text{surface}} < DPT t surface ​ < D PT ).

Apparatus Dew Point ( A D P ADP A D P ): Effective surface saturation temperature of the cooling coil.

Bypass Factor ( B F BF BF ): Fraction of air that passes through the coil untransformed due to imperfect contact: B F = t 2 − t A D P t 1 − t A D P = ω 2 − ω A D P ω 1 − ω A D P = h 2 − h A D P h 1 − h A D P BF = \frac{t_2 - t_{ADP}}{t_1 - t_{ADP}} = \frac{\omega_2 - \omega_{ADP}}{\omega_1 - \omega_{ADP}} = \frac{h_2 - h_{ADP}}{h_1 - h_{ADP}} BF = t 1 ​ − t A D P ​ t 2 ​ − t A D P ​ ​ = ω 1 ​ − ω A D P ​ ω 2 ​ − ω A D P ​ ​ = h 1 ​ − h A D P ​ h 2 ​ − h A D P ​ ​

Contact Factor ( C F CF CF ): Fraction of air coming into perfect contact with coil surface ( C F = 1 − B F CF = 1 - BF CF = 1 − BF ).

Adiabatic Humidification (Evaporative Cooling): Air passes through a water spray recirculated at wet-bulb temperature ( h ≈ const h \approx \text{const} h ≈ const , W B T = const WBT = \text{const} W BT = const , D B T ↓ DBT \downarrow D BT ↓ , ω ↑ \omega \uparrow ω ↑ ).

Adiabatic Mixing of Two Air Streams

In central HVAC systems, outdoor fresh air (stream 1, mass flow m ˙ a 1 \dot{m}_{a1} m ˙ a 1 ​ ) mixes adiabatically with return air from the building space (stream 2, mass flow m ˙ a 2 \dot{m}_{a2} m ˙ a 2 ​ ) to form mixed supply air (stream 3, mass flow m ˙ a 3 = m ˙ a 1 + m ˙ a 2 \dot{m}_{a3} = \dot{m}_{a1} + \dot{m}_{a2} m ˙ a 3 ​ = m ˙ a 1 ​ + m ˙ a 2 ​ ).

Mass and energy conservation yield: Dry Air Mass Balance: m ˙ a 3 = m ˙ a 1 + m ˙ a 2 \text{Dry Air Mass Balance:} \quad \dot{m}_{a3} = \dot{m}_{a1} + \dot{m}_{a2} Dry Air Mass Balance: m ˙ a 3 ​ = m ˙ a 1 ​ + m ˙ a 2 ​ Moisture Balance: m ˙ a 1 ω 1 + m ˙ a 2 ω 2 = m ˙ a 3 ω 3 \text{Moisture Balance:} \quad \dot{m}_{a1} \omega_1 + \dot{m}_{a2} \omega_2 = \dot{m}_{a3} \omega_3 Moisture Balance: m ˙ a 1 ​ ω 1 ​ + m ˙ a 2 ​ ω 2 ​ = m ˙ a 3 ​ ω 3 ​ Enthalpy Balance: m ˙ a 1 h 1 + m ˙ a 2 h 2 = m ˙ a 3 h 3 \text{Enthalpy Balance:} \quad \dot{m}_{a1} h_1 + \dot{m}_{a2} h_2 = \dot{m}_{a3} h_3 Enthalpy Balance: m ˙ a 1 ​ h 1 ​ + m ˙ a 2 ​ h 2 ​ = m ˙ a 3 ​ h 3 ​

