2.2 Pressure-Temperature Dynamics & Operating Pressures
R-410A Refrigerant Certification Study Guide Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview & Refrigeration Fundamentals
1.1 About the R-410A Safety Certification Exam 1.2 Refrigeration Cycle Fundamentals for R-410A Technicians
2 Chapter 2: R-410A & R-407C Properties and Pressures
2.1 Physical & Chemical Properties of R-410A 2.2 Pressure-Temperature Dynamics & Operating Pressures 2.3 R-407C: Glide, Fractionation & Service
3 Chapter 3: System Components & Service Tools
3.1 System Components, Compressor Engineering & Relief Devices 3.2 Condensers, Receivers, Evaporators & Refrigerant Lines 3.3 Metering Devices & Expansion Valves 3.4 Manifold Gauges, Hoses & Service Fittings
4 Chapter 4: Lubricants, Moisture Management & Evacuation
4.1 Polyolester (POE) Lubricants & Oil Chemistry 4.2 Hygroscopic Risks, Hydrolysis & Acid Formation 4.3 Filter-Driers & Deep Evacuation Standards
5 Chapter 5: Charging, Leak Detection & Recovery
5.1 Liquid Charging & Fractionation Control 5.2 Leak Detection Methods & Nitrogen Pressure Testing 5.3 Recovery Equipment, Cylinder Safety & 80% Fill Rule
6 Chapter 6: Safety: Hazards, Personal Protection & Cylinders
6.1 Toxicity, Asphyxiation & Thermal Decomposition Hazards 6.2 Personal Protection & Electrical Safety on R-410A Jobs 6.3 Cylinder Storage, Transport & Equipment-Room Safety
7 Chapter 7: Environmental Regulations & Industry Transition
7.1 EPA Section 608 Rules & AIM Act Leak Repair 7.2 The R-22 Phase-Out, AIM Act & Low-GWP Transitions
8 Chapter 8: System Diagnostics & Retrofitting Rules
8.1 Subcooling and Superheat Diagnostics 8.2 System Troubleshooting & Operating Faults 8.3 Retrofitting Rules & Line Set Management
2.2 Pressure-Temperature Dynamics & Operating Pressures
Key Takeaways Explain This Topic AI
R-410A saturation pressures run roughly 60% to 75% higher than HCFC-22 at typical condensing and evaporating temperatures, so gauges, hoses, and recovery cylinders must be rated for R-410A.
Standard comfort cooling operating pressures range from 100 to 145 psig on the suction low-side (33°F to 50°F evaporator saturation) and 375 to 450+ psig on the liquid high-side (110°F to 125°F condensing saturation).
At a 70°F static equilibrium temperature, an idle R-410A system exhibits an equalized standing pressure of approximately 201 psig, compared to only 121 psig for HCFC-22.
Compression ratios must be calculated using absolute pressures (psia = psig + 14.7); despite high gauge pressures, R-410A maintains low compression ratios (typically 2.8:1 to 3.2:1), sustaining high volumetric efficiency in scroll compressors.
R-410A suction vapor is about 45% denser than R-22 vapor at the same saturation temperature, so a compressor needs roughly 30% less displacement for the same tonnage.
Last updated: October 2026
Quick Reference: Across all operational temperature bands, R-410A generates saturated pressures 50% to 70% higher than HCFC-22 . Normal suction pressures range from 100 to 145 psig ( 33 ∘ F to 50 ∘ F 33^\circ\text{F}\text{ to }50^\circ\text{F} 3 3 ∘ F to 5 0 ∘ F saturation), while normal discharge pressures range from 375 to 450+ psig ( 110 ∘ F to 125 ∘ F 110^\circ\text{F}\text{ to }125^\circ\text{F} 11 0 ∘ F to 12 5 ∘ F saturation). An idle, equalized system at 70 ∘ F 70^\circ\text{F} 7 0 ∘ F rests at approximately 201 psig (vs. 121 psig 121\text{ psig} 121 psig for R-22). Under no circumstances may R-22 components, gauges, or service cylinders be used on an R-410A system.
1. The High-Pressure Operating Differential
The defining operational characteristic of R-410A is its significantly elevated pressure-temperature relationship. Saturated vapor pressure is a fundamental thermodynamic property dictated by molecular kinetic energy and intermolecular bonding forces. The compact molecular geometry of HFC-32 and HFC-125 results in rapid molecular vapor detachment at any given temperature, generating vapor pressures 1.5 to 1.7 times (50% to 70%) higher than HCFC-22 across equivalent saturation temperatures.
This elevated pressure differential governs every aspect of system engineering and field service:
It prohibits "drop-in" conversions of legacy R-22 equipment. Installing R-410A into an R-22 condensing unit or evaporator coil will rupture heat exchanger tubing, blow out compressor hermetic terminals, or cause catastrophic valve plate failure.
It requires heavy-duty service manifolds, burst-resistant charging hoses, and dedicated high-pressure recovery cylinders.
It dictates specialized high-pressure safety cutout controls and internal compressor relief mechanisms.
2. Low-Side and High-Side Operating Parameters
In standard residential and light commercial comfort cooling, vapor compression systems are designed around specific evaporator and condenser saturation targets:
Low-Pressure Side (Evaporator / Suction Zone)
To effectively dehumidify and cool residential indoor air ( 75 ∘ F dry-bulb / 63 ∘ F wet-bulb 75^\circ\text{F}\text{ dry-bulb / }63^\circ\text{F}\text{ wet-bulb} 7 5 ∘ F dry-bulb / 6 3 ∘ F wet-bulb ), the evaporator coil must maintain a refrigerant saturation temperature between 40 ∘ F 40^\circ\text{F} 4 0 ∘ F and 45 ∘ F 45^\circ\text{F} 4 5 ∘ F ( 4.4 ∘ C 4.4^\circ\text{C} 4. 4 ∘ C to 7.2 ∘ C 7.2^\circ\text{C} 7. 2 ∘ C ), keeping coil surfaces safely above freezing ( 32 ∘ F 32^\circ\text{F} 3 2 ∘ F ) while remaining well below the indoor air's dew point ( 54 ∘ F 54^\circ\text{F} 5 4 ∘ F to 58 ∘ F 58^\circ\text{F} 5 8 ∘ F ):
At 40 ∘ F 40^\circ\text{F} 4 0 ∘ F Evaporator Saturation:
HCFC-22 Suction Pressure: 68.5 psig 68.5\text{ psig} 68.5 psig
R-410A Suction Pressure: 118.5 psig 118.5\text{ psig} 118.5 psig (a difference of + 50.0 psi +50.0\text{ psi} + 50.0 psi , or 73 % 73\% 73% higher )
At 45 ∘ F 45^\circ\text{F} 4 5 ∘ F Evaporator Saturation:
HCFC-22 Suction Pressure: 76.0 psig 76.0\text{ psig} 76.0 psig
R-410A Suction Pressure: 130.7 psig 130.7\text{ psig} 130.7 psig (a difference of + 54.7 psi +54.7\text{ psi} + 54.7 psi , or 72 % 72\% 72% higher )
Under varying field load conditions (low indoor airflow, dirty air filters, humid ambient air), the normal operational suction band for R-410A extends from 100 to 145 psig 100\text{ to }145\text{ psig} 100 to 145 psig , corresponding to saturation temperatures of approximately 33 ∘ F to 50 ∘ F 33^\circ\text{F}\text{ to }50^\circ\text{F} 3 3 ∘ F to 5 0 ∘ F . Sustained suction saturation below 32 ∘ F 32^\circ\text{F} 3 2 ∘ F (about 101 psig 101\text{ psig} 101 psig ) means the coil surface can ice up.