On the psychrometric chart, state 3 lies on the straight line connecting state 1 and state 2, positioned such that: h 3 = m ˙ a 1 h 1 + m ˙ a 2 h 2 m ˙ a 1 + m ˙ a 2 , ω 3 = m ˙ a 1 ω 1 + m ˙ a 2 ω 2 m ˙ a 1 + m ˙ a 2 , t 3 ≈ m ˙ a 1 t 1 + m ˙ a 2 t 2 m ˙ a 1 + m ˙ a 2 h_3 = \frac{\dot{m}_{a1} h_1 + \dot{m}_{a2} h_2}{\dot{m}_{a1} + \dot{m}_{a2}}, \quad \omega_3 = \frac{\dot{m}_{a1} \omega_1 + \dot{m}_{a2} \omega_2}{\dot{m}_{a1} + \dot{m}_{a2}}, \quad t_3 \approx \frac{\dot{m}_{a1} t_1 + \dot{m}_{a2} t_2}{\dot{m}_{a1} + \dot{m}_{a2}} h 3 ​ = m ˙ a 1 ​ + m ˙ a 2 ​ m ˙ a 1 ​ h 1 ​ + m ˙ a 2 ​ h 2 ​ ​ , ω 3 ​ = m ˙ a 1 ​ + m ˙ a 2 ​ m ˙ a 1 ​ ω 1 ​ + m ˙ a 2 ​ ω 2 ​ ​ , t 3 ​ ≈ m ˙ a 1 ​ + m ˙ a 2 ​ m ˙ a 1 ​ t 1 ​ + m ˙ a 2 ​ t 2 ​ ​

Air Conditioning Load Calculations & SHF

Cooling load calculations account for heat gain entering the space:

Room Sensible Heat ( R S H RSH RS H ): Conduction through walls/roof/windows ( Q = U A Δ T Q = U A \Delta T Q = U A Δ T ), solar radiation through glass ( Q = A ⋅ SHGC ⋅ I Q = A \cdot \text{SHGC} \cdot I Q = A ⋅ SHGC ⋅ I ), internal lighting, equipment motors, occupant sensible heat.

Room Latent Heat ( R L H RLH R L H ): Moisture gain from human respiration and perspiration, cooking/steam equipment, water vapor infiltration.

Total Room Heat ( T R H TRH TR H ): T R H = R S H + R L H TRH = RSH + RLH TR H = RS H + R L H .

Sensible Heat Factor (SHF)

The ratio of sensible heat to total heat load determines the slope of the room process line on the psychrometric chart: RSHF = R S H R S H + R L H = R S H T R H \text{RSHF} = \frac{RSH}{RSH + RLH} = \frac{RSH}{TRH} RSHF = RS H + R L H RS H ​ = TR H RS H ​

The Grand Sensible Heat Factor ( G S H F GSHF GS H F ) includes the outdoor ventilation air load imposed directly on the cooling coil: G S H F = T S H T S H + T L H = R S H + O A S H T R H + O A L H GSHF = \frac{TSH}{TSH + TLH} = \frac{RSH + OASH}{TRH + OALH} GS H F = TS H + T L H TS H ​ = TR H + O A L H RS H + O A S H ​

ASHRAE Standard 62.1 specifies minimum outdoor air rates to maintain indoor air quality (IAQ): V o t = R p P z + R a A z V_{ot} = R_p P_{z} + R_a A_{z} V o t ​ = R p ​ P z ​ + R a ​ A z ​

where R p R_p R p ​ is outdoor airflow rate per person (L/s ⋅ \cdot ⋅ person or cfm/person), P z P_z P z ​ is zone population, R a R_a R a ​ is outdoor airflow rate per unit area (L/s ⋅ m 2 \cdot\text{m}^2 ⋅ m 2 ), and A z A_z A z ​ is zone floor area.

Step-by-Step Worked Sample Problem

Problem Statement: In a Manila commercial building central air conditioning system, outdoor ventilation air ( m ˙ a 1 = 1.0 kg/s \dot{m}_{a1} = 1.0 \text{ kg/s} m ˙ a 1 ​ = 1.0 kg/s ) at 35.0 ∘ C 35.0^\circ\text{C} 35. 0 ∘ C DBT and 27.0 ∘ C 27.0^\circ\text{C} 27. 0 ∘ C WBT ( h 1 = 85.0 kJ/kg h_1 = 85.0 \text{ kJ/kg} h 1 ​ = 85.0 kJ/kg , ω 1 = 0.0190 kg/kg \omega_1 = 0.0190 \text{ kg/kg} ω 1 ​ = 0.0190 kg/kg ) mixes adiabatically with return room air ( m ˙ a 2 = 4.0 kg/s \dot{m}_{a2} = 4.0 \text{ kg/s} m ˙ a 2 ​ = 4.0 kg/s ) at 24.0 ∘ C 24.0^\circ\text{C} 24. 0 ∘ C DBT and 50 % 50\% 50% RH ( h 2 = 48.0 kJ/kg h_2 = 48.0 \text{ kJ/kg} h 2 ​ = 48.0 kJ/kg , ω 2 = 0.0093 kg/kg \omega_2 = 0.0093 \text{ kg/kg} ω 2 ​ = 0.0093 kg/kg ).