High-Pressure Side (Condenser / Discharge Zone)
An air-cooled condenser must reject both the heat absorbed in the indoor evaporator and the mechanical heat of compression added by the compressor motor. To drive heat from the refrigerant into outdoor ambient air, the condenser coil must operate at a temperature difference (condenser split) above ambient, typically 20 ∘ F 20^\circ\text{F} 2 0 ∘ F to 30 ∘ F 30^\circ\text{F} 3 0 ∘ F higher than outdoor air for standard efficiency systems:
On a standard summer day with 95 ∘ F 95^\circ\text{F} 9 5 ∘ F ( 35 ∘ C 35^\circ\text{C} 3 5 ∘ C ) outdoor ambient, the condensing saturation temperature runs between 115 ∘ F 115^\circ\text{F} 11 5 ∘ F and 125 ∘ F 125^\circ\text{F} 12 5 ∘ F :
At 115 ∘ F 115^\circ\text{F} 11 5 ∘ F Condensing Saturation:
HCFC-22 Discharge Pressure: 242.7 psig 242.7\text{ psig} 242.7 psig
R-410A Discharge Pressure: 390.5 psig 390.5\text{ psig} 390.5 psig (a difference of + 147.8 psi +147.8\text{ psi} + 147.8 psi , or 61 % 61\% 61% higher )
At 125 ∘ F 125^\circ\text{F} 12 5 ∘ F Condensing Saturation:
HCFC-22 Discharge Pressure: 277.9 psig 277.9\text{ psig} 277.9 psig
R-410A Discharge Pressure: 446.5 psig 446.5\text{ psig} 446.5 psig (a difference of + 168.6 psi +168.6\text{ psi} + 168.6 psi , or 61 % 61\% 61% higher )
In standard summer operation, R-410A head pressures run between 375 and 450 + psig 375\text{ and }450+\text{ psig} 375 and 450 + psig . In extreme ambient heat ( 105 ∘ F to 115 ∘ F 105^\circ\text{F}\text{ to }115^\circ\text{F} 10 5 ∘ F to 11 5 ∘ F ) or with obstructed, dirty condenser coils, head pressures rapidly escalate past 500 to 550 psig 500\text{ to }550\text{ psig} 500 to 550 psig , approaching the electrical and mechanical safety limits of the equipment.
3. Standing (Static Equilibrium) Pressures & Field Safety
When an air conditioner or heat pump cycles off, refrigerant stops circulating. Over several minutes, refrigerant vapor equalizes across the metering device until pressure is uniform throughout the entire circuit. The resting pressure of an equalized system is dictated entirely by the surrounding ambient temperature according to saturated vapor-pressure laws.
Standing Pressure Comparison at Common Ambients
Ambient Temperature HCFC-22 Equalized Pressure R-410A Equalized Pressure Pressure Delta (psi)
50 ∘ F 50^\circ\text{F} 5 0 ∘ F ( 10.0 ∘ C 10.0^\circ\text{C} 10. 0 ∘ C ) 84.0 psig 84.0\text{ psig} 84.0 psig 142.9 psig 142.9\text{ psig} 142.9 psig + 58.9 psi +58.9\text{ psi} + 58.9 psi ( + 70.1 % +70.1\% + 70.1% )
70 ∘ F 70^\circ\text{F} 7 0 ∘ F ( 21.1 ∘ C 21.1^\circ\text{C} 21. 1 ∘ C ) 121.4 psig 121.4\text{ psig} 121.4 psig 201.4 psig 201.4\text{ psig} 201.4 psig + 80.0 psi +80.0\text{ psi} + 80.0 psi ( + 65.9 % +65.9\% + 65.9% )
90 ∘ F 90^\circ\text{F} 9 0 ∘ F ( 32.2 ∘ C 32.2^\circ\text{C} 32. 2 ∘ C ) 168.4 psig 168.4\text{ psig} 168.4 psig 274.3 psig 274.3\text{ psig} 274.3 psig + 105.9 psi +105.9\text{ psi} + 105.9 psi ( + 62.9 % +62.9\% + 62.9% )
100 ∘ F 100^\circ\text{F} 10 0 ∘ F ( 37.8 ∘ C 37.8^\circ\text{C} 37. 8 ∘ C ) 195.9 psig 195.9\text{ psig} 195.9 psig 317.4 psig 317.4\text{ psig} 317.4 psig + 121.5 psi +121.5\text{ psi} + 121.5 psi ( + 62.0 % +62.0\% + 62.0% )
110 ∘ F 110^\circ\text{F} 11 0 ∘ F ( 43.3 ∘ C 43.3^\circ\text{C} 43. 3 ∘ C ) 226.4 psig 226.4\text{ psig} 226.4 psig 365.1 psig 365.1\text{ psig} 365.1 psig + 138.7 psi +138.7\text{ psi} + 138.7 psi ( + 61.3 % +61.3\% + 61.3% )
Crucial Safety Implication of Standing Pressure
At a mild room temperature of 70 ∘ F 70^\circ\text{F} 7 0 ∘ F , an idle R-410A system maintains an equalized internal pressure of approximately 201 psig 201\text{ psig} 201 psig , compared to only 121 psig 121\text{ psig} 121 psig for R-22. On a hot summer afternoon where equipment sits at 90 ∘ F 90^\circ\text{F} 9 0 ∘ F before startup, static pressure exceeds 274 psig 274\text{ psig} 274 psig .