The resulting air mixture (state 3) passes through a cooling and dehumidifying coil having an Apparatus Dew Point ( A D P ADP A D P ) of 9.0 ∘ C 9.0^\circ\text{C} 9. 0 ∘ C ( h A D P = 27.0 kJ/kg h_{ADP} = 27.0 \text{ kJ/kg} h A D P ​ = 27.0 kJ/kg , ω A D P = 0.0072 kg/kg \omega_{ADP} = 0.0072 \text{ kg/kg} ω A D P ​ = 0.0072 kg/kg ) and a Bypass Factor ( B F BF BF ) of 0.15 0.15 0.15 .

Calculate:

Total dry air mass flow rate ( m ˙ a 3 \dot{m}_{a3} m ˙ a 3 ​ ) and enthalpy ( h 3 h_3 h 3 ​ ), humidity ratio ( ω 3 \omega_3 ω 3 ​ ), and dry-bulb temperature ( t 3 t_3 t 3 ​ ) of the mixed air entering the cooling coil.

Dry-bulb temperature ( t 4 t_4 t 4 ​ ) and enthalpy ( h 4 h_4 h 4 ​ ) of air leaving the cooling coil.

Total cooling capacity of the cooling coil in kW and Tons of Refrigeration (TR).

Solution Procedure:

Step 1: Calculate mixed air state 3 properties. m ˙ a 3 = m ˙ a 1 + m ˙ a 2 = 1.0 + 4.0 = 5.0 kg/s \dot{m}_{a3} = \dot{m}_{a1} + \dot{m}_{a2} = 1.0 + 4.0 = 5.0 \text{ kg/s} m ˙ a 3 ​ = m ˙ a 1 ​ + m ˙ a 2 ​ = 1.0 + 4.0 = 5.0 kg/s Enthalpy h 3 = m ˙ a 1 h 1 + m ˙ a 2 h 2 m ˙ a 3 = 1.0 ( 85.0 ) + 4.0 ( 48.0 ) 5.0 = 85.0 + 192.0 5.0 = 55.4 kJ/kg \text{Enthalpy } h_3 = \frac{\dot{m}_{a1} h_1 + \dot{m}_{a2} h_2}{\dot{m}_{a3}} = \frac{1.0(85.0) + 4.0(48.0)}{5.0} = \frac{85.0 + 192.0}{5.0} = 55.4 \text{ kJ/kg} Enthalpy h 3 ​ = m ˙ a 3 ​ m ˙ a 1 ​ h 1 ​ + m ˙ a 2 ​ h 2 ​ ​ = 5.0 1.0 ( 85.0 ) + 4.0 ( 48.0 ) ​ = 5.0 85.0 + 192.0 ​ = 55.4 kJ/kg Humidity Ratio ω 3 = 1.0 ( 0.0190 ) + 4.0 ( 0.0093 ) 5.0 = 0.0190 + 0.0372 5.0 = 0.01124 kg/kg \text{Humidity Ratio } \omega_3 = \frac{1.0(0.0190) + 4.0(0.0093)}{5.0} = \frac{0.0190 + 0.0372}{5.0} = 0.01124 \text{ kg/kg} Humidity Ratio ω 3 ​ = 5.0 1.0 ( 0.0190 ) + 4.0 ( 0.0093 ) ​ = 5.0 0.0190 + 0.0372 ​ = 0.01124 kg/kg Dry-Bulb Temp t 3 ≈ 1.0 ( 35.0 ) + 4.0 ( 24.0 ) 5.0 = 35.0 + 96.0 5.0 = 26.2 ∘ C \text{Dry-Bulb Temp } t_3 \approx \frac{1.0(35.0) + 4.0(24.0)}{5.0} = \frac{35.0 + 96.0}{5.0} = 26.2^\circ\text{C} Dry-Bulb Temp t 3 ​ ≈ 5.0 1.0 ( 35.0 ) + 4.0 ( 24.0 ) ​ = 5.0 35.0 + 96.0 ​ = 26. 2 ∘ C