This high standing pressure presents distinct hazards:
Low-Side Gauge Damage: Traditional R-22 compound gauges read to about 120 psig 120\text{ psig} 120 psig with a retard zone to about 250 psig 250\text{ psig} 250 psig . An idle R-410A system at 70 ∘ F 70^\circ\text{F} 7 0 ∘ F already drives that gauge deep into its retard zone, and on a warm day (about 274 psig 274\text{ psig} 274 psig at 90 ∘ F 90^\circ\text{F} 9 0 ∘ F ) the pressure exceeds the retard range and can permanently damage or decalibrate the gauge.
Stored Pneumatic Potential: Even when de-energized, an R-410A condensing unit stores tremendous mechanical energy. Depressurizing service valves or piercing tubing without proper recovery procedures poses severe projectile and blast risks.
4. Compression Ratio Mechanics & Volumetric Efficiency
A common misconception is that because R-410A operates at much higher pressures, its compressor must work under an unsustainably severe compression ratio. Thermodynamic analysis reveals this is untrue when proper absolute pressure conversions are applied.
Calculating Compression Ratio ( C R CR CR )
Compression ratio is defined as absolute discharge pressure divided by absolute suction pressure. It must never be calculated using gauge pressures ( p s i g psig p s i g ):
C R = P discharge, absolute P suction, absolute = P discharge, psig + 14.7 P suction, psig + 14.7 CR = \frac{P_{\text{discharge, absolute}}}{P_{\text{suction, absolute}}} = \frac{P_{\text{discharge, psig}} + 14.7}{P_{\text{suction, psig}} + 14.7} CR = P suction, absolute P discharge, absolute = P suction, psig + 14.7 P discharge, psig + 14.7
Comparative Engineering Calculation
Consider an R-410A system and an R-22 system operating at identical saturation conditions ( 115 ∘ F 115^\circ\text{F} 11 5 ∘ F condensing and 45 ∘ F 45^\circ\text{F} 4 5 ∘ F evaporating):
R-410A System:
P discharge = 390.5 psig → P discharge, abs = 390.5 + 14.7 = 405.2 psia P_{\text{discharge}} = 390.5\text{ psig} \rightarrow P_{\text{discharge, abs}} = 390.5 + 14.7 = 405.2\text{ psia} P discharge = 390.5 psig → P discharge, abs = 390.5 + 14.7 = 405.2 psia
P suction = 130.7 psig → P suction, abs = 130.7 + 14.7 = 145.4 psia P_{\text{suction}} = 130.7\text{ psig} \rightarrow P_{\text{suction, abs}} = 130.7 + 14.7 = 145.4\text{ psia} P suction = 130.7 psig → P suction, abs = 130.7 + 14.7 = 145.4 psia C R R − 410 A = 405.2 145.4 ≈ 2.79 CR_{R-410A} = \frac{405.2}{145.4} \approx \mathbf{2.79} C R R − 410 A = 145.4 405.2 ≈ 2.79
HCFC-22 System:
P discharge = 242.7 psig → P discharge, abs = 242.7 + 14.7 = 257.4 psia P_{\text{discharge}} = 242.7\text{ psig} \rightarrow P_{\text{discharge, abs}} = 242.7 + 14.7 = 257.4\text{ psia} P discharge = 242.7 psig → P discharge, abs = 242.7 + 14.7 = 257.4 psia
P suction = 76.0 psig → P suction, abs = 76.0 + 14.7 = 90.7 psia P_{\text{suction}} = 76.0\text{ psig} \rightarrow P_{\text{suction, abs}} = 76.0 + 14.7 = 90.7\text{ psia} P suction = 76.0 psig → P suction, abs = 76.0 + 14.7 = 90.7 psia C R R − 22 = 257.4 90.7 ≈ 2.84 CR_{R-22} = \frac{257.4}{90.7} \approx \mathbf{2.84} C R R − 22 = 90.7 257.4 ≈ 2.84
Remarkably, the compression ratio of R-410A is slightly lower (2.79:1) than that of R-22 (2.84:1) despite gauge pressures being about 150 psi higher. Because volumetric efficiency falls as compression ratio rises, this low ratio helps R-410A scroll compressors pump efficiently.