Step 2: Calculate coil leaving air state 4 properties using Bypass Factor ( B F = 0.15 BF = 0.15 BF = 0.15 ). B F = t 4 − t A D P t 3 − t A D P ⟹ t 4 = t A D P + B F ( t 3 − t A D P ) BF = \frac{t_4 - t_{ADP}}{t_3 - t_{ADP}} \implies t_4 = t_{ADP} + BF(t_3 - t_{ADP}) BF = t 3 ​ − t A D P ​ t 4 ​ − t A D P ​ ​ ⟹ t 4 ​ = t A D P ​ + BF ( t 3 ​ − t A D P ​ ) t 4 = 9.0 + 0.15 × ( 26.2 − 9.0 ) = 9.0 + 0.15 × 17.2 = 9.0 + 2.58 = 11.58 ∘ C t_4 = 9.0 + 0.15 \times (26.2 - 9.0) = 9.0 + 0.15 \times 17.2 = 9.0 + 2.58 = 11.58^\circ\text{C} t 4 ​ = 9.0 + 0.15 × ( 26.2 − 9.0 ) = 9.0 + 0.15 × 17.2 = 9.0 + 2.58 = 11.5 8 ∘ C B F = h 4 − h A D P h 3 − h A D P ⟹ h 4 = h A D P + B F ( h 3 − h A D P ) BF = \frac{h_4 - h_{ADP}}{h_3 - h_{ADP}} \implies h_4 = h_{ADP} + BF(h_3 - h_{ADP}) BF = h 3 ​ − h A D P ​ h 4 ​ − h A D P ​ ​ ⟹ h 4 ​ = h A D P ​ + BF ( h 3 ​ − h A D P ​ ) h 4 = 27.0 + 0.15 × ( 55.4 − 27.0 ) = 27.0 + 0.15 × 28.4 = 27.0 + 4.26 = 31.26 kJ/kg h_4 = 27.0 + 0.15 \times (55.4 - 27.0) = 27.0 + 0.15 \times 28.4 = 27.0 + 4.26 = 31.26 \text{ kJ/kg} h 4 ​ = 27.0 + 0.15 × ( 55.4 − 27.0 ) = 27.0 + 0.15 × 28.4 = 27.0 + 4.26 = 31.26 kJ/kg

Step 3: Calculate total cooling coil capacity ( Q ˙ coil \dot{Q}_{\text{coil}} Q ˙ ​ coil ​ ). Q ˙ coil = m ˙ a 3 ( h 3 − h 4 ) = 5.0 kg/s × ( 55.4 − 31.26 ) kJ/kg = 5.0 × 24.14 = 120.70 kW \dot{Q}_{\text{coil}} = \dot{m}_{a3} (h_3 - h_4) = 5.0 \text{ kg/s} \times (55.4 - 31.26) \text{ kJ/kg} = 5.0 \times 24.14 = 120.70 \text{ kW} Q ˙ ​ coil ​ = m ˙ a 3 ​ ( h 3 ​ − h 4 ​ ) = 5.0 kg/s × ( 55.4 − 31.26 ) kJ/kg = 5.0 × 24.14 = 120.70 kW

Step 4: Convert cooling capacity to Tons of Refrigeration (TR). Capacity in TR = 120.70 kW 3.517 kW/TR = 34.32 TR \text{Capacity in TR} = \frac{120.70 \text{ kW}}{3.517 \text{ kW/TR}} = 34.32 \text{ TR} Capacity in TR = 3.517 kW/TR 120.70 kW ​ = 34.32 TR