5. Volumetric Refrigerating Capacity & Equipment Design
Volumetric Refrigerating Capacity measures the heat energy (Btu) absorbed in the evaporator per cubic foot of refrigerant vapor entering the compressor suction inlet ( B t u / f t 3 Btu/ft^3 Bt u / f t 3 ). It is the product of vapor density ( ρ v \rho_v ρ v ) and Net Refrigerating Effect (NRE):
Volumetric Capacity = ρ v × NRE \text{Volumetric Capacity} = \rho_v \times \text{NRE} Volumetric Capacity = ρ v × NRE
Because R-410A operates at higher suction pressures, its vapor is substantially denser than R-22 vapor at the same saturation temperature (saturated vapor at 45 ∘ F 45^\circ\text{F} 4 5 ∘ F is about 2.40 lb/ft 3 2.40\text{ lb/ft}^3 2.40 lb/ft 3 for R-410A versus about 1.66 lb/ft 3 1.66\text{ lb/ft}^3 1.66 lb/ft 3 for R-22). The refrigerating effect per pound is nearly the same for both refrigerants, so R-410A delivers roughly 40 % to 50 % 40\%\text{ to }50\% 40% to 50% more cooling per cubic foot of suction vapor than R-22:
Compressor Displacement: To deliver 3 tons ( 36 , 000 Btu/hr 36,000\text{ Btu/hr} 36 , 000 Btu/hr ) of cooling, an R-410A compressor needs roughly 30 % 30\% 30% less displacement than an equivalent R-22 compressor ( 1 ÷ 1.45 ≈ 0.69 1 \div 1.45 \approx 0.69 1 ÷ 1.45 ≈ 0.69 ). This enables smaller, lighter compressors.
Lineset Sizing: Because less vapor volume must be moved for the same heat load, R-410A suction lines are often one size smaller than the R-22 line for the same tonnage. Always size lines from the manufacturer's line-set tables, because oversized suction lines hurt oil return.
6. Structural Safety Margins & Pressure Relief Devices
To safely contain R-410A's elevated pressure profile, manufacturers and safety regulatory codes (such as UL 1995 , UL 60335-2-40 , and ASHRAE Standard 15 ) mandate rigorous structural mechanical ratings:
Tubing and Heat Exchanger Standards
Thin-wall plumbing tubing (Type M) is never used. Field piping is ACR copper (ASTM B280) of the wall thickness the manufacturer specifies for R-410A pressures.
Flare joints must be made with a quality 45 ∘ 45^\circ 4 5 ∘ flaring tool to the dimensions and torque values in the installation manual, using the flare nuts supplied with the R-410A equipment.
Safety Relief Devices
Modern R-410A equipment incorporates multi-layered electro-mechanical safety devices:
High-Pressure Cutout Switch (HPC):
Located directly on the compressor discharge line before the service valve.
Trips to de-energize the compressor contactor if head pressure exceeds safe limits.
R-410A Setting: Typically calibrated to open at 550 to 610 psig 550\text{ to }610\text{ psig} 550 to 610 psig (with an auto-reset close threshold around 420 to 460 psig 420\text{ to }460\text{ psig} 420 to 460 psig or manual reset requirement). By contrast, R-22 cutouts tripped at 375 to 425 psig 375\text{ to }425\text{ psig} 375 to 425 psig .
Internal Pressure Relief (IPR) Valve:
A spring-loaded internal relief bypass valve built into the compressor head between high-discharge and low-suction cavities.
R-410A Calibration: Lifts when differential pressure reaches 550 to 625 psid 550\text{ to }625\text{ psid} 550 to 625 psid (differential pounds per square inch), dumping high-pressure discharge gas directly back into the low-pressure compressor shell to prevent casing rupture. By comparison, R-22 IPR valves lifted at 375 to 450 psid 375\text{ to }450\text{ psid} 375 to 450 psid .
Fusible Plugs / Rupture Discs:
Fusible plugs on some receivers and larger vessels melt at a rated temperature (often around 210 ∘ F 210^\circ\text{F} 21 0 ∘ F ) to vent refrigerant in a fire. Recovery cylinders instead use a spring-loaded pressure relief valve.
7. Pressure-Temperature (P-T) Reference Comparison Table
Temperature (°F) Temperature (°C) R-410A Saturation (psig) HCFC-22 Saturation (psig) Pressure Delta (psi) % Increase over R-22
0 ∘ F 0^\circ\text{F} 0 ∘ F − 17.8 ∘ C -17.8^\circ\text{C} − 17. 8 ∘ C 48.6 48.6 48.6 24.0 24.0 24.0 + 24.6 +24.6 + 24.6 + 102.5 % +102.5\% + 102.5%
20 ∘ F 20^\circ\text{F} 2 0 ∘ F − 6.7 ∘ C -6.7^\circ\text{C} − 6. 7 ∘ C 78.4 78.4 78.4 43.1 43.1 43.1 + 35.3 +35.3 + 35.3 + 81.9 % +81.9\% + 81.9%
32 ∘ F 32^\circ\text{F} 3 2 ∘ F (Ice Point) 0.0 ∘ C 0.0^\circ\text{C} 0. 0 ∘ C 101.4 101.4 101.4 57.5 57.5 57.5 + 43.9 +43.9 + 43.9 + 76.3 % +76.3\% + 76.3%
40 ∘ F 40^\circ\text{F} 4 0 ∘ F (Typical Evap) 4.4 ∘ C 4.4^\circ\text{C} 4. 4 ∘ C 118.5 118.5 118.5 68.5 68.5 68.5 + 50.0 +50.0 + 50.0 + 73.0 % +73.0\% + 73.0%
45 ∘ F 45^\circ\text{F} 4 5 ∘ F (Typical Evap) 7.2 ∘ C 7.2^\circ\text{C} 7. 2 ∘ C 130.7 130.7 130.7 76.0 76.0 76.0 + 54.7 +54.7 + 54.7 + 72.0 % +72.0\% + 72.0%
50 ∘ F 50^\circ\text{F} 5 0 ∘ F 10.0 ∘ C 10.0^\circ\text{C} 10. 0 ∘ C 142.9 142.9 142.9 84.0 84.0 84.0 + 58.9 +58.9 + 58.9 + 70.1 % +70.1\% + 70.1%
70 ∘ F 70^\circ\text{F} 7 0 ∘ F (Standing Amb) 21.1 ∘ C 21.1^\circ\text{C} 21. 1 ∘ C 201.4 201.4 201.4 121.4 121.4 121.4 + 80.0 +80.0 + 80.0 + 65.9 % +65.9\% + 65.9%
90 ∘ F 90^\circ\text{F} 9 0 ∘ F 32.2 ∘ C 32.2^\circ\text{C} 32. 2 ∘ C 274.3 274.3 274.3 168.4 168.4 168.4 + 105.9 +105.9 + 105.9 + 62.9 % +62.9\% + 62.9%
100 ∘ F 100^\circ\text{F} 10 0 ∘ F 37.8 ∘ C 37.8^\circ\text{C} 37. 8 ∘ C 317.4 317.4 317.4 195.9 195.9 195.9 + 121.5 +121.5 + 121.5 + 62.0 % +62.0\% + 62.0%
110 ∘ F 110^\circ\text{F} 11 0 ∘ F 43.3 ∘ C 43.3^\circ\text{C} 43. 3 ∘ C 365.1 365.1 365.1 226.4 226.4 226.4 + 138.7 +138.7 + 138.7 + 61.3 % +61.3\% + 61.3%
115 ∘ F 115^\circ\text{F} 11 5 ∘ F (Typical Cond) 46.1 ∘ C 46.1^\circ\text{C} 46. 1 ∘ C 390.5 390.5 390.5 242.7 242.7 242.7 + 147.8 +147.8 + 147.8 + 60.9 % +60.9\% + 60.9%
120 ∘ F 120^\circ\text{F} 12 0 ∘ F (Typical Cond) 48.9 ∘ C 48.9^\circ\text{C} 48. 9 ∘ C 417.7 417.7 417.7 259.9 259.9 259.9 + 157.8 +157.8 + 157.8 + 60.7 % +60.7\% + 60.7%
125 ∘ F 125^\circ\text{F} 12 5 ∘ F (High Cond) 51.7 ∘ C 51.7^\circ\text{C} 51. 7 ∘ C 446.5 446.5 446.5 277.9 277.9 277.9 + 168.6 +168.6 + 168.6 + 60.7 % +60.7\% + 60.7%
130 ∘ F 130^\circ\text{F} 13 0 ∘ F 54.4 ∘ C 54.4^\circ\text{C} 54. 4 ∘ C 475.6 475.6 475.6 296.8 296.8 296.8 + 178.8 +178.8 + 178.8 + 60.2 % +60.2\% + 60.2%